As requested, the following observations were performed at the referenced lot at the dates indicated
below. As per our observation, it is our opinion that the observed portions of the foundation system
were found to be in general conformance with the foundation plan and requirements of the soil
report for the subject site. Observations were conducted on a periodic, on-call basis.
Date: Observation:
August 12, 2020 Footing (bottom of wall steps, reinforcement, forms and void)
August 17, 2020 Foundation Wall Reinforcement and UFER
August 25, 2020 Stripped Wall Inspection
An electrode is located within and near the bottom of the foundation or footing that is in direct
contact with the earth consisting of at least (20ft) of one or more bare or zinc galvanized or other
electrically conductive steel reinforcing bars or rods of not less than (1/2”) in diameter.
Reinforcing bars are bonded together by steel tie wires or other effective means and stubbed out
for conductor bonding. UFER installed as required.