HomeMy WebLinkAbout130 W OLIVE ST - SPECIAL INSPECTIONS - 7/8/2016Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave., Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 7/8/16 PROJECT The Waffle Lab 130 W. Olive Street Fort Collins, CO ARCHITECT None Shown ENGINEER Abrahamson Engineering, Inc. 3101 Kinzley Court, Unit D La Porte, CO CONTRACTOR Poudre Valley Air 2416 Donella Ct. Fort Collins, CO Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 PROJECT: The Waffle Lab ADDRESS: 130 W. Olive Street Fort Collins, CO The data presented in this report is an exact record of the system performance and was obtained in accordance with NEBB Standard Procedures. Any variances from design quantities which exceed NEBB tolerances are noted throughout the report. The air distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:7/8/16 The hydronic distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:7/8/16 SUBMITTED & CERTIFIED BY NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. TAB SUPERVISOR: David C. Reichel REG. NO.: 2389 SIGNATURE: DATE: 7/8/16 CERTIFICATION EXPIRATION DATE: 3/31/2018 Table of Contents Instrument Calibration Report Abbreviation Report Roof Top Unit Fan Unit Prints 2 3 4 6 7 Page 1 of 9 Project: The Waffle Lab Manufacturer Model Serial Application Cal. Date Alnor HM-680 70552109 Hydronic Press. & Diff. Press. 1/16/2014 Alnor HM-680 70750150 Hydronic Press. & Diff. Press. 12/14/2015 Alnor HM-680 70838501 Hydronic Press. & Diff. Press. 11/30/2015 Alnor HM-680 71021246 Hydronic Press. & Diff. Press. 4/5/2016 Alnor HM-680 71043011 Hydronic Press. & Diff. Press. 6/10/2015 Alnor HM-680 91139097 Hydronic Press. & Diff. Press. 4/10/2015 Cooper SH66A 92711016 Temperature 4/10/2015 Extech 461895 Q394479 Rotation Measurement 10/12/2015 Extech 461895 Q083481 Rotation Measurement 1/9/2014 Extech 461895 Q247569 Rotation Measurement 3/8/2016 Extech 461895 L268576 Rotation Measurement 3/8/2016 Extech 461895 Q331990 Rotation Measurement 11/4/2014 Extech 461895 Q477125 Rotation Measurement 9/25/2015 Extech 461895 Q477126 Rotation Measurement 4/5/2016 Extech 461895 Q527632 Rotation Measurement 4/8/2015 Extech 461895 Q590099 Rotation Measurement 10/12/2015 Extech RH390 9099221 Temperature / Humidity 4/9/2015 Fluke 335 96960004 Electrical Measurement 11/5/2015 Fluke 336 97110539R Electrical Measurement 4/5/2016 Fluke 336 97110538R Electrical Measurement 9/29/2015 Fluke 335 92008180 Electrical Measurement 11/4/2014 Fluke 335 12990071 Electrical Measurement 3/4/2016 Fluke 374 15460133 Electrical Measurement 4/18/2014 Fluke 374 20030351 Electrical Measurement 4/8/2015 Fluke 374 20030354 Electrical Measurement 10/23/2015 Shortridge ADM-860C M05789 Digital Manometer 11/25/2015 Shortridge ADM-860C M06821 Digital Manometer 10/12/2015 Shortridge ADM-860C M07352 Digital Manometer 6/6/2016 Shortridge ADM-860C M09123 Digital Manometer 4/18/2016 Shortridge ADM-860C M09347 Digital Manometer 9/26/2015 Shortridge ADM-860C M10144 Digital Manometer 11/18/2014 Shortridge ADM-860C M10371 Digital Manometer 11/5/2015 Shortridge ADM-860C M11448 Digital Manometer 4/15/2016 Shortridge HDM-300 W02060 Hydronic Press. & Diff. Press. 10/5/2015 Shortridge HDM-250 W09198 Hydronic Press. & Diff. Press. 10/12/2015 Shortridge HDM-250 W98020 Hydronic Press. & Diff. Press. 4/8/2015 REMARKS: Not all equipment shown was used on this project. Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 INSTRUMENT CALIBRATION REPORT Page 2 of 9 Project: The Waffle Lab Symbol Description Symbol Description A Airflow (L/S) NS Not Shown AF Air Foil NT No Information Tag ANA Access Not Available OD Outside Diameter BI Backward Incline RPM Revolution Per Minute CD Ceiling Diffuser SD Supply Diffuser CFM Airflow (Cubic Feet / Minute) SNKL Snorkel DD Direct Drive SP Static Pressure Des Design SPD Static Pressure Drop DWDI Double Width Double Inlet SR Supply Register EF Exhaust Fan SWSI Single Width Single Inlet EG Exhaust Grille T Temperature ( C ) ER Exhaust Register T Temperature ( F ) ESP External Static Pressure TSP Total Static Pressure FC Forward Curve VFD Variable Frequency Drive GPM Waterflow (Gallons / Minute) VS Variable Speed HC Heat Coil W Waterflow (L/S) HER Heat Exchanger HRC Heat Recovery Hz Hertz ID Inside Diameter In. WC Inches of Water Column NA Not Applicable NI Not Installed NIC Not In Contract NM Not Measurable NPT No Pressure Tap NR Not Readable REMARKS: Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 ABBREVIATION REPORT Page 3 of 9 PROJECT: The Waffle Lab LOCATION: Fort Collins, CO DATE: 7/8/2016 CONTACT: Wade Wilson Roof Top Unit Test Date: July 08, 2016 SYSTEM/UNIT: (E)RTU-01 AREA: Tested By: Wade Wilson Unit Data Unit Manufacturer Lennox Unit Model Number GCS16-653-125-3Y Unit Serial Number 5693C02586 Unit Discharge Vertical/Down (E)RTU-01 / Supply Fan Fan Type Forward Curve Fan Size 12" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Horizontal (E)RTU-01 / Filter Bank Filter Manufacturer Flanders Filter Type Pleated Filter Quantity 1 Filter Size 16x25x2 Starter Data (E)RTU-01 / Supply Fan Installed Thermal Internal Test Data Total CFM Design 2610 CFM Total CFM Actual 2377 CFM Outside Air CFM Design 550 CFM Outside Air CFM Actual 569 CFM Return Air CFM Design 2060 CFM Return Air CFM Actual 1815 CFM Motor Data (E)RTU-01 / Supply Fan Motor Manufacturer Magnetek Motor RPM 1075 RPM Motor Rated Volts 208-230 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 4.3 Amps Sheave Data (E)RTU-01 / Supply Fan Motor Sheave Make Direct Drive Test Pressures Fan SP In Actual -0.42 in. wc Fan SP Out Actual 0.16 in. wc Filter SP In 0.0 in. wc Filter SP Out -0.42 in. wc Coil SP In 0.16 in. wc Coil SP Out ANA in. wc (E)RTU-01 Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final PROJECT: The Waffle Lab LOCATION: Fort Collins, CO DATE: 7/8/2016 CONTACT: Wade Wilson Roof Top Unit Test Date: June 29, 2016 SYSTEM/UNIT: MAU-01 AREA: Tested By: Wade Wilson Unit Data Unit Manufacturer Accurex Unit Model Number XDG-109-H10-DB Unit Serial Number 14616194 Unit Discharge Vertical/Down MAU-01 / Supply Fan Fan Type Forward Curve Fan Size 8" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Vertical/Down MAU-01 / Filter Bank Filter Manufacturer MV EZ Kleen Filter Type Washable Filter Quantity 2 Filter Size 12x25x2 Starter Data MAU-01 / Supply Fan Installed Thermal Adjustable Rating (Amps) 3.7-5.5 Amps Thermals Set at: 4.7 Test Data Total CFM Design 2160 CFM Total CFM Actual 2138 CFM Outside Air CFM Design 2160 CFM Outside Air CFM Actual 2138 CFM Return Air CFM Design 0 CFM Return Air CFM Actual 0 CFM MAU-01 / Supply Fan Motor Volts 1 208 Volts Motor Volts 2 209 Volts Motor Volts 3 208 Volts Motor Amps 1 4.2 Amps Motor Amps 2 4.4 Amps Motor Amps 3 4.3 Amps Motor Data MAU-01 / Supply Fan Motor Manufacturer WEG Motor Frame 56H Motor HP 1.5 HP Motor RPM 1760 RPM Motor Rated Volts 208-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 4.64-4.20/2.10 Amps Motor Service Factor 1.15 Nominal Efficiency 86.5 % Power Factor 76 Sheave Data MAU-01 / Supply Fan Motor Sheave Make Power Drive PROJECT: The Waffle Lab LOCATION: Fort Collins, CO DATE: 7/8/2016 CONTACT: Wade Wilson Fan Unit Test Date: June 29, 2016 SYSTEM/UNIT: EF-01 AREA: Tested By: Wade Wilson Unit Data Fan Manufacturer Accurex Fan Model Number XRUB-220HP-15-G Fan Serial Number 14615441 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal Adjustable Rating (Amps) 5-8 Amps Thermals Set at: 5.3 Test Data Total CFM Design 2700 CFM Total CFM Actual 2604 CFM Fan RPM Actual 664 RPM Motor Volts 1 209 Volts Motor Volts 2 208 Volts Motor Volts 3 209 Volts Motor Amps 1 2.4 Amps Motor Amps 2 2.3 Amps Motor Amps 3 2.3 Amps Motor Data Motor Manufacturer WEG Motor Frame 56H Motor HP 1.5 HP Motor RPM 1760 RPM Motor Rated Volts 208-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 4.64-4.20/2.10 Amps Motor Service Factor 1.15 Nominal Efficiency 86.5 % Power Factor 76 Sheave Data Motor Sheave Make Power Drive Motor Sheave Model VP34 Motor Sheave Diam. 3 1/4 in. Motor Operating Diameter 2 1/4 in. Motor Sheave Bore 5/8 in. Fan Sheave Make Power Drive Fan Sheave Model AK61 Fan Sheave Diam. 6 in. Fan Sheave Bore 1 in. Number of Belts 1 Belt Size AX28 in. Sheave Center Line 8 in. * Notes Final Report L.H. Finn and Associates Page 6 of 9 Page 7 of 9 (E) RETURN RELOCATED 17/17 SA UP, 1RANSITION TO !l.&l=.J. SUPPl.Y ZE IN ROC>r CURS (Ei~~@ R8 &JO (E) n<ERMOSTAT TO REMAI' {N) l)f C ON IN (N) METAL STUO WAU., SH elJ1MllU!li. eLMI. SHEET M-2 0~ (E) R£TURN -~- ~~-1~_ 0 _PL__ A_N~~~~~-~ FLAG NOTES: @ EXISTINC MEC><ANICAL WORK TO REMAIN AS IS. @ ElOSTINC MEC><ANICAL WORK TO 8E REIAO'IEO. CloP OR PLUC REMAINING AS REQUIRED. PATOf FlOOR, WAU., CEIJHC, OR ROOF AS REQUIRED. 0 ~~s=n~21·~'i'.'~~~:S~;e~i."c9l' ~6 93% Err FILTER, L55 SERIES E26 CANOPY U<lHT FlXTUR(. (2) 1rtt EXHAUST, 2700 CF\t PR0\110£ WAU.- MOUNTED HE• TINC/COOUNC CON1ROL eox TO PROlllOE 60-70' SUPPL y AIR AT HOOO ON HEATINC (AOJ.) & 55- 65' SAT ON COOUHC (MANUAL ON rOR COOUNC). MAKE-UP AIR U!OT TO 8E INTERLOCKED WITH EXHAUST FAN. W/ ANSUL 3.0, 3 CAL FlRE 51.JPPRESSION SYSTEM IN UTILITY CABINET, PER 509.1, IMC. HOOO 13'x5·x~· oai>, O'IERAU.. © ~:C:~~Tf.i:c~;" ~c~:~~C:.0c~~·:~~"y CONFUCTS WITH ENCINEER. ® FIRE PROTECTION/IJTIUTY CABINET FOR ANSUL R102 SYSTEM I!< CON 1ROLS ON LEFT. GENERAL NOTES: 1. All WORK IS TO 8E OONE IN ACCOROANCE WITH ALL APPLICABLE STA TE ANO LOCAL COOES IHCLUOINC BUT NOT LIMITED TO: THE 2012 INTERNATIONAL BUILOINC COOE, 2012 INTERNATIONAL MECHANICAL COOE, 2012 INTERNATIONAL F1JEl. CAS COOE, ANO 2012 INTERNATIONAL ENERCY CONSERVATION COOE OR ASHRAE 90.1-2007. 2. 10TC><EN HOOO. Fll.TERS. EXHAUST rAH, EXHAUST DUCTS, MAKE-UP AIR UNIT, FlR£ SUPPRESSION SYSTEM, ETC. SHALL All BE IN ACCORDANCE 'MTH SECTIONS 506, ~7. 50&, ANO 509 OF THE 2012 INT. MECHANICAL COOE (IMC). 3. CREASE OUCT FllOll THE HOOO TO THE EXHALIST rAN SHALL 8E 16 CAUCE, 18 CA. STAINLESS STEEL. OR rACTORY-BUILT COllMEROAL KITC><EN CREASE OUCT LISTED ANO LABELEO PER UL 1978 ANO INSTALLED PER SECTION 30<'.1 OF Tl1E 2012 IMC. DUCT-TO-EXHAUST FAN CONNECTION PER 506.J .2. J, AND WTH A "19RATION ISOLATION CONNECTOR PER '°6.J.2.4. TESTED PER 506.3.2.5, ANO 507.16.1. 4. SUPPLY AIR DUCTWORK SHALL BE CALVANIZEO SHEET METAL INSTALL£D IN ACCORDANCE ~lll SMACNA DUCT CONS1RUCTION STANOAROS. VER1rY ALL CLEARANCES IN FlELO PRIOR TO DUCT FABRCATION. 5. All RECTANCULAR SUPPLY DUCTS ARE TO 9( UNEO WITH I " THICK DUCT UHER. NOTE THAT SIZE USTEO ON PLANS IS THE CLEAR INSIOE OIMENSION. AOO 2" TO EACH DIMENSION FOR Page 8 of 9 " " or v uP_/:" : IN WALL :: " " " /WALL ii: 11 ___6' __MAX. ____ - 1)1" TRAP ARM.2--------1 ,..,,,_ ,, / 2·wJ~ 1/4" lURN7 ANGLE STOP. 1"". NOTES OH!S Qff,!,ll QN! yl- COUNITR ~FLOOR TlilS DETAIL TO 9-IOW PIPING CONNECTIONS. NOT LOCATIONS. LOC .. TE PIPING AS REOUIRED TO MAKE CONNECTIONS. SINK PIPING DETAIL 5' MIN. F'ROM BU!lDINC r-'----~­ · 1 24" RlNG/CO~ W/ CONCRETE SHIMS AS REQUIRED TO BRING' 2" v / CRADE UP TO CRADE " /GLEANOUT ¢ 4" CREASE_/ WASTE IN SECTION APPROX. WATER CAPACITY (GALLONS): 750 APPROX. WEICHT (LBS): 1 M54 PRE-CAST GREASE ¢ ~ 4• WASTE OUT 6'" WALLS INTERCEPTOR DETAIL NO SCALE 1/2" cw. 1'" DRAIN ABOVE CEIUNG r-- ------ 1 I r--!O I l I ~-------------- 1 ... CREA.SE WASTE~ I •• IN cco EL£VA AT TlON, APPROX. CONTRACTOR •' -o· OROP TO I I CONF1RM W/ (E) SEWER DEP™" I IN ALLEY BEFORE INSTALLATION ".IQI v 2" BURIED VENT I r-----v----.J I I Page 9 of 9 0 .. x x x LEGEND SYMBOL DESCRIPTION SYMBOL OESCRtPTION SYMBOL OESCRIF"TION - OOMESTIC COLO WA mo PIPING (Cw) ,. ---- DOMESTIC HOT WATER PIPING (HW) * NEW DUCTWORK (SHAOED) AFF ABOVE FlNISHEO FLOOR ~ * BB BASE BlO -----T--- - DCM. DOMESTIC HOT WATER TEMPER£D REORC\HOT UTIHC WATER PIPING PIPING (H-.0:(:) T) EXISTING DUCTWORK TO REY.A.IN BOO BOTTOM ~ OUCT ~:4fff-?~ -------o-v---- - - ORAJN WASTE \/ENT PIPING PIPING PIPING (V) (BELOW 0) CRAOE (W) ,? ~ * MANUAL EXISTING VOLUME DUCTWORK DAMPER TO BE (MVO) REMO\/EO (EA CA ON E) EXHAUST EXISTING 00"COMBUSTION " AIR AJR --G-- NA nJRAL GAS PIPING (C) q cc GENERAL CONTRACTOR EXISTING PIPING TO REMAIN (LICHT LINE) TURNING YANES IN DUCT E\BOW IE IN\-£RT El£VA TlON ~- EXISTING PIPING TO BE REMOVED 1.W. INDIRECT WASTE ---0-- FlOOR CU:AN OUT (rco) MAY MANUAL AIR VENT ------12r-<-ti - CRACE WAU. CU:CU:AN AN OUT OUT (111:(GCO) 0) D ' SQUARE TO ROUND DUCT TRANSITION NIC (N) NEW NOT IN CONTRACT 04RECTION ~ FlOW ARROW ~ Fl£Xl8l.E DUCT OA OUTSIDE AJR PIPE UP, PIPE TEE OO'Mi, PIPE ELBOW OO'Mll 0 0 RA RETURN AIR PPE CONTINUATION BREAK, PIPE CAP CR PlUC SUPPLY DIFFUSER; EXHAUST, RET\JRN, RB REBALANQE BAU VALVE, CATE VALVE TRANSFER CRIU£ SA SU?PLY AIR ~- CHECI< YAL\/E (1'.) THERMOSTAT OR TEMP. SENSOR (T- STAT) TA TRANSFER AIR GAS COCK (!). (!), NIGHT, ZONE •x• THERlAOSTA T OR SENSOR TCC TEMPERA T\JRE CONTROL CONTRACTOR UNION OR Fl.ANGE FlTTINC .....!IL. UN04ERCUT OOOR Fl£XIBLE PIPE CONNECTOR 0 FlRE DAMPER PlPE REDUCER OR INCREASER Fl TTINC • VTR VENT THROUGH ROOF PIPE CUlOE. PIPE ANCHOR PRESSURE REOUONG YAL\/E (PRY) W/ .. TH PIPE WITH SLEEVE ----Lj- PRESSURE/TEMPERATURE RELIEF VALVE W/0 .. THOUT WO WALL OPENING (ABOVE OEILING) (PIPE DRAIN TO fl.OOR DRAIN OR OU~O£) ~ POINT OI' CONNECTION, NEW TO ElOSTING (POC) MAKE-UP AIR UNIT SCHEDULE NO. I LOCATION I MAKE de MOOEL NUMBER I aM I •H20 ESP I fAN HP I 00/BO I RPM/SPEED I rue DATA I FlA I FUEL HEATING I INPUT MBH I 5000' OUTPUT I I M:IGiT I MAU-1 I ON ROOF I CAPTIVEAIRE A1-0.250-CIO I 2160 I 0.5 I 2.0 I BO I 1280 I 208/J/60 I 5.9 I NC I 164.6 I 151.4 1 616 1 REMARKS 0 OIRECT-FlREO NAT. CAS @ w/ EYAP. coouNG, SIZE 2 CELDEK. w/ FREEZE-PROOF Fll.L ANO DRAIN KIT TO ORAJN AT 40· r OAT EXHAUST FAN SCHEDULE NO. I LOCATION I MAKE • MOOEL NUM8£R I CfM I PO "H20 I SONES I ~ I HP/1'U I rue DATA I v.c1CHT I CONTROL I REMARKS Ef- 1 I ON ROOF I TWN CITY BCRUR 210BHP I 2100 1 1.25 I 1J.• 1 992 1 1/5.5 1 208/J/60 I 210 1 0 I CD (i) UPBLAST r AN W/ BO DAMPER " VENTILATED. FlAT ROOF CURB w/ HINOCO BAS£ " CREASE COLLECTOR 0 ~ ~~~~p'lio~~ ~~~~;~~~.r1~RLOCK .. TH ANY~ THE THREE COOKING APPUANOES BY MEANS~ HEAT SENSORS s .~ < . ~ CREASE i5 TRAP ~ 2 .z =" . > ROOF DECK DD DD D D v.n.DED DUCT BY MC MIN . ~ 16° ABOVE ROOF OECK PER NrPA I I STANOARO ROOF OJRB fl I Fl..ASHEO TO ROOF PER I ARCHITECTURAL ORA\tt1NCS 1-- 2s.s·x2e.s· -' FIRE SEAL ROOF OPENING ZERO CU:ARANQE CREASEOUCT INSULATION GREASE HOOD EXHAUST FAN DETAIL NO SCALE HINC€D CURB ACOESS +4• HOSE CONNECTION w I VACUUM BREAKER a: BAU VALVE MAKE-UP AIR UNIT 1/2" c w 1· COPPER ORAJN NOTES cru1s PETt\ll ONLY)· /AIR GAP, TYP. • "-FlOOR SINK OR MOP SER\1CE BASIN 1. SLOPE ALL PIPING TO ORAIH POIN PS. 2. SEE DRAWINGS FOR DRAIN SIZES. EVAPORATIVE COOLER PIPING DETAIL NO SCALE 1· G J FLAG NOTES: 0 EXISTING MECHANICAL WORK TO REMAJN AS IS. @ ~~~~~~t'~~~~1~~I~JEFt~~~~ c~C:C.~G ROOF AS REQUIRED. (D GAS PIPE TO EQUIPMENT W/ CAS COCK, 6" LONG fULL DIAMETER DIRT LEG, ANO UNlON - SIZE AS NOTID. © CONNECT NEW 1 /2• CW F'~ EVAP COOl£R TO NEAREST CW IN SPACE. SEE fYAPMADyE COOi EB p1p1NC QEfA!! THIS SHEET. ORAJN TO MSB OR ro. INSULATE W/ 1/2" CW PIPE ® INSULATION SEE GBEASf' W/ HOO[VAPOR ) EXHAUST BARRIER. FAN QEIA!L THIS SHEET. © (N) 1Y." NATURAL GAS TO (E) GAS MEltR. CONTRACTOR TO COORDINATE Wlll-l QTY METER DEPARTMENT TO VERIFY PROPER SIZE Of GAS METER. NEW TOTAL CAS LOAD • 886 MBH INPUT. @ RE-BALANCE MINIMUM OA OAMPER FOR 550 CFM. (N) 1~" ON TO KITCHEN EQUIP. CAP (E) 3/4" /-0 (E) VTR O r{1) (E) EXHAUST / - f AN 0 (E) J/4" C ON TO r{1) (E) WATER HEATER / - 125 MBH G----<> l kl ~TENANT (E) GAS SPACES TO OTHER -~4 -~_A_1 ~ __ 0 __ R_O_O_F_P_LA__N __ ~~ Ill <( ....J .... w w w (.cc ./.) . ....J LL w LL> <( 6 ~ ­ w := :c 0 I- ~ JOB NUMBER 1525 DRAWN KJK DESIGNED KJK/ROA CHECKED ROA ISSUE 1/29/2016 REVISIONS SHEET NAME .q- C\I IO 0 co 0 (.) <z Ji ::i ...J 0 (.) .cc ... 0 LL MECHANICAL PLAN SHEET NUMBER M-3 3 OF 3 I I 2'" V UP ALONG WALL 1 O' ABOVE CR ADE ) FLOOR SINK TO REMAIN ON DOMESTIC WASTE 1-1::= ===!: ( l~(E)WASTE -~e-~~-1 ~-0 ~_IN_G_PL_A_N ___ _.$ _,... ""= """"' NO WORK IN RESTROOMS FLAG NOTES: 0 EXISTING MECHANICAL WORK TO REMAIN AS IS. @ ~~;:i~~~~~:~~E~P:~BE,i~~~~ c~c:c.~c ROOf' AS REOUIREO. @ GAS PIPE TO EQUIPMENT W/ GAS COC1<, 6° LONG FULL DIAMETER DIRT L£C, ANO UNION - S.ZE AS NOTED. © CONNECT NEW 1 /2'" CW FOR f>/AP COOLER TO NEAREST CW IN SPACE. SEE ( YApOBAD'tf'. CQ()L,£R p!P!NC DETAIL SHEET M-3. ORAJN TO FLOOR SINK. INSULATE W / 1 /2" CW PIPE INSULATION W/ VAPOR BARRIER. @~~~~~Ai'._~~ ~~T~~LG~~~~~~r°1~~~ IFC REQUIREMENTS. ACCESSIBlE ABOVE CEIUNG. @ SINK, 1/2" HW, 1/2" CW, 2"W, 1~· V. W/ niERMOSTATIC MIXINC VALVE WATTS lFUSC-6. SE£ SINK Plp!NC QfIAB THIS SHEET. CONNECT (N) HW It CW It VENT P1PES TO NEAREST (E) PIPES. ~HANO SINK - ADVANCE TABCO OL-1-25 DROP IN S.S. SINK, 5• DEEP, W/ FAUCET, 20 GA . .J04 S.S .. 14"x12" O.D .. 1.JWx11X'"x~) 1.0., 4'" FA.UCET CENT£RS. S=.2, DUMP SINK - ADVANCE TABCO st- RS-12 S.S. BLENOER STATION W/ OUtr.tP SNK, 10"X14"XIO". W/ 15A/120V DUPLEX OUTLET BENEA ™ SHELF. 4° BACKSPLASH. 0 ;,:~ ;:p ~-R~iE~~~~· z~::ir,~o~N~~~A~NT. @ (N) GREASE INTERCEPTOR, SEE PRE- CAST GREASE !NJSRCtpltR DETAIL THIS SHEET. COLORAOO PRECAST CONCRETE, INC. ® (N) 1}1" V UP IN WALL. CONTRACTOR CAN COMBINE (E) HANO SINK VENT .. ™ (N) FLOOR SINK VENT, BUT UPSIZE TO 1)1" V. FLOOR SINKS ARE SIZED AT 3" TO ALLOW BO™ FLOOR SINKS TO USE ONE 1)1" VENT, 12' MAX .. PER TABLE 909.1 hlAl!IMUll. DISTANCE (F f!XIlJRt TRAP fROM VENT PER IPC. @) ~t: TE~ ~~g~ (~)..";:D P1;,~~G, P~~·lt "':i~1~~!~E(i) LOCATIONS. @ RE-ROUTE (E) 3-COMPARTMENT SINK DRAIN PIPING TO (N) FLOOR SINK. (E) FLOOR SINK TO REMAIN, BUT NOT TIED INTO CREASE WASTE SYSTEM. @ RE-ROUTE (N) 1)1" GAS PIPE DOWN IN NEW METAL SlUO WALL. SEE GAS PIPING OfTA!I BELOW. @ ICIE MACHINE. 1/2" CW It 3/4" l.W. TO (N) FLOOR SINK. @ DISHWASHER, 3/4" HW It 1)1" LW. TO (E) FLOOR SINK BELOW. STEAM TABLE, 7 MBH~ UP ™RU ROOF" 5 SHUT-OFF (N) 1)1" GAS P1PE TO /!>AUTO. GAS ~l i/ VALVE /,.-~ ./. KITCHEN HOOD ISti:.l DEEP FRYER. 120 MBH EACH,~ ""· (2) 1 ~ (N) 1)1" C IN 12 (N) METAL STVO WALL GAS PIPING DETAIL NO SCALE al <( ....J UJ w ~ w a: ~ Cf) .u....J .w u.. > <( 5 ~. UJ ;: :I: 0 I- ~ JOB NUMBER 1525 DRAWN KJK DESIGNED KJK/ROA CHECKED ROA ISSUE 1/29/2016 REVISIONS SHEET NAME ~ C\I It) 0 CX) 0 0 <Ji z ...J ...J 0 0 a: ~ 0 u.. PLUMBING PLAN SHEET NUMBER M-2 2 OF J CX) CX) 0 -CX) C7> <O 0 ....... C7> METAL DUCT SIZE. 6. All DUCT SEAMS AR£ TO BE SEALED WITH DUCT SEALER. 7. SEPARATE BALANCINC COHlRACTOA ACCEPTA8t.£ TO O..,.,.ER & ENCINEER TO BALANCE HVAC SYSTEM AFTER WOR1< IS COMPLETE. SUBMIT BALANCE REPORT FOR RE\1EW TO ENCINEER. FORT COLUNS/MIOWEST. FlNN OR loPPRO'f:O EQUAL BALANCER TO BALANCE THE EXHAUST rAN, THE MAKE-UP AIR UNIT, ANO THE MINMUM QUTSIOE AIR OF BOTH EXISTINC Rru•s. 8. NEW MANUAL VOLUME DAMPERS TO 8E CENTER PIVOTINC ANO SIHCLE IHICl<NESS 22 CAUCE CALVANIZEO STEEi. AXJ..ES SHALL 8E ~· SQUARE PLATED STER.. BEARINCS SHALL 8E HEAVY DUTY NYLON OR BRONZE TYPE. ACTUATOR SHALL Bf: )f OIAMETER MANUAL LOC10NC QUAORANT. CREENHECK MB0-15 OR PRIOR loPPRO'f:D EOUAL BALANCE FOR COMFORT I!< LOW SOUNO LE\'ELS. 9. INSTALL All EQUIPMENT PER MANUrACTUREJl'S INSTALLATION INSTRUCTIONS. 10. SEAL All WALL ANO ROOF PENETRATIONS AIR I!< WATER-TICHT. 11. PR<MOE THE OWNER WITH (2) SETS OF OPERATION ANO MAiNITNANCE MANUALS IN J-RINC SfNDERS, COMPLETt: wrTH All APPRO'IEO EOU1PMENT SHOP ORAWINCS. TEMPERATURE CONTROL SHOP ORAWINCS. AIR BALANCE REPORT, ANO EQUIPMENT MANUFACTURER'S OPERATION ANO MAINTENANCE MANUALS, RECOMMENOEO SPAR( PARTS LISTS, TRDUBLE-SHOOTINC CUIOEUNES ANO RECOMMENDATIONS, INSTALLATION RECOMMENDATIONS, ETC .. AS NORMALLY OONE. 12. THE CONTRACTOR SHALL INSTRUCT THE OWNER'S MAINTENANCE STAFr ON Tl<E TEMPERATURE CON1ROLS. ANO OPERATION ANO MAINTENANCE or All NEW EQUIPMENT, (2) HOURS MINIMUM. 13. CONTRACTOR SHALL PROVIOE "AS- BUILr DRAWINGS TO THE OWNER. 1<. CAS PIPE SHALL 8E sai 40 STEEl. SCREWEO JOINTS, LEAK-TESTED IN M:COROANCE WT1H INT{RNA110NAI. FlJEL CAS COOE OR LOCAL COOES. THE MOST SlRIHCENT SHAil. APPLY. FOR GAS P1PINC ON ROOF. PROl/IOE I!< INSTALL MIRO INO. PILLOW BLOCK PIPESTANO MODEL 1.5. UV R£SISTANT POLYCAR80NATE RESIN MATERIAL. 6" SO FlLAT DECK PLATE, W/ 'IERTICAL SPACERS AS R£0'0. 15. HANG OR SUPl'ORT All PIPINC PER MANUFACTURER'S RECOMMENOAl10NS, A1ML OR COOPER B-UNE. 16. TEMPERATUR£ CONTROLS TO INCLUOE MUA UNIT OUCT OISCHARCE AIR TEMPERATURE SENSOR, OA TEMPERATURE CONTROLLER, MOTORIZED BACKOfWT DAMPER. COOUHC INTERLOCK RELAY TO LOCK OUT BURNER CIRCUIT, CAS BURNER MOOUV.TIHC CONTROL VAL\'E, TWO-STACE COOUNC THERMOSTAT, FlLL ANO ()RAIN KIT, WATER PRESSURE SWITCH UPSTREAM OF 2-WAY SOLENOIO VALVE. ROOM TEMPERATURE SENSOR, HOOO UCHTINC RELAY, ETC. All PER OWNER'S SUBMITTAL tNFORMATION FROM CAPTIVE-AIRE CO. 17. CONTRACTOR TO CLEAN All (E) SUPPLY I!< RETURN OIFFlJSERS ANO CRILLES. m ... <( w ....J w w .CIJ cc .. ....J u.. w u.. > <( :J 3: 0 w 3: :::c: 0 ~ - C') JOB NUMBER 1525 DRAWN KJK DESIGNED KJK/RDA CHECKED RDA ISSUE 1/29/2016 REVISIONS SHEET NAME HVAC PLAN SHEET NUMBER .q- C\I LO 0 «> 0 0 en z ..J ..J 0 .cc 0 .. 0 LL M-~ 1 OF .3 «> «> «> -0 O> co 0 ...... O> Motor Sheave Model VP34 Motor Sheave Diam. 3 1/4 in. Motor Sheave Bore 5/8 in. Motor Operating Diameter 3 1/4 in. Fan Sheave Make Power Drive Fan Sheave Model AK36 Fan Sheave Diam. 3 1/2 in. Fan Sheave Bore 3/4 in. Number of Belts 1 Belt Size AX27 Sheave Center Line 19 1/2 in. Test Pressures Fan SP In Actual -1.16 in. wc Fan SP Out Actual ANA in. wc External SP In Actual 0.0 in. wc External SP Out Actual ANA in. wc OA Damper Pos Actual 100 % RA Damper Pos Actual 0 % Unit External SP Actual NM in. wc Heat Ex SP In -0.40 in. wc Heat Ex SP Out -1.16 in. wc Filter SP In 0.0 in. wc Filter SP Out -0.27 in. wc Coil SP In -0.27 in. wc Coil SP Out -0.40 in. wc * Notes Final Report L.H. Finn and Associates Page 5 of 9 Prelim Reading Maximum Design AK Factor Outlet Size LxW / D Type System / Unit Area Served Front Of House Outlet-01 (E) 24x24 630 422 594 67 94 Front Of House Outlet-02 (E) 24x24 630 564 571 90 91 Front Of House Outlet-03 (E) 24x24 630 318 552 50 88 Outlet-04 Kitchen (E) 24x24 360 362 344 101 96 Outlet-05 360 312 316 87 88 Totals : - - - 2,610 1,978 2,377 76 - % 91 - % 5-Jul-16 Maximum flow available, unit is a single speed direct drive fan. (E)RTU-01 Wade Wilson (E)RTU-01 8-Jul-16 Wade Wilson OSA damper is broken and is set at a fixed position. 5-Jul-16 Unable to proportion registers due to no balancing dampers on existing ductwork. (E)RTU-01 Wade Wilson * Notes Final Report L.H. Finn and Associates Page 4 of 9