HomeMy WebLinkAbout910 HILL POND RD - 14 - DISCLOSURES - 9/3/2020BUILDING LEAKAGE TEST
InorOut Smart Energy
Randy Bates Rater # 6021967
204 Horizon Ave
Erie, CO 80516
Email: randy@inoroutsmartenergy.com Website: www.inoroutsmartenergy.com
Date of Test: 9/3/2020 Test File: PacRim Builders Master Techtite
Technician: Randy Bates Rater # 6021967
Project Number:
Customer: Matt Chacon
Pacific Rim Builders
Building Address: 910 Hillpond Rd #14
910 Hillpond Rd
Unit 14
Loveland, CO 80526
Test Results
1. Airflow at 50 Pascals: 1305 CFM50 ( +/- 0.4 %)
(50 Pa = 0.2 w.c.) 2.88 ACH50
2. Leakage Area: 71.8 in2 LBL ELA @ 4 Pa
3. Building Leakage Curve: Flow Coefficient (C) = 192.0 ( +/- 12.2 %)
Exponent (n) = 0.490 ( +/- 0.030 )
Correlation Coefficient = 0.99807
4. Test Settings: Test Standard: RESNET Multi-Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 9/3/2020 Test File: PacRim Builders Master Techtite
Building Information
Volume 27219
Surface Area
Floor Area 2126
Height
# of Bedrooms
# of Occupants
Year of Construction 2020
Wind Shield M
Location Climate Information
Ventilation Weather Factor 0.87
Energy Climate Factor 17.00
Heating Degree Days 6128
Cooling Degree Days 297
Design Winter Wind Speed 7.3 mph
Design Summer Wind Speed 9.4 mph
Design Winter Temp Diff 73 deg F
Design Summer Temp Diff 15 deg F
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Retrotech BD2000 102907
Micromanometer Retrotech DM-32 4A
4/27/20
404876 4/27/20
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 9/3/2020 Test File: PacRim Builders Master Techtite
Depressurization Test:
Environmental Data
Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft)
78.0 78.0 5000.0
Data Points -
Nominal
Building Pressure
(Pa)
Baseline Adjusted
Building Pressure
(Pa)
Fan
Pressure
(Pa)
Nominal
Flow
(cfm)
Adjusted
Flow
(cfm) % Error
Fan
Configuration
-0.7 n/a n/a
-50.0 -54.6 57.7 1373 1370 0.5 Ring A
-45.0 -49.6 51.4 1298 1295 -0.5 Ring A
-40.0 -44.6 46.7 1239 1236 0.1 Ring A
-55.0 -59.6 62.4 1427 1423 -0.0 Ring A
-60.0 -64.7 68.0 1488 1484 0.2 Ring A
-50.0 -54.6 57.3 1369 1365 0.1 Ring A
-45.0 -49.6 52.1 1307 1304 0.2 Ring A
-55.0 -59.6 61.6 1418 1414 -0.6 Ring A
10.0 n/a n/a
Time Averaging Period: 30
Deviations from Standard RESNET Multi-Point Test - Test Parameters
None
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 9/3/2020 Test File: PacRim Builders Master Techtite
Comments
House to Garage: -46.2 Pa