HomeMy WebLinkAboutCORRESPONDENCE - PURCHASE ORDER - 91575601995 Logan Avenue PH: 204-633-7220
Winnipeg, Manitoba FAX: 204-694-0614
Canada R2R 0H8 E-Mail: ieman.zeid@carte.ca
Customer: Fort Collins Date:
Page 1 of 2
Quotation No: 16730D
Item:
Customer Ref.:
Specification: IEEE C57.12.24
Quantity: 1
Type: Submersible
kVA: 300
Phase: 3
Temp. Rise (C): 55
Coolant: Oil (ONAN)
Frequency: 60 Hz.
High Voltage (HV): 13200Y/7620
HV kV BIL: 95
HV Taps: 4-2.5% +2,-2
Low Voltage (LV): 208Y/120
LV kV BIL: 30
Winding Material: Aluminum
Paint: Black
HV Bushing: (3) Covermount Well, 200A Welded
LV Bushing: (4) Cover 4 Hole Nema Spade (Epoxy)
Protection: Cooper Magnex MX3BN2SYE18 c/w ELSP Fuses
Switches: () N/A
Shipping Package: Pallet
Accessories: (1) Stainless Steel Nameplate
(1) Small SS PR Device
304L SS 1.5" Tank Base Bars, 304L SS Manhole Cover
Copper Ground Bus Ring
304L SS Tank, Base & Welded Cover
September 4, 2015
1
Form #: CII079 Rev.3 (07/06/20)
1995 Logan Avenue PH: 204-633-7220
Winnipeg, Manitoba FAX: 204-694-0614
Canada R2R 0H8 E-Mail: ieman.zeid@carte.ca
Customer: Fort Collins Date:
Page 2 of 2
Quotation No: 16730D
Item:
Performance Data: Watts Temp Voltage Loss Eval $/Watt
No-Load Loss 620 20 100% 3.900
Load Loss 2164 85 2.300
Total Losses 2784
% Impedance 3.60
Efficiency: DOE 99.27%
Net Price Each (US): (Taxes not included in price)
Shipment from Factory: 28 (weeks after receipt of order)
Free on Board (FOB): Winnipeg
Freight Allowed (FA): Fort Collins
Note -
1) Quoted leadtime is accurate at the time of quotation. Leadtime subject to change without notice as orders are entered into our
production schedule on a first-come, first-served basis.
2) This quotation and any orders placed with Carte International Inc. are subject to our standard Terms and Conditions. This
quotation shall not be binding upon Carte International Inc. until it is accepted by the Purchaser as indicated by our receipt of a
written purchase order and acknowledged by Carte International Inc. in writing.
3) This quotation will remain in effect for 30 days unless changed in the interim upon written notice.
4) Payment terms are net within 30 days from date of shipment unless otherwise specified.
5) Unloading and placement of transformers is Purchaser's responsibility.
6) Unless specifically listed above or otherwise noted, items such as lightning arresters, stress cones, flexible connectors,
bushing connectors, lugs and related hardware, etc. are not included.
7) Routine production testing is included; price adders applicable should temperature rise test or other type tests be required.
8) This transformer has been designed to handle the usual service conditions as stated in CSA and ANSI C57.12.00
paragraph 4, and has not been sized to handle any special loading requirements such as rectifier applications, VFD's, etc..
We assume that the Purchaser has sized the transformer properly to the required load.
9) Price adders may apply in retrofit applications where required dimensions have not been provided.
10) Carte is ISO 9001-2000 registered.
$24,013
September 4, 2015
1
Form #: CII079 Rev.3 (07/06/20)
1995 Logan Avenue PH: 204-633-7220
Winnipeg, Manitoba FAX: 204-694-0614
Canada R2R 0H8 E-Mail: ieman.zeid@carte.ca
Customer: Fort Collins Date:
Page 1 of 2
Quotation No: 16730D
Item:
Customer Ref.:
Specification: IEEE C57.12.24
Quantity: 1
Type: Submersible
kVA: 500
Phase: 3
Temp. Rise (C): 55
Coolant: Oil (ONAN)
Frequency: 60 Hz.
High Voltage (HV): 13200Y/7620
HV kV BIL: 95
HV Taps: 4-2.5% +2,-2
Low Voltage (LV): 208Y/120
LV kV BIL: 30
Winding Material: Aluminum
Paint: Black
HV Bushing: (3) Covermount Well, 200A Welded
LV Bushing: (4) Cover 6 Hole Nema Spade (Epoxy)
Protection: Cooper Magnex MX3BN2SYE30 c/w ELSP Fuses
Switches: () N/A
Shipping Package: Pallet
Accessories: (1) Stainless Steel Nameplate
(1) Small SS PR Device
304L SS 1.5" Tank Base Bars, 304L SS Manhole Cover
Copper Ground Ring Bus
304L SS Tank, Base & Welded Cover
September 4, 2015
2
Form #: CII079 Rev.3 (07/06/20)
1995 Logan Avenue PH: 204-633-7220
Winnipeg, Manitoba FAX: 204-694-0614
Canada R2R 0H8 E-Mail: ieman.zeid@carte.ca
Customer: Fort Collins Date:
Page 2 of 2
Quotation No: 16730D
Item:
Performance Data: Watts Temp Voltage Loss Eval $/Watt
No-Load Loss 1030 20 100% 3.900
Load Loss 2684 85 2.300
Total Losses 3714
% Impedance 2.50
Efficiency: DOE 99.35%
Net Price Each (US): (Taxes not included in price)
Shipment from Factory: 28 (weeks after receipt of order)
Free on Board (FOB): Winnipeg
Freight Allowed (FA): Fort Collins
Note -
1) Quoted leadtime is accurate at the time of quotation. Leadtime subject to change without notice as orders are entered into our
production schedule on a first-come, first-served basis.
2) This quotation and any orders placed with Carte International Inc. are subject to our standard Terms and Conditions. This
quotation shall not be binding upon Carte International Inc. until it is accepted by the Purchaser as indicated by our receipt of a
written purchase order and acknowledged by Carte International Inc. in writing.
3) This quotation will remain in effect for 30 days unless changed in the interim upon written notice.
4) Payment terms are net within 30 days from date of shipment unless otherwise specified.
5) Unloading and placement of transformers is Purchaser's responsibility.
6) Unless specifically listed above or otherwise noted, items such as lightning arresters, stress cones, flexible connectors,
bushing connectors, lugs and related hardware, etc. are not included.
7) Routine production testing is included; price adders applicable should temperature rise test or other type tests be required.
8) This transformer has been designed to handle the usual service conditions as stated in CSA and ANSI C57.12.00
paragraph 4, and has not been sized to handle any special loading requirements such as rectifier applications, VFD's, etc..
We assume that the Purchaser has sized the transformer properly to the required load.
9) Price adders may apply in retrofit applications where required dimensions have not been provided.
10) Carte is ISO 9001-2000 registered.
$35,454
September 4, 2015
2
Form #: CII079 Rev.3 (07/06/20)