HomeMy WebLinkAboutCORRESPONDENCE - BID - 8756 - FORM 2S ELECTRIC METER 9016-5475 (2)CENTRON® II
CENTRON C12.19 C2ST, C2SD, C2SL
Itron introduces the second generation CENTRON, a solid-state single phase meter
that allows utilities the capability to connect and disconnect service remotely without a
service call from fi eld personnel.
With this solid-state meter, Itron presents
the CENTRON platform with Hall Sensor
technology for residential metering that
offers your utility the best in metering
technology proven to easily and affordably
expand as your business needs change.
The service switch feature available in
this new meter for residential markets is
designed for two- way communications.
Mass deployments provide functionality
that helps utilities to lower field service
costs, improve credit management, and
enable prepaid metering.
This ANSI C12.19 compliant residential
solid-state meter utilizes the ANSI Tables
protocol in a Demand (C2SD), a Time-of-
Use (TOU) module with Demand (C2ST),
and a Load Profile module with TOU
and Demand (C2SL) giving utilities the
chance to collect and utilize more detailed
information and better manage demand.
The CENTRON II C12.19 meter provides
robust data storage capability to support
time-of-use (TOU) pricing including Critical
Peak Pricing (CPP) capabilities. In addition,
the meter supports load profile data and
other data-intensive applications as well as
smart grid requirements. Features include
full two-way communication capabilities
for offsite operation when used with OEM
communications systems with a service-
limiting remote disconnect and reconnect
switch as well as the ability to program or
partially reconfigure the meter remotely.
In addition to its remarkable typical
accuracy of 0.3 percent, the CENTRON II
meter delivers advanced voltage monitoring
for power quality auditing and assurance.
FEATURES
Remote Disconnect
Optional 200 Amp remote disconnect
switch is integral to the meter assembly
and provides compact, non-discriminatory
meter profile
Load Profi le
The C2SL module provides 144K RAM for
up to seven channels of load profile data
Bi-Directional Metering
Capable of measuring and displaying
delivered, received, net, and unidirectional
energy (kWh), Kvarh, and Vah delivered,
received, and lag
Non-volatile Memory
All programming, register, TOU and load
profile data are stored in the EEPROM
Product Availablity
Meter Version Class Volts Form
C2SD, C2ST. C2SL 20 120V 3S
C2SD, C2ST. C2SL 20 240V 3S
C2SD, C2ST. C2SL 20 240V 4S
C2SD, C2ST. C2SL 200 120V 1S*
C2SD, C2ST. C2SL 200 240V 2S*
C2SD, C2ST. C2SL 200 120V 12S/25S*
C2SD, C2ST. C2SL 320 240V 2S
*C2SDD, C2STD. C2SLD
*Optional disconnect switch 200A
Specifications
Power Requirements
Voltage rating: 120-240 V (overvoltage
capabilities up to 480V)
Operating voltage: ±20% (60 Hz)
Frequency: 50Hz, 60 Hz
Operating range: ±3 Hz
Battery voltage: 3.6 V nominal
Battery operating range: 3.4 - 3.8 V
Operating Environment
Temperature: -40° to +85°C
Humidity: 0% to 95% non-condensing
General Information
Demand interval lengths: Programmable from
1 to 60 minutes
Demand calculation: Present, Previous,
Cumulative, Continuous Cumulative, Projected,
5 Highest
Peak Demand Energy calculation: Basic
Wh and VAh
Time: Line sync: Power line frequency
Crystal sync: +0.01% @ 25°C; +0.025% over
full temperature range
Battery: +0.005%@25°C; +0.005% to -0.02%
over full temp range
Display
Nine-digit liquid crystal display
Annunciator height: 0.088”
Six-digit data height: 0.4”
Display duration: 1-15 seconds
Three-digit code number height: 0.24”
3-segment electronic load indicator
» The optical port can also be disabled/enabled remotely via the
head end system
Voltage Measurement
» On board voltage measurement allows for end of line voltage
monitoring and residential voltage profiling for troubleshooting
and diagnostics
The CENTRON II C12.19 meter supports the measurement of
average voltage data, instantaneous voltages and tracks minimum/
maximum voltages during each interval up to three phases. The
interval data for each phase is compared with the configured
thresholds at each EOI. Events are recorded for the first interval
when a threshold is exceeded, when it returns to normal, and when
it is exceeded again. To minimize recording excessive events, only
one event is recorded when multiple successive intervals exceed
thresholds.
Temperature Measurement
Internal temperature monitoring in centigrade from the metrology
every 1 second. This can be used for local device temperature
status and profiling capability
Technical Data
Meets applicable standards:
» ANSI C12.1 - 2008
» ANSI C12.20 (Class 0.5) - 2010
» ANSI C12.18 - 2006
» ANSI C12.19 - 2008
» ANSI C12.21
» FCC CRF Title 47 Part 15.247 Subclass C
» Industry Canada RSS-210
Reference Information
» CENTRON II Technical Reference Guide
» Electricity Price Bulletin
» Hardware Specification Form
» Information developer kits are available that outline standard
processes and easy-to-use interfaces that are available for rapid
OEM development
While Itron strives to make the content of its marketing materials as timely and accurate as possible, Itron makes no claims, promises,
or guarantees about the accuracy, completeness, or adequacy of, and expressly disclaims liability for errors and omissions in, such
materials. No warranty of any kind, implied, expressed, or statutory, including but not limited to the warranties of non-infringement of third
party rights, title, merchantability, and fitness for a particular purpose, is given with respect to the content of these marketing materials.
© Copyright 2014, Itron. All rights reserved. 101019SP-05-1/15
CORPORATE HEADQUARTERS
2111 N Molter Road
Liberty Lake, WA 99019
USA
Phone: 1.800.635.5461
Fax: 1.509.891.3355
Join us in creating a more resourceful world.
To learn more, visit itron.com
during a power outage. A battery maintains
only the clock circuitry during a power
outage
Standard Features
» Electronic LCD display
» Polycarbonate cover
» Optical tower
» Customer Interface Button
Option Availability
» 200A remote service switch
Optical Port Communication
» Each module can be programmed to
communicate at 28800, 19200, 14400 or
9600 baud through the optical tower
SPECIFICATIONS