HomeMy WebLinkAboutCORRESPONDENCE - BID - 8679 500 KVA PAD-MOUNTED TRANSFORMER 300-0513 Phase Padmounted Transformer Bid Evaluation # Units 6 Xfmr Type 3P Pad Bid #: 8679 Size 500 kVA Secondary V 480/277 Date: February 13, 2018 NL Loss Cost $ 3.90 Stock # T300051 FL Loss Cost $ 2.30 Specified Impedance % 3.04 (See Impedance Requirements Table in Specification) Supplier Manufacturer Base Bid $ / Each Del/Wks Guar No Load Loss Guar Full Load Loss Impedance Meet Specs? Escalation (is / is not) a factor Guar Total Load Loss Includes Winding's Stray Losses & Losses Associated with Auxiliary Devices (Yes / No) Winding's Stray Losses Losses associated with Auxiliary Devices Impedance Variance Evaluated Bid Base Bid Extended Cost (Total $) NL Loss * NL Loss Cost FL Loss * FL Loss Cost Rank Based on Bid (1 is best choice) Rank Based on Evaluated bid (1 is best choice) Border States Howard Industries $ 12,080.42 6-8wks ARO 995 2661 3.10 Yes is not 3656 Yes 108.6 0 1.97% $ 22,081.22 $ 72,482.52 $ 3,880.50 $ 6,120.30 5 4 Peterson Company Central Moloney $ 11,239.00 10-12 wks 949 2413 2.87 Yes w/ Exception is 3362 Yes 315 0 -5.59% $ 20,490.00 $ 67,434.00 $ 3,701.10 $ 5,549.90 3 2 Western United WEG TRANSFORMERS $ 10,994.00 6-8 WEEKS 887 2595 3.04 Yes is not 3482 No 1035.76 0 0.00% $ 20,421.80 $ 65,964.00 $ 3,459.30 $ 5,968.50 2 1 Western United ERMCO $ 10,618.00 8-10 weeks 1031 2233 3.00 No is 3264 Yes 261 0 -1.32% $ 19,774.80 $ 63,708.00 $ 4,020.90 $ 5,135.90 1 - Western United Howard Industries $ 11,758.00 6-8wks ARO 995 2661 3.10 Yes No 3656 Yes 108.6 0 1.97% $ 21,758.80 $ 70,548.00 $ 3,880.50 $ 6,120.30 4 3 Technology International, INC CES 0 0 -100.00% $ - $ - $ - $ - - - WESCO DIST. ABB Inc. $ 13,611.40 12-16 Weeks 693 3235 3.04 Yes w/ Exception is not 3928 Yes 124 0 0.00% $ 23,754.60 $ 81,668.40 $ 2,702.70 $ 7,440.50 6 5 0 -100.00% $ - $ - $ - $ - - - 0 -100.00% $ - $ - $ - $ - - - IEEE C57.12.00, Section 9.2 Tolerances for impedance The tolerances for impedance shall be as follows: a) The impedance of a two-winding transformer with an impedance voltage greater than 2.5% shall have a tolerance of ±7.5% of the specified value, and those with an impedance voltage of 2.5% or less shall have a tolerance of ±10% of the specified value. Differences of impedance between duplicate two-winding transformers, when two or more units of a given rating are produced by one manufacturer at the same time, shall not exceed 7.5% of the specified value. b) The impedance of a transformer having three or more windings, or having zigzag windings, shall have a tolerance of ±10% of the specified value. Differences of impedance between duplicate three-winding or zigzag transformers, when two or more units of a given rating are produced by one manufacturer at the same time, shall not exceed 10% of the specified value. c) The impedance of an autotransformer shall have a tolerance of ±10% of the specified value. Differences of impedance between duplicate autotransformers, when two or more units of a given rating are produced by one manufacturer at the same time, shall not exceed 10% of the specified value. d) Transformers shall be considered suitable for operation in parallel when reactances come within the limitations of the preceding paragraphs, provided that turns ratios and other controlling characteristics are suitable for such operation.