HomeMy WebLinkAboutRESPONSE - BID - 8259 TRANSFORMERS 500 & 750 KVA THREE PHASE PADMOUNTED (2)FCU Stock #
T3000050
It Units
6
Size
500kVA
NL Loss Cost
$
FL Loss Cost
S
Supplier MIU Will
Fort Collins Utilities Transformer Bid Loss Data Sheet
Bid n:
Preparer Name:
Mark Baragary
Date:
1 N1Preparer Contact Num:
303-217-7516
Includes Winding's
Stray Losses &
Escalation
Losses Associated
Base Bid $ /
Guar No Load Guar Full Load Meet Specs?
(Is / la not) Guar Total
with Auxiliary
Each DeVWks
Loss Loss Impedance (Yes / No)
a factor Load Loss
Devices (Yes / No)
10,1g5.30 7-9 Woeks
i77 '150.7 3,02 Yos
Not 5071
Yes
Losses
associated
Winding's with Auxiliary NL Lon ' NL
Stray Losses Devices Loss Cost
IW 0 $
2) Full load losses — it shall be clearly stated whether this number includes the winding's expected stray losses and losses associated with auxiliary devices
3) Winding's expected stray losses related to quoted transformer design
4) Losses associated with auxiliary devices such as fuses, breakers, switches, etc.
Base Bid
FL Loss' FL Evaluated Extended Cost
Loss Cost Bid (Total $)
$ - $ 10,105.30 $ 60,631.80
All quoted loss values shall be corrected to a reference temperature of 85°C. Quotations submitted during the bid process without the required losses information shall be deemed unresponsive and are subject
to rejection by the City of Fort Collins.
1) Fill out the information in the cells with blue text.
2) Save the file using your company name and the bid number and e-mail it to: purchasing@fcgov.com
(Example: TransfornerSales_Sid_58.xis)
To protect this file, take the following steps:
1) Select Tools, Options
2) Select Security Tab
3) Type your password in the "Password to Open" field.
4) Re-enter your password to confirm it.
Importantl Please remember to include this password in the bid information that will be sealed in the envelope that will be
unsealed at Bid Opening. This will secure your data until the time of the bid opening.
5) Save the file and e-mail it to: purchasing@fcgov.com
FCU Stock #
T3000075
# Units
Size
750 kVA
NL Loss Cost
$
FL Loss Cost
$
Supplier Mir /Mh#
ABB 750KVA
Fort Collins Utilities Transformer Bid Loss Data Sheet
Bid a:
Preparer Name:
Mark Baragary
Date:
,. , Preparer Contact Num:
303-217-7516
Includes Winding's
Stray Losses a
Escalation
Losses Associated
Base Bid $ /
Guar No Load Guar Full Load Meet Specs?
(Is / Is not) Guar Total
with Auxiliary
Each DBI/Wks
Loss Loss Impedance (Yes / No)
a factor Load Loss
Devices (Yes / No)
S 16.289.50 9- 11 weeks
57n Yos
Not 5731
Ye,
Losses
associated
Winding's with Auxiliary NL Loss' NL
Stray Losses Devices Loss Cost
607 (I $
Quoted losses submitted by manufacturers shall include the following:
1) No load losses
2) Full load losses — it shall be clearly stated whether this number includes the winding's expected stray losses and losses associated with auxiliary devices
3) Winding's expected stray losses related to quoted transformer design
4) Losses associated with auxiliary devices such as fuses, breakers, switches, etc.
Base Bid
FL Loss' FL Evaluated Extended Cost
Loss Cost Bid (Total $)
$ - $ 16,209.50 $ 48,868.50
All quoted loss values shall be corrected to a reference temperature of 85'C. Quotations submitted during the bid process without the required losses information shall be deemed unresponsive and are subject
to rejection by the City of Fort Collins.
Fill out the information in the cells with blue text.
Save the file using your company name and the bid number and e-mail it to: purchasing@fcgov.com
(Example: Tmnsformer5ales_Bid-58.xis)
1) Select Tools, Options
2) Select Security Tab
3) Type your password in the "Password to Open" field.
4) Re-enter your password to confirm it.
Importantl Please remember to include this password in the bid information that will be sealed in the envelope that will be
unsealed at Bid Opening. This will secure your data until the time of the bid opening.
5) Save the file and e-mail it to: purchasing@fcgov.com
J
AL It It
^,.,.
Neg #: 1602910335 City of Fort Collins / Wesco Distribution, Inc / City of Fort
Collins
To:
City of Fort Collins
11333 East 55th Ave
Denver
CO 80239
Phone:
Fax:
From:
Mark Baragary
Wesco Distribution, Inc.
Phone: 303-217-7516
Fax: 303-217-7535
Email: mbaragary@wesco.com
Item Alt Oty Description Price Each (USD)
10 3 750 KVA Liquid Filled Padmounted Transformer $16,289.50
DTR 2401, Jefferson City, USA (9AAE300179), PDC: 9AAC30400147, DTAN-L3S135
500 KVA Liquid Filled Padmounted Transformer
20 6 DTR 2401, Jefferson City, USA (9AAE300179). PDC: 9AAC30400147, DTAN-L3S135 $10,105.30
ABB Page I of 6 2/260-016
NOTICE-- This document may contain confidential and privileged information for the sole use of the intended recipient. If you are nor the intended recipient You may not review, copy
or distribute this message. Any review or distribution by others is .strictly prohibited. If you are not the intended recipient, please contact the sender immediately and delete all copies.
Neg #: 16Q2910335 City of Fort Collins / Wesco Distribution, Inc / City of Fort
Collins
ITEM
QTY
kVA
EACH (USD)
Altitude
I NIL
I LL
I TL
Conductor
10
3
750
$16,289.50
3300
1 994 0 20 14737
@ 85
1 5731
AI/AI
nit
ITEM
%Z
Shipment
10
5.79
6946
9-11
Weeks
Quoted loss values are subjected to ANSI Test Tolerances. All weights and dimensions are approximate.
Lead times for orders subject to drawing approval will be confirmed upon receipt of approval and release for manufacturing.
Description:
Type Liquid -Filled MTR Padmounted Transformer
Fluid Mineral Oil
Core Grain Oriented Steel
Phase
3 Phase
Frequency
60 Hz
Average Winding Rise
65 °C
Ambient Temperature
30 °C
High Voltage
1320OGrdY/7620
High Voltage Taps
+2 -2 2.5%
High Voltage BIL
95kV BIL
Low Voltage
208Y/120
Low Voltage BIL
30kV BIL
Neutral
HOXO bushing with ground strap
Feed Configuration
Loop feed
Color
Desert tan paint (Munsell 1 OYR 6.0/3.0)
Customer Specification
368-300 Rev PP, 5/8/2014
Features (included in price):
TANK & CABINET
• Undercoat
• Penta-head cabinet handle bolt
BUSHINGS
• Threaded stud LV bushings x 4
• Loadbreak Inserts (dead front) x 6
• HV Bushing pattern per ANSI standard C57.12.26, Fig 6A & 7 (5.0" spacing)
• 200 amp HV bushing wells x 6
• 6-hole NEMA spade terminals x 4
• Spade Supports
• ANSI C57.12.26 Fig 7&8a specific stgrd LV bushing pattern
FUSES
• Fused bayonet no isolation link x 3
• Oil -immersed partial range current limiting fuse x 3
MONITORING
• Internal Fault Detector (IFD)
ABB Page 2 of 6 2/26/2016
NOTICE— This document mar contain confidential and privileged inforn nation for the sole use of the intended recipient. If you are not the intended recipientyou may not review. coPy
or distribute this message. Any review or distribution by others is strictiv prohibited. if you are not the intended recipient, please contact the .tender immediately and delete all copies.
AL N! I!
rRIL111111/
Neg #: 16Q2910335 City of Fort Collins / Wesco Distribution, Inc / City of Fort
Collins
• Liquid level gauge
• Pressure relief valve
• Dial type thermometer
• Provisions for pressure/vacuum gauge
FITTINGS
• Drain valve and sampler
MARKINGS
• Non -PCB label
OTHER
• Bushing leads long enough for field replacement
• LV compartment width min 28", LV bushing height 46", LV spacing per page 14, Max dims per pad drawing on
page 15
• 9.5" x 17.5" Tank Handhole Cover
• 18" deep cabinet
• DOE Efficiency (2016)
Item 10 General Comments and Exceptions
• Stray Losses
Item 10 - 660 Watts
Ass
Page 3 of 6
2/26/2016
NOTICE- This document mac contain confidential and privileged information for the sole use of the intended recipient. If you are not the intended recipient you map not review. cope
or distribute this message. Anr review or distribution by others is strictly prohibited. If you are not the intended recipient, please contact the .sender immediateh• and delete all copies.
/L 1! 1!
P%IPIP
Neg #: 16Q2910335 City of Fort Collins / Wesco Distribution, Inc / City of Fort
Collins
ITEM QTY kVA EACH USD) Altitude NIL LL TL Conductor
20 6 500 $10,105.30 A 3300 1527 @ 20 4544 ® 85 5071 AI/AI
nit
ITEM
%Z
Shipment
20
1 3.02
1 5545
7-9 Weeks
Quoted loss values are subjected to ANSI Test Tolerances. All weights and dimensions are approximate.
Lead times for orders subject to drawing approval will be confirmed upon receipt of approval and release for manufacturing.
Description:
Type
Fluid
Core
Phase
Frequency
Average Winding Rise
Ambient Temperature
High Voltage
High Voltage Taps
High Voltage BIL
Low Voltage
Low Voltage BIL
Neutral
Feed Configuration
Color
Customer Specification .
Liquid -Filled MTR Padmounted Transformer
Mineral Oil
Grain Oriented Steel
3 Phase
60 Hz
65 °C
30 °C
1320OGrdY/7620
+2 -2 2.5%
95kV BIL
208Y/120
io 11VA1:311111
HOXO bushing with ground strap
Loop feed
Desert tan paint (Munsell 1 OYR 6.0/3.0)
368-300 Rev PP, 5/8/2014
Features (included in price):
TANK & CABINET
• Undercoat
• Penta-head cabinet handle bolt
BUSHINGS
• Threaded stud LV bushings x 4
• Loadbreak Inserts (dead front) x 6
• ANSI C57.12.34 Fig 98,11 HV bushing pattern (minimum)
• 200 amp HV bushing wells x 6
• 6-hole NEMA spade terminals x 4
• Spade Supports
• ANSI C57.12.26 Fig 38,4a minimum stgrd LV bushing pattern
FUSES
• Fused bayonet no isolation link x 3
• Oil -immersed partial range current limiting fuse x 3
MONITORING
• Internal Fault Detector (IFD)
• Liquid level gauge
ABB Page 4 of 6 2/26/2016
NOTICE— This document nmY contain confidential and privileged information for the .sole use n(the intended recipient. Ifyou are not the intended recipient you nurc not review. copy
or distribute this message. Anv review or distribution by others is strictly prohibited If you are not the intended recipient please contact the .sender immediately and delete all copies.
A MIND
P119111
Neg #: 1602910335 City of Fort Collins / Wesco Distribution, Inc / City of Fort
Collins
• Pressure relief valve
• Dial type thermometer
• Provisions for pressure/vacuum gauge
FITTINGS
• Drain valve and sampler
MARKINGS
• Non -PCB label
OTHER
• Bushing leads long enough for field replacement
• LV compartment width min 28", LV bushing height 31 ", LV spacing per page 14, Max dims per pad drawing on
page 15
• 9.5" x 17.5" Tank Handhole Cover
• 18" deep cabinet
• DOE Efficiency (2016)
Item 20 General Comments and Exceptions
• Stray Losses
Item 20 - 190 Watts
KVA
FEED
A
9
C
D
E
F
WT
750
Loop
68
82
60.8
50.8
66
18
7400
(Dead)
500
Loop
56
68
58.8
48.8
62
18
5600
(Dead)
All weights and dimensions are approximate.
Dimensions may change to meet specific customer
requirements. Weights are in pounds. Dimensions are
in inches.
Cooling fins may be required on the back and/or side of
the tank if necessary. Maximum cooling fin depth is 16".
Top Yew
FINS
L -
-B
FINS
TANK FINS
CABLE OPENING
ABB Page 5 of 6 2/26/2016
NOTICE --This document nuty contain confidential and privileged information for the sole use of the intended recipient. If you are not the intended recipient you nmv not review, ropy
or distribute this message. Any review or distribution by others is strictly prohibited. If you are not the intended recipient. please contact the sender immediately and delete all copies.
A It it
P♦ Ip l!
Neg #: 1602910335 City of Fort Collins / Wesco Distribution, Inc / City of Fort
Collins
Side Yew
Front View
City of Fort Collins
2/26/2016 1 3-Phase Padmounted Transformer I ABB Inc, Jefferson City, MO
ABB
Page 6 of 6
2/26/2016
NOTICE-- This document mar contain confidential and privileged information for the sole use of the intended ret ipient. If you are not the intended recipient You may not rn'iew. copy
or distribute this message. My review or distribution by others is strictly prohibited. If you are not the intended reripinu, please contact the sender immedtarelr and delete all copies.