HomeMy WebLinkAboutBID - 8195 TRANSFORMERS 50KVA PAD-MOUNTED SINGLE PHASE8195 Transformer, 50kVA, Pad-mounted, Single Phase Page 1 of 5
INVITATION TO BID
8195 TRANSFORMERS, 50 KVA PAD-MOUNTED, SINGLE PHASE
The City of Fort Collins is requesting bids from firms for 50kVA, pad-mounted, single
phase transformers.
Bid submission via email is preferred. The Bid Loss Data Sheet shall be
submitted in Microsoft Excel only. Other documents may be submitted in Word or
PDF format. All documents are to be emailed to: purchasing@fcgov.com. If electing to
submit hard copy bids instead, three (3) copies, will be received at the City of Fort
Collins' Purchasing Division, 215 North Mason St., 2nd floor, Fort Collins, Colorado
80524. Bids will be received before 3:00 p.m. (our clock), November 23, 2015 and
referenced as Bid No. 8195. If delivered, they are to be sent to 215 North Mason
Street, 2
nd
Floor, Fort Collins, Colorado 80524. If mailed, the address is P.O. Box 580,
Fort Collins, 80522-0580.
The City encourages all disadvantaged business enterprises to submit bid in response
to all invitations and will not be discriminated against on the grounds of race, color,
national origin.
All questions or inquiries regarding this bid should be directed to: Pat Johnson,
CPPB, Senior Buyer at (970) 221-6816 or pjohnson@fcgov.com, prior to November 16,
2015 at 5:00 p.m.
A copy of the Bid may be obtained by downloading the RFP from the Rocky Mountain
E-Purchasing System at www.rockymountainbidsystem.com.
Special Instructions
All bids must be properly signed by an authorized representative of the company with
the legal capacity to bind the company to the agreement. Bids may be withdrawn up to
the date and hour set for closing. Once bids have been accepted by the City and
closing has occurred, failure to enter into contract or honor the purchase order will be
cause for removal of supplier's name from the City of Fort Collins' bidders list for a
period of twelve months from the date of the opening. The City may also pursue any
remedies available at law or in equity. Bid prices must be held firm for a period of forty-
five (45) days after bid openings.
Submission of a bid is deemed as acceptance of all terms, conditions and specifications
contained in the City's specifications initially provided to the bidder. Any proposed
modification must be accepted in writing by the City prior to award of the bid.
Only bids properly received by the Purchasing Office will be accepted. All bids should
Financial Services
Purchasing Division
215 N. Mason St. 2nd Floor
PO Box 580
Fort Collins, CO 80522
970.221.6775
970.221.6707
fcgov.com/purchasing
8195 Transformer, 50kVA, Pad-mounted, Single Phase Page 2 of 5
be clearly identified by the bid number and bid name contained in the bid proposal.
No proposal will be accepted from, or any purchase order awarded, to any person, firm
or corporation in default on any obligation to the City.
Bids must be furnished exclusive of any federal excise tax, wherever applicable.
Bidders must be properly licensed and secure necessary permits wherever applicable.
New Vendors:
The City requires new vendors receiving awards from the City to fill out and submit an
IRS form W-9 and to register for Direct Deposit (Electronic) payment. If needed, the W-
9 form and the Vendor Direct Deposit Authorization Form can be found on the City’s
Purchasing website at www.fcgov.com/purchasing under Vendor Reference
Documents.
The City may elect where applicable, to award bids on an individual item/group basis or
on a total bid basis, whichever is most beneficial to the City. The City reserves the right
to accept or reject any and all bids, and to waive any irregularities or informalities.
Sales prohibited/conflict of interest: no officer, employee, or member of City Council,
shall have a financial interest in the sale to the City of any real or personal property,
equipment, material, supplies or services where such officer or employee exercises
directly or indirectly any decision-making authority concerning such sale or any
supervisory authority over the services to be rendered. This rule also applies to
subcontracts with the City. Soliciting or accepting any gift, gratuity, favor,
entertainment, kickback or any items of monetary value from any person who has or is
seeking to do business with the City of Fort Collins is prohibited.
Freight terms: unless otherwise noted, all freight is F.O.B. Destination, Freight Prepaid.
All freight charges must be included in prices submitted on proposal.
Discounts: any discounts allowed for prompt payment, etc., must be reflected in bid
figures and not entered as separate pricing on the proposal form.
Purchasing restrictions: your authorized signature of this bid assures your firm's
compliance with the City's purchasing restrictions. A copy of the resolutions is available
for review in the Purchasing Office or the City Clerk's Office. Request Resolution 91-
121 for cement restrictions.
Collusive or sham bids: any bid deemed to be collusive or a sham bid will be rejected
and reported to authorities as such. Your authorized signature of this bid assures that
such bid is genuine and is not a collusive or sham bid.
Bid results will be posted online at www.rockymountainbidsystem.com.
Gerry S. Paul
Director of Purchasing and Risk Management
8195 Transformer, 50kVA, Pad-mounted, Single Phase Page 3 of 5
FIRM NAME:_____________________________
CITY OF FORT COLLINS
8195 TRANSFORMERS, 50KVA PAD-MOUNTED, SINGLE PHASE
WE HEREBY ENTER OUR BID FOR THE CITY OF FORT COLLINS'
REQUIREMENTS FOR TRANSFORMERS, 50KVA, PAD-MOUNTED, SINGLE
PHASE PER THE BID INVITATION AND ANY REFERENCED SPECIFICATIONS.
QUANTITY: DESCRIPTION:
30 ea. T1200150 TRANSFORMER, 50 KVA PAD-MOUNTED,
ANSI TYPE 1, COMPARTMENTAL TYPE, SINGLE PHASE
DISTRIBUTION WITH SEPARABLE INSULATED LOAD
BREAK HIGH VOLTAGE CONNECTORS. HIGH VOLTAGE
RATING: 13200 GRDY/7620. LOW VOLTAGE RATING:
240/120. SERIAL NUMBER 150 TO BE IN ACCORDANCE
WITH SPECIFICATION #368-120-150, REVISION GG.
Please complete the Excel spreadsheet issued separately
for bid submittal. The spreadsheet MUST be submitted
in Excel format only.
IF YOU ELECT TO PASSWORD PROTECT YOUR BID,
PLEASE NOTE THAT PASSWORD BELOW.
_______________________________
*Any surcharges or additional costs shall be noted & included in bid submittal.
The items being bid meet or exceed the specifications. _______ Yes ______No. If not,
please list exceptions (specifying paragraph reference number) on a separate sheet of
paper and submit with your bid documents.
List exceptions (specifying paragraph reference number) on a separate sheet of paper
and submit with your bid documents.
If escalation applies, the bidder shall indicate in his bid the specific items or materials
subject to escalation, and shall give the method and indices to be used in computing the
amount thereof. Escalation occurring after the quoted delivery date will not be paid
unless delays are the result of actions by the city. Escalation occurring after
acceptance, if purchaser exercises the option to delay shipment after manufacturing is
completed, will not be paid.
Delivery lead time may be a consideration of bid award.
8195 Transformer, 50kVA, Pad-mounted, Single Phase Page 4 of 5
For purposes of warranty and service ONLY approved manufacturers or distributors
authorized by an approved manufacturer to serve the Fort Collins area may bid.
Awards from this bid will be based primarily on the evaluated bid price. Delivery lead
times, escalation and exceptions taken will also be considered. The City of Fort Collins
reserves the right to split the bid award in whatever percentages are most
advantageous to the City.
Future orders of Transformers, 50kVA, Pad-Mounted, Single Phase may be
authorized, at the option of the City, from this bid for a period of five years after bid due
date. Satisfactory pricing, losses and delivery are required for future orders based on
this bid.
Pages 3 and 5 of this bid document comprise the bid submittal, along with the Excel
Spreadsheet. Failure to submit any of these in the format requested may cause the
submittal to be deemed incomplete and may be subject to rejection.
8195 Transformer, 50kVA, Pad-mounted, Single Phase Page 5 of 5
EXHIBIT A
BID ACKNOWLEDGEMENT
Contractor hereby acknowledges receipt of the City of Fort Collins Utilities’ Request for
Bids for the Transformers and acknowledges that it has read and agrees to be fully
bound by all of the terms, conditions and other provisions set forth in the Bid.
Additionally, the Contractor hereby makes the following representations to Utilities:
a. All of the statements and representations made in this bid are true to the best of
the Contractor’s knowledge and belief.
b. The Contractor has obtained all necessary authorizations and approvals that will
enable the Contractor to commit to the terms provided in this bid submittal.
c. This bid submittal is a firm and binding offer, for a period of 45 days from the date
hereof.
d. I further agree that the method of award is acceptable to my company.
e. I acknowledge receipt of addenda.
Contractor Firm Name:
Physical Address:
Remit to Address:
Phone:
Authorized Agent of Firm Name:
Signature of Authorized Agent:
Primary Contact for Project:
Title: Email Address:
Phone: Cell Phone:
THE CITY OF FORT COLLINS
Light and Power Department
P.O. Box 580
Fort Collins, CO 80522
SPECIFICATION NO: 368-120
PAD-MOUNTED COMPARTMENTAL-TYPE, SINGLE-PHASE
DISTRIBUTION TRANSFORMERS
WITH SEPARABLE INSULATED LOAD BREAK HIGH-VOLTAGE CONNECTORS
UPDATED BY:
Adam Bromley
Senior Electrical Engineer
APPROVED BY:
Kraig E. Bader
Standards Engineering Manager
ORIGINATED: 09/14/72
LAST REVISED: 2 April 2013
ITEMS COVERED BY THIS SPECIFICATION
DESCRIPTION
STOCK NO.
SPECIFICATION
NO.
SERIAL
25 KVA, 120/240 ANSI Type 1 Transformer. 368-120 -130
50 KVA, 120/240 ANSI Type 1 Transformer. 368-120 -150
100 KVA, 120/240 ANSI Type 1 Transformer. 368-120 -170
167 KVA, 120/240 ANSI Type 1 Transformer. 368-120 -180
250 KVA, 120/240 ANSI Type 1 Transformer. 368-120 -190
REV. SYM: GG
2
368-120
PREVIOUS REVISION DESCRIPTIONS ON FILE
REVISION DESCRIPTION APPROVED
REVISION DD:
Paragraph 3.2.2.7.5: Editorial
Add paragraph 3.2.2.9.4 requiring pentahead locking bolts
Paragraph 3.2.2.13 add glossy to paint requirement
Paragraph 4.2.2: Clarify impedance requirement
Sagen 10/21/94
REVISION EE:
Paragraph 5.0: revised pallet size from 28 to 34 inches
Sagen 2/25/98
REVISION FF
Added 50kVA ANSI Type 2 Transformer (368-120-155) to Specification
Changed paint color to standard Munsell Green
Reorganized to consolidate impedance and fusing requirements into one table.
Consolidated secondary terminal requirements into one table.
Added maximum impedance requirement for 250kVA transformer (+/-7.5% from nominal for
transformers with impedance greater than 2.5%) per ANSI/IEEE C57.12.00-2000.
Re-evaluated fusing requirements of all transformers in this specification. Went from dual
sensing bay-o-net (expulsion) fuses to current sensing bay-o-net (expulsion) fuses. Fuse
sizing was changed as follows:
Changed 25 kVA from 8A expulsion / 40 amp CL to 10A expulsion / 30A CL
Changed 50 kVA from 15A expulsion / 80 amp CL to 15A expulsion / 40A CL
Changed 100 kVA from 25A expulsion / 175 amp CL to 25A expulsion / 80A CL
Changed 167 kVA from 40A expulsion / 200amp CL to 40A expulsion / 125A CL
Changed 250 kVA from 65A expulsion / 350amp CL to 65A expulsion / 125A CL
Kraig Bader
7/21/2004
REVISION GG
Deleted ANSI Type 2, 50 kVA, transformers from the Specification. Fort Collins is no longer
purchasing Type 2 transformers because most maintenance situations require Type 1 bushing
heights.
Updated all references from ANSI to IEEE standards. The standards development process
utilized by IEEE is approved by ANSI, so they do not explicitly place their name on each
standard anymore.
Eliminated “Not Used” sections.
Updated references to IEEE C57.12.25, which is no longer active, to now reference IEEE
C57.12.38 and the corresponding sections and figures within the new standard.
Added IEEE C57.12.37 – Electronic Reporting of Distribution Transformer Test Data as a
reference standard. Amended section 5.1.2 to include details for the application of IEEE
C57.12.37.
Added “Operation Test” to the required design tests contained within C57.12.28 to Section
3.1.3.2.
Added section on DOE Energy Efficiency Requirements.
Amended section 3.2.2.4.3 to require that locking nuts be provided on all low-voltage line and
neutral terminals.
Adam Bromley
Kraig Bader
4/3/2013
REV. SYM: GG
3
368-120
Amended section 3.2.2.6.6 to specify a pressure relief device that includes detection and
indication of internal transformer faults. The approved device is manufactured by IFD
Corporation.
Moved and updated section on Losses (now Section 4) to include new required information
to be submitted by manufacturers during the bid process. Additional information to be
supplied includes expected winding’s stray losses and losses associated with auxiliary
devices such as fuses, breakers, switches, etc. Also updated Special Conditions and
Supplemental Instructions to Bidders with new required losses information.
Removed General Electric as an approved manufacturer and added Central Moloney to the
Conditionally Approved Manufacturers list.
Deleted Individual Transformer Loss Evaluation Form. Typically, orders include more than
one unit and the average form is used. Fort Collins Utilities has always and continues to
reserve the right to calculate losses and assess penalties individually, if favorable to Fort
Collins Utilities.
Added Special Conditions and Supplemental Instructions to Bidders to the end of this
specification. Previously, this had been submitted to Bidders separately. This merge helps to
maintain consistency among transformer specifications.
REV. SYM: GG
4
368-120
TABLE OF CONTENTS
PREVIOUS REVISION DESCRIPTIONS ON FILE ................................................................................................................ 2
1 SCOPE .................................................................................................................................................................................
5
2 APPLICABLE DOCUMENTS .............................................................................................................................................. 5
3 REQUIREMENTS ................................................................................................................................................................ 5
3.1 GENERAL REQUIREMENTS FOR DESIGN ................................................................................................................. 5
3.2 SPECIFIC DESIGN REQUIREMENTS .......................................................................................................................... 6
4 LOSSES ...............................................................................................................................................................................
9
5 QUALITY ASSURANCE .................................................................................................................................................... 10
5.1 GENERAL .................................................................................................................................................................... 10
5.2 TEST CONDITIONS .................................................................................................................................................... 10
5.3 TESTS ......................................................................................................................................................................... 10
6 PREPARATION FOR DELIVERY ..................................................................................................................................... 11
7 DEFINITIONS AND ABBREVIATIONS ............................................................................................................................. 11
APPENDIX A – TRANSFORMER STOCK NUMBER CODING .......................................................................................... 12
APPENDIX B – DIMENSIONAL DRAWINGS ...................................................................................................................... 13
APPENDIX C – APPROVED MANUFACTURERS .............................................................................................................. 15
TRANSFORMER LOSS EVALUATION - AVERAGE LOSSES .......................................................................................... 16
SPECIAL CONDITIONS AND SUPPLEMENTAL INSTRUCTIONS TO BIDDERS APPLICABLE TO SPECIFICATION
368-120 .................................................................................................................................................................................
17
1 SC
T
di
13
fo
T
tra
2 AP
T
do
3 RE
3.1
COPE
his Specificat
ielectric fluid-
3,200 Grd Y/7
or step down p
his standard g
ansformers, C
PPLICABLE
he following d
ocument is no
IEEE C
Transf
IEEE C
IEEE C
IEEE C
Voltag
IEEE
Transf
IEEE C
IEEE C
IEEE C
IEEE 3
EQUIREMEN
GENERAL R
3.1.1 BASIC
Trans
requir
parag
a)
b)
3.1.2 KILOV
Kilovo
tempe
65°C
The tr
3.1.3 GENE
3.1.3.
cable
termin
WITH SE
tion establishe
immersed, se
7620 volts, w
purposes from
generally con
C57.12.38.
DOCUMEN
documents fo
REV. SYM: GG
6
368-120
mounting on a pad. There shall be no exposed screws, bolts, or other fastening devices which are externally
removable. The cover shall be welded construction. There shall be no opening through which foreign objects
such as sticks, rods, or wires might be inserted to contact live parts. Suitable means for padlocking the
compartment door(s) shall be provided.
3.1.3.2 In addition to the enclosure security design tests listed in Section 4.3.1 of IEEE C57.12.28, the
manufacturer shall perform an “Operation test”. The unit shall be lifted, utilizing provided lifting lugs, at least
one meter in accordance with the manufacturer’s standard lift instructions and then set again on a flat surface.
The doors shall be easily opened, closed, latched and locked without requiring adjustments to the cabinet,
latch mechanism and/or enclosure door(s). All of the door latch points must fully engage when the door is
closed.
3.1.3.3 The high- and low-voltage compartment shall be located side by side on one side of the transformer
tank. When facing the compartment, the low-voltage side shall be on the right.
3.1.3.4 Construction of the unit shall be such that it can be lifted, skidded, and slid into place on the mounting
pad without disturbing the entrance cables.
3.1.3.5 An undercoating over the regular finish or an equivalent treatment shall be applied to all surfaces that
are in contact with the pad to minimize corrosion.
3.1.3.6 Minimum dimensions for Type 1 transformers shall be as shown in Figure 1, Appendix B.
3.1.4 ENERGY EFFICIENCY
Transformers shall be designed to meet the minimum energy efficiency ratings defined in the United States
Department of Energy October 12, 2007 Final Rule: 10 CFR Part 31, Energy Conservation Program for
Commercial Equipment: Distribution Transformers Energy Conservation Standards.
3.2 SPECIFIC DESIGN REQUIREMENTS
3.2.1 FUNCTIONAL DESCRIPTION
The transformer shall be a single phase, pad mounted, loop feed-safe break, "dead-front" type for use on a
13.8 kV grounded "Y" distribution system.
3.2.2 DESIGN AND CONSTRUCTION
3.2.2.1 RATING
The transformer shall be rated as follows:
a) High Voltage 13,200 Grd Y/7620 volts
b) Low Voltage 240/120
c) Taps Two - 2½% FC above and below normal
d) Polarity Additive
e) Capacity, Impedance values, and fusing for transformers in this specification shall conform to
Table 1.
3.2.2.2 OVERCURRENT PROTECTION
An RTE / Cooper Power Systems BAY-O-NET current sensing fuse and internally mounted partial range
current limiting fuse shall be furnished as shown in Table 1.
REV. SYM: GG
7
368-120
Table 1 – Transformer Capacity, Impedance and Fuse Selection
Stock
Number
kVA
Capacity
Min.
Impedance
Max.
Impedance
Bay-O-Net
Fuse1,2
Current Limiting
Fuse(s)2
368-120-130 25 1.77% 2.16% 10 Amp
4000353C06
ELSP 3544030M61M (30 A)
368-120-150 50 1.77% 2.16% 15 Amp
4000353C08
ELSP 3543040M61M (40 A)
368-120-155 50 1.77% 2.16% 15 Amp
4000353C08
ELSP 3543040M61M (40 A)
368-120-170 100 1.95% 2.38% 25 Amp
4000353C10
ELSP 3543080M71M (80 A)
368-120-180 167 2.28% 2.79% 40 Amp
4000353C12
ELSP 3543125M71M (125 A)
368-120-190 250 5.75% 6.61% 65 Amp
4000353C14
ELSP 3543125M71M (125 A)
1 The BAY-O-NET fuse shall be located in the high voltage side of the compartment.
2 The approved manufacturer for the fuses is Cooper Power Systems. Other fuses meeting the
requirements defined in this specification shall be specifically approved in writing by Fort Collins Utilities
Engineering Standards Division
3.2.2.3 INSULATION LEVEL
3.2.2.3.1 The basic impulse insulation level (BIL) of completely assembled high-voltage and low-voltage
terminals shall be 95 kV and 30 kV respectively.
3.2.2.3.2 Dielectric test levels shall be in accordance with the distribution levels in Section 4 of ANSI
C57.12.00.
3.2.2.4 HIGH-VOLTAGE TAPS
A no-load tap changer with external operating handle shall provide two - 2½% full capacity taps above and
below normal. The tap changer operating handle shall be located within the high-voltage terminal side of the
terminal compartment.
3.2.2.5 BUSHING WELLS AND TERMINALS
3.2.2.5.1 The number, location, and arrangement of bushing wells, terminals and parking stands shall be
as shown in Fig. 1 in Appendix B. All low-voltage bushings and high-voltage wells shall be externally
clamped and shall have leads of sufficient length to allow them to be changed without removing the
cover. Welded bushings and wells are expressly prohibited.
3.2.2.5.2 High-voltage bushing wells shall be 200 A load-break interface 8.3/14.4 kV bushings in
accordance with IEEE 386. Two wells shall be provided and shall be connected in a feed-through
configuration. Loadbreak bushing inserts in accordance with IEEE 386 will be purchaser furnished.
3.2.2.5.3 Low-voltage line and neutral terminals shall be sized as shown in Table 2 in accordance with
IEEE C57.12.38. Bushing arrangement and spacing shall be as shown in Fig. 1 in Appendix B. All low-
voltage line and neutral terminals shall be equipped with locking nuts.
Table 2 – Low Voltage Terminal Sizes
3.2.2.5.4 The low-voltage X2 bushing shall be a fully insulated bushing. A ground pad shall be provided
REV. SYM: GG
8
368-120
3.2.2.5.5 The high-voltage neutral shall be securely grounded internally.
3.2.2.6 ACCESSORY CABINET
3.2.2.6.1 The accessory cabinet shall consist of a compartment containing high- and low-voltage bushings
constructed in accordance with applicable IEEE specifications, including IEEE C57.12.28. Dimensions
shall be in accordance with Fig. 1 of this specification.
3.2.2.6.2 Cabinet doors shall be hinged, removable, lockable, and of sufficient size to provide adequate
working space when removed or open. Unlocking the padlock shall permit access to both the high- and
low-voltage terminations. Stainless steel hinge pins shall be provided.
3.2.2.7 ACCESSORY EQUIPMENT
Accessory equipment shall be provided in accordance with the following details:
3.2.2.7.1 The transformer base shall be arranged for rolling in two directions: Parallel to and at right
angles to the center line of the high-voltage bushings.
3.2.2.7.2 Lifting lugs or bosses for screw-in lift bolts shall be provided. These lugs or bosses shall be
adequate strength and size and arranged on the tank to provide a suitable balanced lift for the completely
assembled unit.
3.2.2.7.3 The base of the assembly shall be provided with suitable means for mounting the unit on the
pad. An internal flange shall be provided at the base of the accessory compartment to provide means for
mounting the unit on the pad. (Fig. 1, Appendix B).
3.2.2.7.4 Terminal designations are shown in Figure 1, Appendix B. The identification of terminal
connections shall be shown on the instruction nameplate. Instruction nameplate shall be located in the
low-voltage side and shall be readable with cables in place. Where the nameplate is mounted on a
removable part, the manufacturer's name and transformer serial number shall be permanently affixed to a
non-removable part.
Instruction nameplate shall contain the information specified in 5.12 of IEEE C57.12.00-2010. Also, on
the nameplate, or label affixed near it, the manufacturer shall indicate that the dielectric fluid contains less
than 1 ppm PCB.
3.2.2.7.5 A suitable marking inside of the tank shall indicate the correct oil level at 25°C.
3.2.2.7.6 A non-resettable device which detects and provides external indication of internal transformer
faults, as well as incorporating automatic pressure relief functionality shall be provided. The pressure
relief device shall meet the following requirements:
¼" NPT or larger male Inlet Port.
Exposed parts of weather and corrosion resistant materials.
Non-deteriorating gasket and o-ring material.
Manual pull ring able to withstand a static force of 25 pounds for 1 minute without permanent
deformation. The valve shall also withstand for 1 minute a static force of 100 lbf applied normal to its
longitudinal axis at the outermost extremity of the body.
Bug shield to prevent entry of dust, moisture, and insects before and after the valve has operated.
Cracking pressure of 10 ± 2 psig.
Resealing pressure of 8 ± 2 psig.
Zero leakage from resealing pressure to -8 psig.
Minimum flow rate of 35 SCFM at 15 psig.
The approved manufacturer for this device is IFD Corporation. Other devices meeting the requirements
defined in this specification shall be specifically approved in writing by Fort Collins Utilities Engineering
Standards Division.
4 LO
The t
tests
dupli
Supp
rates
addit
spec
and t
Exce
Loss
be gi
If any
witho
equa
Exce
(Load
3.2.2.
Trans
the ta
will re
3.2.2.
The ta
minim
parag
3
3
7/
3
on
co
3
3.2.2.
The m
ampe
3.2.2.
The a
3.2.2.
The b
dimen
3.2.2.
EEI "F
3.2.2.
NEMA
labels
OSSES
total losses o
shall be perf
cate units. Lo
plemental Inst
s. If tested los
tional cost inc
ified rates an
the following
ess loss $ = [N
Evaluation $
ven the Supp
y unit or units
out express pe
ation:
Quot
All qu
witho
Collin
5 QU
5.1
5.2 T
U
5.3 T
T
a
ted losses sub
No load lo
Full load l
losses ass
Winding’s
Losses as
uoted loss va
out the require
ns.
UALITY ASS
GENERAL
5.1.1 RESP
Unles
specif
labora
of the
5.1.2 TEST
The m
data a
cover
The e
4.2 an
as sp
Sectio
addre
TEST CONDIT
Unless otherw
5.2.1 REFE
The re
85°C.
5.2.2 TOLER
Imped
5.2.3 TOLER
The p
voltag
TESTS
The kinds of t
and C57.12.9
5.3.1 DIELE
No ap
termin
1000
bmitted by ma
osses
osses – it sha
6 PR
Trans
Units
Units
acco
trans
weig
or mo
7 DE
Vend
Artic
5.3.2 IMPED
Imped
tests
REPARATIO
sformers sha
s shall be pac
s shall be fully
mmodate min
sformer. The S
hs over 5,000
odifications s
EFINITIONS
dor or Suppli
cle, Unit, Ass
DC or d.c.
AC or a.c.
°C - Degre
°F - Degree
kV - 1000 v
CPS or Hz
psig - Pou
V or v - Vo
KVA - 100
DANCE AND
dance and loa
made on a du
ON FOR DEL
ll be prefilled
ckaged in suc
y palletized on
nimum fork sp
Supplier shall
0 pounds. In
hown on the
AND ABBR
er - The man
embly - All re
- Direct Curre
- Alternating
ee Celsius (Ce
REV. SYM: GG
12
368-120
APPENDIX A – Transformer Stock Number Coding
Below are examples that demonstrate the coding method used by City of Fort Collins to establish
transformer stock numbers.
I. SINGLE PHASE
Example #1: 368 - 1 BC - X Y Z
II. THREE PHASE
Example #2 368 - 300 - XYZ
Other
KVA
0 = 5 5 = 50
1 = 10 6 = 75
2 = 15 7 = 100
3 = 25 8 = 167
4 = 37.5 9 = 250
1 = single voltage
2 = dual voltage
Transformer
00 = 13.2Y/7620 &
7620/13.2Y x
2400/4160 outside
pole
05 = 13.2Y7620 ESNA pole
20 = 13.2Y/7620 ESNA pad
Single Phase
Transformer
3 Phase
Pad
KVA
006 = 75 075 = 750
015 = 150 100 = 1000
030 = 300 150 = 1500
050 = 500
All suffixes indicate 208Y/120 sec.
For 480Y/277 sec., add 1 to XYZ
(ie. 007 would indicate a 75kVA with
480Y/277 sec.)
REV. SYM: GG
13
368-120
APPENDIX B – DIMENSIONAL DRAWINGS
Figure 1 – Type 1 Transformer Dimensions and bushing Designations (not to scale)
REV. SYM: GG
14
368-120
Pad Dimensions
This drawing is not intended to dictate requirements for items purchased under Specification 368-120 but is included as
an aid to those users desiring a minimum of pad designs for the transformers covered by Specification 368-120.
The dimensions in inches of Figure 2 will fit the minimum compartments on transformers covered by this Specification as
well as the maximum transformer envelope.
Figure 2 – Pad Dimensions
3"
3" 3"
LENGTH AND WIDTH
FOUR #3 REBAR
3"
3"
FRONT
12" PRIMARY SECONDARY
12"
4 1/2"
18"
48"
48"
7 1/2"
Notes on Pad Material -
1. Concrete must be 3,000 psi minimum.
2. Maximum coarse aggregate size 1 1/2 inches.
Space requirements for pad and primary switching cabinet will generally
be 9' X 12'. Factors to be considered in locating the pad include -
1. Accessibility - The transformer pad shall be accessible to
line boom trucks equipped for the installation and removal of
heavy transformers. Such accessibility shall not require
intrusion on adjacent property.
2. Proximity of Buildings, Walls, Barriers, and/or Overhangs -
In addition to the clearances required for installation and
removal, the minimum clearance in front of the transformer pad
shall be eight (8) feet and the minimum clearance from all
other sides shall be two (2) feet. If the building has an
overhang, clearance to the edge of the transformer pad shall
be measured horizontally from the outer edge of the overhang.
Transformers through 300 KVA may be installed under the
overhang if the vertical clearance between the pad and the
overhang is at least 25 feet and the location is accessible to
line boom trucks.
3. Codes and Standards - In addition to the above, the
installation shall conform to the National Electric Code and
federal, state and city codes and standards.
2"
15" 6" 15"
REV. SYM: GG
15
368-120
APPENDIX C – Approved Manufacturers
Transformers purchased under this Specification shall be of the make shown below. Manufacturers not listed below may
submit written proposals demonstrating compliance with these Specifications for consideration of addition to the accepted
manufacturers list prior to the next request for bids. In addition to inclusion on the list below, manufacturer's equipment
must also satisfy all requirements of this Specification to be acceptable. Approved manufacturers must have constructed
and submitted prototype units for inspection and deemed satisfactory by the Fort Collins Utilities Electric Department.
APPROVED MANUFACTURERS
ABB
Cooper Power Systems
Howard Industries
The manufacturers in the following list have been conditionally approved and may bid as an alternate. The definition and
intent of "Conditional Approval" of a manufacturer is to allow the City to gain some experience with the manufacturer's
product. In order to be added to the Conditionally Approved List, the manufacturer shall submit drawings demonstrating
that their design meets technical and dimensional requirements contained within this Specification. Should a conditionally
approved manufacturer be the evaluated low bidder, the City reserves the right to award all, part, or none of the order to
them, dependant upon the current needs of the City for that item or items.
CONDITIONALLY APPROVED MANUFACTURERS
Central Moloney
REV. SYM: GG
16
368-120
TRANSFORMER LOSS EVALUATION - AVERAGE LOSSES
City Order No. __________________________ S/N __________________________________
Manufacturer ___________________________ Invoice No. __________________________
KVA/Unit _____________________________
LINE
DESCRIPTION AMOUNT
(1) No. of units
________
(2) Average core losses
________
(3) Quoted core losses
________
(4) Excess average core losses:
line (2) less line (3)
________
(5) Penalty for excess average core losses:
line (1) x line (4) x $____________
________
(6) Average copper losses
________
(7) Quoted copper losses
________
(8) Excess average copper losses:
line (6) less line (7)
________
(9) Penalty for excess average copper losses:
line (1) x line (8) x $_______________
________
(10) Penalty to be assessed manufacturer:
line (5) plus line (9) but not less
than zero
________
Date ______________________________ Prepared By: _____________________________
Design Engineering
NOTE: If any unit(s) exceeds the loss tolerances of IEEE C57.12.00, Utilities Electric Department will (1) either reject it, (2)
include it on these averages, or (3) calculate losses and assess penalties individually, whichever is most favorable to
Utilities Electric Department.
REV. SYM: GG
17
368-120
Special Conditions and Supplemental Instructions to Bidders Applicable to
Specification 368-120
A. Data to be supplied with Bidder's Proposal
The following data shall be supplied with the bidder's proposal in addition to that information required by the "Invitation
to Bid" and the "Purchase Requisition".
1. Impedance volts in percent (%) at full load, high voltage to low voltage at 85°C
2. No load losses, full load losses, total losses, expected winding’s stray losses, auxiliary devices’ losses all
corrected to a reference of 85°C. Please see Section 4 – Losses for more information.
3. Delivery in weeks
4. A statement indicating compliance with our Specification with exception or a detailed list of exceptions.
5. Escalation IS ______ / IS NOT ______ applicable for the transformers bid. If escalation applies, the Bidder
shall indicate in his bid, the specific items or materials subject to escalation and shall provide the method and
indices to be used in computing the amount thereof. Escalation occurring after acceptance, if Purchaser
exercises the option to delay shipment after manufacturing is completed, will not be paid.
If the above information and compliance statement are not supplied the proposal will not be evaluated.
An alternate bid for the total order may be submitted in addition to the unit bids.
B. Loss Evaluations
Loss penalties and loss evaluations will be based on the following values:
1. No-load or excitation losses at $3.90/watt
2. Load losses at $1.50/watt
C. Shipping Terms
Ship F.O.B. point of destination, freight prepaid.
D. Terms of Payment
1. If escalation applies, the City of Fort Collins shall not be billed for escalation occurring after the promised
delivery date.
2. Electronic test reports as describe in Section 5.1.2 sent via E-mail shall accompany the invoice sent to the
Material Control Section. If test reports do not accompany the invoice, late payment penalty charges incurred
due to delays in obtaining the test reports will not be paid. Electronic test reports shall also be sent via E-mail to
Engineering Standards Division, Fort Collins Utilities - Light & Power.
3. Loss penalty credits and escalation charges shall be itemized on the invoice.
e Fahrenheit
volts.
z - Cycles per
nds per squa
olts.
0 Volt-ampere
LOAD-LOSS
ad-loss tests s
uplicate unit is
LIVERY
with the appr
h a way as to
n two-way pa
pacing) and lo
l give 24 hour
addition to th
purchase ord
REVIATIONS
ufacturer and
efer to the equ
ent.
Current.
entigrade)
second.
re inch gauge
es.
TESTS
shall be made
s available.
ropriate amou
o provide for e
llets or four-w
oaded on the
r notice prior t
ese requirem
er and/or sup
S
/or manufactu
uipment define
e.
e on each un
unt of transfor
ease of handl
way universal
truck for side
to delivery for
ments, the Sup
pplemental ins
urer's agent su
ed by this Spe
it and may no
rmer oil and s
ing and to pro
pallets with 3
e removal. Pa
r any shipme
pplier shall co
structions.
upplying or qu
ecification.
ot be omitted
shall be shipp
otect units fro
30” minimum
allets shall be
nts where an
omply with an
uoting on the
RE
11
368-
even if a reco
ped by open-b
om shipping d
openings (to
e independent
individual tra
ny additional r
specified artic
EV. SYM: GG
1
120
ord of such
bed truck.
damage.
t of the
ansformer
requirements
cle.
G
sociated with
s expected str
ssociated with
lues shall be
ed losses info
SURANCE
ONSIBILITY
ss otherwise s
fied herein. E
atory accepta
e inspections s
REPORT
manufacturer
as specified in
r letter. The m
electronic repo
nd 4.3, respec
ecified in sec
on along with
esses shall be
TIONS
wise specified
RENCE TEM
eference tem
RANCE ON IM
dance on com
RANCE ON IM
percent depar
ge shall not be
ests to be pe
0 except as s
ECTRIC TEST
pplied potentia
nals of one w
volts plus 3.4
anufacturers
all be clearly
auxiliary dev
ray losses rela
h auxiliary dev
corrected to a
ormation shal
FOR INSPEC
specified, the
Except as oth
able to the City
set forth in th
shall furnish t
n IEEE C57.1
manufacturer’
orts shall inclu
ctively, of IEE
tion 5.3 of IEE
the invoice, a
e provided to
d, testing requ
PERATURE
perature to w
MPEDANCE
mpleted units
MPEDANCE
rture of tested
e greater than
rformed and t
specified here
TS
al test shall b
inding a volta
46 times the ra
shall include
stated whethe
vices
ated to quote
vices such as
a reference te
l be deemed
CTION
vendor is res
erwise specif
y of Fort Colli
is Specificatio
to the purcha
2.37. Unsign
s Quality Con
ude the stand
EE C57.12.37
EE C57.12.37
and to the En
manufacturer
uired by Sectio
which losses, i
VOLTAGE
shall fall with
VOLTAGE O
d impedance v
n the total tap
the test proce
ein.
e made. The
age which will
ated transform
the following:
er this numbe
d transforme
s fuses, break
emperature o
unresponsive
sponsible for t
fied, the vend
ins Utilities. T
on where suc
ser, prior to p
ed copies are
ntrol Manager
dard data set
7-2006. These
7-2006. Thes
gineering Sta
r upon award
on 5.4 shall b
impedance, r
in the range s
N A TAP
voltage on an
p voltage rang
edures shall b
e induced-pot
develop from
mer winding v
:
er includes th
r design
kers, switches
of 85˚C. Quota
e and are sub
the performan
dor may utilize
The City rese
ch inspections
payment, elec
e not accepta
r shall review
and the exten
e reports shal
se reports sha
andards Divis
of bid.
be conducted
regulation, an
specified here
ny tap from te
ge expressed
be as specifie
tential test sha
m high-voltage
voltage.
e winding’s e
s, etc.
ations submit
bject to rejecti
nce of all insp
e his own faci
erves the right
s are deemed
ctronic reports
able even if ac
w and approve
nded data set
ll be formatted
all be sent to t
sion via Electr
under the fol
d efficiency a
ein.
sted impedan
as a percent
ed in IEEE C5
all be made b
e line termina
RE
10
368-
expected stray
tted during the
on by the City
pection requir
ilities or any c
t to perform o
d necessary.
s including tra
ccompanied b
e each test rep
t as specified
d in a comma
the Material C
ronic Mail (E-
lowing condit
are corrected
nce voltage a
tage of the ra
57.12.20, ANS
by applying be
als to ground a
EV. SYM: GG
0
120
y losses and
e bid process
y of Fort
rements as
commercial
or witness any
ansformer tes
by a signed
port.
d in sections
a delimited file
Control
mail). E-mail
tions:
shall be
t rated
ted voltage.
SI C57.12.00,
etween the
a voltage of
G
s
y
st
e
ess loss $ = (N
d Loss Evalua
8 OIL PRES
sformers shall
ank from the a
emain effectiv
9 TANKS
ank shall be d
mum of 500 lb
graphs 6.1 and
.2.2.9.1 The c
.2.2.9.2 Tank
/16 inch deep
.2.2.9.3 These
ne in the high
ompartments
.2.2.9.4 Locki
10 COMPON
minimum curre
eres (continuo
11 AUDIBLE
audible sound
12 BASE PL
base plan of a
nsions shown
13 PAINT
Finishing Guid
14 SAFETY
A 1260 Safety
s after delivery
f a transforme
formed and re
oss evaluatio
tructions to B
sses exceed q
curred from th
d will be dedu
equation “Un
No. of units] [(
$) (Avg. Load
plier.
s exceed the t
ermission fro
No Load Loss
ation $) (Load
ERVATION
l be of sealed
atmosphere, a
ely sealed for
domed or slop
s. vertical loa
d 6.6.
cover shall be
grounding pr
p.
e ground pad
h-voltage side
are separate
ng bolts shall
NENTS FOR
ent-carrying c
ous) and 10,0
E SOUND LEV
level shall be
LAN
a completely a
in Fig. 1B.
delines" spec
LABELS
y Labels shal
y.
er shall be the
eported on all
ons and loss c
idders.” Tran
quoted losses
he differential
ucted from the
its” shall mea
(No Load Los
Losses – Quo
tolerances of
m the City. If
s Evaluation $
d Losses – Q
d-tank constru
and in which t
r a top-oil tem
ped to shed w
ad. Construct
e welded cons
rovision shall
ds shall be we
e and one in th
e, provisions s
l be pentahea
LOOPED PR
capability of c
00 amperes s
VEL
e in accordan
assembled un
cification shall
l not be applie
e sum of the e
units regardl
costs will be b
nsformers will
s but are with
of losses will
e original Pur
an “Transform
ss Evaluation
oted Load Lo
paragraph 9.
f accepted, th
$) (No Load L
uoted Losses
uction. Seale
the gas plus t
mperature ran
water. The ta
tion of the tan
struction.
consist of two
elded on the tr
he low-voltag
shall be made
ad.
RIMARY
components fo
symmetrical (
nce with NEM
nit shall be su
l apply. Finis
ed by the ma
excitation los
ess of whethe
based on the v
be evaluated
hin the toleran
be calculated
rchase Order
mers of the sam
$) (Avg. No L
osses)]. If this
3, IEEE C57.
he deduction f
Losses – Quot
s) But Not Les
d-tank constr
the oil volume
ge of -5°C to
ank shall be o
nk shall be in
o steel pads,
ransformer ba
ge side. In ca
e for electrica
or the looped
(momentary).
A Standard T
uch that it can
h coat shall b
nufacturer; P
ses and the l
er or not a re
values shown
d on excitatio
nces of parag
d using the fo
or back char
me size and d
Load Losses
s equation res
.12.00-2010,
for excess los
ted No Load
ss Than Zero
ruction is that
e remains con
105°C.
of sufficient st
accordance w
each with ½
ase or on the
ases where th
ally connecting
primary cabl
TR1-1980.
n be installed
be Munsell Gr
urchaser will
oad losses (I2
cord of such
n in the “Spec
n losses and
raph 9.3, IEE
ollowing equa
rged to the ma
design on one
– Quoted No
sults in a neg
that unit or un
sses will be b
Losses) But N
.
RE
9
368-
which seals
nstant. The tr
trength to sup
with ANSI C5
inch - 13 NC
e tank wall nea
he transforme
g them.
e system sha
on a pad of th
reen, glossy.
apply custom
2R losses). L
tests is availa
cial Condition
I2R losses at
EE C57.12.00
ation and the a
anufacturer.
e order.”
Load Losses
ative number
nits shall not
ased on the f
Not Less Tha
EV. SYM: GG
9
120
the interior of
ransformer
pport a
7.12.25-1981
tapped hole,
ar the base,
r tank and
all be 200
he
m warning
Load loss
able on
s and
t the specified
-2010, the
above
In Table 18
s) + (Load
r no credit wil
be shipped
following
an Zero +
G
f
,
d
l
on the outer surface of the tank and an external removable copper ground strap shall be provided and
connected between the low-voltage X2 bushing and the ground pad.
Stock Number kVA Capacity Low voltage Terminal Size
368-120-130 25 5/8" x 11” UNC-2A copper studs
368-120-150 50 5/8" x 11” UNC-2A copper studs
368-120-170 100 1” x 14” UNC-2A copper studs
368-120-180 167 1" x 14” UNC - 2A copper studs
368-120-190 250 1¼" x 12 UNF - 2A copper studs.
ot dated, the
C57.12.00 – S
formers
C57.12.28 – S
C57.12.37 – S
C57.12.38 – S
e, 34 500 Grd
C57.12.70 –
formers
C57.12.80 – S
C57.12.90 – S
C57.91 – Guid
386 – Separab
NTS
REQUIREMEN
C DESIGN ST
sformers purc
rements of the
graphs. In cas
) This Specifi
) Applicable I
VOLT-AMPER
olt-ampere rat
erature or an
when measu
ransformers s
ERAL CONST
1 The pad-m
terminating c
nating compa
PA
SINGLE
PARABLE IN
es the minimu
elf-cooled, pa
ith separable
m an undergro
nforms to IEE
NTS
orm a part of t
latest issue in
Standard for G
Standard for P
Standard for th
Standard for
dY/19 920 V a
Standard fo
Standard Term
Standard Test
de for Loading
ble Insulated
NTS FOR DES
TANDARDS
hased under
e applicable I
se of conflict,
ication
IEEE Standar
RE TEMPERA
tings are cont
80°C hot spo
red near the t
shall be desig
RUCTION
mounted-type
compartment
artment and ta
SPEC
D-MOUNTED
E-PHASE DIS
NSULATED L
um electrical
d-mounted di
insulated loa
ound primary
E requiremen
his Specificat
n effect on the
General Requ
Pad-Mounted
he Electronic
Pad-Mounted
and Below, Lo
or Standard T
minology for P
t Code for Liqu
g Mineral-Oil-I
Connectors fo
SIGN
these Specifi
EEE Standar
the requirem
rds
ATURE RATIN
tinuous and a
ot temperature
top of the tan
gned for overlo
transformers
constructed i
ank shall be a
CIFICATION
D COMPARTM
STRIBUTION
LOAD BREAK
requirements
istribution tran
ad break high
y cable supply
nts for pad-mo
tion to the ext
e date of invit
uirements for
Equipment –
Reporting of D
d-Type, Self-C
ow Voltage, 24
Terminal Mar
Power and Dis
uid-Immersed
Immersed Tra
or Power Distr
ications shall
rds and the m
ments of the fo
NGS
are based on
e rise. The te
nk. The tempe
oads based o
shall consist
n accordance
assembled as
FOR
MENTAL-TYP
TRANSFOR
K HIGH-VOLT
s and mechan
nsformers rat
voltage conn
y.
ounted-type,
tent specified
tation for bids
Liquid-Immer
Enclosure Int
Distribution Tr
Cooled, Single
40/120 V; 167
rkings and C
stribution Tran
d Distribution,
ansformers an
ribution Syste
be new and,
modifications a
ollowing docu
not exceedin
emperature ris
erature rise is
on IEEE C57.
t of a transform
e with IEEE C
s an integral u
PE
RMERS
TAGE CONN
nical features
ted 250 KVA
nectors. Thes
self-cooled, s
d herein. In th
s shall form a
rsed Distribut
tegrity
ransformer Te
e-Phase Distr
7 kVA and Sm
Connections f
nsformers
Power, and R
nd Step-Volta
ems above 60
unless otherw
and additions
uments shall a
ng either a 65°
se of the insu
s based on an
91.
mer tank and
C57.12.28 and
unit, tamperpr
RE
5
368-
ECTORS
of single pha
and smaller,
se transforme
single-phase,
hose cases w
part of this S
ion, Power, a
est Data
ribution Trans
maller
for Distributio
Regulating Tra
ge Regulators
00 V
wise specified
s given in the
apply in the p
°C average w
ulating oil sha
n altitude of 3
d a high and lo
d C57.12.38.
roof and weat
EV. SYM: GG