Loading...
HomeMy WebLinkAboutBID - 8110 TRANSFORMERS 3-PHASE PAD-MOUNTED 150, 500 & 750 KVA (3)Addendum 2 - TRANSFORMERS, PAD-MOUNTED, 3 PHASE: 150, 500 and 750KVA Page 1 of 1 ADDENDUM NO. 2 SPECIFICATIONS AND CONTRACT DOCUMENTS Description of BID 8110: TRANSFORMERS, PAD-MOUNTED, 3 PHASE: 150, 500 and 750KVA OPENING DATE: 3:00 PM (Our Clock) May 1, 2015 To all prospective bidders under the specifications and contract documents described above, the following changes/additions are hereby made and detailed in the following sections of this addendum: QUESTION & ANSWER Q1. Received your addendum for the bid on the 150, 500, and 750kVA to use 1.9 impedance per the spec. This works for the 150KVA but it is too low for units over 150kva. It is best to have an impedance range. For the 500 and 750 may we use the range in Table 1 of your spec instead of 1.9? 500kVA 2.81% - 3.27% 750kVA 5.32% - 6.18% A1. Please reference Table 1 in Material Specification 368-300 for acceptable impedance ranges for each size of transformer. Please contact Pat Johnson, CPPB, Senior Buyer at (970) 221-6816 with any questions regarding this addendum. RECEIPT OF THIS ADDENDUM MUST BE ACKNOWLEDGED BY A WRITTEN STATEMENT ENCLOSED WITH THE BID/QUOTE STATING THAT THIS ADDENDUM HAS BEEN RECEIVED. Financial Services Purchasing Division 215 N. Mason St. 2nd Floor PO Box 580 Fort Collins, CO 80522 970.221.6775 970.221.6707 fcgov.com/purchasing