HomeMy WebLinkAboutAddenda - RFP - 8898 TRANSFORT NATURAL GAS COMPRESSORAddendum 1 – 8898 Transfort Natural Gas Compressor Page 1 of 2
ADDENDUM NO. 1
SPECIFICATIONS AND CONTRACT DOCUMENTS
Description of RFP 8898: Transfort Natural Gas Compressor
OPENING DATE: 3:00 PM (Our Clock) May 9, 2019
To all prospective bidders under the specifications and contract documents described above, the
following changes/additions are hereby made and detailed in the following sections of this
addendum:
Exhibit 1 – Questions & Answers
Please contact Doug Clapp, CPPB, Senior Buyer, at (970) 221-6776 or dclapp@fcgov.com with
any questions regarding this addendum.
RECEIPT OF THIS ADDENDUM MUST BE ACKNOWLEDGED BY A WRITTEN STATEMENT
ENCLOSED WITH THE BID/QUOTE STATING THAT THIS ADDENDUM HAS BEEN
RECEIVED.
Financial Services
Purchasing Division
215 N. Mason St. 2nd Floor
PO Box 580
Fort Collins, CO 80522
970.221.6775
970.221.6707
fcgov.com/purchasing
Addendum 1 – 8898 Transfort Natural Gas Compressor Page 2 of 2
Exhibit 1
Questions & Answers
Q1. Please provide the number and size of conduits between utility transformer and
CT cabinet.
A1: There are 2 3” conduits.
Q2: What conductors are in the above conduits (quantity and sizes)?
A2: Conduit 1- 4 500MCM CU
conduit 2- 4 1/0 CU
Q3: What is the max available service from the current 300Kva transformer?
A3: The transformer can handle an 800amp service.
Q4: What will be the required minimum setbacks around the transformer?
A4: Please refer to City Building and City Utilities requirements.
Q5: What will be the required setbacks around the new service?
A5: Please refer to City Utilities requirements.