HomeMy WebLinkAboutPROSPECT AND COLLEGE HOTEL - PDP190014 - SUBMITTAL DOCUMENTS - ROUND 2 - SUPPORTING DOCUMENTATIONPreliminary Water Report for Prospect and College Hotel Fort Collins, CO Prepared For Saunders Commercial Development Company 1705 17th Street, Suite 350 Denver, CO, 80202 2/26/2020 Project No. 18111 February 26, 2020 Project No. 18111 PRELIMINARY WATER REPORT FOR PROSPECT AND COLLEGE HOTEL A PORTION OF LOT 2 OF FOX SHOPPING CENTER SUBDIVISION FORT COLLINS, COLORADO OVERVIEW NARRATIVE The proposed College and Prospect Hotel is located on a Portion of Lot 2 of Fox Shopping Center Subdivision. The site has a net area of approximately 2.0083 acres and is located within the city limits of Fort Collins. The proposed project will consist of a new 6-story hotel building with approximately 83,356 square- feet of gross floor area and supporting utilities consisting of storm sewer, sanitary sewer and waterline improvements. Surface improvements include a new paved parking lot, landscaped areas and concrete sidewalk surrounding the buildings. Part of the City of Fort Collins required improvements will include the extension of utility services from existing sewer, water, and storm drain that are not located within the boundary of Lot 2. The purpose of this report is to verify that the existing off-site 6-inch cast iron water main adjacent to- and west of the subject property is sufficiently sized to deliver adequate fire flow to the proposed building on Lot 2. 1. Existing and Proposed Water System The existing water line to be analyzed is a 6-inch cast iron main installed in 1969. This main connects to a newly installed 8-Inch PVC main in the adjacent property to the south and connects to an 8-inch main across West Prospect Road to the north. There is an existing fire hydrant at the northwest corner of Lot 2 (referred to in this report as “North FH”) and an existing fire hydrant approximately 250 feet to the south of Lot 2 (referred to in this report as “South FH”). P:18111_College and Prospect Hotel_Prelim Wat Rpt_2-26-20 2 2/26/20 Fire flow tests were performed by the City for the existing north and south hydrants with the results as follows: North FH: Static pressure: 85 PSI Residual pressure: 80 PSI South FH: Static pressure: 90 PSI Residual pressure: 75 PSI Flow Hydrant: Flowed Nozzle Size: 4.5 IN Flowed at: 38 PSI Flow: 2041 GPM Proposed services to serve the building from the existing 6-inch water main includes a 3-inch domestic service and a 6-inch fire supply line. A new fire hydrant is also proposed off the northwest corner of the proposed building. 2. Criteria and Assumptions The criteria used for the required fire flow was the Table B105.1 of the 2015 IFC. Based on the construction type of IIA, gross floor area to be sprinkled of 83,320 square feet and an occupancy group of R-1, the required fire flow was determined to be 4,250 gpm. Because the building will be sprinkled, a reduction of 75% was used to bring the revised fire flow to 1,063 gpm. 1,500 gpm at 20 psi residual pressure was used, however, since this is the minimum required. A maximum domestic peak demand for the building was assumed at 160 gpm, based on the plumbing fixture calculation and resulting peak water flow provided by G2 Consulting Engineers, Inc. Refer to calculations in the Appendix A Based on assumptions provided by the fire suppression designer at Total Fire Protection, a 6-inch fire supply line and a maximum demand for the sprinkler system of 750 gpm was assumed (fire pump assumed not to be required). Refer to Appendix A for email correspondence with the fire suppression designer. P:18111_College and Prospect Hotel_Prelim Wat Rpt_2-26-20 3 2/26/20 3. Modeling and Results The following is a summary of the scenarios employed: Scenario #1: Static Condition The static scenario was modeled first, which established available water pressures for the site with no demands placed on the system. This model demonstrates that all pressure requirements are maintained. Scenario #2: Fire Flow and Peak Demand The second scenario was run with the peak hour demand of the proposed hotel and fire flow. 1,500 GPM was used at the proposed hydrant. An assumed value of 160 GPM for the peak demand of the hotel, and a value of 750 GPM was assumed for the fire sprinklers within the building. The modeling information is presented in the Appendix B. Based on the analyzed scenarios given the outlined assumptions, the existing 6-inch cast iron water main, from which the proposed domestic service, fire supply line and fire hydrant will be served, is adequately sized to deliver the required peak demand and fire flows for the proposed building on Lot 2. If you have any questions or need additional information please contact me at 970/488-0169 or email me at csonnier@sandersonstewart.com. Thank you. SANDERSON STEWART Charles Sonnier, PE Senior Engineer/Project Manager APPENDIX A Prospect and College Hotel – Fort Collins, CO 18111 Project: Date: Calculation By: PIPE SIZE FU TOTAL CW FU PIPE SIZE FU TOTAL HW FU FU TOTAL FU Bathroom Group Private Tank 150 3/4" 2.7 405 3/4" 1.5 225 3.6 540 2" 5 750 Bathroom Group Public Valve 1" 6 0 3/4" 3 0 8 0 2" 6 0 Bathtub Private - 1/2" 1 0 1/2" 1 0 1.4 0 1-1/2" 2 0 Bathtub Public - 1/2" 3 0 1/2" 3 0 4 0 1-1/2" 2 0 Bidet Private - 1/2" 1.5 0 1/2" 1.5 0 2 0 1-1/4" 1 0 Combination Fixture Private - 3/4" 2.25 0 3/4" 2.25 0 3 0 1-1/2" 2 0 Dishwashing Machine Private - - - - 1/2" 1.4 0 1.4 0 1-1/2" 2 0 Drinking Fountain Public - 1 1/2" 0.25 0.25 - - 0.25 0.25 1-1/4" 0.5 0.5 Kitchen Sink Private - 1/2" 1 0 1/2" 1 0 1.4 0 1-1/2" 2 0 Kitchen Sink Public - 1 3/4" 3 3 3/4" 3 3 4 4 2" 3 3 Lavatory Private - 1/2" 0.5 0 1/2" 0.5 0 0.7 0 1-1/4" 1 0 Lavatory Public - 6 1/2" 1.5 9 1/2" 1.5 9 2 12 1-1/2" 1 6 Service Sink Public - 2 3/4" 2.25 4.5 3/4" 2.25 4.5 3 6 2" 3 6 Shower Head Public - 3/4" 3 0 3/4" 3 0 4 0 1-1/2" 2 0 Shower Head Private - 1/2" 1 0 1/2" 1 0 1.4 0 1-1/2" 2 0 Urinal - 1" Flushvalve Public Valve 1" 10 0 - - - 10 0 2" 4 0 Urinal - 3/4" Flushvalve Public Valve 3/4" 5 0 - - - 5 0 2" 2 0 Washing Machine (8lb) Private - 1/2" 1 0 1/2" 1 0 1.4 0 2" 2 0 Washing Machine (8lb) Public - 3/4" 2.25 0 1/2" 2.25 0 3 0 2" 3 0 Washing Machine (15lb) Public - 4 3/4" 3 12 3/4" 3 12 4 16 2" 3 12 Water Closet - Tank Private Tank 1/2" 2.2 0 - - - 2.2 0 3" 3 0 Water Closet - Valve Public Valve 8 1" 10 80 - - - 10 80 3" 4 32 Water Closet - Tank Public Tank 1/2" 5 0 - - - 5 0 3" 4 0 Hose Bib Public - 4 3/4" 2.25 9 - - - 2.25 9 - - - Emergency Floor Drain Public - - - - - - - - - 2" 0 0 2" Floor Drain Public - - - - - - - - - 2" 3 0 3" Floor Drain Public - - - - - - - - - 3" 5 0 2" Floor Sink Public - - - - - - - - - 2" 3 0 3" Floor Sink Public - - - - - - - - - 3" 5 0 4" Floor Sink Public - - - - - - - - - 4" 6 0 Kitchen Equipment Hand Sink 2 1/2" 1 2 1/2" 1 2 1.5 3 1-1/2" 2 Dish Machine Kitchen 1 - - - 3/4" 2 2 2 2 2" 3 2 Compartment Sink Kitchen 1 1/2" 1 1/2" 1 1 1.5 1.5 1-1/2" 2 3 Compartment Sink Kitchen 1 3/4" 2 3/4" 2 2 2.5 2.5 1-1/2" 2 Booster Heater Kitchen - - - 3/4" 2.5 0 2.5 0 2" 3 Blender Station Kitchen 1/2" 1 1/2" 1 0 1.5 0 1-1/2" 2 Ice Machine Kitchen 5 1/2" 1 - - - 1 5 1" 0.5 Food Warmer with Autofill Kitchen - - - 1/2" 1 0 1 0 2" 3 Combi Oven Kitchen 3/4" 2 - - - 2 0 2" 3 Steamer Kitchen 3/4" 2 - - - 2 0 2" 3 Disposal w/ Spray Rinse Kitchen 3/4" 2 3/4" 2 0 2.5 0 2" 3 1/2" CW Kitchen 1/2" 1 - - - 1 0 1" 0.5 1/2" HW Kitchen - - - 1/2" 1 0 1 0 1" 0.5 3/4" CW Kitchen 3/4" 2 - - - 2 0 2" 3 3/4" HW Kitchen - - - 3/4" 2 0 2 0 2" 3 1/2" CW, 1/2" HW Kitchen 1/2" 1 1/2" 1 0 1.5 0 2" 3 3/4" CW, 3/4" HW Kitchen 3/4" 2 3/4" 2 0 2.5 0 2" 3 TOTAL CW FU 524.75 TOTAL HW FU 260.5 TOTAL 681.25 TOTAL WASTE DFU 809.5 160 GPM Water Meter / Tap Size Review Assumed Pressure Range: 50-60 PSI 1 Charles Sonnier From: Stewart Garrett <SGarrett@totalfire.biz> Sent: Wednesday, January 29, 2020 10:40 AM To: Charles Sonnier Cc: Gabe Dunbar; Scott Mikulak; John Tufte Subject: RE: FoCo Midtown Hotel Charles, I would use 750 gpm as your max flow rate. This should be worst case scenario. Thanks Stewart Garrett Total Fire Protection (970)613.1370 Office (720)245.7797 Cell E-mail: sgarrett@totalfire.biz From: Charles Sonnier <Csonnier@sandersonstewart.com> Sent: Wednesday, January 29, 2020 9:47 AM To: Stewart Garrett <SGarrett@totalfire.biz> Cc: Gabe Dunbar <g.dunbar@saundersheath.com>; Scott Mikulak <s.mikulak@saundersheath.com>; John Tufte <Jtufte@sandersonstewart.com> Subject: FW: FoCo Midtown Hotel Hi Stewart, We are the civils on this project and are currently modeling the existing water main to see if it will need to be upsized to accommodate the fire/domestic demand for the hotel. Do you have a max flowrate (gpm) we can use for the fire supply line in our model? Thanks, Charles Sonnier PE, CFM Senior Engineer SANDERSONSTEWART t: 970-893-2863 m: 970-488-0169 From: Gabe Dunbar <g.dunbar@saundersheath.com> Sent: Wednesday, January 29, 2020 9:14 AM 2 To: Charles Sonnier <Csonnier@sandersonstewart.com>; John Tufte <Jtufte@sandersonstewart.com> Cc: Scott Mikulak <s.mikulak@saundersheath.com> Subject: FW: FoCo Midtown Hotel John/Charles, See below from Total Fire regarding the fire line size. Gabriel Dunbar Project Manager/Estimator 1212 Riverside Avenue, Suite 130, Fort Collins, CO 80524 d (970) 490-8040 o (970) 221-4195 m (303) 905-3901 G.dunbar@saundersheath.com www.saundersheath.com CONFIDENTIALITY NOTICE: This email transmission, and any documents, files or previous email messages attached to it, may contain confidential information, some or all of which may be legally privileged. If you are not the intended recipient or a person responsible for delivering it to the intended recipient, please be advised that any disclosure, copying, distribution or use of any of the information contained in or attached to this email transmission is prohibited. If you have received this email transmission in error, please immediately notify us by reply email or via telephone, and destroy the original email transmission and its attachments. From: Stewart Garrett <SGarrett@totalfire.biz> Sent: Thursday, January 23, 2020 10:47 AM To: Scott Mikulak <s.mikulak@saundersheath.com> Cc: Gabe Dunbar <g.dunbar@saundersheath.com> Subject: RE: FoCo Midtown Hotel This message originated outside your organization. Scott/Gabe, Based on the flow test data provided a 6” fire service line to this building will be sufficient. This size assumes that a fire pump is not required, based on code and conversations with PFA I do not believe this building will need a pump. Below is the info I received from PFA, there is an outside chance that could change during drawing review, but it sounds unlikely. Let me know if you need anything else. Thanks Info from Poudre Fire Authority: “In buildings not classified as a high-rise building, manual wet standpipes are acceptable in accordance with NFPA 14 Section 5.4.1.1. Please keep in mind, if this project is being constructed under an alternative method that requires high- rise provisions be implemented (as is often done to address a lack of aerial access and addressed in development plan review), then NFPA 14 Section 5.4.1.2 and 5.4.1.2.1 will apply and all standpipes in the building are required to be automatic. If this building is not classified as a high-rise (by base building code definition or alternative methods), a manual standpipe is not required to have an automatic water supply capable of supplying 100 psi at the top. In accordance with NFPA 14 Section 7.8.1.2, manual standpipe systems are required to be designed to provide 100 psi at the topmost 3 outlet, but designed so fire apparatus can supply the needed pressure and flow. PFA apparatus is rated to supply 1,500 gpm at 150 psi at the FDC connection.” Stewart Garrett Total Fire Protection (970)613.1370 Office (720)245.7797 Cell E-mail: sgarrett@totalfire.biz From: Scott Mikulak <s.mikulak@saundersheath.com> Sent: Friday, January 17, 2020 4:39 PM To: Stewart Garrett <SGarrett@totalfire.biz> Cc: Gabe Dunbar <g.dunbar@saundersheath.com> Subject: FW: FoCo Midtown Hotel Does this help the pump discussion? Thanks, Scott Mikulak Director of Preconstruction 1212 Riverside Avenue, Suite 130, Fort Collins, CO 80524 d (970) 490-8032 o (970) 221-4195 m (303) 710-1903 s.mikulak@saundersheath.com www.saundersheath.com CONFIDENTIALITY NOTICE: This email transmission, and any documents, files or previous email messages attached to it, may contain confidential information, some or all of which may be legally privileged. If you are not the intended recipient or a person responsible for delivering it to the intended recipient, please be advised that any disclosure, copying, distribution or use of any of the information contained in or attached to this email transmission is prohibited. If you have received this email transmission in error, please immediately notify us by reply email or via telephone, and destroy the original email transmission and its attachments. From: Charles Sonnier <Csonnier@sandersonstewart.com> Sent: Friday, January 17, 2020 9:15 AM To: Kalib Ainsworth <kainsworth@g2ce.com>; dmanring@g3ce.com Cc: Scott Mikulak <s.mikulak@saundersheath.com>; Matt Rausch <mrausch@aircomfortcolorado.com>; Aaron Pollick <a.pollick@saundersinc.com>; Travis Slisher <tslisher@neuworksmechanical.com>; Gabe Dunbar <g.dunbar@saundersheath.com>; John Tufte <Jtufte@sandersonstewart.com> Subject: RE: FoCo Midtown Hotel This message originated outside your organization. APPENDIX B Prospect and College Hotel – Fort Collins, CO 18111 SCENARIO #1 - STATIC ANALYSIS Midtown Fort Collins Hotel – Fort Collins, CO 18111 Preliminary Water Report Analysis Static Junction Table - Time: 0.00 hours Pressure (psi) Hydraulic Grade (ft) Demand (gpm) Demand Collection Elevation Zone (ft) ID Label <Collection: 0 0 5,209.90 91 32 J1 5,000.00 <None> items> <Collection: 0 0 5,209.90 91 34 J5 5,000.00 <None> items> <Collection: 0 0 5,209.90 91 36 J6 5,000.00 <None> items> <Collection: 0 0 5,209.90 91 38 J7 5,000.00 <None> items> <Collection: 0 0 5,209.90 91 40 J8 5,000.00 <None> items> <Collection: 0 0 5,209.90 91 42 J9 5,000.00 <None> items> <Collection: 0 0 5,209.90 91 59 J4 5,000.00 <None> items> <Collection: 0 0 5,209.90 91 62 J2 5,000.00 <None> items> <Collection: 1 0 5,209.90 91 65 J10 5,000.00 <None> item> <Collection: 1 0 5,209.90 91 66 J12 5,000.00 <None> item> <Collection: 0 0 5,209.90 91 70 J3 5,000.00 <None> items> <Collection: 1 0 5,209.90 91 73 J11 5,000.00 <None> item> 27 Siemon Company Drive Suite 200 W Watertown, CT Page 1 of 8 06795 USA +1-203-755-1666 2/24/2020 WaterCAD CONNECT Edition Update 1 WATER MODEL.wtg Bentley Systems, Inc. Haestad Methods Solution Center [10.01.01.04] Preliminary Water Report Analysis Reservoir Table - Time: 0.00 hours Hydraulic Grade (ft) Flow (Out net) (gpm) Elevation Zone (ft) ID Label SOUTH 5,002.00 <None> 0 5,002.00 46 RESERVOIR NORTH 5,003.00 <None> 0 5,003.00 47 RESERVOIR 27 Siemon Company Drive Suite 200 W Watertown, CT Page 2 of 8 06795 USA +1-203-755-1666 2/24/2020 WaterCAD CONNECT Edition Update 1 WATER MODEL.wtg Bentley Systems, Inc. Haestad Methods Solution Center [10.01.01.04] Preliminary Water Report Analysis Pump Table - Time: 0.00 hours Pump Head (ft) Flow (Total) (gpm) Hydraulic Grade (Discharge) (ft) Hydraulic Grade (Suction) (ft) Pump Status (Initial) Definition Elevation (ft) ID Label NORTH 5,000.00 North Pump On 5,003.00 5,209.90 0 0.00 31 HYDRANT SOUTH 5,002.00 South Pump On 5,002.00 5,209.90 0 207.90 84 HYDRANT 27 Siemon Company Drive Suite 200 W Watertown, CT Page 3 of 8 06795 USA +1-203-755-1666 2/24/2020 WaterCAD CONNECT Edition Update 1 WATER MODEL.wtg Bentley Systems, Inc. Haestad Methods Solution Center [10.01.01.04] Preliminary Water Report Analysis Pipe Table - Time: 0.00 hours Has Check Valve? Hazen-Williams C Diameter Material (in) Length Start Node Stop Node (Scaled) (ft) ID Label NORTH J1 24.0 Cast Iron 130.0 False 33 P2 10 HYDRANT 37 P7 77 J5 J6 8.0 Cast Iron 130.0 False 39 P8 123 J6 J7 8.0 Cast Iron 130.0 False 41 P9 28 J8 J7 8.0 Cast Iron 130.0 False 43 P10 11 J9 J8 8.0 Cast Iron 130.0 False NORTH 24.0 Cast Iron 130.0 False HYDRANT NORTH 48 P1 10 RESERVOIR 63 P3 137 J1 J2 6.0 Cast Iron 130.0 False 67 P15 160 J4 J12 6.0 PVC 150.0 False 68 P13 111 J2 J10 6.0 PVC 150.0 False 69 P6 266 J4 J5 6.0 Cast Iron 130.0 False 71 P4 65 J2 J3 6.0 Cast Iron 130.0 False 72 P5 8 J3 J4 6.0 Cast Iron 130.0 False 74 P14 160 J3 J11 3.0 PVC 150.0 False SOUTH 24.0 Cast Iron 130.0 False HYDRANT SOUTH 85 P12 11 RESERVOIR SOUTH J9 24.0 Cast Iron 130.0 False 86 P11 97 HYDRANT Length (User Defined) (ft) Has User Defined Length? Headloss Gradient (ft/ft) Velocity (ft/s) Flow (gpm) Minor Loss Coefficient (Local) 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 SCENARIO #2 – PEAK DEMAND + FIRE FLOW Midtown Fort Collins Hotel – Fort Collins, CO 18111 Preliminary Water Report Analysis Peak Demand + Fireflow Junction Table - Time: 0.00 hours Pressure (psi) Hydraulic Grade (ft) Demand (gpm) Demand Collection Elevation Zone (ft) ID Label <Collection: 0 0 5,193.70 84 32 J1 5,000.00 <None> items> <Collection: 0 0 5,195.68 85 34 J5 5,000.00 <None> items> <Collection: 0 0 5,197.16 85 36 J6 5,000.00 <None> items> <Collection: 0 0 5,199.50 86 38 J7 5,000.00 <None> items> <Collection: 0 0 5,200.04 87 40 J8 5,000.00 <None> items> <Collection: 0 0 5,200.25 87 42 J9 5,000.00 <None> items> <Collection: 0 0 5,175.15 76 59 J4 5,000.00 <None> items> <Collection: 0 0 5,175.01 76 62 J2 5,000.00 <None> items> <Collection: 1 1,500 5,161.66 70 65 J10 5,000.00 <None> item> <Collection: 1 750 5,169.79 73 66 J12 5,000.00 <None> item> <Collection: 0 0 5,175.09 76 70 J3 5,000.00 <None> items> <Collection: 1 160 5,166.15 72 73 J11 5,000.00 <None> item> 27 Siemon Company Drive Suite 200 W Watertown, CT Page 5 of 8 06795 USA +1-203-755-1666 2/24/2020 WaterCAD CONNECT Edition Update 1 WATER MODEL.wtg Bentley Systems, Inc. Haestad Methods Solution Center [10.01.01.04] Preliminary Water Report Analysis Peak Demand + Fireflow Reservoir Table - Time: 0.00 hours Hydraulic Grade (ft) Flow (Out net) (gpm) Elevation Zone (ft) ID Label SOUTH 5,002.00 <None> 1,023 5,002.00 46 RESERVOIR NORTH 5,003.00 <None> 1,387 5,003.00 47 RESERVOIR 27 Siemon Company Drive Suite 200 W Watertown, CT Page 6 of 8 06795 USA +1-203-755-1666 2/24/2020 WaterCAD CONNECT Edition Update 1 WATER MODEL.wtg Bentley Systems, Inc. Haestad Methods Solution Center [10.01.01.04] Preliminary Water Report Analysis Peak Demand + Fireflow Pump Table - Time: 0.00 hours Pump Head (ft) Flow (Total) (gpm) Hydraulic Grade (Discharge) (ft) Hydraulic Grade (Suction) (ft) Pump Status (Initial) Definition Elevation (ft) ID Label NORTH 5,000.00 North Pump On 5,003.00 5,193.70 1,387 190.70 31 HYDRANT SOUTH 5,002.00 South Pump On 5,002.00 5,200.26 1,023 198.26 84 HYDRANT 27 Siemon Company Drive Suite 200 W Watertown, CT Page 7 of 8 06795 USA +1-203-755-1666 2/24/2020 WaterCAD CONNECT Edition Update 1 WATER MODEL.wtg Bentley Systems, Inc. Haestad Methods Solution Center [10.01.01.04] Preliminary Water Report Analysis Peak Demand + Fireflow Pipe Table - Time: 0.00 hours Has Check Valve? Hazen-Williams C Diameter Material (in) Length Start Node Stop Node (Scaled) (ft) ID Label NORTH J1 24.0 Cast Iron 130.0 False 33 P2 10 HYDRANT 37 P7 77 J5 J6 8.0 Cast Iron 130.0 False 39 P8 123 J6 J7 8.0 Cast Iron 130.0 False 41 P9 28 J8 J7 8.0 Cast Iron 130.0 False 43 P10 11 J9 J8 8.0 Cast Iron 130.0 False NORTH 24.0 Cast Iron 130.0 False HYDRANT NORTH 48 P1 10 RESERVOIR 63 P3 137 J1 J2 6.0 Cast Iron 130.0 False 67 P15 160 J4 J12 6.0 PVC 150.0 False 68 P13 111 J2 J10 6.0 PVC 150.0 False 69 P6 266 J4 J5 6.0 Cast Iron 130.0 False 71 P4 65 J2 J3 6.0 Cast Iron 130.0 False 72 P5 8 J3 J4 6.0 Cast Iron 130.0 False 74 P14 160 J3 J11 3.0 PVC 150.0 False SOUTH 24.0 Cast Iron 130.0 False HYDRANT SOUTH 85 P12 11 RESERVOIR SOUTH J9 24.0 Cast Iron 130.0 False 86 P11 97 HYDRANT Length (User Defined) (ft) Has User Defined Length? Headloss Gradient (ft/ft) Velocity (ft/s) Flow (gpm) Minor Loss Coefficient (Local) 0.000 1,387 0.98 0.000 False 0 0.000 -1,023 6.53 0.019 False 0 0.000 -1,023 6.53 0.019 False 0 0.000 1,023 6.53 0.019 False 0 0.000 1,023 6.53 0.019 False 0 0.000 1,387 0.98 0.000 False 0 0.000 1,387 15.74 0.136 False 0 0.000 750 8.51 0.033 False 0 0.000 1,500 17.02 0.121 False 0 0.000 -1,023 11.60 0.077 False 0 0.000 -113 1.28 0.001 False 0 0.000 -273 3.09 0.007 False 0 0.000 160 7.26 0.056 False 0 0.000 1,023 0.73 0.000 False 0 0.000 1,023 0.73 0.000 False 0 27 Siemon Company Drive Suite 200 W Watertown, CT Page 8 of 8 06795 USA +1-203-755-1666 2/24/2020 WaterCAD CONNECT Edition Update 1 WATER MODEL.wtg Bentley Systems, Inc. Haestad Methods Solution Center [10.01.01.04] 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 0.000 0 0.00 0.000 False 0 27 Siemon Company Drive Suite 200 W Watertown, CT Page 4 of 8 06795 USA +1-203-755-1666 2/24/2020 WaterCAD CONNECT Edition Update 1 WATER MODEL.wtg Bentley Systems, Inc. Haestad Methods Solution Center [10.01.01.04] Assumed Max Developed Length: 100 ft Assumed Flush Valves for public fixtures Meter and Service Pipe: 2" Distribution Pipe: 2-1/2" Max Water Supply Fixture Units Allowable (IPC): 533 Meter and Service Pipe: 3" Distribution Pipe: N/A Max Flow Rate Allowable (meter limits): 220-360 Actual WSFU = 682 Peak Water Flow = 160 GPM Water Meter and Service Size Required= 3" AC Marriott 1/15/2020 KMA SANITARY TOTAL DFU WASTE DFU DRAIN SIZE FIXTURE INFORMATION FIXTURE OCCUP. TYPE QTY. COLD WATER HOT WATER COMBINED TOTAL DOMESTIC WATER