INVITATION TO BID
7282 LP Transformers, 25kVA & 100kVA, Padmounted, Single Phase
BID OPENING: 3:00 P.M. (our clock), October 7, 2011
1
Sealed bids will be received and publicly opened at the office of the Director of Purchasing and Risk
Management, PO Box 580, 215 North Mason St., 2nd floor, Fort Collins, Colorado 80522, at the
time and date noted on the bid pro osal and/or contract documents. If delivered, they are to be
sent to 215 North Mason Street, 2" Floor, Fort Collins, Colorado 80524. If mailed, the address is
P.O. Box 580, Fort Collins, 80522-0580.
Bids must be received at the Purchasing Office prior to 3:00 p.m. (our clock), October 7,
2011.
Questions regarding bid submittal or process should be directed to Opal Dick, CPPO, Senior Buyer
at (970) 221-6778 or odick@fcgov.com.
A copy of the Bid may be obtained as follows:
Come by Purchasing at 215 North Mason St., 2nd floor, Fort Collins, and request a
copy of the Bid.
Special Instructions
All bids must be properly signed by an authorized representative of the company with the legal
capacity to bind the company to the agreement. Bids maybe withdrawn up to the date and hour set
for closing. Once bids have been accepted by the City and closing has occurred, failure to enter
into contract or honor the purchase orderwill be cause for removal of supplier's name from the City
of Fort Collins' bidders list for a period of twelve months from the date of the opening. The City may
also pursue any remedies available at law or in equity. Bid prices must be held firm for a period of
forty-five (45) days after bid openings.
Submission of a bid is deemed as acceptance of all terms, conditions and specifications contained
in the City's specifications initially provided to the bidder. Any proposed modification must be
accepted in writing by the City prior to award of the bid.
Only bids properly received by the Purchasing Office will be accepted. All bids should be clearly
identified by the bid number and bid name contained in the bid proposal.
No proposal will be accepted from, or any purchase order awarded, to. any person, firm or
corporation in default on any obligation to the City.
Bids must be furnished exclusive of any federal excise tax, wherever applicable.
Bidders must be properly licensed and secure necessary permits wherever applicable.
Bidders not responding to this bid will be removed from our automated vendor listing for the subject
commodities.
REV. SYM: FF
SPECIFICATION FOR
PAD -MOUNTED COMPARTMENTAL -TYPE
SINGLE-PHASE DISTRIBUTION TRANSFORMERS
WITH SEPARABLE INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS
1 SCOPE
This Specification establishes the minimum electrical requirements and mechanical features of single phase, 60 HZ,
mineral oil immersed, self -cooled, pad -mounted, compartmental -type distribution transformers rated 250 KVA and
smaller, high voltage 13,200 Grd Y/7620 volts, with separable insulated load break high voltage connectors. These
transformers are used for step down purposes from an underground primary cable supply.
This standard generally conforms with ANSI requirements for pad -mounted compartmental -type, self -cooled, single-
phase, distribution transformers, C57.12.25.
2 APPLICABLE DOCUMENTS
The following documents of the issue shown form a part of this Specification to the extent specified herein. In those
cases when the document is note dated, the latest issue in effect on the date of invitation for bids shall form a part of
this Specification.
2.1 ANSI C57.12.00 - Distribution, power, and regulating transformers, and shunt reactors, general requirements for.
2.2 ANSI C57.12.25 - Pad mounted, compartmental -type, single-phase, distribution transformers with separable H-V
connectors, standard requirements for.
2.3 ANSI C57.12.28 - Switchgear and Transformers - Pad -Mounted Equipment -Enclosure Integrity.
2.4 ANSI C57.12.70 - Terminal markings and connections for distribution and power transformers.
2.5 ANSI C57.12.80 - Terminology for power and distribution transformers.
2.6 ANSI C57.12.90 - Distribution, power, and regulating transformers, and shunt reactors, test code for.
2.7 IEEE C57.91 - Guide for Loading Mineral -Oil -Immersed Overhead and Pad -Mounted Distribution Transformers
Rated 500 kVA and Less with 650C or 550C Average Winding Rise.
3 REQUIREMENTS
3.1 GENERAL REQUIREMENTS FOR DESIGN
3.1.1 BASIC DESIGN STANDARDS
Transformers purchased under these Specifications shall be new and, unless otherwise specified, meet
the requirements of the applicable ANSI Standards and the modifications and additions given in the
subsequent paragraphs. In case of conflict, the requirements of the following documents shall apply in
the priority shown:
a) This Specification
b) Applicable ANSI Standards
Approved manufacturers are listed in Appendix C.
3bb-12U
REV. SYM: FF
3.1.2 KILOVOLT -AMPERE TEMPERATURE RATINGS
Kilovolt -ampere ratings are continuous and are based on not exceeding either a 650C average winding
temperature or an 800C hot spot temperature rise. The temperature rise of the insulating oil shall not
exceed 650C when measured near the top of the tank. The temperature rise is based on an altitude of
3,300 feet. The transformers shall be designed for overloads based on IEEE C57.91.
3.1.3 GENERAL CONSTRUCTION
3.1.3.1 The pad -mounted compartmental -type transformers shall consist of the transformer tank and high -and -low -
voltage cable terminating compartment constructed in accordance with ANSI C57.12.25 and ANSI C57.12.28.
The terminating compartment and tank shall be assembled as an integral unit, tamperproof and weatherproof for
mounting on a pad. There shall be no exposed screws, bolts, or other fastening devices which are externally
removable. The cover shall be welded construction. There shall be no opening through which foreign objects
such as sticks, rods, or wires might be inserted to contact live parts. Suitable means for padlocking the
compartment door(s) shall be provided.
3.1.3.2 The high- and low -voltage compartment shall be located side by side on one side of the transformer tank. When
facing the compartment, the low -voltage side shall be on the right.
3.1.3.3Construction of the unit shall be such that it can be lifted, skidded, and slid into place on the mounting pad
without disturbing the entrance cables.
3.1.3.4 An undercoating over the regular finish or an equivalent treatment shall be applied to all surfaces that are in
contact with the pad to minimize corrosion.
3.1.3.5 Minimum dimensions for Type 1 transformers shall be as shown in Figure 1, Appendix B. Minimum dimensions
for Type 2 transformers shall be as shown in Figure 2, Appendix B.
3.2 SPECIFIC DESIGN REQUIREMENTS
3.2.1 FUNCTIONAL DESCRIPTION
The transformer shall be a single phase, pad mounted, loop feed -safe break, "dead -front" type for use on
a 13.8 kV grounded "Y" distribution system.
3.2.2 DESIGN AND CONSTRUCTION
3.2.2.1 RATING
The transformer shall be rated as follows:
a) High Voltage 13,200 Grd. Y/7620 volts
b) Low Voltage 240/120
c) Taps Two - 2%% FC above and below normal
d) Polarity Additive
e) Capacity, Impedance values, and fusing for transformers in this specification shall conform to Table 1:
368-12u
REV. SYM: FF
Table 1 — Transformer Capacity, Impedance and Fuse Selection
Stock
kVA
Min.
Max.
Bay-9-Net
Current Limiting Fuse(s)
Number
Capacity
Impedance
Im edance
Fuse
368-120-130
25
1.77%
2.16%
10 Amp
ELSP 354403OM61 M (30 A)
4000353C06
368-120-150
50
1.77%
2.16%
15 Amp
ELSP 354304OM61M (40 A)
4000353C08
368-120-155
50
1.77%
2.16%
15 Amp
ELSP 354304OM61 M (40 A)
4000353C08
368-120-170
100
1.95%
2.38%
25 Amp
ELSP 3543080M71 M (80 A)
4000353C10
368-120-180
167
2.28%
2.79% j
40 Amp
ELSP 3543125M71 M (125 A)
4000353C12
368-120-190
250
5.75%
6.61 %
65 Amp
ELSP 3543125M71 M (125 A)
4000353C14
*The BAY-O-NET fuse shall be located in the high voltage side of the compartment.
3.2.2.2INSULATION LEVEL
3.2.2.2.1 The basic impulse insulation level (BIL) of completely assembled high -voltage and low -voltage terminals
shall be 95 kV and 30 kV respectively.
3.2.2.2.2 Dielectric test levels shall be in accordance with the distribution levels in Section 4 of ANSI C57.12.00.
3.2.2.3 HIGH -VOLTAGE TAPS
A no-load tap changer with external operating handle shall provide two - 2'/z% full capacity taps above and
below normal. The tap changer operating handle shall be located within the high -voltage terminal side of the
terminal compartment.
3.2.2.4 NOT USED
3.2.2.5 BUSHING WELLS AND TERMINALS
3.2.2.5.1 The number, location, and arrangement of bushing wells, terminals and parking stands shall be as
shown in Fig. 1 or Fig. 2 in Appendix B. All low -voltage bushings and high -voltage wells shall be
externally clamped and shall have leads of sufficient length to allow them to be changed without
removing the cover. Welded bushings and wells are expressly prohibited.
3.2.2.5.2 High -voltage terminals shall be universal flowerpot bushing wells in accordance with Figure 3 of
ANSI/IEEE 386-1985. Two wells shall be provided and shall be connected in a feed -through
configuration. Loadbreak bushing inserts in accordance with Figure 5 of ANSI/IEEE 386-1985 will be
owner furnished.
3.2.2.5.3 Low -voltage line and neutral terminals shall be sized as shown in Table 2 in accordance with ANSI
C57.12.25. Bushing arrangement and spacing shall be shown in Fig. 1 or Fig. 2 in Appendix B.
Table 2 — Low Voltage Terminal Sizes
Stock Number
kVA Capacity
Low voltage Terminal Size
368-120-130
25
5/8" x 11" UNC-2A copper studs
368-120-150
50
5/8" x 11" UNC-2A copper studs
368-120-155
50
5/8" x 11" UNC-2A copper studs
368-120-170
100
1" x 14" UNC-2A copper studs
368-120-180
167
1" x 14" UNC - 2A copper studs
368-120-190
250
1'/4" x 12 UNF - 2A copper studs.
3.2.2.5.4 The low -voltage XZ bushing shall be a fully insulated bushing. A ground pad shall be provided on the
outer surface of the tank and an external removable copper ground strap shall be provided and
connected between the low -voltage XZ bushing and the ground pad.
3.2.2.5.5 The high -voltage neutral shall be securely grounded internally.
6
368-120
REV. SYM: FF
3.2.2.6ACCESSORY CABINET
3.2.2.6.1 The accessory cabinet shall consist of a compartment containing high- and low -voltage bushings
constructed in accordance with applicable ANSI specifications, including ANSI C57.12.28. Dimensions
shall be in accordance with Fig. 1 of this specification.
3.2.2.6.2 Cabinet doors shall be hinged, removable, lockable, and of sufficient size to provide adequate working
space when removed or open. Unlocking the padlock shall permit access to both the high- and low -
voltage terminations. Stainless steel hinge pins shall be provided.
3.2.2.7ACCESSORY EQUIPMENT
Accessory equipment shall be provided in accordance with the following details:
3.2.2.7.1 Deleted
3.2.2.7.2 The transformer base shall be arranged for rolling in two directions: Parallel to and at right angles to the
center line of the high -voltage bushings.
3.2.2.7.3 Lifting lugs or bosses for screw -in lift bolts shall be provided. These lugs or bosses shall be adequate
strength and size and arranged on the tank to provide a suitable balanced lift for the completely
assembled unit.
3.2.2.7.4 The base of the assembly shall be provided with suitable means for mounting the unit on the pad. An
internal flange shall be provided at the base of the accessory compartment to provide means for
mounting the unit on the pad. (Fig. land Figure 2, Appendix B).
3.2.2.7.5 Terminal designations are shown in Figure 1 and Figure 2, Appendix B. The identification of terminal
connections shall be shown on the instruction nameplate. Instruction nameplate shall be located in the
low -voltage side and shall be readable with cables in place. Where the nameplate is mounted on a
removable part, the manufacturer's name and transformer serial number shall be permanently affixed to
a non -removable part.
Instruction nameplate shall contain the information specified in 5.12 of ANSI C57.12.00-1987, Nameplate
A. Also, on the nameplate, or label affixed near it, the manufacturer shall indicate that the dielectric fluid
contains less than 1 ppm PCB.
3.2.2.7.6 A suitable marking inside of the tank shall indicate the correct oil level at 25°C.
3.2.2.7.7 An automatic pressure relief device shall be located within the compartment. This device shall meet the
following requirements:
• 'W NPT or larger male Inlet Port.
• Exposed parts of weather and corrosion resistant materials.
• Non -deteriorating gasket and o-ring material.
• Manual pull ring able to withstand 25 pound force minimum.
• Body able to withstand 100 pound shear force minimum.
• Bug shield.
• Cracking pressure of 10 t 2 psig.
• Resealing pressure of 8 t 2 psig.
• Zero leak rate from 8 t 2 psig to -8 psig.
• Minimum flow rate of 35 SCFM at 15 psig.
3.2.2.7.8 An RTE BAY-O-NET current sensing fuse and internally mounted partial range current limiting fuse shall
be furnished as shown in Table 1.
3.2.2.8O1L PRESERVATION
Transformers shall be of sealed -tank construction. Sealed -tank construction is that which seals the interior
of the tank from the atmosphere, and in which the gas plus the oil volume remains constant. The
transformer will remain effectively sealed for a top -oil temperature range of -50C to 105°C.
3.2.2.9TANKS
The tank shall be domed or sloped to shed water. The tank shall be of sufficient strength to support a
minimum of 500 lbs. vertical load. Construction of the tank shall be in accordance with ANSI C57.12.25-
1981, paragraphs 6.1 and 6.6.
7
368-120
REV. SYM: FF
3.2.2.9.1 The cover shall be welded construction.
3.2.2.9.2 Tank grounding provision shall consist of two steel pads, each with Y: inch - 13 NC tapped hole, 7/16
inch deep.
3.2.2.9.3 These ground pads shall be welded on the transformer base or on the tank wall near the base, one in
the high -voltage side and one in the low -voltage side. In cases where the transformer tank and
compartments are separate, provisions shall be made for electrically connecting them.
3.2.2.9.4 Locking bolts shall be pentahead.
3.2.2.10 COMPONENTS FOR LOOPED PRIMARY
The minimum current -carrying capability of components for the looped primary cable system shall be 200
amperes (continuous) and 10,000 amperes symmetrical (momentary).
3.2.2.11 AUDIBLE SOUND LEVEL
The audible sound level shall be in accordance with NEMA Standard TR1-1980.
3.2.2.12 BASE PLAN
The base plan of a completely assembled unit shall be such that it can be installed on a pad of the
dimensions shown in Fig. 1 B.
3.2.2.13 PAINT
EEI "Finishing Guidelines" specification shall apply. Finish coat shall be Munsell Green, glossy.
3.2.2.14 LOSSES
The total losses of transformer shall be the sum of the excitation losses and the load losses (IZR losses).
Load loss tests shall be performed and reported on all units regardless of whether or not a record of such
tests is available on duplicate units. Loss evaluations and loss costs will be based on the values shown in
the "Special Conditions and Supplemental Instruction to Bidders." Transformers will be evaluated on
excitation losses and IZR losses at the specified rates. If tested losses exceed quote losses but are within
the tolerances of Table 18, ANSI C57.12.00-1987, the additional cost incurred from the differential of losses
will be calculated using the following equation and the above specified rates and will be deducted from the
original Purchase Order or back charged to the manufacturer. In Table 18 and the following equation "Units"
shall mean "Transformers of the same size and design on one order ".
Excess loss $ _ [No. of units] [(No Load Loss Evaluation $) (Avg. No Load Losses - Quoted No Load
Losses) + (Load Loss Evaluation $) (Avg. Load Losses - Quoted Load Losses)]. If this equation results in a
negative number, no credit will be given the Supplier.
If any unit or units exceed the tolerances of Table 18, ANSI C57.12.00-1987, that unit or units shall not be
shipped without express permission from the City. If accepted, the deduction for excess losses will be based
on the following equation: Excess loss $ _ (No Load Loss Evaluation $) (No Load Losses - Quoted No Load
Losses) But Not Less Than Zero + (Load Loss Evaluation $) (Load Losses - Quoted Losses) But Not Less
Than Zero.
3.2.2.15 SAFETY LABELS
NEMA 1260 Safety Labels shall not be applied by the manufacturer: Purchaser will apply customer warning
labels after delivery.
368-120
REV. SYM: FF
4 QUALITY ASSURANCE
4.1 GENERAL
4.1.1 RESPONSIBILITY FOR INSPECTION
Unless otherwise specified, the vendor is responsible for the performance of all inspection requirements
as specified herein. Except as otherwise specified, the vendor may utilize his own facilities or any
commercial laboratory acceptable to the City of Fort Collins. The City reserves the right to perform or
witness any of the inspections set forth in this Specification where such inspections are deemed
necessary.
4.1.2 TEST REPORT
The manufacturer shall furnish to the purchaser certified copies of the results of loss tests prior to
payment. Copies shall be sent to the Design Section as well as with the invoice. Unsigned copies are
not acceptable even if accompanied by a signed cover letter. The Quality Control Manager shall review
and sign each test report.
4.2 TEST CONDITIONS
Unless otherwise specified, testing required by Section 4.4 shall be conducted under the following
conditions:
4.2.1 REFERENCE TEMPERATURE
The reference temperature to which losses, impedance, regulation, and efficiency are corrected shall be
85°C.
4.2.2 TOLERANCE ON IMPEDANCE VOLTAGE
Impedance on completed units shall fall within the range specified herein.
4.2.3 TOLERANCE ON IMPEDANCE VOLTAGE ON A TAP
The percent departure of tested impedance voltage on any tap from tested impedance voltage at rated
voltage shall not be greater than the total tap voltage range expressed as a percentage of the rated
voltage.
4.3 Not used.
4.4 TESTS
The kinds of tests to be performed and the test procedures shall be as specified in ANSI C57.12.20, ANSI
C57.12.00, and C57.12.90 except as specified herein.
4.4.1 DIELECTRIC TESTS
No applied potential test shall be made. The induced -potential test shall be made by applying between
the terminals of one winding a voltage which will develop from high -voltage line terminals to ground a
voltage of 1000 volts plus 3.46 times the rated transformer winding voltage.
4.4.2 IMPEDANCE AND LOAD -LOSS TESTS
Impedance and load -loss tests shall be made on each unit and may not be omitted even if a record of
such tests made on a duplicate unit is available.
5 PREPARATION FOR DELIVERY
Transformers shall be prefilled with the appropriate amount of transformer oil and shall be shipped by open -bed truck.
Units shall be packaged in such a way as to provide for ease of handling and to protect units from shipping damage.
358-120
REV. SYM: FF
Units shall be packaged on four-way universal pallets with 34 inches minimum opening and loaded on the truck for
side removal. The Supplier shall give 24 hour notice prior to delivery for any shipments where an individual
transformer weighs over 5,000 pounds. In addition to these requirements, the Supplier shall comply with any
additional requirements or modifications shown on the purchase order and/or supplemental instructions.
6 DEFINITIONS AND ABBREVIATIONS
Vendor or Supplier - The manufacturer and/or manufacturer's agent supplying or quoting on the specified article.
Article, Unit, Assembly - All refer to the equipment defined by this Specification.
• DC or d.c. - Direct Current.
• AC or a.c. - Alternating Current.
• °C - Degree Celsius (Centigrade)
• °F - Degree Fahrenheit
• kV - 1000 volts.
• CPS or Hz - Cycles per second.
• psig - Pounds per square inch gauge.
• V or v - Volts.
• KVA - 1000 Volt-amperes.
10
368-120
REV. SYM: FF
APPENDIX A — Transformer Stock Number Coding
Below are examples that demonstrate the coding method used by City of Fort Collins to establish
transformer stock numbers.
I. SINGLE PHASE
Example #1-0==>
Transformer
Single Phase
00 = 13.2Y/7620 &
7620/13.2Y x
2400/4160 outside
pole
05 = 13.2Y7620 ESNA pole
20 = 13.2Y/7620 ESNA pad
II. THREE PHASE
Example #2 00=>
Transformer
3 Phase
Pad
368 - 300 - XYZ
Other
KVA
0 = 5 5=50
1=10 6=75
2=15 7=100
3=25 8=167
4=37.5 9=250
1 = single voltage
2 = dual voltage
KVA
006 = 75 075 = 750
015 = 150 100 = 1000
030 = 300 150 = 1500
050 = 500
• All suffixes indicate 208Y/120 sec.
• For 480Y/277 sec., add 1 to XYZ
(ie. 007 would indicate a 75kVA with
480Y/277 sec.)
APPENDIX B — DIMENSIONAL DRAWINGS
40' MAX
20' MIN
41{I MIN I MIN I M N I MIN MN• MIN I MIN 1 MIN
H1A /IJ H1B X3
` CABLE ACCESSORY
z PARKING STAND ,
X2
N N
O� GROUND PAD �O
MAX.
DIM.
KV
A
A
WITHOUT
RADIATORS
WITH
RADIATORS
25 k 5o
32.5"
--
100
--
42'
167
420
530
250
5Y
X1
REV. SYM: FF
1
4v MIN
7'z1� 32*max
I
18'=2'
1
s MINIMUM OPENING
IN BOTTOM OF COMPARTMENT
FOR CABLE ENTRANCE
Figure 1 — Type 1 Transformer Dimensions and bushing Designations (not to scale)
17
REV. SYM: FF
4 . 4INSIDE
IQNSIDE 2ejp j 10 r1 II MIN a
z FLANGE � TONI I ; ((KIM2) MIN
TANK SURFACE ` - - - - _ - - INSIDE
DETAIL a 4 MIN - - - - - I
CABLE ACCESSORY IJ MAX t= IB MIN OPENING ARBITRARY POINT
PARKING STAID (NOTE 2) 2_1
HIGFWOLTAGE CONNECTDRS 22 I 2
CABLE ACCESSORY S I MIN 23 MIN
PARKING STAND 2 2
.0 11/2 His 60o01504 MIN
X
SEE CABLE ACCESSORY 5: I
PARKING STAND E
DETAIL A SEE DETAIL A - / 6 kI
T 2&1 /2 t 1 5 _ 1
r le HIA B (NOTE 131
2 p 13 MIN D ail
s BA E �
SILL PLANE
GRouND PAD
10 ARBITRARY 4
POINT
Stock Number Dimension A Dimension B Dimension C Dimension D Dimension E
368-120-155 13" 5" 4" 0" 3
Figure 2 - Type 2 Transformer Dimensions and bushing Designations (not to scale)
13
368-120
The City may elect where applicable, to award bids on an individual item/group basis or on a total
bid basis, whichever is most beneficial to the City. The City reserves the right to accept or reject
any and all bids, and to waive any irregularities or informalities.
Sales prohibited/conflict of interest: no officer, employee, or member of City Council, shall have a
financial interest in the sale to the City of any real or personal property, equipment, material,
supplies or services where such officer or employee exercises directly or indirectly any decision -
making authority concerning such sale or any supervisory authority over the services to be
rendered. This rule also applies to subcontracts with the City. Soliciting or accepting any gift,
gratuity, favor, entertainment, kickback or any items of monetary value from any person who has or
is seeking to do business with the City of Fort Collins is prohibited.
Freight terms: unless otherwise noted, all freight is F.O.B. Destination, Freight Prepaid. All freight
charges must be included in prices submitted on proposal.
Discounts: any discounts allowed for prompt payment, etc., must be reflected in bid figures and not
entered as separate pricing on the proposal form.
Purchasing restrictions: your authorized signature of this bid assures your firm's compliance with
the City's purchasing restrictions. A copy of the resolutions is available for review in the Purchasing
Office or the City Clerk's Office. Request Resolution 91-121 for cement restrictions.
Collusive or sham bids: any bid deemed to be collusive or a sham bid will be rejected and reported
to authorities as such. Your authorized signature of this bid assures that such bid is genuine and is
not a collusive or sham bid.
Bid results: for information regarding results for individual bids send a self-addressed, self -stamped
envelope and a bid tally will be mailed to you. Bid results will be posted in our office 7 days after
the bid opening.
James B. O'Neill II, CPPO, FNIGP
Director of Purchasing and Risk Management
REV. SYM: FF
Pad Dimensions
This drawing is not intended to dictate requirements for items purchased under Specification 368-120 but is included as
an aid to those users desiring a minimum of pad designs for the transformers covered by Specification 368-120.
The dimensions in inches of Figure 3 will fit the minimum compartments on transformers covered by this Specification as
well as the maximum transformer envelope.
48'
48-
12
PRIMARY
SECONDARY
0 12'
ROM
15' — 8' 12-
8'
3--
15• —'
FO
LEN
3'
3'
71/TY T
Notes on Pad Matenal -
1. Concrete must be 3,000 psi minimum.
2. Maximum coarse aggregate size 1 12 inches.
Space requirements for pad and primary switching cabinet will generally
be 9' X 12'. Factors to be considered in locating me pad Include -
1. Amessibility - The transformer pad shall be accessible to
line boom trucks equipped for the installation and removal of
heavy transformers. Such accessibility shall not require
intrusion on adjacent property.
2. Proximity of Buildings, Walls, Barriers, and/or Overhangs -
In addition to the clearances required for installation and
removal, the minimum clearance in front of Me transformer pad
shall be eight (8) feet and the minimum clearance from all
other sides shall be two (2) feet. If the building has an
overhang, clearance to the edge of the transformer pad shall
be measured horizontally from the outer edge of the overhang.
Transformers through 300 KVA may be installed under the
overhang if the vertical clearance between the pad and the
overhang is at least 25 feet and the location is accessible to
line boom trucks.
3. Codes and Standards - In addition to the above, the
installation shall conform to the National Electric Code and
federal, state and city codes and standards.
Figure 3 — Pad Dimensions
L
T3.
F3"
T
T2.
11R Q REBAR
GTH AND WIDTH
14
368-120
REV. SYM: FF
APPENDIX C — Approved Manufacturers
Transformers purchased under this Specification shall be of the make shown below. Manufacturers not listed below may
submit written proposals demonstrating compliance with these Specifications for consideration of addition to the accepted
manufacturers list prior to the next request for bids. In addition to inclusion on the list below, manufacturer's equipment
must also satisfy all requirements of this Specification to be acceptable.
MANUFACTURER SERIAL NO.
ABB
All
Cooper Power Systems All
General Electric All
Howard Industries All
The manufacturers in the following list have been conditionally approved and may bid as an alternate. The definition and
intent of "Conditional Approval' of a manufacturer is to allow the City to gain some experience with the manufacturer's
product. Should a conditionally approved manufacturer be the evaluated low bidder, the City reserves the right to award
all, part, or none of the order to them, dependant upon the current needs of the City for that item or items.
15
368-120
TRANSFORMER LOSS EVALUATION - AVERAGE LOSSES
City Order No. S/N
Manufacturer Invoice No.
KVA/Unit
LINE
DESCRIPTION
(1)
No. of units
(2)
Average core losses
(3)
Quoted core losses
(4)
Excess average core losses:
line (2) less line (3)
(5)
Penalty for excess average core losses:
line (1) x line (4) x $
(6)
Average copper losses
(7)
Quoted copper losses
(8)
Excess average copper losses:
line (6) less Ie (7)
(9)
Penalty for excess average copper losses:
line (1) x line (8) x $
(10)
Penalty to be assessed manufacturer:
line (5) plus line (9) but not less
than zero
Date Prepared By:
Design Engineering
AMOUNT
REV. SYM: FF
NOTE: If any unit(s) exceeds the loss tolerances of ANSI C57.12.00, Light & Power will either reject it,
include it on these averages, or calculate losses using the Individual Transformer Losses Evaluation
Form, whichever is most favorable to Light and Power.
I
JWw ILV
INDIVIDUAL TRANSFORMER LOSS EVALUATION
City Order No. S/N
Manufacturer Invoice No.
KVA/Unit
LINE DESCRIPTION AMOUNT
(1) Tested core losses
(2) Quoted core losses
(3) Excess core losses
line (1) less line (2) but not less
than zero
(4) Percent difference %
line (3) ❑ line (2) x 100
(5) Tested total losses
(6) Quoted total losses
(7) Excess total losses
line (5) less line (6) but not less
than zero
(8) Percent difference %
line (7) ❑ line (6) x 100
(9) Tested copper losses
(10) Quoted copper losses
(11)Excess copper losses
(12) line (9) less line (10) but not less
than zero
(12) Penalty for excess core losses
line (3) x $
(13) Penalty for excess copper losses
line (11) x $
(14) Penalty to be assessed manufacturer
line (12) plus line (13)
Date Prepared By:
Design Engineering
REV. SYM: FF
368-120
Issued: 8/17/72
Revised: 1 /21 /94
Special Conditions and
Supplemental Instructions to Bidders
Applicable to
Specification 368-120
A. Data to be Supplied with Bidder's Proposal
The following data shall be supplied with the bidder's proposal in addition to that
information required by the "Invitation to Bid".and the "Purchase Requisition".
A typical list of users of 1 phase padmounted distribution class
transformers manufactured by the bidder during the past.five years.
2. A typical drawing of the transformers showing that they will meet the
critical dimensions required by the Specification.
3. Impedance volts in % at full load, high voltage to low voltage at 850C.
4. No load and total losses at 850C.
5. Delivery in weeks.
6. A statement indicating compliance with our Specification without
exception or a detailed list of exceptions.
7. Escalation is — is not _applicable for the transformers bid. If escalation
applies, the Bidder shall indicate in his bid the specific items or materials
subject to escalation, and shall give the method and indices to be used in
computing the amount thereof. Escalation occurring after the quoted
delivery date will not be paid unless delays are the result of actions by the
City. Escalation occurring after acceptance, if Purchaser exercises the
option to delay shipment after manufacturing is completed, will not be
paid.
If the above information and compliance statement are not supplied, the proposal will not
be evaluated.
An alternate bid for the total order may be submitted in addition to the unit bids.
B. Loss Evaluations
Loss penalties and loss evaluations will be based on the
following values:
No load or excitation losses at $3.90/watt.
2. Load losses at $1.50/watt.
C. Shipping Terms
Ship F.O.B. point of destination, freight prepaid.
D. Terms of Payment
I. If escalation applies, the City of Fort Collins shall not be billed for
escalation occurring after the promised delivery date.
2. Test reports shall accompany the invoice. If test reports do not accompany the
invoice, late payment penalty charges incurred due to delays in obtaining the test
reports will not be paid. Certified copies of test reports shall be sent to the Design
Section, Fort Collins Light and Power Utility.
3. Loss penalty credits and escalation charges shall be itemized on the
invoice.
FIRM
CITY OF FORT COLLINS
BID PROPOSAL
BID NO. 7282
LP Transformers, 25kVA & 100kVA, Padmounted, Single Phase
BID DATE: 3:00 p.m. (Our clock) October 7, 2011
WE HEREBY ENTER OUR BID FOR THE CITY OF FORT COLLINS' REQUIREMENTS FOR LP
Transformers, 25kVA & 100kVA, Padmounted, Single Phase, PER THE BID INVITATION AND ANY
REFERENCED SPECIFICATIONS.
QUANTITY: DESCRIPTION:
30 Ea. TRANSFORMER, 25 KVA PAD -MOUNTED, ANSI TYPE 1,
COMPARTMENTAL -TYPE, SINGLE PHASE DISTRIBUTION WITH
SEPARABLE INSULATED LOAD BREAK HIGH -VOLTAGE
CONNECTORS.
HIGH VOLTAGE RATING: 13200 GRDY/7620.
LOW VOLTAGE RATING: 240/120.
SERIAL NUMBER 130 TO BE IN ACCORDANCE WITH
SPECIFICATION #368-120-130, REVISION FF.
PLEASE COMPLETE THE ATTACHED EXCEL SPREAD SHEET FOR
BID SUBMITTAL.
IF YOU ELECT TO PASSWORD PROTECT YOUR BID, PLEASE
NOTE THAT PASSWORD BELOW.
*Any surcharges or additional costs shall be noted & included in bid submittal.
The transformers being bid meet or exceed the specifications. Yes No. If not,
please list exceptions,(specifying paragraph reference number) on a separate sheet of paper and
attach to your bid.
Escalation is , is not applicable for the transformers bid. If escalation applies, the
bidder shall indicate in his bid the specific items or materials subject to escalation, and shall give
the method and indices to be used in computing the amount thereof. Escalation occurring after the
quoted delivery date will not be paid unless delays are the result of actions by the city. Escalation
occurring after acceptance if purchaser exercises the option to delay shipment after manufacturing
is completed, will not be paid.
20 Ea. TRANSFORMER, 100 kVA PAD -MOUNTED COMPARTMENTAL
TYPE, SINGLE PHASE DISTRIBUTION WITH SEPARABLE
INSULATED LOAD BREAK HIGH VOLTAGE CONNECTORS.
HIGH VOLTAGE RATING: 13200 GRDY/7620.
LOW VOLTAGE RATING: 240/120.
SERIAL NUMBER 170 TO BE IN ACCORDANCE
WITH SPECIFICATION #368-120-170, REVISION FF
PLEASE COMPLETE THE ATTACHED EXCEL SPREAD SHEET FOR
BID SUBMITTAL.
IF YOU ELECT TO PASSWORD PROTECT YOUR BID, PLEASE
NOTE THAT PASSWORD BELOW.
*Any surcharges or additional costs shall be noted & included in bid submittal
The transformers being bid meet or exceed the specifications. Yes No. If not,
please list exceptions,(specifying paragraph reference number) on a separate sheet of paper and
attach to your bid.
Escalation is , is not applicable for the transformers bid. If escalation applies, the
bidder shall indicate in his bid the specific items or materials subject to escalation, and shall give
the method and indices to be used in computing the amount thereof. Escalation occurring after the
quoted delivery date will not be paid unless delays are the result of actions by the city. Escalation
occurring after acceptance if purchaser exercises the option to delay shipment after manufacturing
is completed, will not be paid.
Delivery may be a consideration of bid award.
For purposes of warranty and service ONLY approved manufacturers or distributors authorized by an
approved manufacturer to serve the Fort Collins area may bid.
The City of Fort Collins reserves the right to split the bid in whatever percentages are most
advantageous to the City.
Future orders of LP Transformers 25kVA & 100kVA, Padmounted, Single Phase may be
authorized, at the option of the City, from this bid for a period of five years after date of award.
Satisfactory pricing and delivery is required for future orders based on this bid.
SUPPLEMENTAL INSTRUCTIONS
Prices quoted must remain firm for a 30 day period after the opening date.
Freight terms: F.O.B. destination freight prepaid. All freight charges must be included in pricing
submitted on proposal and not entered as separate pricing.
Any discount allowed by Vendor for prompt payment, etc. must be reflected in quoted figure, and
riot entered as separate pricing.
The City reserves the right to accept or reject any and all quotes.
Bidder not responding to the services requested in this bid shall be removed from our automated
listing for: Not Applicable
Any questions or inquiries regarding this bid should be directed to:
Opal F. Dick, CPPO, Senior Buyer
(970)221-6778
SIGNATURE AND TITLE: TYPED OR PRINTED NAME AND TITLE
COMPANY NAME: (AREA CODE) TELEPHONE NUMBER/FAX NUMBER
ADDRESS: STREET, CITY, STATE, ZIP DATE
EMAIL:
Purchase Order Te= and Conditions
1. COMMERCIAL DET.IBS.
Ts exemptions. By sramce the City of Fort Collier is er hurt suite and local tams. Our Exemption Number a
9"502. Federal rx.i a Ts Exemption Catificace of Registry gg6000587 is regismed with the Collector of
Internal Regime, Demo, Colorado (Ref Colorado Recsd Stamps 1973, Chapter 39-26, 114 Ca).
Goods Rejected GOODS REJECTED due to faih¢e to mart specifications, sths when shipped or doe to defects of
damage in nmsi5 may be renamed m you m credit and are not in be replaced except upon receipt of written
instructions from the City of Fan Collins.
Inspection. GOODS an subject in the City ofFon Collins inspection on arrival.
Fined Acceptance. Receipt of the m�rF•Mic>, services as equigmmr m response m this order can result in
ame„d.ed payment on the pan of the City of Fort Collins. However, it is in be understood mat FINAL
ACCEPTANCE is depeadem apom completiou of aB apptirabie regmmd tnspecrim pmedores.
Freight Teems. Shipments toot be F.O.B., City of Purr Collins, 700 Woad St, Fort Collins, CO 80521 unless
otherwise specified On this Order. If permission is given in prepay freight and charge wpaately, the anginal freight
b>D mast ucompmy invoice. Additiovat changes fan part. willrutb accepted
Shipment Dimace. When mamGcnovs have distributing pasta in vmioo pan of the compy, shipment is
expected from the mm art thsmbudon point in destination, and excess freight will be deducted from Invoice when
shipments artmadefromgrewerdirtz a.
Permits. Seller shall Fructose it sellers sole cost all necessary peffiR csti5cares and licenses required by all
applsable, laws, regulations, mdmmces and rules of she sum, mmwipality, terrimry Or political sabdivlvon where
the wort is performed, or required by any nabs duly crosthmed public smbmhy having jmidicom mzr the wink
of vedco. Sens meths agrees to hold the City of Fan Collins harmless from and against all Imbilky and loss
incurred by them by reason of an asserted or muddished violaom of nay inch Laws, regulations, ordinates, rules
and req®mm¢
Authorization All pores to this commit agree that the cepreseomtives are, in fart, born fide and possess fall and
complete mmmty in bind said pores.
LI ITATWN OF TERMS, This Purchase Order expressly times acceptance in the terms and conditions rated
herein rat ford and M mpplare nary a addaena arms and conditions annexed hereto Or incorporated harem by
reference. Any addrmal or difirent terms and conditions proposed by seller are objee4d to and benby rejected
2. DELIVERY
-
PLEASE ADIME PURCHASING AGENT rarely if you canvas make camplew shipment to, amen on your
promoted delivery date a noted I= is of the essence Delivery and performance mart be effected within the time
stated On the parchrse ads and it* disconnects atucbed harem. No tin of the Aactasas including without
limtaron, acceptance of partial late deliveries, shall operate as a waives of tbis pravivoa In the event of my delay,
the Purchaser shag have, in addition ro other legal and equitablesemedies, the option of plrcmg thisorderebewbere
and holds% the Sells ruble for dosages. Aaveva, the Seger shall rut be 1nablafm damages u a resort of delays
due to causes ono reasonably foreseeable winch an beyond in reasonable control and without in fault of negligence,
such acts of Gad, acts of evil or military authorities, governmental pliames, furs, strikes, flood, epidemics, wan or
iron provided that notice of the candiuons cursive such delay is given m the Purchases witho five (5) days of the
time when the Sells fast received kanwledge thereof In the event of my such delay, the date of delivery shall be
extended for the period equal is, the time actually lost by ream of the delay.
3. WARRANTY
The Seller wammn that all goods, mrdes, materials and word covered by this order will conform with applicable
drawings specifications. samples aodror other descriptions given, will be fit for the purposes intended, and
performed with the bigbest degree of cm and cotunesmc , in accordance with accepted stmdads for wend of a
rmun, came The Seller agrees m hold the purchases hamless from any Ions, damage or expense which the
Purchase msy ruffs a ntcm on ccoom of the SeUm breach of warrmty. Tie Sens shag replace, repair or make
good widow cost in the purchaser, any detects Or faults miring wnhm one (1) year or within inch longs period of
core n may be prescribed by Ina or by the terms of any applicable wmmry provided by the Sells tits the daft of
accep®ce of the goods famished beeaer (acceptance our in be unreasonably delayed), resulting from Imperfect
or defecose wod done or matsiais form bed by rh Sells. Acceptance or me of goods by the Purchaser shall em
constiame a waiver of my claim under this wmmty. Except as orhawise provided in this purchase Order, the Sellers
liability hereunder sban extend to all damages Proximately carried by the breach of may, of the foregoing waaanms
or guarantees, but wash liability shall in our event wclude loss of profits or lass of nits NO IMPLIED WARRANTY
OR b>EIICHANTAB11TfY OR OF FITNESS FOR PURPOSE SHALL APPLY.
4. CHANGES IN LEGAL TERMS.
The Purchaser may mate changes to legal terms by wsittm change order.
5. CHANCES IN COMMERCIAL TERNS_
The Purchases may mate any changes in the terms, other than legal terms, including sddidar, in or deknom from
the gmmurn orogreffiy ordered on the specifications Or dtawmp by cabal Or written change Order. If any such
change ifsts the rumors doe Or the time ofpexSommce hereunder, m equitable adjosimm r shall be merle.
6. TERMINATIONS.
The Purchases may n my noun by written change Order, terminate this agremeat as many or all pomms of the
goods than rut shipped subject o any eguiwble edjnat ceor between me parties a in my wod Or materials this in
progress provided that the Purchaser shall not be liable for any claims fur anticipated podia on the uncompleted
potim of the goods =&in work, for iucidenw] or consequential dmages, and ma on such adjustment be made in
fare of the Seller with respect o any goods which are the Sellers standard sock No such termination shall relieve
tit Parchass orthe Sells of my of theirobligations m m any goods ddivsedbands_
7. CLA54S FOR ADILSTMENT.
Any demo fur adjmmeor mint ba assented within minty (30) days from the dace the h— Or tetmmatm is
ordered.
S. COMPLIANCE WITH LAW.
The Seller warmer that all goads sold hereuner shall have been produced sold delivered and fomisbd in sma
compliance with an applicable Laws and regaLatom Or which the goads are subject The Seller shelf secrete and
deliver such docomests as may be required to effectOr evidence compliance. All laws and regulations required to be
incorporated in agreements, of this character are hereby incorporated herein by dus reference. The Seller agrees to
indemnify and hold the Purchaser harmless from all corn and dsrnagas suffered by me Pmcbrum as a result of the
Sellers failure in comply, with such Law.
9. ASSIGNMENT.
Neither pasty shell assign, trmsfs, or county this order, or any tries due or to became due hereunder without the
prior wrimen consent of the other pony.
10. TITLE.
The SeI4s wartanrs full, dear and mresmcted title to the Purchaser for,ul egmpmen; matendu, and item famished
in performance of this agreement, free and clear of my and an Bens, resmctivas, reservations, security concert
encumbrances and claims of others.
11. NONWARER
Failure of ilia Purchaser in insist upon strict performance of the terns and conditions hereof, bit =err delay in
emrdse my rights Or remedies provided hereon or by law, failure to promptly may the Seller in the e-mt of a
breech, the acceptance ofar payment for goods hereunder Or Vp r xI of the design, shell not reteme the Seller of
my of the warranties or obligatiom of this purchase Order and shall Out be deemed a waive of my right of the
purchase to insist upon strict performance hereof or any of in ruts or remedies u m any inch goods, rt;ardl.
of when shipped, received or accerped, n to, my prior or subsequent defmlt he[smder, Hoer shall my purported
and modification or res¢asiw of this purchase Order by the purchaser operate a a wader of any of the arms
hereof
12. ASSIGNMENT OF ANTITRUST CLAIMS.
Seller and the Posthaste secagoire the in cool economic practice, overcharges resulting from antltsm-t
violations an in fact bone by the Purchaser. Theretofore, for good cause and ss consideration for exercising this
purchase Order, the Seller hereby mrigns in the Purchaser any and all claims it may now have a hereafter
acquired order federal or some austrint laws for such overcbarges rely®g to the particular goads or services
purchased or, acquired by the Pmclrasset posu>o in this pmchae Order.
13. PURCHASERS PERFORMANCE UPSET r pure OBLIGATIONS.
If the Purchaser direcn the Seller to correct omwMaming or defective goods by a dace to be agreed upon by the
Purcbssec and the Seller, and the Sells tbereafRr indicates on mabilry, or mwitlirguers m comply, the Purchaser
may cans, the weds to be performed by the most expeditions means available m a, and the Sells shall pay all
cost, asoclated with sari, ninth.
The Sells slug release the Purchaser and in contactors of any tier from all liability and claims of any uanue
resulting from the performance of such word.
This release shall apply even in the event of (ants of negligmce of the party released and shall eased in the
directors, offess and employees of such lorry.
The Sellers r unuacmal obligations, including warranty, shag not be deemed to be reduced. in any way, because
such wad u performed or caused to be performed by the Purchases.
14. PATENTS.
Whenaver the Seller is required m use any design, device, rtutndad a process covered by letter, patent, nademad
or copynght, the Sells shall indemnify and save harmless the Purchaser from my and all dorms Orr iafrioegrmem
by reason of the use of such patented design, deice, megrim] or process in connection with the contract, suit
shall mnd nrmify the Purchaser for my cost, expense Or damage wbwb U may be obliged to pay by reason of curb
mfr extent at my titan shoring the Prosecution Or after the completion of the work to case said egtsm,v_em or
any pan thereof Or the intended use of the goods, is in such suit held in insurance iafrmgeement and the use of
mid egmpmem or pm is enjoined, the Seller shag a in awn expense and it in option, enber pocore fur the
Purchaser de right to comome wing said egmpmem Or psis, replace the sure with substantially equal but
m^ aging ;�=, Or modify b so it becomes oamfiingiog.
15. INSOLVENCY.
If dw Sells &bell become mirin-m w bivinaps, mate an asstgo for the heretic a creditors, appoint a
receiver or rusme for any of she Sells property or business, that order may forthwith be canceled try the
Purchaser erttbunt liability.
16.00%9MNINGLAW.
The demddms of arms used at the interpretation of she agteemem and the rights of all parties hereunder shall be
cousrued undet and governed by the laws of the Sum of Colorado, USA.
The following Additional Conditions apply Orly m cases where the Seller is m perform wort beteoder,
mcldmg the services of SellersRepre ssicare(s), on de premises ofodws_
17. SELLERS RESPONSIBILITY.
The Seller shall carry on said wort a Sellers own risk ®1 the same is fully completed and accepted, end sha1L
in case of any ccider; deswcrm or injury to the went andr'or uratmals before Sellers final completion and
acceptance, carnpkw de worka SeWs owur expense and o the musbc of the Potthass. Whm matsiah
ad equipment m furnished by others for m.tallat n,, or eserboa by the Seller, the Seller shall receive, mload
wine and hand, same at the rare and become responsible therefor a thoagh such materials andor equipment
wse being famished by the Seller seder the order.
Is. INSURANCE
The Sells shag at his own expense, provide for the payment of w it ers compensation, including occupations
disease bme5n, to in employees employed urn Or in romectim wins the wmnc .mueted by rlis pmcluse weer,
andtor m !hart depeadmis in accordance with the laws of the son in which ate work is to be done. The Seer
shall also carry comprelxasne general liability including, but not limited in. contracted and antomobne public
kabitry insurance with bodily injury and death 1imm of at kern $300,000 for say, am person, $500 000 fur, any
one acrfdet and property damage limit per accident of S400,000. The Seller shall ttewise require his
contractors, if any, to proride for such compensation and msmauce. Before any of the Sellers or his conwacca s
employees shall do ray, wod upon the p®irea of odsy the Seller shin In— the Purchases with a ceittft me,
that such compensation and mom mse lu ve been prorided Such certifica es shall specify the date when such
comisemaroo and insorme have been Presided Such remficates shell specify the data when such compmsatwn
and insurance spires. The Sells agrees that such compensation and res exu ce shall be --i- .m d until acts the
eutire work is completed and accepted
19. PROTECTION AGAINST ACCIDENTS AND DAMAGES.
The Sells hereby aroma the come responsibility and liability for any and an damage, loss or calory of any, kind
err omme wharsaees m Pevom u property caused by or reminng from the easvmon of the work provided for in
this purchase odv or in connection hsewith. The Sells win indemnify and hold hatless the Purchases a any
or a0 of the Purchasers officers, agents ad employees from and against any ad all claims, lasts, damages,
chugs Or expmse> whether duct or indirect; and whether in persons or property m which the Purchaser may
be pm Or subject try reason of any act, action, neglect, omission or defaeh on the pan of the Seller, any of his
conaurors, or any of the Sellers or cantrxmrs afbcen, agent or employees. In case any suit or other
proceedings span be brought againtt the Pmrbaser, a is affairs, agems or employees a my time as accoot or
by reason of my act, urns, ncglecl emisnon or desalt of the Seller of any of his contractors or any of in or
their officers, agents Or employees u aforesaid the Seller bereby agrees in assome the defend thereof and to
deft -]the sure at the Sellers own expmae, m pay any and all costs, charges, atarmays fees and other expenses,
my and an judgmmrs that may be incurred by or remit against the Purchases or any of in or them Officers,
agents or amployees in such sain Or other proceedings, and in rase judgment in Omer lien be placed anon or
obramd agmst the property of the Pocbases, Or said parties in Or as a remk of such stun Or atlas proceedings,
theSeller will atonce came the same to be dissolved and discharged by Citing bond or otherwise. The Sells ad
his (mum in shall take an safety PrsaEmOm, furnish ad icsan all goads necessary fun the Preiention of
accidents, comply with an laws and regulations with regard in safety mchithng. but without Initiation, the
Occapatioml Safety and hearth Act of 1970 and an rules and regulatio s issued pmamr therm.
Revised 03R010
THE CITY OF FORT COLLINS
Light and Power Department
P.O. Box 580
Fort Collins, CO 80522
SPECIFICATION NO: 368-120
TITLE: PAD -MOUNTED COMPARTMENTAL -TYPE, SINGLE-PHASE
DISTRIBUTION TRANSFORMERS
WITH SEPARABLE
INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS
APPROVED BY:
Kraig E. ad
Standards Engineering Manager
ORIGINATED: 09/14/72
LAST REVISED: 7/21/2004
ITEMS COVERED BY THIS SPECIFICATION
DESCRIPTION
STOCK NO.
SPECIFICATION
NO.
SERIAL
25 KVA, 120/240 ANSI Type 1 Transformer.
368-120
-130
50 KVA, 120/240 ANSI Type 1 Transformer.
368-120
-150
50 KVA, 120/240 ANSI Type 2 Transformer.
368-120
- 155
100 KVA, 120/240 ANSI Type 1 Transformer.
368-120
-170
167 KVA, 120/240 ANSI Type 1 Transformer.
368-120
-180
250 KVA, 120/240 ANSI Type 1 Transformer.
368-120
-190
REV. SYM: FF
PREVIOUS REVISION DESCRIPTIONS ON FILE
REVISION DESCRIPTION
APPROVED
REVISION DD:
Sagen
• Paragraph 3.2.2.7.5: Editorial
10/21/94
• Add paragraph 3.2.2.9.4 requiring pentahead locking bolts
• Paragraph 3.2.2.13 add glossy to paint requirement
• Paragraph 4.2.2: Clarify impedance requirement
REVISION EE:
Sagen
• Paragraph 5.0: revised pallet size from 28 to 34 inches
2/25/98
REVISION FF
Kraig Bader
• Added 50kVA ANSI Type 2 Transformer (368-120-155) to Specification
7/21/2004
• Changed paint color to standard Munsell Green
• Reorganized to consolidate impedance and fusing requirements into one table.
• Consolidated secondary terminal requirements into one table.
• Added maximum impedance requirement for 250kVA transformer (+/-7.5% from nominal for
transformers with impedance greater than 2.5%) per ANSI/IEEE C57.12.00-2000.
• Re-evaluated fusing requirements of all transformers in this specification. Went from dual
sensing bay-o-net (expulsion) fuses to current sensing bay-o-net (expulsion) fuses. Fuse sizing
was changed as follows:
Changed 25 kVA from 8A expulsion / 40 amp CL to 10A expulsion / 30A CL
• Changed 50 kVA from 15A expulsion / 80 amp CL to 15A expulsion / 40A CL
• Changed 100 kVA from 25A expulsion / 175 amp CL to 25A expulsion / 80A CL
• Changed 167 kVA from 40A expulsion / 200amp CL to 40A expulsion 1125A CL
• Changed 250 kVA from 65A expulsion / 350amp CL to 65A expulsion / 125A CL
2
368-120
I:l:kTA&'/&1t32
TABLE OF CONTENTS
PREVIOUS REVISION DESCRIPTIONS ON FILE..........................................................................................................................2
1 SCOPE
2 APPLICABLE DOCUMENTS............................................................................................................................................................4
2.1 ANSI C57.12.00 - DISTRIBUTION, POWER, AND REGULATING TRANSFORMERS, AND SHUNT REACTORS, GENERAL REQUIREMENTS
FOR......................................................................................................................................................................................................... 4
2.2 ANSI C57.12.25 - PAD MOUNTED, COMPARTMENTAL -TYPE, SINGLE-PHASE, DISTRIBUTION TRANSFORMERS WITH SEPARABLE H-V
CONNECTORS, STANDARD REQUIREMENTS FOR.......................................................................................................................................4
2.3 ANSI C57.12.28 - SWITCHGEAR AND TRANSFORMERS - PAD -MOUNTED EQUIPMENT -ENCLOSURE INTEGRITY...............................4
2.4 ANSI C57.12.70 - TERMINAL MARKINGS AND CONNECTIONS FOR DISTRIBUTION AND POWER TRANSFORMERS...............................4
2.5 ANSI C57.12.80 - TERMINOLOGY FOR POWER AND DISTRIBUTION TRANSFORMERS........................................................................4
2.6 ANSI C57.12.90 - DISTRIBUTION, POWER, AND REGULATING TRANSFORMERS, AND SHUNT REACTORS, TEST CODE FOR.................4
2.7 IEEE C57.91 - GUIDE FOR LOADING MINERAL -OIL -IMMERSED OVERHEAD AND PAD -MOUNTED DISTRIBUTION TRANSFORMERS
RATED 500 KVA AND LESS WITH 650C OR 550C AVERAGE WINDING RISE.........................................................................................4
3 REQUIREMENTS................................................................................................................................................................................4
3.1 GENERAL REQUIREMENTS FOR DESIGN...............................................................................................................................4
3.2 SPECIFIC DESIGN REQUIREMENTS..........................................................................................................................................5
4 QUALITY ASSURANCE
7
4.1 GENERAL.......................................................................................................................................................................................9
4.2 TEST CONDITIONS.......................................................................................................................................................................9
4.3 NOT USED.........................................................................................................................................................................................9
4.4 TESTS..............................................................................................................................................................................................9
5 PREPARATION FOR DELIVERY....................................................................................................................................................9
6 DEFINITIONS AND ABBREVIATIONS........................................................................................................................................10
APPENDIX A -TRANSFORMER STOCK NUMBER CODING...................................................................................................11
APPENDIX B - DIMENSIONAL DRAWINGS.................................................................................................................................12
PADDIMENSIONS..............................................................................................................................................................................14
APPENDIX C - APPROVED MANUFACTURERS.........................................................................................................................15
TRANSFORMER LOSS EVALUATION - AVERAGE LOSSES....................................................................................................16
INDIVIDUAL TRANSFORMER LOSS EVALUATION.................................................................................................................17
3
368-120