INVITATION TO BID
7229 LP Transformers 75kVA Single Phase Underground
BID OPENING: 3:00 P.M. (our clock), April 26, 2011
Sealed bids will be received and publicly opened at the office of the Director of Purchasing and Risk
Management, PO Box 580, 215 North Mason St., 2nd floor, Fort Collins, Colorado 80522, at the
time and date noted on the bidProposal and/or contract documents. If delivered, they are to be sent
to 215 North Mason Street, 2" Floor, Fort Collins, Colorado 80524. If mailed, the address is P.O.
Box 580, Fort Collins, 80522-0580.
Bids must be received at the Purchasing Office prior to 3:00 p.m. (our clock), April 26, 2011.
Questions regarding bid submittal or process should be directed to Opal Dick, CPPO, Senior Buyer
at (970) 221-6778.
Special Instructions
All bids must be properly signed by an authorized representative of the company with the legal
capacity to bind the company to the agreement. Bids may be withdrawn up to the date and hour set
for closing. Once bids have been accepted by the City and closing has occurred, failure to enter into
contract or honor the purchase order will be cause for removal of supplier's name from the City of
Fort Collins' bidders list for a period of twelve months from the date of the opening. The City may
also pursue any remedies available at law or in equity. Bid prices must be held firm for a period of
forty-five (45) days after bid openings.
Submission of a bid is deemed as acceptance of all terms, conditions and specifications contained
in the City's specifications initially provided to the bidder. Any proposed modification must be
accepted in writing by the City prior to award of the bid.
Only bids properly received by the Purchasing Office will be accepted. All bids should be clearly
identified by the bid number and bid name contained in the bid proposal.
No proposal will be accepted from, or any purchase order awarded, to any person, firm or
corporation in default on any obligation to the City.
Bids must be furnished exclusive of any federal excise tax, wherever applicable.
Bidders must be properly licensed and secure necessary permits wherever applicable.
Bidders not responding to this bid will be removed from our automated vendor listing for the subject
commodities.
The City may elect where applicable, to award bids on an individual item/group basis or on a total
bid basis, whichever is most beneficial to the City. The City reserves the right to acceptor reject any
and all bids, and to waive any irregularities or informalities.
Rev Sym: B
Specification for Single Phase Submersible Cover Mount Transformer
1SCOPE
This specification establishes the minimum requirements for single phase, 60 hertz, mineral oil filled, self cooled,
vault type distribution transformers purchased by the City of Fort Collins Electric Department.
Transformers of this design are for installation on an underground power system utilizing separable insulated
connectors and may be installed in underground vaults subject to submersion. The transformer tank and all
external appurtenances shall be of corrosion -resistant material, unless they are otherwise rendered corrosion
resistant.
2 APPLICABLE DOCUMENTS
Unless otherwise stated in this Specification, all transformers shall be new and shall conform to the American
National Standard Requirements for Underground Type, Self Cooled, Single Phase Distribution Transformers,
ANSI C57.12.23 - latest revision. In case of conflict, the requirements of the following documents shall apply in
the priority shown:
1. This Specification.
2. Referenced ANSI Standards.
Approved manufacturers are listed in Appendix C. For purposes of warranty and service, any distributor
bidding must be an authorized distributor appointed by an approved manufacturer to serve the Fort Collins
area. The following standards for distribution, power, and regulating transformers and shunt reactors form a
part of this Specification:
• General Requirements
C57.12.00
• Underground Type Distribution Transformers
C57.12.23
• Terminal Marking and Connections
C57.12.70
• Terminology
C57.12.80
• Test Code
C57.12.90
• Appendix to ANSI C57.12.20
C57.91
• Separable Insulated Connectors
ANSI/IEEE 386
3 KILOVOLT -AMPERE RATINGS
Kilovoltampere ratings shall be continuous and based on, but not exceeding, an average winding temperature rise
of 55 'C and a hottest -spot temperature rise of 70 'C. The temperature rise of the insulating oil shall be measured
near the top of the tank and shall not exceed 55 'C. The transformers shall have a temperature -rise insulation
system of 65 'C.
The kilovoltampere ratings for transformers conforming to this standard shall be suitable for continuous operation at
the rated kilovoltamperes, provided that the temperature of the cooling air (enclosure ambient temperature) does
not exceed 50 'C and the average temperature of the cooling air does not exceed 40 'C for any 24-hour period.
KVA ratings shall be in accordance with Table-1.
4 BUSHINGS AND TERMINALS
All internal leads and connections, on both high and low voltage, shall be sized to carry full ampere rating, including
overload rating of transformer.
4.1 HIGH VOLTAGE TERMINALS
The number and electrical characteristics of the high voltage terminals required are specified in Table 1. High -
voltage bushing wells shall be top -mounted 200A load -break interface bushings rated for 8.3/14.4 kV
4
368-110
Rev Sym: B
maximum continuous voltage, and 95W BIL and full wave crest voltage in accordance with ANSI/IEEE
Standard 386. It is not required that bushing well Inserts be supplied with the transformers.
On phase -to -ground transformers, the F+ end of the high -voltage winding shall be connected to the tank
internally. This connection shall be independent of all other electrical connections.
42 LOW VOLTAGE TERMINALS
Terminal type and number shall be in accordance with Table 1 of this specification, and shall be positioned for
additive polarity per ANSI C57.12.23 - 2000. Terminals shall be welded Central Moloney 5/8' threaded copper
stud -type bushings with external epoxy. The low voltage terminals shall have a BIL of 3OkV.
Terminals shall be singly mounted on the top at 5.5 to 7.5 inch center to center spacing. Stud type terminals
shall be Central Moloney bushings with a 5/8" copper stud. Bushings shall have dimensions in accordance
with Figure 1 of this specification, with a bushing sealing surface diameter no greater than 1.38". All non-
metallic components of the terminals shall be manufactured of a material resistant to ultra -violet degradation.
Mounting hardware shall be corrosion resistant.
5/8° Threaded Copper Stud
Max_ 1.38" dia. Sealing Surface
Figure 1 —Secondary Bushing Dimensions
The low -voltage neutral (X2) connection of the winding shall be made to the tank or cover but not to the core clamp.
When a fully insulated terminal is used for this low -voltage neutral connection, it shall be externally identified as
being internally connected to the tank or cover.
5 ELECTRICAL REQUIREMENTS
T_Ul_ A
HIGH VOLTAGE
LOW VOLTAGE
STOCK
386.
N105
KVA
PROTECTION
TYPE t11
TAPS
TYPEAND
-O.
% z
RATING
TERMINALS)
RATING
NUMBER OF
SERIAL
ABOVE
BELOW
TERMINALS
-
25
1 77 to 2 16
13200 GRDYP620
One bush:ng well
None
None
1201240
Three CU stud
CP
-150
1 50 11.77
to 2.18
13200 GRDW7620
One bushing well
None
None
120/240
Three CU stud
CP
-181
75
1.77 to 2.18
13200 GRDY/7620
One bushing well
None
None
120/240
Three CU stud
CP
fix rn
_ ^...-_-'
_-_,_-'1--'---
---"-- ^
^- -
i —• ��...-... �.......w..y l.aaiv uvVUVn v, vvol Wll 011l rl VItlWVII/,
$ = conventional;
Fusing - current limiting protection (see section 6, Overcurent Protection)
TBD = To be Determined
5
368-110
Rev Sym: B
6 OVERCURRENT PROTECTION
6.1 CURRENT PROTECTING (CP)
Current -protecting (CP) when specified in Table 1 shall include:
• Full range, current limiting, under -oil primary fuse (see paragraph 6.2).
• Low voltage (secondary) breaker
• Signal light (if practical for particular design)
• Emergency control handle
6.2 FUSING
Internally mounted 8.3kV rated under -oil full range current limiting fuse which shall operate in conjunction with
a secondary breaker.
WA
I Current UrnItInA Fuse
50
1 12 Am HI -Tech TrensGuard FX
75
1 20 Amp HI -Tech TmnsGuard FX
7 TANK DESIGN
7.1 TANK MATERIAL
Tank, cover and bottom shall be stainless steel manufactured with one of the following alloys:
1. Tank: 400CB SST or 409 SST
2. Cover & bottom: 304L SST for square tank designs or 409SST for round tank designs
7.2 TANK THICKNESS
The tank shall be of sufficient strength to withstand a static internal pressure of 50 kPa gauge (7.25 psig)
without permanent distortion and 140 We gauge (20.3 psig) without rupturing.
7.3 TANK DIMENSIONS
Figure 2 (below) shows maximum outside tank dimensions.
cf... 9
Maximum Clearance Dimensions inches
WA
A
B
1C'
50 75
27
33
1 44
C dimension is measured to the top or ousnmg wen insert pnsen Is provided by uusuesr
6
368-110
Rev Sym: B
7.4 TANK -MOUNTED ACCESSORIES
The following tank -mounted accessories shall be provided:
• (1) Tomko 1720K-1 Or Qualitrol 202-014-02 submersible stainless steel pressure relief device located
on cover
• (1) Tomko LG35 or Haroo HLG-1065 sight gauge%il level coupling located on cover
• (1) Tank drain 1.000 NPT flush coupling with brass pipe plug
• (2) 1.00" NPT fill couplings located on cover with brass pipe plugs
• (2) IN -13 SST ground pads centered on tank below primary bushing 7" from top and 7" from base,
respectively
• (1)'/:' -13 SST ground pad on top near primary bushing
• (1) Stainless steel pocket type parking stand for a loadbreak stand-off device
• (2) Lifting hooks opposite each other, welded on the front and backside of the tank near the top
• (1) Stainless steel cover -mounted instruction nameplate
7.5 TANK COATINGS
An adequate tank coating for underground vault application shall be provided. Appendix B Is provided as a reference for
comparing coating requirements. Fort Collins Utilities Electric Department, Engineering Division, shall be the only authority
regarding the adequacy of proposed coatings. The final color shall be ANSI compliant light gray paint.
8 MARKINGS
• X1, X2 & X3 stainless steel identification tags with black lettering
• 'X2 Int. Gnd' stenciled in black on cover
• Bayonet warning decals located near bayonet fuse
• Cover mounted stainless steel nameplate instruction nameplate conforming to 5.12 of ANSI C57.12.00-
2000, Nameplate A. On the nameplate or a label affixed near it, the manufacturer shall indicate that the
dielectric fluid contains less than 1 ppm PCB.
• Temporary seriallshipping card attached to tank lift -eye
9 LOSSES
The total losses of a transformer shall be the sum of the excitation losses and the load losses (12R losses). Load
loss tests shall be performed and reported on all units regardless of whether or not a record of such tests is
available on duplicate units. Loss evaluations and loss costs will be based on the values shown in the "Special
Conditions and Supplemental Instructions to Bidders." Transformers will be evaluated on excitation losses and 12R
losses at the specified rates. If tested losses exceed quoted losses but are within the tolerances of paragraph 9.3,
ANSI C57.12.00-2000, the additional cost incurred from the differential of losses will be calculated using the
following equation and the above specified rates and will be deducted from the original Purchase Order or back
charged to the manufacturer. In the following equation "Units' shall mean "Transformers of the same size and
design on one order."
Excess loss $ = [# of units] [(No Load Loss Evaluation $) (Avg. No Load Losses - Quoted No Load Losses) + (Load
Loss Evaluation $) (Avg. Load Losses - Quoted Load Losses)]. If this equation results in a negative number, no
credit will be given the Supplier.
If any unit or units exceed the tolerances of paragraph 9.3, ANSI C57.12.00-2000, that unit or units shall not be
shipped'wlthout express permission from the City. If accepted, the deduction for excess losses will be based on
the following equation:
Excess loss $ = (No Load Loss Evaluation $) (No Load Losses • Quoted No Load Losses) But Not Less Than Zero
+ (Load Loss Evaluation $) (Load Losses - Quoted Losses) But Not Less Than Zero.
7
368-110
Rev Sym: B
10 QUALfTY ASSURANCE
10.1 GENERAL
10.1.1 RESPONSIBILITY FOR INSPECTION
Unless otherwise speed, the vendor is responsible for the performance of all inspection requirements
as specified herein. Except as otherwise specified, the vendor may utilize his own facilities or any
commercial laboratory acceptable to the City of Fort Collins. The City reserves the right to perform or
witness any of the inspections set forth in this Specification where such inspections are deemed
necessary.
10.1.2 TEST REPORT
The manufacturer shall fumish to the purchaser certified copies of the results of loss tests prior to
payment. Copies of loss tests shall be sent to Standards and shall be attached to the invoice.
Unsigned copies are not acceptable even if accompanied by a signed cover letter.
10.2 TEST CONDITIONS
Unless otherwise specified, testing required by Section 4.4 shall be conducted under the following
conditions.
10.2.1 REFERENCE TEMPERATURE
The reference temperature to which losses, impedance, regulation, and efficiency are corrected shall be
85°C.
10.2.2 TOLERANCE ON IMPEDANCE VOLTAGE
Nominal impedance voltage shall be in accordance with Table 1 of this specification. Completed units
may vary from the specified nominal up to the tolerance specified in ANSI C57.12.00.
10.2.3 TOLERANCE ON IMPEDANCE VOLTAGE ON A TAP
The percent departure of tested impedance voltage on any tap from tested impedance voltage at rated
voltage shall not be greater than the total tap voltage range expressed as a percentage of the rated
voltage.
10.3 TESTS
The tests to be performed and the test procedures required are specified in ANSI C57.12.00, and
C57.12.90. Exception: impedance and load -loss tests shall be made on each unit and may n93 be
omitted even if a record of such tests made on a duplicate unit is available.
11 PREPARATION FOR DELIVERY
Transformers shall be prefiled with the appropriate amount of transformer oil and shall be shipped by open -bed
truck. Units shall be packaged in such a way as to provide for ease of handling and to protect units from shipping
damage. Units shall be packaged on two-way pallets or four-way universal pallets with 34 inch minimum opening
and loaded on the truck for side removal. The Supplier shall provide 24-hour notice prior to delivery for any
shipments where an individual transformer weighs over 5,000 pounds. In addition to these requirements, the
Supplier shall oomply with any additional requirements or modifications shown on the purchase order and/or
supplemental instructions.
8
368-110
Rev Sym: B
APPENDIX A — Transformer Stock Number Coding
Below are examples that demonstrate the coding method used by City of Fort Collins to establish
transformer stock numbers.
I. SINGLE PHASE
Example #1: V-* 368 -1
Transformer Class
Single Phase
00=13.2Yl7620 &
7620113.2Y x
2400/4160 outside
pole
05 = 13.2Yl7620 ESNA
pole or
10 - 13 W7620 ESNA
Submersible
20=13.2Yl7620 ESNA pad
II. THREE PHASE
Example #2 9--* 368 -
Transformer Class I--
3 Phase
Pad
N
Other
KV9
0=5
5=50
1 =10
6=75
2=15
7=100
3=25
8=167
4=37.5
9=250
1 = single voltage
2 = dual voltage
0
006 = 75 075 = 750
015 =150 100 =1000
030 = 300 150 =1500
060 = 600
• All suffixes indicate 208Y/120 sec.
For 480Y/277 sec.. add 1 to XYZ
(le. 907 would Indicate a 75kVA with
480Y/277 sea)
9
368-110
Rev Sym: B
APPENDIX B -TANK COATING COMPARISON
This Appendix is not intended to dictate requirements for items purchased under Specification 366-110, but is included
as an aid in comparing coatings for manufacturers attempting to meet the requirements of this design.
Tank coatings listed here are for reference only and shall not be oonsidered as complete. The City of Fort Collins
Utilities shall not be held responsible for patent infringements incurred through the use of this information.
8.1 ARMORTEC, a fusion bonded vinyl resin having a minimum coating thickness of 15 mils.
B.2 Coal -tar Epoxy having a minimum thickness of 15 mils applied in two coats over a zinc rich primer and
overooated with flow coat applied black enamel paint.
B.3 Electrostatically applied thermosetting polyester applied as follows:
1. Five Stage Wash - alkaline detergent, water rinse, phosphate treatment, water rinse, and sealing rinse.
2. Delay Line - dry and cool.
3. Coat - Electrostatically coat with a thermosetting polyester.
4. Bake - Heat as recommended by polyester manufacturer to set polyester.
5. Cool.
6. Repeat Process - Repeat applicable steps of above process to obtain a minimum dry build of 6 mils.
B.4 Cailcote Flakeline 252 (minimum thickness 35 mils).
10
366-110
Rev Sym: B
APPENDIX C - APPROVED MANUFACTURERS
Transformers purchased under this SpecificaUon shall be of the make shown below. Manufacturers not listed below
may submit written proposals demonstrating compliance with these Specifications for consideration of addition to the
accepted manufacturer list prior to the next request for bids. In addition to inclusion on the list below, manufacturer's
equipment must also satisfy all requirements of this Specification to be acceptable.
APPROVED MANUFACTURERS
Howard Industries
The manufacturers in the following list have been conditionally approved and may bid as an aftemate. The definition
and Intent of "Conditional Approvar of a manufacturer Is to allow the Utllities to gain some experience with the
manufacturers product Should a conditionally approved manufacturer be the evaluated low bidder, Utilities reserves
the right to award all, part, or none of the order to them, dependant upon the current needs of the Utility for that item or
items.
CONDITIONALLY APPROVED MANUFACTURERS
ABB
Central Moloney
11
368-110
Rev Sym: B
TRANSFORMER LOSS EVALUATION FORM- AVERAGE LOSSES
City Order No. S/N
Manufacturer Invoice No.
KVA/Unit
LINE
DESCRIPTION AMOUNT
(1)
No. of units
(2)
Average core losses
(3)
Quoted core losses
(4)
Excess average core losses:
line (2) less line (3)
(5)
Penalty for excess average core losses:
line (1) x line (4) x $
6)
Average copper losses
(7)
Quoted copper losses
(8)
Excess average copper losses:
line (6) less line (7)
(9)
Penalty for excess average copper losses:
line (1) x line (8) x $
(10)
Penalty to be assessed manufacturer.
line (5) plus line (9) but not less
than zero
Date Prepared By:
Design Engineering
NOTE: If any unit(s) exceeds the loss tolerances of ANSI C57.12.00, Utilities Electric will either
reject it, include it on these averages, or calculate losses using the Individual Transformer Losses
Evaluation Form, whichever is most favorable to Utilities Electric.
12
36s-110
INDIVIDUAL TRANSFORMER LOSS EVALUATION FORM
City Order No. S/N
Manufacturer Invoice No.
KVA/Unit
LINE DESCRIPTION AMOUNT
(1) Tested core losses
(2) Quoted core losses
(3) Excess core losses
line (1) less line (2) but not less
than zero
(4)
Percent difference
line (3). line (2) x 100
(5)
Tested total losses
(6)
Quoted total losses
(7)
Excess total losses
line (5) less line (6) but not less
than zero
(8)
Percent difference
line (7) , line (6) x 100
(9)
Tested copper losses
(10)
Quoted copper losses _
(11)
Excess copper losses
line (9) less line (10) but not less
than zero
(12)
Penalty for excess core losses
line (3) x $
(13)
Penalty for excess copper losses
line (11) x $
(14)
Penalty to be assessed manufacturer
line (12) plus line (13)
Date
Prepared By: (Design Engineering)
Rev Sym: B
13
368-110
Sales prohibited/conflict of interest: no officer, employee, or member of City Council, shall have a
financial interest in the sale to the City of any real or personal property, equipment, material,
supplies or services where such officer or employee exercises directly or indirectly any decision -
making authority concerning such sale or any supervisory authority over the services to be rendered.
This rule also applies to subcontracts with the City. Soliciting or accepting any gift, gratuity, favor,
entertainment, kickback or any items of monetary value from any person who has or is seeking to do
business with the City of Fort Collins is prohibited.
Freight terms: unless otherwise noted, all freight is F.O.B. Destination, Freight Prepaid. All freight
charges must be included in prices submitted on proposal.
Discounts: any discounts allowed for prompt payment, etc., must be reflected in bid figures and not
entered as separate pricing on the proposal form.
Purchasing restrictions: your authorized signature of this bid assures your firm's compliance with
the Citys purchasing restrictions. A copy of the resolutions is available for review in the Purchasing
Office or the City Clerk's Office. Request Resolution 91-121 for cement restrictions.
Collusive or sham bids: any bid deemed to be collusive or a sham bid will be rejected and reported
to authorities as such. Your authorized signature of this bid assures that such bid is genuine and is
not a collusive or sham bid.
Bid results: for information regarding results for individual bids send a self-addressed, self -stamped
envelope and a bid tally will be mailed to you. Bid results will be posted in our office 7 days after the
bid opening.
James B. O'Neill II, CPPO, FNIGP
Director of Purchasing and Risk Management
0
B.
791
Rev Sym: B
SPECIAL CONDITIONS ANDSUPPLEMENTAL INSTRUCTIONS TO BIDDERS
Applicable to Specification 368-110
The following data shall be supplied with the bidders proposal in addition to that information
required by the "Invitation to Bid" and the "Purchase Requisition".
1. Impedance volts in % at full load, high voltage to low voltage at 85°C.
2. No load and total losses at 85°C.
3. Protective tank coating specification.
4. A statement indicating compliance with our Specification without exception.
5. Escalation is _, is not _ applicable for the transformers bid. If escalation applies, the Bidder
shall indicate in his bid the specific items or materials subject to escalation, and shall give the
method and indices to be used in computing the amount thereof. Escalation occurring after the
quoted delivery date will not be paid unless delays are the result of actions by the City. Escalation
occurring after acceptance, if Purchaser exercises the option to delay shipment after manufacturing
is completed, will not be paid.
Failure to supply the above data shall constitute a basis for rejection of the bid.
Loss Evaluations
Loss penalties and loss evaluations will be based on the following values:
1. No load or excitation losses at $3.25/watt.
2. Load losses at $1.10/watt.
Shiooina Terms
Ship F.O.B. point of destination, freight prepaid.
Terms of Payment
1. If escalation applies, the City of Fort Collins shall not be billed for escalation occurring after the
promised delivery date. Escalation charges shall be itemized on the invoice.
2. Test reports shall accompany the invoice. If test reports do not accompany the invoice, late
payment penalty charges incurred due to delays in obtaining the test reports will not be paid.
Certified copies of test reports shall be sent to the Design Section, Fort Collins Light and Power
Utility.
3. Loss penalty credits and escalation charges shall be itemized on the invoice.
1_
368-110
FIRM NAM
CITY OF FORT COLLINS
BID PROPOSAL
BID NO. 7229
LP Transformers75kVA Single Phase Underground
BID DATE: 3:00 p.m. (Our clock) April 26, 2011
WE HEREBY ENTER OUR BID FOR THE CITY OF FORT COLLINS' REQUIREMENTS FOR LP
Transformers 75kVA Single Phase Underground, PER THE BID INVITATION AND ANY
REFERENCED SPECIFICATIONS.
QUANTITY: DESCRIPTION:
10 Ea. TRANSFORMER, 75 KVA SUBMERSIBLE, SINGLE PHASE WITH
OVERCURRENT PROTECTION PER SPECIFICATION #368-110-
161, REVISION B. ONE COVER MOUNTED SEPARABLE
INSULATED LOAD BREAK HIGH VOLTAGE BUSHING WELL,
THREE COVER MOUNTED STUD SECONDARY BUSHINGS.
HIGH VOLTAGE RATING: 13200 GRDY/7620, LOW VOLTAGE
RATING: 240/120.
PLEASE COMPLETE THE ATTACHED EXCEL SPREAD SHEET
FOR BID SUBMITTAL.
IF YOU ELECT TO PASSWORD PROTECT YOUR BID, PLEASE
NOTE THAT PASSWORD BELOW.
'Any surcharges or additional costs shall be noted & included in bid submittal
The transformers being bid meet or exceed the specifications. Yes No. If not,
please list exceptions, (specifying paragraph reference number) on a separate sheet of paper and
attach to your bid.
Escalation is , is not applicable for the transformers bid. If escalation applies, the
bidder shall indicate in his bid the specific items or materials subject to escalation, and shall give the
method and indices to be used in computing the amount thereof. Escalation occurring after the
quoted delivery date will not be paid unless delays are the result of actions by the city. Escalation
occurring after acceptance if purchaser exercises the option to delay shipment after manufacturing
is completed, will not be paid.
Delivery may be a consideration of bid award.
For purposes of warranty and service ONLY approved manufacturers or distributors authorized by
an approved manufacturer to serve the Fort Collins area may bid.
The City of Fort Collins reserves the right to split the bid in whatever percentages are most
advantageous to the City.
Future orders of LP Transformers 75kVA Single Phase Underground may be authorized, at the
option of the City, from this bid for a period of five years after date of award. Satisfactory pricing and
delivery is required for future orders based on this bid.
SUPPLEMENTAL INSTRUCTIONS
Prices quoted must remain firm for a 30 day period after the opening date.
Freight terms: F.O.B. destination freight prepaid. All freight charges must be included in pricing
submitted on proposal and not entered as separate pricing.
Any discount allowed by Vendor for prompt payment, etc. must be reflected in quoted figure, and not
entered as separate pricing.
The City reserves the right to accept or reject any and all quotes.
Bidder not responding to the services requested in this bid shall be removed from our automated
listing for: Not Applicable
Any questions or inquiries regarding this bid should be directed to:
Opal F. Dick, CPPO, Senior Buyer
(970) 221-6778
SIGNATURE AND TITLE: TYPED OR PRINTED NAME AND TITLE
COMPANY NAME: (AREA CODE) TELEPHONE NUMBER/FAX NUMBER
ADDRESS: STREET, CITY, STATE, ZIP DATE
EMAIL:
Purchase Ordc( Terms and Conditions
I. COMMERUA. UI•.l'AIIS.
Tonemngainvs. ilymm,enth City of1'anf•Ngaenexcn;u frommacedhas Imvn(hw Ii mplinn Nmabe,e
98-04502. ]weml Exam 1'ax Ewmpgam Cenifumc of Regimry 84441111587 is regeond with Ibe Cog ctor of
IMaal RaIaam% 17cnvcr. Cokua a (Ref CoWmlo Resissd Ssvtmes 1973. (lopeN9 2(,114 (oL
Goods RejeeraL GUOUS RIUIX TEE due up Lv"Grc m noel.,pcifivtnm cider asev xldpad an doe mJclmts of
da age in for a. my be warned In you fn cndn ad are not (n be repLaccd excerd n,,n receiptor wmian
outrvaauts fmm lln Cay of Fort Cnnirn
Imfectiom GOfHri are whim to the Cay of I'M Collins inspeerion am arivaL
Iiml,\ccepaue. {heeip ufghe nrrekadioe services mcaruipmut in rtynn¢ In the oNeramh a,vh n a,ksvN
payments ou the pat of Ihe Cay of Fan CoIWa. I however, a e m be understand ilea I1NAL ACCEIyANCE in
depedeo tgnn conppletlon of all vpplicahle nyuierd inspection pmmdurcs.
li'eighl']'I.. Shipment. mwa be I'.oa. city of Inn Collins. 700 Wood SI_ Pon Carim. CO RII552. mks,
nlMaise specified on this order If pmhiesam is given In prepay freight and chase sepvwely, the original Imigln
hill mum accompany invoice. Additional chap, for packing win wit be accped.
Shipmrly Dimmea. \Yherc n umrfaaunas lave Jimrdmlmi; pomin in rmmon pars of mk aowwry, dhig na i in
expected from the neural tgnlailnmnm pains to destinann will a.. fniglu will he dcdrnN fmm hroice when
shipants we node fmm greater distnnca.
Permits. Seiler 4ua0 pmnmo M sailers mile cam an nnssary petits, ovnifwasen ad lieenea n+ryired by sill
applicable laws mgulaniOm ONinvccs and mies of the Male. Municipality, lenaorym p,8lic.I.Ahsisna whre toe
work is prfomad. In required by my nther duty wrmitusd public authority having jusisdktian river ale work Of
vinegar. Sal ar fur lar agrcas In hold the City r on Calfim hamleu fmm and agmam an fiahiWy ad Ion itavmvl
by them by mono of m Muened sir amahlidkd violation Of any such lawn, regulasimm ordinonce, mks and
m luaeavnu.
Awhorirmno. Ag parties go this comma agruc that the rtpresealairas ace, in fan, hem fide and pa sell full and
..Tlctc awwrily In lid said panics.
LIMITATION UP TERMS. The Purchase Order expressly gmirn accepaaa in the terms and rnnditnm mad
Men set f nth and any wPpleMMeMsry at wMannvl terms, wd conditions, me exed damn orinempnmled herein by
refinercr. Any ddainml or diffec m lemn and condaiom pmppned by sclkc Me ohjVavd to and h Vehy mjvcud.
2. DELIVERY.
PLEASE ADVISE PURCHASING AGENTintnNialclyifyamc:moo nuke complete shipnm maniveonymr
pnnnxd hgverydoe an wand. l ilia a of (he esume. Unth,cryad perfornvmce ram heeffacged uillw toe lino,
mated tin the purchase rider and (be davnrcms attached herein. No was of the lurthawn bending. without
lnmmnn accepano of partial lane deg varies. shag aprne as a waver nobs pmvisina In the evvt ofary delay.
the Pnel,wr shun Mvv. in additnn Io Caber kgd ad apiohk rennalim the opion nfpIamg the Mdar vbwwhere
and holding in, Seger liable for dam gas I Inwev m rhe Seller shag eat be gable rn damagas ass rewh nr&L3),de
In cows rim reasonably rnnseeahle which are beyond an mawpmble moral and whim, its faun nfagfgeMha, such
msofGwL own of civil or mimicry=ban'ics, governmental priorities. foes strikes nand ep ictim wanor anon
provkkd deal white of the condition causing such delay is given In the Iurchxr within five (5) days of the titre
when the Seger fuss received knowledge thereof. In the n,eru ufwymMhdeiy. the date ufdcgverymmnbe emending
for the peril opal In the Ire almlly king by reason of the delay.
5. WARRANTY.
The Seller warams thin an goats ankles• materials and work covered by this order wdl end mn with applicahle
dro-ingc specifcmimtt.emhple. nndfr olar desmipnm given willow In far the pugann imadtaL and redomad
with thehighem Jvgme ('retire and mrgqulanee in accordance wish accepted saadards for work of u sinilar mture.
The Seller ngrccs in hold the prcclawrhamlas fmm any hiss dm,ge orexpvnac w'hichiloc Purhaermny sufferer
incur on accum of the S-11 rs hcach nfwaryway. lbm Seller shall replace. repair or mode good without cam m (he
purchaser, nay defects sir fuhhn wising within one (11 yea or withinsuch longer period ofsine asmaybe prescribed
by law at by the name army y oPPgcahk warranty pmvidcd by the Seger after Ik date of aceptince of the goods
Wrasied heaeuncrlave farce sum lobe uvreaoablydelayedl. resulting Ganninppcnfvcl ordloctnc workdmmnr
rmteniak fumidocd by the Seller. Acceptance nr use of goods by the Parchwer deg col carammie a water of any
clean under Ills warrior. Except an mlemiw provided in dais purchase order. Ilk Seger liability, hereunder shell
emcd I all dmnges pmximvely caned by the Imach of any of [h foregoing wvmamin or guarantees. No such
liability shall in no awns dochdc it. of Profits sir 6a of one. NO IMPLIED WARRANTY OR
MERCI IAND\UIU TY OR OP hTINESS rh R PI1RPoSE SIIAI. APPLY.
h. CTIANG]S IN II:GALTERMS.
The Iurehnser may take charges to legal knits by written change order.
5. CHANGES IN COMMERCIAL TERMS.
lle lumhawr rmy nekc my changes to the teams mhcr (hit legallema, achhling mklkinm to nr Jekainm fmm
Mbe . uamitles originally oNercJ n tk speifeakum sir drawings. hY send or wriuev <habge nNer. If any such
chose affects the amount due or the lire of rwrfnrmuue henvnAr, an Vpmahk mignmovo dun be node.
S TERMINATIONS.
The Purchaser ray M any limo by evrillco change order. Im immn this agreern m as in my w an poniom of the
goads then wit shipped subject to any cquitahk Am,,, bmween the parties as to any work or =crisis lhen in
pngraa provided Ihm the Purehaer shag wil be gahle for my claim fur arucipmed profits on she uncompleted
portion of plc gods o dfor woh, for incidental orcoracquandsp damages, and Jut am each adjuration be nude in
favor o(Ibe Seller with nspect In my gndf which an the Sellers standard met No such wmtiutim slain rbevu
the Purehaner or the Seller of any of their Obligations an In my goods dc8verd hmudw.
7. CLAIMS fOR ADIUS'TMENT.
Any claim her djusinsnt rambe awned whim rdiny (70) days imam be date he change sir nomination anNcaL
8. COMPLIANCE Wllll LAW,
The Seller warnings that all gran; saki hercua er.shall have been produced. sold, delivered and furnished in prim
compgamc with an applicable laws ad regudalions to which the goods we suhjcel. The Sener.thsil execute and
deliver such documents as limy be raquired m e(fa( or evidence compgane. All laws and regulatnns ruquired to be
incorporated in agreements of Ibis character we heaaby incorporated herein by the referenv. The Seger agrees to
indemrdy and hold the Purchaser Mrrn ess from ill cons and danuses suffered by [he Purdraer as a result of the
SeOen Iakre go consply with such law.
9. ASSIGNMENT.
Neither parry mull assign Mmseler. or comeythis roger. or any modes due or m becorte due hercuder without the
prior wraten consent of the other pity.
10. TITLE,
Pic Seller waraos fun. clear and unrmricted title Io the Purchaser for allequipment, nsvcriats. and it. furnished
in rerfommna of this agraneo. Inc and clear of my and an fens. restrictions, rtservmiom seevri(y interest
ercuaNwmoco and chains of then.
11. NI INWAIVER.
I whue of the Puchaner In insisl upon mrid pmfomcuce orth Icon and cordianns hemnf. ponure or delay to
exercise any rights or renedks provided herein or by law• feature to pmmpl ly ratify the Seger in theerem of a
Mesh de a c •pane of sir guynen fnsdpds bercuder sir appnrd aOk tladgn shots rim rekac the Sclhnof
any '('he wamltics sir ohkgamen Or the' lamhane nnkr and slug am he decried a wawa N any righ of the
prchawr os insim uponstria MCOm vhmnfnrivy of itsrights or rema nit in my machgolds, regardless
of -bell shipped. revived Or acaped as Ia any prier or suhayam, defmk hnwakr. a w sbanarypluponed oral
mrdffti,vionor resch,siva Of This plrehaw order by Ihe Purchawr oprme as a waver afeny nllhe tem , hemE
C. ASSIGNMENT Of: ANTbIRUST CI.VMS.
Seller and the Phmhawr recogare that in actual mmmnie pwei ice. mcrc,rges rewhng Irmo imilmsl violations
are in fan home by the lurehasur. Thercrofore, for god cams o and as consideminn for euaaaing the purchase
tinier. the Seller hereby nuigm to the Purchaser my ad all chi" it army new have at hereager atpsind trader
hderal or same antitrust laws In, such ov'cnharges ralung to the particular sands or mniccn purehmed or
acquired by she Purchaser pormnl go [his puchnc order.
Id. PURCIIASURS PERFORMANCE OF SIi1II3R6 OIIIJGATIf INS.
If arc Puaehmcr directs Ihe Sclkrin corns) nonewitfu rung or deractive goods by a dale In be agreed upon hy(k
ILmhawr and tin- Seller, and Ism Seller abervaller indicates in hahikry sir unwillingness in comply, the purchaser
noyeauw the work to he performed hyshe met expeditious mew available In it. and Ida Seller shall pay anrnsts
asmaimed with.such work.
'Ire Seller shall release Ida Perchmer and its cam mason of any tier fmm all liability mood ckdnn of any aware
muhion from th pvrfommusev of such work.
lids rekw shag apply even in (be event of fault Of Iegligance of the party tclemcd and shall extend lO he
directnn, officers and employees of such party.
'Ow Segue cmumetual nhggvnm inchuling warranty, fall an[ he doe ad to he reduced. in any way, because
such work in performed sir caused to be prfnnmJ by the Ihuchaar.
Id. PA'TINI'S.
Whetcrer the Seller a implored In uw anyt esign device, nwcaial or proem cnerrvd by hiller. pacnl. Irdroak
nrcopyaighl.the SclkrshagidemNfyandswvbandits the Purchaser fmmmyadagcIa mfarhiftenem by
reasan of Ile a no, of such pmeoed design dr ic, rimer ed sir Pmcas in connection wish the camvct. and shag
i dcsanify the Purchaser for any con, capnw or damage widch it tnry he obliged to pay by reason of such
infringar ant at myliru during the pmseaunn or after Ihe camp letinn oOhe work-. In cxe said aparpmmt, assay
pan thereof or the wedad tune of the gods is in such wit held Io constitute nhingrrnnl and tie we, of.. od
apipnaM nr Pen isenjoined. Ili Seller shag a its own expo- and as its apnn either procure far the Purchaser
the right Io common, using said .ydp erg or pans replace the same with MIME noisily equal but non -infringing
aluipram. or modify it w it becomes con-iNratgng. r
I5. INSOLVENCY.
Iftk ScRrshagbecore mookent sirbadmp. Make an assignlreM frthebenftt oferedaon, appddo a on hW
or Inmm forairy ofth Sellerspmpnyrrhu must. thin riderray fordavahbeaimed bribe Wrrhvwrwahe,
liability.
id. GOVERNING LAW.
lbw defsine, of tams uad sir the imcTmwiOn oche agreement and the rights of an parties licrcundtt shall be
contained under and governed by the lawn of the Stem of Colorado. USA.
lie fffinving Additional Condainm apply nNy in cows where the Seger is to perfnnn work henvder, including
the aniccs of Scilen Reprvwnuuivelsl. on the premises ofnthrs
17. SELLERS RESPONSIBILITY.
lk Seger mill carry on sail wort: In Sallers own risk until the.s sm: is fully completed and occupied and nhall. in
caw of my accident. dcmmcrnn or injury to be work and/or Materials Were Sellers fuel care pletirin aid
aapmce. camplala the work M Sellers own expert e and I (he sakfunion oft Purchaser. when Materials and
aquiprvnt ace furnished by ahem for amallwi(m orcrection by the Seller, the Segersha8 mcne. unkuad mnoand
bounce sirs: M Je idle and become: responsible therefor as thnugh such Materials vMwVor equipment were being
famished by Ihe Seller under the order.
I8. INSURANCE
Out Seger shall w his own cxpenne, Provide for The poyrtao of workerscompensaina including ncupwlona
Jsvm hmefus In its employees employed an or in cmmection wish the work covered by this purehane order.
a dwI to teadepmkos in accodake with the laws ofhe awe in which the work is to be don. The Scherdun
olio carry comPlehemive general liability including. b, rim Wtued In, contractual and aulnmntdk public gahigly
insurance with IWilyupuy Mail fins ofm eat 10(m.000 for any oat Peron i500.000(ieranym n nccidlm
said property d'unage Writ per accident of S100.0M The Seller shall hYcwise ogdr s he comsaaoes if any, to
provide fur such cusp mention and insurance. war, my or(he Sellers or his coosvaar V playea hall do my
work upon the Prean ten or whirs. the Seller shall furnish he puchmar with a acnifkwe thin each Vmgnww w
and 4nsanr8e have teen pmvidd. Such a tilkwes shag spumy Ibe time when such compeowim and insurance
have been PmviJed Such vnifcales shag specify the time when.wch compensation and insurance expose, The
Seller agrees that such compctnarion and insurance often be Maintained um after the entire work is completed sal
eaceped.
19. PROTECTION AGAINST ACCIDENTS AND DAMAGES.
The Seller hereby M e men the emirs responsibility and liability for anyad all damage. kill or injury army kind or
mature whwsam'vr to penomor property caused by or ranging from the execution o0he work provided fare this
purehaw order or in connection horinvuh, The Seger will indemnify and hold hamdeu the Purchaser and my or all
of (he Phnhawn affcan, agents and employees fmm and agmiw any and all claims• lasses. damages, charges or
expenses, whether direct or idi eV. and whither la rknom or propny to which the Purchaser maybe put ar
whject by reason or my act. action, negkm omission or default on Ihe pan oche Seller. my nfltis contractors. or
my alline Sellers or contractors al0cersliner agena or employees. In case my suit or other la,, madmy shallbe
brought against the Pmhawr, or its olBcers agents or employee at my the on account or by reaum of any lit.
action neglect. omission or default of (he Seller of my of he coMosdnrs or any of its or their officers. S.M.aor
employees a aforesaid, (he Seiler hervby agrees In assume the defense lhertofand to defend the seam 0 the Seiko
own expense. to Pay any and an costs, charges, attorneys fen nod arberexpeon s. any and alljdgmms thin may
be incurred by or obtain against the Purchaser wary of ds or their op0am agents or employes in such will or
other ptkedng, and in case judsnea or other lien he placed upon or ('blamed against the pmpeny of the
purchaser. or said Portia in or as a rauh of such wits or other proceedings. the Senor will w Mae cause the same
In he diswhd and discharged by giving hand or otherwise. The Seller wall he contractors than lake an safety
l teeautiom furnish and install all guards acessary for the prevention of accidents, comply with an laws and
ngulatnln with regard to mfay including. but wiiho, grritaiOn the (kcupmionalSafdy and Health Ad N 1970
and a0 mks and mgulviom issued pureaom (ammo.
Revised
ar_
No Text
THE CITY OF FORT COLLINS
UTILITIES
Light and Power Department
P.O. Box 580
Fort Collins, CO 80522
SPECIFICATION NO: 368-110
TITLE: Single Phase Submersible Cover Mount Transformer
APPROVED BY:
Kraig
Standards Engineering Manager
ORIGINATED: June 1999
LAST REVISED: September 20. 2005
Rev Sym: B
REVISION DESCRIPTIONS
REVISION A
i im sagen
• Revised tank material in section 6
Bill Bray
12/152000
REVISION B
Kraig Bader
• Rewrote specification with reference to IEEE submersible specification C57.12.23.
9202005
• Overcurrent protection changed:
Secondary breaker in conjunction with under -oil full range current limiting primary
fuse.
• Only one thermal design is specified now. Previous revision allowed two thermal
designs, but did not indicate a preference.
2
368-110
Rev Sym: B
TABLE OF CONTENTS
REVISION DESCRIPTIONS.......................................................................... 2
...................................................
1 cope.........................................................................................................................................................................4
2 Applicable Documents ........................................ 4
................................................................................
3 Kilovolt -ampere ratings................................................................................. 4
........................................
4 bushings and Terminals ..................................................................................................
4
4.1 HIGH VOLTAGE TERMINALS..................................................................................................4
4.2
LOW VOLTAGE TERMINALS... ....5
.................... .
Electrical Requirements .....................................................................................................5
........................................
6 ercurrent protection...............................................................................................................................................6
6.1 CURRENT PROTECTING(CP)....................................... 6
...........................
6.2 FUSING............................................................................................ ............................6
.......................................
tank design......................................................... ...6
.....................................................................................................
7.1 TANK MATERIAL................................................................................................................................................6
7.2 TANK THICKNESS.............................................................................................................................................6
7.3 TANK DIMENSIONS........................................................... 6
........................................................................
77.4 TANK -MOUNTED ACCESSORIES....................................................................................................................7
.5 TANK COATINGS...............................................................................................................................................7
8 Markings....................................................................................................................................................................7
9 Losses..........................................:
........................................................
.......................................... ........................... 7
10 QUALITY ASSURANCE..........................................................................................................................................8
10.1 GENERAL.......................................................................................................................................:.................8
10.1.1 RESPONSIBILITY FOR INSPECTION......................................................................................................8
10.1.2 TEST REPORT..................................:........................................................................................................8
10.2 TEST CONDITIONS.........................................................................................................................................8
10.2.1 REFERENCE TEMPERATURE............................................................................................ 8
.....................
.2.2 TOLERANCE ON IMPEDANCE VOLTAGE...............................................................................................8
10.2.3 TOLERANCE ON IMPEDANCE VOLTAGE ON A TAP.............................................................................8
10.3 TESTS...............................................................................................................................................................8
11 Preparation for delivery ............................................................................................
.......................8
APPENDIX B — Tank Coating Comparison................................................................................................................10
APPENDIX C —Approved Manufacturers ....I................................................................11
.............................................
Transformer Loss Evaluation Form- AVERAGE LOSSES ........................................................................................12
Individual Transformer Loss Evaluation.........................................
Form...... .. ............13
Special Conditions andSupplemental Instructions to Bidders....................................................................................14
_3
368-110