BID
7167
167 WA Pad -Mounted Compartmental -Type,
Single -Phase Distribution Transformers
BID DATE: 2:00 P.M. (Our clock) August 26, 2010
REV. SYM: FF
TABLE OF CONTENTS
PREVIOUS REVISION DESCRIPTIONS ON FILE..........................................................................................................................2
1 SCOPE...................................................................................................................................................................................................4
2 APPLICABLE DOCUMENTS............................................................................................................................................................4
2.1 ANSI C57.12.00 - DISTRIBUTION, POWER, AND REGULATING TRANSFORMERS, AND SHUNT REACTORS, GENERAL REQUIREMENTS
FOR......................................................................................................................................................................................................... 4
2.2 ANSI C57.12.25 - PAD MOUNTED, COMPARTMENTAL -TYPE, SINGLE-PHASE, DISTRIBUTION TRANSFORMERS WITH SEPARABLE H-V
CONNECTORS, STANDARD REQUIREMENTS FOR.......................................................................................................................................4
2.3 ANSI C57.12.28 - SWITCHGEAR AND TRANSFORMERS - PAD -MOUNTED EQUIPMENT -ENCLOSURE INTEGRITY...............................4
2.4 ANSI C57.12.70 - TERMINAL MARKINGS AND CONNECTIONS FOR DISTRIBUTION AND POWER TRANSFORMERS...............................4
2.5 ANSI C57.12.80 - TERMINOLOGY FOR POWER AND DISTRIBUTION TRANSFORMERS........................................................................4
2.6 ANSI C57.12.90 - DISTRIBUTION, POWER, AND REGULATING TRANSFORMERS, AND SHUNT REACTORS, TEST CODE FOR.................4
2.7 IEEE C57.91 - GUIDE FOR LOADING MINERAL -OIL -IMMERSED OVERHEAD AND PAD -MOUNTED DISTRIBUTION TRANSFORMERS
RATED 500 KVA AND LESS WITH 650C OR 550C AVERAGE WINDING RISE..........................................................................................4
3 REQUIREMENTS................................................................................................................................................................................4
3.1 GENERAL REQUIREMENTS FOR DESIGN...............................................................................................................................4
3.2 SPECIFIC DESIGN REQUIREMENTS..........................................................................................................................................5
4 QUALITY ASSURANCE.....................................................................................................................................................................9
4.1 GENERAL.......................................................................................................................................................................................9
4.2 TEST CONDITIONS.......................................................................................................................................................................9
4.3 NOT USED.........................................................................................................................................................................................9
4.4 TESTS..............................................................................................................................................................................................9
5 PREPARATION FOR DELIVERY....................................................................................................................................................9
6 DEFINITIONS AND ABBREVIATIONS........................................................................................................................................10
APPENDIX A - TRANSFORMER STOCK NUMBER CODING...................................................................................................I I
APPENDIX B - DIMENSIONAL DRAWINGS.................................................................................................................................12
PADDIMENSIONS..............................................................................................................................................................................14
APPENDIX C-APPROVED MANUFACTURERS.........................................................................................................................15
TRANSFORMER LOSS EVALUATION - AVERAGE LOSSES....................................................................................................16
INDIVIDUAL TRANSFORMER LOSS EVALUATION.................................................................................................................17
3
368-120
REV. SYM: FF
SPECIFICATION FOR
PAD -MOUNTED COMPARTMENTAL -TYPE
SINGLE-PHASE DISTRIBUTION TRANSFORMERS
WITH SEPARABLE INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS
1 SCOPE
This Specification establishes the minimum electrical requirements and mechanical features of single phase, 60 HZ,
mineral oil immersed, self -cooled, pad -mounted, compartmental -type distribution transformers rated 250 KVA and
smaller, high voltage 13,200 Grd Y/7620 volts, with separable insulated load break high voltage connectors. These
transformers are used for step down purposes from an underground primary cable supply.
This standard generally conforms with ANSI requirements for pad -mounted compartmental -type, self -cooled, single-
phase, distribution transformers, C57.12.25.
2 APPLICABLE DOCUMENTS
The following documents of the issue shown form a part of this Specification to the extent specified herein. In those
cases when the document is note dated, the latest issue in effect on the date of invitation for bids shall form a part of
this Specification.
2.1 ANSI C57.12.00 - Distribution, power, and regulating transformers, and shunt reactors, general requirements for.
2.2 ANSI C57.12.25 - Pad mounted, compartmental -type, single-phase, distribution transformers with separable H-V
connectors, standard requirements for.
2.3 ANSI C57.12.28 - Switchgear and Transformers - Pad -Mounted Equipment -Enclosure Integrity.
2.4 ANSI C57.12.70 - Terminal markings and connections for distribution and power transformers.
2.5 ANSI C57.12.80 - Terminology for power and distribution transformers.
2.6 ANSI C57.12.90 - Distribution, power, and regulating transformers, and shunt reactors, test code for.
2.7 IEEE C57.91 - Guide for Loading Mineral -Oil -Immersed Overhead and Pad -Mounted Distribution Transformers
Rated 500 kVA and Less with 65°C or 55°C Average Winding Rise.
3 REQUIREMENTS
3.1 GENERAL REQUIREMENTS FOR DESIGN
3.1.1 BASIC DESIGN STANDARDS
Transformers purchased under these Specifications shall be new and, unless otherwise specified, meet
the requirements of the applicable ANSI Standards and the modifications and additions given in the
subsequent paragraphs. In case of conflict, the requirements of the following documents shall apply in
the priority shown:
a) This Specification
b) Applicable ANSI Standards
Approved manufacturers are listed in Appendix C.
4
368-120
REV. SYM: FF
3.1.2 KILOVOLT -AMPERE TEMPERATURE RATINGS
Kilovolt -ampere ratings are continuous and are based on not exceeding either a 65°C average winding
temperature or an 80°C hot spot temperature rise. The temperature rise of the insulating oil shall not
exceed 65°C when measured near the top of the tank. The temperature rise is based on an altitude of
3,300 feet. The transformers shall be designed for overloads based on IEEE C57.91.
3.1.3 GENERAL CONSTRUCTION
3.1.3.1 The pad -mounted compartmental -type transformers shall consist of the transformer tank and high -and -low -
voltage cable terminating compartment constructed in accordance with ANSI C57.12.25 and ANSI C57.12.28.
The terminating compartment and tank shall be assembled as an integral unit, tamperproof and weatherproof for
mounting on a pad. There shall be no exposed screws, bolts, or other fastening devices which are externally
removable. The cover shall be welded construction. There shall be no opening through which foreign objects
such as sticks, rods, or wires might be inserted to contact live parts. Suitable means for padlocking the
compartment door(s) shall be provided.
3.1.3.2The high- and low -voltage compartment shall be located side by side on one side of the transformer tank. When
facing the compartment, the low -voltage side shall be on the right.
3.1.3.3 Construction of the unit shall be such that it can be lifted, skidded, and slid into place on the mounting pad
without disturbing the entrance cables.
3.1.3.4An undercoating over the regular finish or an equivalent treatment shall be applied to all surfaces that are in
contact with the pad to minimize corrosion.
3.1.3.5 Minimum dimensions for Type 1 transformers shall be as shown in Figure 1, Appendix B. Minimum dimensions
for Type 2 transformers shall be as shown in Figure 2, Appendix B.
3.2 SPECIFIC DESIGN REQUIREMENTS
3.2.1 FUNCTIONAL DESCRIPTION
The transformer shall be a single phase, pad mounted, loop feed -safe break, "dead -front" type for use on
a 13.8 kV grounded "Y" distribution system.
3.2.2 DESIGN AND CONSTRUCTION
3.2.2.1 RATING
The transformer shall be rated as follows
a) High Voltage 13,200 Grd. Y/7620 volts
b) Low Voltage 240/120
c) Taps Two - 2Y2% FC above and below normal
d) Polarity Additive
e) Capacity, Impedance values, and fusing for transformers in this specification shall conform to Table 1:
5
368-120
REV. SYM: FF
Table 1 — Transformer Capacity, Impedance and Fuse Selection
.Stock
kVA
Min.
Max.
Bay-O-Net.
Current Limiting Fuse(s)
Number
Capacity
Impedance
Impedance
Fuse
368-120-130
25
1.77%
2.16%
10 Amp
ELSP 354403OM61 M (30 A)
4000353C06
368-120-150
50
1.77%
2.16%
15 Amp
ELSP 354304OM61 M (40 A)
4000353C08
368-120-155
50
1.77%
2.16%
15 Amp
ELSP 354304OM61 M (40 A)
4000353C08
368-120-170
100
1.95%
2.38%
25 Amp
ELSP 354308OM71 M (80 A)
4000353C10
368-120-180
167
2.28%
2.79%
40 Amp
ELSP 3543125M71 M (125 A)
4000353C12
368-120-190
250
5.75%
6.61 %
65 Amp
ELSP 3543125M71 M (125 A)
4000353C14
"The BAY-0-NET fuse shall be located in the high voltage side of the compartment.
3.2.2.2INSULATION LEVEL
3.2.2.2.1 The basic impulse insulation level (BIL) of completely assembled high -voltage and low -voltage terminals
shall be 95 kV and 30 kV respectively.
3.2.2.2.2 Dielectric test levels shall be in accordance with the distribution levels in Section 4 of ANSI C57.12.00.
3.2.2.3 HIGH -VOLTAGE TAPS
A no-load tap changer with external operating handle shall provide two - 2Y2% full capacity taps above and
below normal. The tap changer operating handle shall be located within the high -voltage terminal side of the
terminal compartment.
3.2.2.4 NOT USED
3.2.2.5 BUSHING WELLS AND TERMINALS
3.2.2.5.1 The number, location, and arrangement of bushing wells, terminals and parking stands shall be as
shown in Fig. 1 or Fig. 2 in Appendix B. All low -voltage bushings and high -voltage wells shall be
externally clamped and shall have leads of sufficient length to allow them to be changed without
removing the cover. Welded bushings and wells are expressly prohibited.
3.2.2.5.2 High -voltage terminals shall be universal flowerpot bushing wells in accordance with Figure 3 of
ANSI/IEEE 386-1985. Two wells shall be provided and shall be connected in a feed -through
configuration. Loadbreak bushing inserts in accordance with Figure 5 of ANSI/IEEE 386-1985 will be
owner furnished.
3.2.2.5.3 Low -voltage line and neutral terminals shall be sized as shown in Table 2 in accordance with ANSI
C57.12.25. Bushing arrangement and spacing shall be shown in Fig. 1 or Fig. 2 in Appendix B.
Table 2 — Low Voltage Terminal Sizes
Stock Number
kVA Capacity
Low voltage Terminal Size
368-120-130
25
5/8" x 11" UNC-2A copper studs
368-120-150
50
5/8" x 11" UNC-2A copper studs
368-120-155
50
5/8" x 11" UNC-2A copper studs
368-120-170
100
1" x 14" UNC-2A copper studs
368-120-180
167
1" x 14" UNC - 2A copper studs
368-120-190
250
1 %" x 12 UNF - 2A copper studs.
3.2.2.5.4 The low -voltage XZ bushing shall be a fully insulated bushing. A ground pad shall be provided on the
outer surface of the tank and an external removable copper ground strap shall be provided and
connected between the low -voltage XZ bushing and the ground pad.
3.2.2.5.5 The high -voltage neutral shall be securely grounded internally.
6
368-120
REV. SYM: FF
3.2.2.6ACCESSORY CABINET
3.2.2.6.1 The accessory cabinet shall consist of a compartment containing high- and low -voltage bushings
constructed in accordance with applicable ANSI specifications, including ANSI C57.12.28. Dimensions
shall be in accordance with Fig. 1 of this specification.
3.2.2.6.2 Cabinet doors shall be hinged, removable, lockable, and of sufficient size to provide adequate working
space when removed or open. Unlocking the padlock shall permit access to both the high- and low -
voltage terminations. Stainless steel hinge pins shall be provided.
3.2.2.7ACCESSORY EQUIPMENT
Accessory equipment shall be provided in accordance with the following details:
3.2.2.7.1 Deleted
3.2.2.7.2 The transformer base shall be arranged for rolling in two directions: Parallel to and at right angles to the
center line of the high -voltage bushings.
3.2.2.7.3 Lifting lugs or bosses for screw -in lift bolts shall be provided. These lugs or bosses shall be adequate
strength and size and arranged on the tank to provide a suitable balanced lift for the completely
assembled unit.
3.2.2.7.4 The base of the assembly shall be provided with suitable means for mounting the unit on the pad. An
internal flange shall be provided at the base of the accessory compartment to provide means for
mounting the unit on the pad. (Fig. land Figure 2, Appendix B).
3.2.2.7.5 Terminal designations are shown in Figure 1 and Figure 2, Appendix B. The identification of terminal
connections shall be shown on the instruction nameplate. Instruction nameplate shall be located in the
low -voltage side and shall be readable with cables in place. Where the nameplate is mounted on a
removable part, the manufacturer's name and transformer serial number shall be permanently affixed to
a non -removable part.
Instruction nameplate shall contain the information specified in 5.12 of ANSI C57.12.00-1987, Nameplate
A. Also, on the nameplate, or label affixed near it, the manufacturer shall indicate that the dielectric fluid
contains less than 1 ppm PCB.
3.2.2.7.6 A suitable marking inside of the tank shall indicate the correct oil level at 25°C.
3.2.2.7.7 An automatic pressure relief device shall be located within the compartment. This device shall meet the
following requirements:
• %d' NPT or larger male Inlet Port.
• Exposed parts of weather and corrosion resistant materials.
• Non -deteriorating gasket and o-ring material.
• Manual pull ring able to withstand 25 pound force minimum.
• Body able to withstand 100 pound shear force minimum.
• Bug shield.
• Cracking pressure of 10 t 2 psig.
• Resealing pressure of 8 t 2 psig.
• Zero leak rate from 8 t 2 psig to -8 psig.
• Minimum flow rate of 35 SCFM at 15 psig.
3.2.2.7.8 An RTE BAY-O-NET current sensing fuse and internally mounted partial range current limiting fuse shall
be furnished as shown in Table 1.
3.2.2.8OIL PRESERVATION
Transformers shall be of sealed -tank construction. Sealed -tank construction is that which seals the interior
of the tank from the atmosphere, and in which the gas plus the oil volume remains constant. The
transformer will remain effectively sealed fora top -oil temperature range of -5°C to 105°C.
3.2.2.9 TAN KS
The tank shall be domed or sloped to shed water. The tank shall be of sufficient strength to support a
minimum of 500 lbs. vertical load. Construction of the tank shall be in accordance with ANSI C57.12.25-
1981, paragraphs 6.1 and 6.6.
7
368-120
REV. SYM: FF
3.2.2.9.1 The cover shall be welded construction.
3.2.2.9.2 Tank grounding provision shall consist of two steel pads, each with inch - 13 NC tapped hole, 7/16
inch deep.
3.2.2.9.3 These ground pads shall be welded on the transformer base or on the tank wall near the base, one in
the high -voltage side and one in the low -voltage side. In cases where the transformer tank and
compartments are separate, provisions shall be made for electrically connecting them.
3.2.2.9.4 Locking bolts shall be pentahead.
3.2.2.10 COMPONENTS FOR LOOPED PRIMARY
The minimum current -carrying capability of components for the looped primary cable system shall be 200
amperes (continuous) and 10,000 amperes symmetrical (momentary).
3.2.2.11 AUDIBLE SOUND LEVEL
The audible sound level shall be in accordance with NEMA Standard TR1-1980.
3.2.2.12 BASE PLAN
The base plan of a completely assembled unit shall be such that it can be installed on a pad of the
dimensions shown in Fig. 1 B.
3.2.2.13 PAINT
EEI "Finishing Guidelines" specification shall apply. Finish coat shall be Munsell Green, glossy.
3.2.2.14 LOSSES
The total losses of transformer shall be the sum of the excitation losses and the load losses (IZR losses).
Load loss tests shall be performed and reported on all units regardless of whether or not a record of such
tests is available on duplicate units. Loss evaluations and loss costs will be based on the values shown in
the "Special Conditions and Supplemental Instruction to Bidders." Transformers will be evaluated on
excitation losses and IZR losses at the specified rates. If tested losses exceed quote losses but are within
the tolerances of Table 18, ANSI C57.12.00-1987, the additional cost incurred from the differential of losses
will be calculated using the following equation and the above specified rates and will be deducted from the
original Purchase Order or back charged to the manufacturer. In Table 18 and the following equation "Units"
shall mean 'Transformers of the same size and design on one order ".
Excess loss $ _ [No. of units] [(No Load Loss Evaluation $) (Avg. No Load Losses - Quoted No Load
Losses) + (Load Loss Evaluation $) (Avg. Load Losses - Quoted Load Losses)]. If this equation results in a
negative number, no credit will be given the Supplier.
If any unit or units exceed the tolerances of Table 18, ANSI C57.12.00-1987, that unit or units shall not be
shipped without express permission from the City. If accepted, the deduction for excess losses will be based
on the following equation: Excess loss $ _ (No Load Loss Evaluation $) (No Load Losses - Quoted No Load
Losses) But Not Less Than Zero + (Load Loss Evaluation $) (Load Losses - Quoted Losses) But Not Less
Than Zero.
3.2.2.15 SAFETY LABELS
NEMA 1260 Safety Labels shall not be applied by the manufacturer: Purchaser will apply customer warning
labels after delivery.
368-120
REV. SYM: FF
4 QUALITY ASSURANCE
4.1 GENERAL
4.1.1 RESPONSIBILITY FOR INSPECTION
Unless otherwise specified, the vendor is responsible for the performance of all inspection requirements
as specified herein. Except as otherwise specified, the vendor may utilize his own facilities or any
commercial laboratory acceptable to the City of Fort Collins. The City reserves the right to perform or
witness any of the inspections set forth in this Specification where such inspections are deemed
necessary.
4.1.2 TEST REPORT
The manufacturer shall furnish to the purchaser certified copies of the results of loss tests prior to
payment. Copies shall be sent to the Design Section as well as with the invoice. Unsigned copies are
not acceptable even if accompanied by a signed cover letter. The Quality Control Manager shall review
and sign each test report.
4.2 TEST CONDITIONS
Unless otherwise specified, testing required by Section 4.4 shall be conducted under the following
conditions:
4.2.1 REFERENCE TEMPERATURE
The reference temperature to which losses, impedance, regulation, and efficiency are corrected shall be
85°C.
4.2.2 TOLERANCE ON IMPEDANCE VOLTAGE
Impedance on completed units shall fall within the range specified herein.
4.2.3 TOLERANCE ON IMPEDANCE VOLTAGE ON A TAP
The percent departure of tested impedance voltage on any tap from tested impedance voltage at rated
voltage shall not be greater than the total tap voltage range expressed as a percentage of the rated
voltage.
4.3 Not used.
4.4 TESTS
The kinds of tests to be performed and the test procedures shall be as specified in ANSI C57.12.20, ANSI
C57.12.00, and C57.12.90 except as specified herein.
4.4.1 DIELECTRIC TESTS
No applied potential test shall be made. The induced -potential test shall be made by applying between
the terminals of one winding a voltage which will develop from high -voltage line terminals to ground a
voltage of 1000 volts plus 3.46 times the rated transformer winding voltage.
4.4.2 IMPEDANCE AND LOAD -LOSS TESTS
Impedance and load -loss tests shall be made on each unit and may not be omitted even if a record of
such tests made on a duplicate unit is available.
5 PREPARATION FOR DELIVERY
Transformers shall be prefilled with the appropriate amount of transformer oil and shall be shipped by open -bed truck.
Units shall be packaged in such a way as to provide for ease of handling and to protect units from shipping damage.
9
368-120
REV. SYM: FF
Units shall be packaged on four-way universal pallets with 34 inches minimum opening and loaded on the truck for
side removal. The Supplier shall give 24 hour notice prior to delivery for any shipments where an individual
transformer weighs over 5,000 pounds. In addition to these requirements, the Supplier shall comply with any
additional requirements or modifications shown on the purchase order and/or supplemental instructions.
6 DEFINITIONS AND ABBREVIATIONS
Vendor or Supplier - The manufacturer and/or manufacturer's agent supplying or quoting on the specified article.
Article, Unit, Assembly - All refer to the equipment defined by this Specification.
• DC or d.c. - Direct Current.
• AC or a.c. - Alternating Current.
• °C - Degree Celsius (Centigrade)
• °F - Degree Fahrenheit
• kV - 1000 volts.
• CPS or Hz - Cycles per second.
• psig - Pounds per square inch gauge.
• V or v - Volts.
• KVA - 1000 Volt-amperes.
10
368-120
REV. SYM: FF
APPENDIX A — Transformer Stock Number Coding
Below are examples that demonstrate the coding method used by City of Fort Collins to establish
transformer stock numbers.
I. SINGLE PHASE
Example #1=>
Transformer
Single Phase
00 = 13.2Y/7620 &
7620/13.2Y x
2400/4160 outside
pole
05 = 13.2Y7620 ESNA pole
20 = 13.2Y/7620 ESNA pad
II. THREE PHASE
368 -1 BC - X Y Z
Example #2 0 => 368 - 300 -
Transformer /
3 Phase
Pad
Other
KVA
0 = 5 5=50
1=10 6=75
2=15 7=100
3=25 8=167
4=37.5 9=250
1 = single voltage
2 = dual voltage
INIMI
006 = 75 076 = 750
015 = 150 100 = 1000
030 = 300 150 = 1500
050 = 500
• All suffixes indicate 208Y/120 sec.
• For 480Y/277 sec., add 1 to XYZ
(ie. 007 would indicate a 75kVA with
480Y/277 sec.)
11
368-120
APPENDIX B — DIMENSIONAL DRAWINGS
1
41C MIN
40' MAX
20' MIN
A
IIN
ING*
REV. SYM: FF
3%4' 5' 5' 4$' 1 34 3$' 316,
4V MIN
1
MIN MIN I MIN MIN MIN MIN MIN
H1A HIB X3 X1
CABLE ACCESSARY
7's1' 32'muxJ
PARKING STAND t
X2
GROUND PAD �
0 0
78"12'
1
MAX.
DIM.
KVQ
A
A
WITHOUT
RADIATORS
WITH
RADIATORS
25 & 50
3 2.5,"
--
100
--
42'
167
42'
53'
250
44'
S5'
s MINIMUM OPENING
IN BOTTOM OF COMPARTMENT
FOR CABLE ENTRANCE
Figure 1 — Type 1 Transformer Dimensions and bushing Designations (not to scale)
12
368-120
CITY OF FORT COLLINS
INVITATION TO BID
BID #7167
167 kVA PAD -MOUNTED COMPARTMENTAL -TYPE, SINGLE-PHASE
DISTRIBUTION TRANSFORMERS
Sealed bids will be received and publicly opened at the office of the Director Of Purchasing and
Risk Management, PO Box 580, 215 North Mason St., 2nd floor, Fort Collins, Colorado 80524, at
the time and date noted on the bid proposal and/or contract documents. If delivered, they are to be
delivered to 215 North Mason Street, 2"d Floor, Fort Collins, Colorado 80524. If mailed, the
address is P.O. Box 580, Fort Collins, 80522-0580.
Bids must be received at the Purchasing Office prior to 2:00 P.M. (Our clock) August 26,
2010
Special Instructions
All bids must be properly signed by an authorized representative of the company with the legal
capacity to bind the company to the agreement. Bids may be withdrawn up to the date and hour
set for closing. Once bids have been accepted by the City and closing has occurred, failure to
enter into contract or honor the purchase order will be cause for removal of supplier's name
from the City of Fort Collins' bidders list for a period of twelve months from the date of the
opening. The City may also pursue any remedies available at law or in equity. Bid prices must
be held firm for a period of forty-five (45) days after bid openings.
Submission of a bid is deemed as acceptance of all terms, conditions and specifications
contained in the City's specifications initially provided to the bidder. Any proposed modification
must be accepted in writing by the City prior to award of the bid.
Only bids properly received by the Purchasing Office will be accepted. All bids should be clearly
identified by the bid number and bid name contained in the bid proposal.
No proposal will be accepted from, or any purchase order awarded, to any person, firm or
corporation in default on any obligation to the City.
Bids must be furnished exclusive of any federal excise tax, wherever applicable.
Bidders must be properly licensed and secure necessary permits wherever applicable.
Bidders not responding to this bid will be removed from our automated vendor listing for the
subject commodities.
The City may elect where applicable, to award bids on an individual item/group basis or on a
total bid basis, whichever is most beneficial to the City. The City reserves the right to accept or
reject any and all bids, and to waive any irregularities or informalities.
Sales prohibited/conflict of interest: no officer, employee, or member of City Council, shall have a
financial interest in the sale to the City of any real or personal property, equipment, material,
supplies or services where such officer or employee exercises directly or indirectly any decision -
making authority concerning such sale or any supervisory authority over the services to be
rendered. This rule also applies to subcontracts with the City. Soliciting or accepting any gift,
INSIDE
0�
TANK SURFACE
DETAIL A
CABLE ACCESSORY
PARKING STAND
!15MIN ' ,- - ---
BOTTOM
INSIDE j r
10-1
FLANGE A
3MIN L
-
---------
IJ MAX 18 MIN OPENING -
(NOTE 2)
HIGH -VOLTAGE CONMCTORS
CABLE ACCESSORY B t MIN _
PARKING STAND 2
T
C
1/2
# 1/2 Hi8
60°. 15�
_ T
x3
SEA
CABLE ACCESSORY
DETAIL A
PARKING STAND
SEE DETAIL A
E 9
12.I°
B
2+3.1/8 f 1
(NOTE Ell-��q
D NIA
6MIN
BASE 11
Sill
GROUNDPAD
r, POINT
REV. SYM: FF
i t J.
i OPENING A
{NO1E 2) INSIDE
ARBITRARY PONNT
2sl
—zs 2 2
.3 Z FAIN
4 2 MIN
531
5:1
8#1
-Law
PLANE
74
Stock Number Dimension A Dimension B Dimension C Dimension D ' Dimension E
368-120-155 13" 5" 4" 0" 3 '/4"
Figure 2 - Type 2 Transformer Dimensions and bushing Designations (not to scale)
13
368-120
REV. SYM: FF
Pad Dimensions
This drawing is not intended to dictate requirements for items purchased under Specification 368-120 but is included as
an aid to those users desiring a minimum of pad designs for the transformers covered by Specification 368-120.
The dimensions in inches of Figure 3 will fit the minimum compartments on transformers covered by this Specification as
well as the maximum transformer envelope.
48" I
L
T3"
48"
12" PRIMARY SECONDARY
4 1/2" FRONT
�— 15" — 6" 12" 15"
FOUR #3 REBAR
18" LENGTH AND WIDTH
�3.�
3„
71/T2"
T
Notes on Pad Material -
1. Concrete must be 3,000 psi minimum.
2. Maximum coarse aggregate size 1 1/2 inches.
Space requirements for pad and primary switching cabinet will generally
be 9' X 12'. Factors to be considered in locating the pad include -
1. Accessibility - The transformer pad shall be accessible to
line boom trucks equipped for the installation and removal of
heavy transformers. Such accessibility shall not require
intrusion on adjacent property.
2. Proximity of Buildings, Walls, Barriers, and/or Overhangs -
In addition to the clearances required for installation and
removal, the minimum clearance in front of the transformer pad
shall be eight (8) feet and the minimum clearance from all
other sides shall be two (2) feet. If the building has an
overhang, clearance to the edge of the transformer pad shall
be measured horizontally from the outer edge of the overhang.
Transformers through 300 KVA may be installed under the
overhang if the vertical clearance between the pad and the
overhang is at least 25 feet and the location is accessible to
line boom trucks.
3. Codes and Standards - In addition to the above, the
installation shall conform to the National Electric Code and
federal, state and city codes and standards.
Figure 3 — Pad Dimensions
1d
+i i art•J
REV. SYM: FF
APPENDIX C — Approved Manufacturers
Transformers purchased under this Specification shall be of the make shown below. Manufacturers not listed below may
submit written proposals demonstrating compliance with these Specifications for consideration of addition to the accepted
manufacturers list prior to the next request for bids. In addition to inclusion on the list below, manufacturer's equipment
must also satisfy all requirements of this Specification to be acceptable.
MANUFACTURER SERIAL NO.
ABB
All
Cooper Power Systems All
General Electric All
Howard Industries All
The manufacturers in the following list have been conditionally approved and may bid as an alternate. The definition and
intent of "Conditional Approval' of a manufacturer is to allow the City to gain some experience with the manufacturer's
product. Should a conditionally approved manufacturer be the evaluated low bidder, the City reserves the right to award
all, part, or none of the order to them, dependant upon the current needs of the City for that item or items.
15
368-120
REV. SYM: FF
TRANSFORMER LOSS EVALUATION - AVERAGE LOSSES
City Order No. S/N
Manufacturer Invoice No.
KVA/Unit
LINE
DESCRIPTION AMOUNT
(1)
No. of units
(2)
Average core losses
(3)
Quoted core losses
(4)
Excess average core losses:
line (2) less fine (3)
(5)
Penalty for excess average core losses:
line (7) x line (4) x $
(6)
Average copper losses
(7)
Quoted copper losses
(8)
Excess average co per losses:
line (6) less 9ne (7)
(9)
Penalty for excess average copper losses:
line (1) x line (8) x $
(10)
Penalty to be assessed manufacturer:
line (5) plus line (9) but not less
than zero
Date Prepared By:
Design Engineering
NOTE: If any unit(s) exceeds the loss tolerances of ANSI C57.12.00, Light & Power will either reject it,
include it on these averages, or calculate losses using the Individual Transformer Losses Evaluation
Form, whichever is most favorable to Light and Power.
16
368-120
City Order No.
Manufacturer
KVA/Unit
LINE
(1)
(2)
(3)
INDIVIDUAL TRANSFORMER LOSS EVALUATION
S/N
Invoice No.
DESCRIPTION
Tested core losses
Quoted core losses
Excess core losses
line (1) less line (2) but not less
than zero
(4) Percent difference
line (3) ❑ line (2) x 100
(5) Tested total losses
(6) Quoted total losses
(7) Excess total losses
line (5) less line (6) but not less
than zero
(8) Percent difference
line (7) ❑ line (6) x 100
(9) Tested copper losses
(10) Quoted copper losses
(11)Excess copper losses
(12) line (9) less line (10) but not less
than zero
(12) Penalty for excess core losses
line (3) x $
(13) Penalty for excess copper losses
line (11) x $
(14) Penalty to be assessed manufacturer
line (12) plus line (13)
Date Prepared By:
Design Engineering
AMOUNT
REV. SYM: FF
17
368-120
Issued: 8/17/72
Revised: 1/21/94
Special Conditions and
Supplemental Instructions to Bidders
Applicable to
Specification 368-120
A. Data to be Supplied with Bidder's Proposal
The following data shall be supplied with the bidder's proposal in addition to that
information required by the "Invitation to Bid." and the "Purchase Requisition".
A typical list of users of 1 phase padmounted distribution class
transformers manufactured by the bidder during the past five years.
2. A typical drawing of the transformers showing that they will meet the
critical dimensions required by the Specification.
3. Impedance volts in % at full load, high voltage to low voltage at 850C.
4. No load and total losses at 850C.
5. Delivery in weeks.
6. A statement indicating compliance with our Specification without
exception or a detailed list of exceptions.
7. Escalation is _.is not _applicable for the transformers bid. If escalation
applies, the Bidder shall indicate in his bid the specific items or materials
subject to escalation, and shall give the method and indices to be used in
computing the amount thereof. Escalation occurring after the quoted
delivery date will not be paid unless delays are the result of actions by the
City. Escalation occurring after acceptance, if Purchaser exercises the
option to delay shipment after manufacturing is completed, will not be
paid.
If the above information and compliance statement are not supplied, the proposal will not
be evaluated.
An alternate bid for the total order may be submitted in addition to the unit bids.
B. Loss Evaluations
Loss penalties and loss evaluations will be based on the
following values:
No load or excitation losses at $3.90/watt.
2. Load losses at $1.50/watt.
C. Shipping Terms
Ship F.O.B. point of destination, freight prepaid.
D. Terms of Payment
1. If escalation applies, the City of Fort Collins shall not be billed for
escalation occurring after the promised delivery date.
2. Test reports shall accompany the invoice. If test reports do not accompany the
invoice, late payment penalty charges incurred due to delays in obtaining the test
reports will not be paid. Certified copies of test reports shall be sent to the Design
Section, Fort Collins Light and Power Utility.
3. Loss penalty credits and escalation charges shall be itemized on the
invoice.
Fort Collins Utilities Transformer Bid Loss Data Sheet
# Units
Bid #
7167
Preparer Name :
Name
Size
Date:
Preparer Contact Num:
Number
NL Loss Cost
FL Loss Cost
Escalation
Base Bid
Base
Bid $ /
Guar No Load Guar Full Load
Meet Specs?
(is / is not) Guar Total
NIL Loss * NIL
FL Loss * FL
Evaluated
Extended Cost
Supplier
Mfr / Mfr#
Each
Del/Wks Loss
Loss
Impedance (Yes / No)
a factor Load Loss
Loss Cost
Loss Cost
Bid
(Total $)
Westerm United
GE
$
3,682.00
8
240
1378
1.82 y
1618
$ -
$ -
$
3,682.00
$ 44,184.00
Howard
$
3,900.00
8
283
1339
2.50 y
1622
$ -
$ -
$
3,900.00
$ 46,800.00
Hartigan
Central Moloney
$
3,400.00
8
0
0
0.00
0
$ -
$ -
$
3,400.00
$ 40,800.00
Stuart C. Irby
COOPER
$
3,166.05
8
227
1575
2.28
1802
$
3,166.05
$ 37,992.60
Wesco
ABB
$
3,311.58
10 to 12
244
1621
2.52 y
$
3,311.58
$39,738.96
1) Fill out the information in the cells with blue text.
2) Save the file using your company name and the bid number and e-mail it to: purchasing@fcgov.com
(Example: TransformerSales_Bid_58.xls)
If you are concerned about security, you may password -protect this file after You have entered
your data.
To protect this file, take the following steps:
1) Select Tools, Options
2) Select Security Tab
3) Type your password in the 'Password to Open" field.
4) Re-enter your password to confirm it.
Important! Please remember to include this password in the bid information that will be sealed in the envelope that will be
unsealed at Bid Opening. This will secure your data until the time of the bid opening.
5) Save the file and e-mail it to: purchasing@fcgov.com
gratuity, favor, entertainment, kickback or any items of monetary value from any person who has or
is seeking to do business with the City of Fort Collins is prohibited.
Freight terms: unless otherwise noted, all freight is F.O.B. Destination, Freight Prepaid. All
freight charges must be included in prices submitted on proposal.
Discounts: any discounts allowed for prompt payment, etc., must be reflected in bid figures and
not entered as separate pricing on the proposal form.
Purchasing restrictions: your authorized signature of this bid assures your firm's compliance
with the City's purchasing restrictions. A copy of the resolutions are available for review in the
Purchasing Office or the City Clerk's Office. Request Resolution 91-121 for cement restrictions.
Collusive or sham bids: any bid deemed to be collusive or a sham bid will be rejected and
reported to authorities as such. Your authorized signature of this bid assures that such bid is
genuine and is not a collusive or sham bid.
Bid results: for information regarding results for individual bids send a self-addressed,
self -stamped envelope and a bid tally will be mailed to you. Bid results will be posted in our
office 7 days after the bid opening.
James B. O'Neill II, CPPO, FNIGP
Director of Purchasing and Risk Management
FIRM NAME:
CITY OF FORT COLLINS
BID PROPOSAL
BID NO. 7167
167 kVA Pad -Mounted Compartmental -Type, Single -Phase Distribution Transformers
BID DATE: 2:00 p.m. (Our clock) August 26, 2010
WE HEREBY ENTER OUR BID FOR THE CITY OF FORT COLLINS' REQUIREMENTS
FOR 167 kVA PAD -MOUNTED COMPARTMENTAL -TYPE, SINGLE-PHASE DISTRIBUTION
TRANSFORMERS, PER THE BID INVITATION AND ANY REFERENCED SPECIFICATIONS.
QUANTITY: DESCRIPTION:
12 Ea. 167 kVA Pad -Mounted Compartmental -Type, Single -Phase
Distribution Transformers with Separable Insulated Load Break High -
Voltage Connectors.
HIGH VOLTAGE RATING: 13200 GRDY/7620 VOLTS.
LOW VOLTAGE RATING: 240/120.
SERIAL NUMBER 180 TO BE IN ACCORDANCE WITH
SPECIFICATION #368-120-180, REVISION FF
PLEASE COMPLETE THE ATTACHED EXCEL SPREAD SHEET
FOR BID SUBMITTAL.
IF YOU ELECT TO PASSWORD PROTECT YOUR BID, PLEASE
NOTE THAT PASSWORD BELOW.
*Any surcharges or additional costs shall be noted & included in bid submittal.
The transformers being bid meet or exceed the specifications. Yes No. If not,
please list exceptions,(specifying paragraph reference number) on a separate sheet of paper and
attach to your bid.
Escalation is , is not applicable for the transformers bid. If escalation applies, the
bidder shall indicate in his bid the specific items or materials subject to escalation, and shall give
the method and indices to be used in computing the amount thereof. Escalation occurring after the
quoted delivery date will not be paid unless delays are the result of actions by the city. Escalation
occurring after acceptance if purchaser exercises the option to delay shipment after manufacturing
is completed, will not be paid.
Delivery may be a consideration of bid award.
For purposes of warranty and service ONLY approved manufacturers or distributors authorized
by an approved manufacturer to serve the Fort Collins area may bid.
The City of Fort Collins reserves the right to split the bid in whatever percentages are most
advantageous to the City.
Future orders of Pad -Mounted Compartmental -Type, Single -Phase Distribution
Transformers may be authorized, at the option of the City, from this bid for a period of five
years after date of award. Satisfactory pricing and delivery is required for future orders based on
this bid.
SUPPLEMENTAL INSTRUCTIONS
Prices quoted must remain firm for a 30 day period after the opening date.
Freight terms: F.O.B. destination freight prepaid. All freight charges must be included in pricing
submitted on proposal and not entered as separate pricing.
Any discount allowed by Vendor for prompt payment, etc. must be reflected in quoted figure, and
not entered as separate pricing.
The City reserves the right to accept or reject any and all quotes.
Bidder not responding to the services requested in this bid shall be removed from our automated
listing for: Not Applicable
Any questions or inquiries regarding this bid should be directed to:
Opal F. Dick, CPPO, Senior Buyer
(970)221-6778
SIGNATURE AND TITLE: TYPED OR PRINTED NAME AND TITLE
COMPANY NAME: (AREA CODE) TELEPHONE NUMBER/FAX NUMBER
ADDRESS: STREET, CITY, STATE, ZIP DATE
EMAIL:
Purchase Order Terms and Conditions
1. COSMERCTAL DETAILS.
Tax exemptions. By stamen the City of Fort Collins is exempt from state and local taxes. Our Exemption Number is I L NONWAIVER
98-M502. Federal Excise Tax Exemption Cemf-re of Registry 846000597 is registered with the Collector of Failure of the Purchaser in insist upon strict performance of the terms and conditions hereof failure or delay to
Internal Revenue. Dearer, Colorado (Ref. Colorado Revised Statures 1973, Chapter 39-26, 114 (a). exern a any, rights or remedies provided herein or by Law, failure to promptly notify the Seller in the event of a
bread the acceptance ofor payment for goods hereunder or approval of the design, shall not release the Seller of
Good.- k,;Krwd. GOODS RRMCTRD doe to failure to meet �pc cnri—, dd—wbm :Lipped oz doe m defeea of a^Y of rho warranties rc nNi�prirma of rhic pmrha.e nrdw .rod chap rot he dowmM a wars— of any tf eM of rho
damage in rmnsit, may be returned to you for credit and ace not to be replaced except upon recaps of written Purchases` to insist ap= strict performance hereof or any of its rights or remedies as to any such goods, regardless
instructions from the City of Fort Collins. of when shipped received or accepsd, as many. prior or subsequent default hereunder, nor shall nay purported
oral modibratian car rescission of this purchase order by the Purchaser operate as a waiver of any of the terms
Inspection. GOODS are subject to the Ctry of Fort Collins inspection an arrival. hereof
Final Acceptance, Receipt of the merchandise, services or equipment in response to this order can result in 12 ASSIGNMENT OF ANTITRUST CLAMS.
authorized payment on the pan of the City of Fort Collins. However, it is to be understood that FINAL Seller and the Purchaser recognise that in actual economic practise, overcharges resulting from antatu t
ACCEPTANCE is dependent upon completion of all applicable required inspection procedures, violations are in fact borne by the Purchaser. Theretofore, for good cause and as consideration for executing this
purchase order, the Seller hereby assigns m the Purchaser nay and all claims it may now have or bereafter
Freight Tams. Shipments most be F.OB., City of Fort Collins, 700 Wood SL, Fort Collins, CO 80522. unless acquired under federal or state antimrst Laws for such overcharges relating to the particular bads or services
otherwise specified on this order. If permission is, given to prepay freight and charge separately, the original freight purchased or acquired by the Purchaser pursuam m this purchase order.
brill most accompany invoice. Additional chaps for parking will not be accepted
Shipment Distance. Where-anfurmers have distributingpoints in various parts of the cottony, shipment is
expected from the nearest distribution, point to destination, and excess freight will be deducted from Invoice when
shipments are made from greater distance.
Permits. Seller shall procure at sellers sole cost all necessary permits, certificates and licenses reganed by all
applicable laws, regulations, ordinances and rules of the state, municipality, territory ar political subdivision where
the work is performed, or regmmd by any other daily convarwed public authority having jmisdimon aver the walk
of vendor: Seller further agrees to hold the City of Fort Collin harmless from and against all liability and loss
incurred by them by reason of an asserted or established violation of any such laws, regolatiam, ordinances, roles
and requirements.
Audiatiutioa All parties to this contract agree that the representatives are, in fiat; bons fide and possess fall and
complete authority to bind said panties.
LMICATION OF TERMS. This Purchase Order expressly limits acceptance. to the corms wad comments stated
beiem set forth and, any supplementary or additional term: and conditions maexed hereto or mccapotated herein by
reference. Any additional a different terms and conditions proposed by seller we objected to and hereby rejected
2. DELIVERY.
PLEASE ADVISE PURCHASING AGENT immediately if you canna make complete shipment to active on your
promised dehvay dace as noted Time is of the essence. Delivery and performance mast be effected within the erne
stated on. the purchase orderand the documents attached hereto. No acts of the Purchasers including, without
limmation• acceptance of partial late deliveries, shall operate as a waiver of this "provision In the event of any delay:
the Purchaser shall have, in addition to other legaland equitable remedies. the option ofphcing this order elsewhere
and holding the Seller liable for damages. However, the Seller shall not be liable for damages as a result of delays
due to causes no reasonably foreseeable which are beyond its ressanable control and without its fault of negligence
such acts of God, acts of civil m military authorities, goveran rental priorities, fires, strflin, flood, epidemics, %— or
riots provided that notice of the conditions cansfng inch delay is given to the Purchaser within five (5) days of the
time when the Sella first received knowledge thereof In the event of any such delay, the dam of delivery shall be
extended for the period equal to the time actually lost by reason of the decay.
3. WARRANTY-.
The Seller transmits that all goods, articles, trumrials and work covered by this orderwill conform with applicable
drawings, specifications, samples md'or otbu descriptions given. will be fit for the purposes intended, and
performed with the highest degree of care and competence in accordance with accepted standards for work of a
simile ast re. The Seller agrees to hold the purchaser harmless from any toss, damage or expense, which the
Purchaser may suffer a mcm on accottm of the Sellers breach of warranty. The Seller shall replace, repair or make
good, without cost to the pmdhaser. any defects or faults wising within one (1) year or within such longer period of
time as may be prescribed by taw or by the terms of any applicable warmary provided by the .Sella after the date of
accept -re of the goods f rr ushed hereunder (acceptance not m be raweasombly delayed), resutndg from imperfect
or defective work dotter or materials famished by the Sella. Acceptance or use of goods by the Purchaser shall not
constitute a warier of nay shim under this warrmry. Except. w otherwise provided in this purchase mdu. the Sellers
liability hereunder shall emend to all damage proximately caused by the breach of my of the foregoing Warranries
or goaramees, but such liability shall in no event include lam of profa s a loss of are. NO IMPLIED WARRANTY
OR MERCHANTABILITY OR OF FITNESS FOR PURPOSE SHALL APPLY.
4. CHANGES IN LEGAL TER1fS.
The Purchaser may make changes to legal terms by written chin— order.
5. CHANGES IN COMMERCIAL TMIS.
The Purchases may make any changes to the terms. odia than legal terns, including additions to or deletions from
the.gmntities originally ordered in the spedficatioas or drawings, by verbal or written change order. If any such
change affects the amount deg or the time of performance hereunder, an equitable adjustment shall be made.
6: TERINM70.TIONS.
The Porrhasa may at any tare by written change order, terminate this agreement as m nay or all portions of the
goods rhea not slipped, subject to my equitable adjustment berween the parties as to sir wads or mareriaia then in
progress provided that the Purchaser shall not be liable far my claims for anticipated profits on the uncompleted
portion of the goods andtor work, for incidental or consequential damages, and that no such adjustment be made in
favor of the Sella with respect to any goods which we die Sellers standard stock. No such termiavtion shallrelieve
the Purchaser or the Seller of nay of their obligations as to my goods delivered hereunder.
7. CLAMS FOR ADIIISTNIENT.
Any claim for adjustment mast be asserted within thirty (30) days from the dam the change at miminman is
ordered
S. COMPLIANCE WITH LAW.
The Seller warrants that all goods wild hereunder shalt have been produced, sold, delivered and furnished in strict
compliance with all applicable laws and regulations in which the good are mbiKL The Sella shall execate and
deliversuch documents as may be requied to effect or evidence compliance. All laws and regulations required to be
incorporated in agreemems of this character are hereby i rotpomted herein by dus reference. The Sella agrees to
indemnify. and bold the Purchaser harmless from all costs and damages suffaed by the Pachsser as a result of the
Sellers failure to comply with such law.
9. ASSIGNMENT.
Neither patty shall assign, transfer, or convey this order, or my monies due or to become doe hereunder withtmt the
prior written consent of the other parry.
10. TITLE.
The Sella wsrrams fall, clear and unrestricted tide to the Purchaser for all equipment, tmtmW% and items banished
in performance of this agreement, free and clew of my and all liens, restrictions, reservanans security interest
encumbrmces and claims of others.
13. PURCHASERS PERFORt.L404CE OF SELLERS OBLIGATIONS.
If the Purchase directs the Seller to correct nonconforming or defective goods by a dam to be agreed upon by the
Pmchr and the Seller, and the Seiler ibeteafter indicates its mabRny or unwillingness to comply, the Purchaser
may cause the work to be performed by the must expeditious merms available to a, and the Seller shall pay all
costs associated with such work.
The Seller shall release the Purchaser and its contractors of any tier from all liability and claims of any nature
resulting from the performance of such work.
This release shall apply -even in the event of fault of negligence of the parry released and shall extend to the
directors, officers and employees of sash party.
The Sellet's rocia-mal obligations, including warram y, sbatl not be deemed to be redwed in any way, because
such cork is performed or caused to be performed by the Purchaser.
14_ PATENTS.
Whimever the Seller. is required to use my design, device, material or process coveted by letter, patent trademad
at copyright, the Seller shall indemnify and save harmless the Purchaser from any and all claims for infringement
by reasons of the use of such patemed design, device, material or process in connection frith the couracf and
shad indemnify the Purchaser, for mycost, expense ordamage which it may be obliged to pay.by reason of such
infringement at any time daring. the prosecution a after the completion of the work. In case said egaipmem, or
any pan thereof or the intended use ofthe goods, a in stiih suit held to constitute infringement and the use of
said equipment or pan is eajoined the Seller shag at its own expense and at is "option, either procure for the
Purchaser the. rightto comimme using said eq.4- rat "or parts, replace the same with mbstand lly equal but
=,infringing equipment, or modify it so it becomes a infruq=g
I5. INSOLVENCY_
If the Seller shall become insolvent or bankrupt, make an assignment for: the benefit of creditors, appoint a
receuver m trustee for army of the. Sellers property or business, this order may forthwith be canceled by the
Purchaser without liability.
16. GOVERNING LOW.
The definitions of tends toed or the interpretation of the agreemert and the rights of all parties hereunder &half be
canstrued under and governed by the laws of the State of Colorado, USA.
The following Additional Conditions apply: only in cases where die Seiler is m perform work hereunder:
mrlffiing the services of Sellers Represenmtive(s), on the premises of odien.
17. Sum t rue RESPONSIBILITY.
The Sella shall carry on said wort at Seller% own itsk mail the same is filly completed and accepted, and shall,
in case of any accident, destruction or im1my to the work andtor materials before Sell final completion and
acceptance, complete the work at SeBets awn expense and to the satisfaction of due Purchaser. When materials
and equipment are f=ished by others for installation or erection by the Sella, the Seller shall receive,milaad
x and tmivIle an..••' m the site -d Laysrme reaykruulde wnetw as dvuaL arsb mk 1w h —d'- espkipr••e,.i
were being famished by the Seller order the ardet.
IS. INSURANCE_
The Sella shall at bus own expense, provide for the payment of workers compesatiou, including occupational
disease benefits, to its Employees employed on or in counecnam with the wort coffered by this purchase order,
anXw to then dependents in accordance with the laws of the state in which the work is to be done. The Seller
shall also carry comprehensive general liability including, but not limited to, coaaacrosl and automobile public
liabilityiasarence with bodily mjuiy and death limi,s of at least $300,000 for my one petsoo, $500,000 fm aay
one accident andPropertydamage limit per accident of $400.000. The Sella shall likewise require his
connectors, if ate, to provide for such compensation and mstnance. Before any of the Sellers or his contraRors
employees shall do my work upon the premises of others, the Sella shall furnish the Puachas r with a certificate
that such compensation and insurance have been provided Such certificates shall specify the dam 'when such
compensation and insurance have been provided. Such certificates shall specify the date when such marpensation
and insurance expares..The Sella agrees that such compensation and insurance shall be mainnined until alher the
eaaie work is completed and accepted.
19. PROTECTION AGAINST ACCIDENTS AND DAMAGES.
The Seller hereby assumes :he enure responsibility and liability for ate• and alldamage, loss or injury of my kind
or nature whatsoever to persons or property caused by or resulting from the execution of the work provided for in
this purchase order orin connection herewith The Sella will indemnify and hold harmless the Purchases and any
or all of due Purchasers officers, agents and employees from and against any and all claims, losses, damages,
charges a expenses, whether direct or indirect, and whether to persons or property to which the Purchaser may
be put orsubject by reason of say act, action, neglect omission. or default on the pan of the Seller, any of bus
contractors, or any of the Sellers or comractors officers, agents or employees. In case my sort or other
proceedings shall be brought against the Purchaser,. or its officers, agents or employees at my time an account or
by reason of any act, action, neglect, omission or default of the Seller of any of his contractors w my of its or
their officers, agents or employees as aforesaid the Seller hereby agrees to assume the defense thereof and to
defend the same at the Sellers own expense, to pay any and all costs, charges, attorneys fees and other expenses,
my and all judgments that may be incurred by or obtained against the Purchaser or army of its or their officers,
agents a employees in such suits a other proceedings, and incase judgment or other Lim be placed upon or
obtained against the property of the Purchaser, or said parties in or as a result of such suits or other proceedings,
the Sella will at once cause the same to be dissolved and discharged by giving bond or otherwise. The Sella and
his contractors shall take all safety precautions, furnish and install all guards necessary for the prevention of
students, comply with all laws and regulations with regard to safety including, but with" humastion, the
Occupational Safety and Rea" Act of 1970 and all rules and regulations issued purstiat thereto.
Revised 0312010
Fort Collins Utilities Transformer Bid Loss Data Sheet
# Units
Bid # 7167
Preparer Name :
Name
Size
Date:
Preparer Contact Num:
Number
NL Loss Cost
$
FL Loss Cost
$
Supplier
Mfr/Mfr#
Base Bid $1
Each
DeIM1kS
Guar No Load
ILoss
Guar Full Load
Loss
Impedance
Meet Specs?
(Yes I No)
Escalation (is I is
not) a factor
Guar Total Load
Loss
NL Loss' NL
Loss Cost
FL LossFL
Loss Cost
Evaluated Bid
Base Bid
E)dended Cost
(Total $)
Supplier 1
Mfg 1
$
0
0
0.00
-
0
$
$
$
$
Supplier 2
Mfr2
$
0
0
0.00
0
$
$
$
$
Supplier 3
Mfr3
$
0
0
0.00
0
$
$
$
$
Directions for Bidders:
1) Fill out the information in the cells with blue text.
2) Save the file using your company name and the bid number and e-mail it to: purchasing@fcgov.com
(Example: TransformerSales_Bid_.xls)
If you are concerned about security, you may password -protect this file after you have entered your data.
To protect this file, take the following steps:
A) Select Tools, Options
B) Select Security Tab
C) Type your password in the "Password to Open" field.
D) Re-enter your password to confirm it.
Important! Please remember to include this password in the bid information that will be sealed in the envelope that will be
unsealed at Bid Opening. This will secure your data until the time of the bid opening.
E) Save the file and e-mail it to: purchasing@fcgov.com
THE CITY OF FORT COLLINS
Light and Power Department
P.O. Box 580
Fort Collins, CO 80522
SPECIFICATION NO: 368-120
TITLE: PAD -MOUNTED COMPARTMENTAL -TYPE, SINGLE-PHASE
DISTRIBUTION TRANSFORMERS
WITH SEPARABLE
INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS
APPROVED BY:
Kraig E. ad
Standards Engineering Manager
ORIGINATED: 09/14/72
LAST REVISED: 7/21/2004
ITEMS COVERED BY THIS SPECIFICATION
DESCRIPTION
STOCK NO.
SPECIFICATION
NO.
SERIAL
25 KVA, 120/240 ANSI Type 1 Transformer.
368-120
-130
50 KVA, 120/240 ANSI Type 1 Transformer.
368-120
-150
50 KVA, 120/240 ANSI Type 2 Transformer.
368-120
- 155
100 KVA, 120/240 ANSI Type 1 Transformer.
368-120
-170
167 KVA, 120/240 ANSI Type 1 Transformer.
368-120
-180
250 KVA, 120/240 ANSI Type 1 Transformer.
368-120
-190
REV. SYM: FF
PREVIOUS REVISION DESCRIPTIONS ON FILE
REVISION DESCRIPTION
APPROVED
REVISION DD:
Sagen
• Paragraph 3.2.2.7.5: Editorial
10/21/94
• Add paragraph 3.2.2.9.4 requiring pentahead locking bolts
• Paragraph 3.2.2.13 add glossy to paint requirement
• Paragraph 4.2.2: Clarify impedance requirement
REVISION EE:
Sagen
• Paragraph 5.0: revised pallet size from 28 to 34 inches
2/25/98
REVISION FF
Kraig Bader
• Added 50kVA ANSI Type 2 Transformer (368-120-155) to Specification
7/21/2004
• Changed paint color to standard Munsell Green
• Reorganized to consolidate impedance and fusing requirements into one table.
• Consolidated secondary terminal requirements into one table.
• Added maximum impedance requirement for 250kVA transformer (+/-7.5% from nominal for
transformers with impedance greater than 2.5%) per ANSI/IEEE C57.12.00-2000.
• Re-evaluated fusing requirements of all transformers in this specification. Went from dual
sensing bay-o-net (expulsion) fuses to current sensing bay-o-net (expulsion) fuses. Fuse sizing
was changed as follows:
• Changed 25 kVA from 8A expulsion / 40 amp CL to 10A expulsion / 30A CL
• Changed 50 kVA from 15A expulsion / 80 amp CL to 15A expulsion / 40A CL
• Changed 100 kVA from 25A expulsion / 175 amp CL to 25A expulsion / 80A CL
• Changed 167 kVA from 40A expulsion / 200amp CL to 40A expulsion / 125A CL
• Changed 250 kVA from 65A expulsion / 350amp CL to 65A expulsion / 125A CL
368-120