HomeMy WebLinkAboutBID - 7167 PAD-MOUNTED COMPARTMENTAL-TYPE, SINGLE-PHASE DISTRIBUTION TRANSFORMERSCity of Fort Collins Bid Proposal Financial Services Purchasing Division 215 N. Mason St. 2nd Floor PO Box 580 Fort Collins, CO 80522 970.221.6775 970.221.6707 kgov.com/Purchasing BID 7167 167 WA Pad -Mounted Compartmental -Type, Single -Phase Distribution Transformers BID DATE: 2:00 P.M. (Our clock) August 26, 2010 REV. SYM: FF TABLE OF CONTENTS PREVIOUS REVISION DESCRIPTIONS ON FILE..........................................................................................................................2 1 SCOPE...................................................................................................................................................................................................4 2 APPLICABLE DOCUMENTS............................................................................................................................................................4 2.1 ANSI C57.12.00 - DISTRIBUTION, POWER, AND REGULATING TRANSFORMERS, AND SHUNT REACTORS, GENERAL REQUIREMENTS FOR......................................................................................................................................................................................................... 4 2.2 ANSI C57.12.25 - PAD MOUNTED, COMPARTMENTAL -TYPE, SINGLE-PHASE, DISTRIBUTION TRANSFORMERS WITH SEPARABLE H-V CONNECTORS, STANDARD REQUIREMENTS FOR.......................................................................................................................................4 2.3 ANSI C57.12.28 - SWITCHGEAR AND TRANSFORMERS - PAD -MOUNTED EQUIPMENT -ENCLOSURE INTEGRITY...............................4 2.4 ANSI C57.12.70 - TERMINAL MARKINGS AND CONNECTIONS FOR DISTRIBUTION AND POWER TRANSFORMERS...............................4 2.5 ANSI C57.12.80 - TERMINOLOGY FOR POWER AND DISTRIBUTION TRANSFORMERS........................................................................4 2.6 ANSI C57.12.90 - DISTRIBUTION, POWER, AND REGULATING TRANSFORMERS, AND SHUNT REACTORS, TEST CODE FOR.................4 2.7 IEEE C57.91 - GUIDE FOR LOADING MINERAL -OIL -IMMERSED OVERHEAD AND PAD -MOUNTED DISTRIBUTION TRANSFORMERS RATED 500 KVA AND LESS WITH 650C OR 550C AVERAGE WINDING RISE..........................................................................................4 3 REQUIREMENTS................................................................................................................................................................................4 3.1 GENERAL REQUIREMENTS FOR DESIGN...............................................................................................................................4 3.2 SPECIFIC DESIGN REQUIREMENTS..........................................................................................................................................5 4 QUALITY ASSURANCE.....................................................................................................................................................................9 4.1 GENERAL.......................................................................................................................................................................................9 4.2 TEST CONDITIONS.......................................................................................................................................................................9 4.3 NOT USED.........................................................................................................................................................................................9 4.4 TESTS..............................................................................................................................................................................................9 5 PREPARATION FOR DELIVERY....................................................................................................................................................9 6 DEFINITIONS AND ABBREVIATIONS........................................................................................................................................10 APPENDIX A - TRANSFORMER STOCK NUMBER CODING...................................................................................................I I APPENDIX B - DIMENSIONAL DRAWINGS.................................................................................................................................12 PADDIMENSIONS..............................................................................................................................................................................14 APPENDIX C-APPROVED MANUFACTURERS.........................................................................................................................15 TRANSFORMER LOSS EVALUATION - AVERAGE LOSSES....................................................................................................16 INDIVIDUAL TRANSFORMER LOSS EVALUATION.................................................................................................................17 3 368-120 REV. SYM: FF SPECIFICATION FOR PAD -MOUNTED COMPARTMENTAL -TYPE SINGLE-PHASE DISTRIBUTION TRANSFORMERS WITH SEPARABLE INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS 1 SCOPE This Specification establishes the minimum electrical requirements and mechanical features of single phase, 60 HZ, mineral oil immersed, self -cooled, pad -mounted, compartmental -type distribution transformers rated 250 KVA and smaller, high voltage 13,200 Grd Y/7620 volts, with separable insulated load break high voltage connectors. These transformers are used for step down purposes from an underground primary cable supply. This standard generally conforms with ANSI requirements for pad -mounted compartmental -type, self -cooled, single- phase, distribution transformers, C57.12.25. 2 APPLICABLE DOCUMENTS The following documents of the issue shown form a part of this Specification to the extent specified herein. In those cases when the document is note dated, the latest issue in effect on the date of invitation for bids shall form a part of this Specification. 2.1 ANSI C57.12.00 - Distribution, power, and regulating transformers, and shunt reactors, general requirements for. 2.2 ANSI C57.12.25 - Pad mounted, compartmental -type, single-phase, distribution transformers with separable H-V connectors, standard requirements for. 2.3 ANSI C57.12.28 - Switchgear and Transformers - Pad -Mounted Equipment -Enclosure Integrity. 2.4 ANSI C57.12.70 - Terminal markings and connections for distribution and power transformers. 2.5 ANSI C57.12.80 - Terminology for power and distribution transformers. 2.6 ANSI C57.12.90 - Distribution, power, and regulating transformers, and shunt reactors, test code for. 2.7 IEEE C57.91 - Guide for Loading Mineral -Oil -Immersed Overhead and Pad -Mounted Distribution Transformers Rated 500 kVA and Less with 65°C or 55°C Average Winding Rise. 3 REQUIREMENTS 3.1 GENERAL REQUIREMENTS FOR DESIGN 3.1.1 BASIC DESIGN STANDARDS Transformers purchased under these Specifications shall be new and, unless otherwise specified, meet the requirements of the applicable ANSI Standards and the modifications and additions given in the subsequent paragraphs. In case of conflict, the requirements of the following documents shall apply in the priority shown: a) This Specification b) Applicable ANSI Standards Approved manufacturers are listed in Appendix C. 4 368-120 REV. SYM: FF 3.1.2 KILOVOLT -AMPERE TEMPERATURE RATINGS Kilovolt -ampere ratings are continuous and are based on not exceeding either a 65°C average winding temperature or an 80°C hot spot temperature rise. The temperature rise of the insulating oil shall not exceed 65°C when measured near the top of the tank. The temperature rise is based on an altitude of 3,300 feet. The transformers shall be designed for overloads based on IEEE C57.91. 3.1.3 GENERAL CONSTRUCTION 3.1.3.1 The pad -mounted compartmental -type transformers shall consist of the transformer tank and high -and -low - voltage cable terminating compartment constructed in accordance with ANSI C57.12.25 and ANSI C57.12.28. The terminating compartment and tank shall be assembled as an integral unit, tamperproof and weatherproof for mounting on a pad. There shall be no exposed screws, bolts, or other fastening devices which are externally removable. The cover shall be welded construction. There shall be no opening through which foreign objects such as sticks, rods, or wires might be inserted to contact live parts. Suitable means for padlocking the compartment door(s) shall be provided. 3.1.3.2The high- and low -voltage compartment shall be located side by side on one side of the transformer tank. When facing the compartment, the low -voltage side shall be on the right. 3.1.3.3 Construction of the unit shall be such that it can be lifted, skidded, and slid into place on the mounting pad without disturbing the entrance cables. 3.1.3.4An undercoating over the regular finish or an equivalent treatment shall be applied to all surfaces that are in contact with the pad to minimize corrosion. 3.1.3.5 Minimum dimensions for Type 1 transformers shall be as shown in Figure 1, Appendix B. Minimum dimensions for Type 2 transformers shall be as shown in Figure 2, Appendix B. 3.2 SPECIFIC DESIGN REQUIREMENTS 3.2.1 FUNCTIONAL DESCRIPTION The transformer shall be a single phase, pad mounted, loop feed -safe break, "dead -front" type for use on a 13.8 kV grounded "Y" distribution system. 3.2.2 DESIGN AND CONSTRUCTION 3.2.2.1 RATING The transformer shall be rated as follows a) High Voltage 13,200 Grd. Y/7620 volts b) Low Voltage 240/120 c) Taps Two - 2Y2% FC above and below normal d) Polarity Additive e) Capacity, Impedance values, and fusing for transformers in this specification shall conform to Table 1: 5 368-120 REV. SYM: FF Table 1 — Transformer Capacity, Impedance and Fuse Selection .Stock kVA Min. Max. Bay-O-Net. Current Limiting Fuse(s) Number Capacity Impedance Impedance Fuse 368-120-130 25 1.77% 2.16% 10 Amp ELSP 354403OM61 M (30 A) 4000353C06 368-120-150 50 1.77% 2.16% 15 Amp ELSP 354304OM61 M (40 A) 4000353C08 368-120-155 50 1.77% 2.16% 15 Amp ELSP 354304OM61 M (40 A) 4000353C08 368-120-170 100 1.95% 2.38% 25 Amp ELSP 354308OM71 M (80 A) 4000353C10 368-120-180 167 2.28% 2.79% 40 Amp ELSP 3543125M71 M (125 A) 4000353C12 368-120-190 250 5.75% 6.61 % 65 Amp ELSP 3543125M71 M (125 A) 4000353C14 "The BAY-0-NET fuse shall be located in the high voltage side of the compartment. 3.2.2.2INSULATION LEVEL 3.2.2.2.1 The basic impulse insulation level (BIL) of completely assembled high -voltage and low -voltage terminals shall be 95 kV and 30 kV respectively. 3.2.2.2.2 Dielectric test levels shall be in accordance with the distribution levels in Section 4 of ANSI C57.12.00. 3.2.2.3 HIGH -VOLTAGE TAPS A no-load tap changer with external operating handle shall provide two - 2Y2% full capacity taps above and below normal. The tap changer operating handle shall be located within the high -voltage terminal side of the terminal compartment. 3.2.2.4 NOT USED 3.2.2.5 BUSHING WELLS AND TERMINALS 3.2.2.5.1 The number, location, and arrangement of bushing wells, terminals and parking stands shall be as shown in Fig. 1 or Fig. 2 in Appendix B. All low -voltage bushings and high -voltage wells shall be externally clamped and shall have leads of sufficient length to allow them to be changed without removing the cover. Welded bushings and wells are expressly prohibited. 3.2.2.5.2 High -voltage terminals shall be universal flowerpot bushing wells in accordance with Figure 3 of ANSI/IEEE 386-1985. Two wells shall be provided and shall be connected in a feed -through configuration. Loadbreak bushing inserts in accordance with Figure 5 of ANSI/IEEE 386-1985 will be owner furnished. 3.2.2.5.3 Low -voltage line and neutral terminals shall be sized as shown in Table 2 in accordance with ANSI C57.12.25. Bushing arrangement and spacing shall be shown in Fig. 1 or Fig. 2 in Appendix B. Table 2 — Low Voltage Terminal Sizes Stock Number kVA Capacity Low voltage Terminal Size 368-120-130 25 5/8" x 11" UNC-2A copper studs 368-120-150 50 5/8" x 11" UNC-2A copper studs 368-120-155 50 5/8" x 11" UNC-2A copper studs 368-120-170 100 1" x 14" UNC-2A copper studs 368-120-180 167 1" x 14" UNC - 2A copper studs 368-120-190 250 1 %" x 12 UNF - 2A copper studs. 3.2.2.5.4 The low -voltage XZ bushing shall be a fully insulated bushing. A ground pad shall be provided on the outer surface of the tank and an external removable copper ground strap shall be provided and connected between the low -voltage XZ bushing and the ground pad. 3.2.2.5.5 The high -voltage neutral shall be securely grounded internally. 6 368-120 REV. SYM: FF 3.2.2.6ACCESSORY CABINET 3.2.2.6.1 The accessory cabinet shall consist of a compartment containing high- and low -voltage bushings constructed in accordance with applicable ANSI specifications, including ANSI C57.12.28. Dimensions shall be in accordance with Fig. 1 of this specification. 3.2.2.6.2 Cabinet doors shall be hinged, removable, lockable, and of sufficient size to provide adequate working space when removed or open. Unlocking the padlock shall permit access to both the high- and low - voltage terminations. Stainless steel hinge pins shall be provided. 3.2.2.7ACCESSORY EQUIPMENT Accessory equipment shall be provided in accordance with the following details: 3.2.2.7.1 Deleted 3.2.2.7.2 The transformer base shall be arranged for rolling in two directions: Parallel to and at right angles to the center line of the high -voltage bushings. 3.2.2.7.3 Lifting lugs or bosses for screw -in lift bolts shall be provided. These lugs or bosses shall be adequate strength and size and arranged on the tank to provide a suitable balanced lift for the completely assembled unit. 3.2.2.7.4 The base of the assembly shall be provided with suitable means for mounting the unit on the pad. An internal flange shall be provided at the base of the accessory compartment to provide means for mounting the unit on the pad. (Fig. land Figure 2, Appendix B). 3.2.2.7.5 Terminal designations are shown in Figure 1 and Figure 2, Appendix B. The identification of terminal connections shall be shown on the instruction nameplate. Instruction nameplate shall be located in the low -voltage side and shall be readable with cables in place. Where the nameplate is mounted on a removable part, the manufacturer's name and transformer serial number shall be permanently affixed to a non -removable part. Instruction nameplate shall contain the information specified in 5.12 of ANSI C57.12.00-1987, Nameplate A. Also, on the nameplate, or label affixed near it, the manufacturer shall indicate that the dielectric fluid contains less than 1 ppm PCB. 3.2.2.7.6 A suitable marking inside of the tank shall indicate the correct oil level at 25°C. 3.2.2.7.7 An automatic pressure relief device shall be located within the compartment. This device shall meet the following requirements: • %d' NPT or larger male Inlet Port. • Exposed parts of weather and corrosion resistant materials. • Non -deteriorating gasket and o-ring material. • Manual pull ring able to withstand 25 pound force minimum. • Body able to withstand 100 pound shear force minimum. • Bug shield. • Cracking pressure of 10 t 2 psig. • Resealing pressure of 8 t 2 psig. • Zero leak rate from 8 t 2 psig to -8 psig. • Minimum flow rate of 35 SCFM at 15 psig. 3.2.2.7.8 An RTE BAY-O-NET current sensing fuse and internally mounted partial range current limiting fuse shall be furnished as shown in Table 1. 3.2.2.8OIL PRESERVATION Transformers shall be of sealed -tank construction. Sealed -tank construction is that which seals the interior of the tank from the atmosphere, and in which the gas plus the oil volume remains constant. The transformer will remain effectively sealed fora top -oil temperature range of -5°C to 105°C. 3.2.2.9 TAN KS The tank shall be domed or sloped to shed water. The tank shall be of sufficient strength to support a minimum of 500 lbs. vertical load. Construction of the tank shall be in accordance with ANSI C57.12.25- 1981, paragraphs 6.1 and 6.6. 7 368-120 REV. SYM: FF 3.2.2.9.1 The cover shall be welded construction. 3.2.2.9.2 Tank grounding provision shall consist of two steel pads, each with inch - 13 NC tapped hole, 7/16 inch deep. 3.2.2.9.3 These ground pads shall be welded on the transformer base or on the tank wall near the base, one in the high -voltage side and one in the low -voltage side. In cases where the transformer tank and compartments are separate, provisions shall be made for electrically connecting them. 3.2.2.9.4 Locking bolts shall be pentahead. 3.2.2.10 COMPONENTS FOR LOOPED PRIMARY The minimum current -carrying capability of components for the looped primary cable system shall be 200 amperes (continuous) and 10,000 amperes symmetrical (momentary). 3.2.2.11 AUDIBLE SOUND LEVEL The audible sound level shall be in accordance with NEMA Standard TR1-1980. 3.2.2.12 BASE PLAN The base plan of a completely assembled unit shall be such that it can be installed on a pad of the dimensions shown in Fig. 1 B. 3.2.2.13 PAINT EEI "Finishing Guidelines" specification shall apply. Finish coat shall be Munsell Green, glossy. 3.2.2.14 LOSSES The total losses of transformer shall be the sum of the excitation losses and the load losses (IZR losses). Load loss tests shall be performed and reported on all units regardless of whether or not a record of such tests is available on duplicate units. Loss evaluations and loss costs will be based on the values shown in the "Special Conditions and Supplemental Instruction to Bidders." Transformers will be evaluated on excitation losses and IZR losses at the specified rates. If tested losses exceed quote losses but are within the tolerances of Table 18, ANSI C57.12.00-1987, the additional cost incurred from the differential of losses will be calculated using the following equation and the above specified rates and will be deducted from the original Purchase Order or back charged to the manufacturer. In Table 18 and the following equation "Units" shall mean 'Transformers of the same size and design on one order ". Excess loss $ _ [No. of units] [(No Load Loss Evaluation $) (Avg. No Load Losses - Quoted No Load Losses) + (Load Loss Evaluation $) (Avg. Load Losses - Quoted Load Losses)]. If this equation results in a negative number, no credit will be given the Supplier. If any unit or units exceed the tolerances of Table 18, ANSI C57.12.00-1987, that unit or units shall not be shipped without express permission from the City. If accepted, the deduction for excess losses will be based on the following equation: Excess loss $ _ (No Load Loss Evaluation $) (No Load Losses - Quoted No Load Losses) But Not Less Than Zero + (Load Loss Evaluation $) (Load Losses - Quoted Losses) But Not Less Than Zero. 3.2.2.15 SAFETY LABELS NEMA 1260 Safety Labels shall not be applied by the manufacturer: Purchaser will apply customer warning labels after delivery. 368-120 REV. SYM: FF 4 QUALITY ASSURANCE 4.1 GENERAL 4.1.1 RESPONSIBILITY FOR INSPECTION Unless otherwise specified, the vendor is responsible for the performance of all inspection requirements as specified herein. Except as otherwise specified, the vendor may utilize his own facilities or any commercial laboratory acceptable to the City of Fort Collins. The City reserves the right to perform or witness any of the inspections set forth in this Specification where such inspections are deemed necessary. 4.1.2 TEST REPORT The manufacturer shall furnish to the purchaser certified copies of the results of loss tests prior to payment. Copies shall be sent to the Design Section as well as with the invoice. Unsigned copies are not acceptable even if accompanied by a signed cover letter. The Quality Control Manager shall review and sign each test report. 4.2 TEST CONDITIONS Unless otherwise specified, testing required by Section 4.4 shall be conducted under the following conditions: 4.2.1 REFERENCE TEMPERATURE The reference temperature to which losses, impedance, regulation, and efficiency are corrected shall be 85°C. 4.2.2 TOLERANCE ON IMPEDANCE VOLTAGE Impedance on completed units shall fall within the range specified herein. 4.2.3 TOLERANCE ON IMPEDANCE VOLTAGE ON A TAP The percent departure of tested impedance voltage on any tap from tested impedance voltage at rated voltage shall not be greater than the total tap voltage range expressed as a percentage of the rated voltage. 4.3 Not used. 4.4 TESTS The kinds of tests to be performed and the test procedures shall be as specified in ANSI C57.12.20, ANSI C57.12.00, and C57.12.90 except as specified herein. 4.4.1 DIELECTRIC TESTS No applied potential test shall be made. The induced -potential test shall be made by applying between the terminals of one winding a voltage which will develop from high -voltage line terminals to ground a voltage of 1000 volts plus 3.46 times the rated transformer winding voltage. 4.4.2 IMPEDANCE AND LOAD -LOSS TESTS Impedance and load -loss tests shall be made on each unit and may not be omitted even if a record of such tests made on a duplicate unit is available. 5 PREPARATION FOR DELIVERY Transformers shall be prefilled with the appropriate amount of transformer oil and shall be shipped by open -bed truck. Units shall be packaged in such a way as to provide for ease of handling and to protect units from shipping damage. 9 368-120 REV. SYM: FF Units shall be packaged on four-way universal pallets with 34 inches minimum opening and loaded on the truck for side removal. The Supplier shall give 24 hour notice prior to delivery for any shipments where an individual transformer weighs over 5,000 pounds. In addition to these requirements, the Supplier shall comply with any additional requirements or modifications shown on the purchase order and/or supplemental instructions. 6 DEFINITIONS AND ABBREVIATIONS Vendor or Supplier - The manufacturer and/or manufacturer's agent supplying or quoting on the specified article. Article, Unit, Assembly - All refer to the equipment defined by this Specification. • DC or d.c. - Direct Current. • AC or a.c. - Alternating Current. • °C - Degree Celsius (Centigrade) • °F - Degree Fahrenheit • kV - 1000 volts. • CPS or Hz - Cycles per second. • psig - Pounds per square inch gauge. • V or v - Volts. • KVA - 1000 Volt-amperes. 10 368-120 REV. SYM: FF APPENDIX A — Transformer Stock Number Coding Below are examples that demonstrate the coding method used by City of Fort Collins to establish transformer stock numbers. I. SINGLE PHASE Example #1=> Transformer Single Phase 00 = 13.2Y/7620 & 7620/13.2Y x 2400/4160 outside pole 05 = 13.2Y7620 ESNA pole 20 = 13.2Y/7620 ESNA pad II. THREE PHASE 368 -1 BC - X Y Z Example #2 0 => 368 - 300 - Transformer / 3 Phase Pad Other KVA 0 = 5 5=50 1=10 6=75 2=15 7=100 3=25 8=167 4=37.5 9=250 1 = single voltage 2 = dual voltage INIMI 006 = 75 076 = 750 015 = 150 100 = 1000 030 = 300 150 = 1500 050 = 500 • All suffixes indicate 208Y/120 sec. • For 480Y/277 sec., add 1 to XYZ (ie. 007 would indicate a 75kVA with 480Y/277 sec.) 11 368-120 APPENDIX B — DIMENSIONAL DRAWINGS 1 41C MIN 40' MAX 20' MIN A IIN ING* REV. SYM: FF 3%4' 5' 5' 4$' 1 34 3$' 316, 4V MIN 1 MIN MIN I MIN MIN MIN MIN MIN H1A HIB X3 X1 CABLE ACCESSARY 7's1' 32'muxJ PARKING STAND t X2 GROUND PAD � 0 0 78"12' 1 MAX. DIM. KVQ A A WITHOUT RADIATORS WITH RADIATORS 25 & 50 3 2.5," -- 100 -- 42' 167 42' 53' 250 44' S5' s MINIMUM OPENING IN BOTTOM OF COMPARTMENT FOR CABLE ENTRANCE Figure 1 — Type 1 Transformer Dimensions and bushing Designations (not to scale) 12 368-120 CITY OF FORT COLLINS INVITATION TO BID BID #7167 167 kVA PAD -MOUNTED COMPARTMENTAL -TYPE, SINGLE-PHASE DISTRIBUTION TRANSFORMERS Sealed bids will be received and publicly opened at the office of the Director Of Purchasing and Risk Management, PO Box 580, 215 North Mason St., 2nd floor, Fort Collins, Colorado 80524, at the time and date noted on the bid proposal and/or contract documents. If delivered, they are to be delivered to 215 North Mason Street, 2"d Floor, Fort Collins, Colorado 80524. If mailed, the address is P.O. Box 580, Fort Collins, 80522-0580. Bids must be received at the Purchasing Office prior to 2:00 P.M. (Our clock) August 26, 2010 Special Instructions All bids must be properly signed by an authorized representative of the company with the legal capacity to bind the company to the agreement. Bids may be withdrawn up to the date and hour set for closing. Once bids have been accepted by the City and closing has occurred, failure to enter into contract or honor the purchase order will be cause for removal of supplier's name from the City of Fort Collins' bidders list for a period of twelve months from the date of the opening. The City may also pursue any remedies available at law or in equity. Bid prices must be held firm for a period of forty-five (45) days after bid openings. Submission of a bid is deemed as acceptance of all terms, conditions and specifications contained in the City's specifications initially provided to the bidder. Any proposed modification must be accepted in writing by the City prior to award of the bid. Only bids properly received by the Purchasing Office will be accepted. All bids should be clearly identified by the bid number and bid name contained in the bid proposal. No proposal will be accepted from, or any purchase order awarded, to any person, firm or corporation in default on any obligation to the City. Bids must be furnished exclusive of any federal excise tax, wherever applicable. Bidders must be properly licensed and secure necessary permits wherever applicable. Bidders not responding to this bid will be removed from our automated vendor listing for the subject commodities. The City may elect where applicable, to award bids on an individual item/group basis or on a total bid basis, whichever is most beneficial to the City. The City reserves the right to accept or reject any and all bids, and to waive any irregularities or informalities. Sales prohibited/conflict of interest: no officer, employee, or member of City Council, shall have a financial interest in the sale to the City of any real or personal property, equipment, material, supplies or services where such officer or employee exercises directly or indirectly any decision - making authority concerning such sale or any supervisory authority over the services to be rendered. This rule also applies to subcontracts with the City. Soliciting or accepting any gift, INSIDE 0� TANK SURFACE DETAIL A CABLE ACCESSORY PARKING STAND !15MIN ' ,- - --- BOTTOM INSIDE j r 10-1 FLANGE A 3MIN L - --------- IJ MAX 18 MIN OPENING - (NOTE 2) HIGH -VOLTAGE CONMCTORS CABLE ACCESSORY B t MIN _ PARKING STAND 2 T C 1/2 # 1/2 Hi8 60°. 15� _ T x3 SEA CABLE ACCESSORY DETAIL A PARKING STAND SEE DETAIL A E 9 12.I° B 2+3.1/8 f 1 (NOTE Ell-��q D NIA 6MIN BASE 11 Sill GROUNDPAD r, POINT REV. SYM: FF i t J. i OPENING A {NO1E 2) INSIDE ARBITRARY PONNT 2sl —zs 2 2 .3 Z FAIN 4 2 MIN 531 5:1 8#1 -Law PLANE 74 Stock Number Dimension A Dimension B Dimension C Dimension D ' Dimension E 368-120-155 13" 5" 4" 0" 3 '/4" Figure 2 - Type 2 Transformer Dimensions and bushing Designations (not to scale) 13 368-120 REV. SYM: FF Pad Dimensions This drawing is not intended to dictate requirements for items purchased under Specification 368-120 but is included as an aid to those users desiring a minimum of pad designs for the transformers covered by Specification 368-120. The dimensions in inches of Figure 3 will fit the minimum compartments on transformers covered by this Specification as well as the maximum transformer envelope. 48" I L T3" 48" 12" PRIMARY SECONDARY 4 1/2" FRONT �— 15" — 6" 12" 15" FOUR #3 REBAR 18" LENGTH AND WIDTH �3.� 3„ 71/T2" T Notes on Pad Material - 1. Concrete must be 3,000 psi minimum. 2. Maximum coarse aggregate size 1 1/2 inches. Space requirements for pad and primary switching cabinet will generally be 9' X 12'. Factors to be considered in locating the pad include - 1. Accessibility - The transformer pad shall be accessible to line boom trucks equipped for the installation and removal of heavy transformers. Such accessibility shall not require intrusion on adjacent property. 2. Proximity of Buildings, Walls, Barriers, and/or Overhangs - In addition to the clearances required for installation and removal, the minimum clearance in front of the transformer pad shall be eight (8) feet and the minimum clearance from all other sides shall be two (2) feet. If the building has an overhang, clearance to the edge of the transformer pad shall be measured horizontally from the outer edge of the overhang. Transformers through 300 KVA may be installed under the overhang if the vertical clearance between the pad and the overhang is at least 25 feet and the location is accessible to line boom trucks. 3. Codes and Standards - In addition to the above, the installation shall conform to the National Electric Code and federal, state and city codes and standards. Figure 3 — Pad Dimensions 1d +i i art•J REV. SYM: FF APPENDIX C — Approved Manufacturers Transformers purchased under this Specification shall be of the make shown below. Manufacturers not listed below may submit written proposals demonstrating compliance with these Specifications for consideration of addition to the accepted manufacturers list prior to the next request for bids. In addition to inclusion on the list below, manufacturer's equipment must also satisfy all requirements of this Specification to be acceptable. MANUFACTURER SERIAL NO. ABB All Cooper Power Systems All General Electric All Howard Industries All The manufacturers in the following list have been conditionally approved and may bid as an alternate. The definition and intent of "Conditional Approval' of a manufacturer is to allow the City to gain some experience with the manufacturer's product. Should a conditionally approved manufacturer be the evaluated low bidder, the City reserves the right to award all, part, or none of the order to them, dependant upon the current needs of the City for that item or items. 15 368-120 REV. SYM: FF TRANSFORMER LOSS EVALUATION - AVERAGE LOSSES City Order No. S/N Manufacturer Invoice No. KVA/Unit LINE DESCRIPTION AMOUNT (1) No. of units (2) Average core losses (3) Quoted core losses (4) Excess average core losses: line (2) less fine (3) (5) Penalty for excess average core losses: line (7) x line (4) x $ (6) Average copper losses (7) Quoted copper losses (8) Excess average co per losses: line (6) less 9ne (7) (9) Penalty for excess average copper losses: line (1) x line (8) x $ (10) Penalty to be assessed manufacturer: line (5) plus line (9) but not less than zero Date Prepared By: Design Engineering NOTE: If any unit(s) exceeds the loss tolerances of ANSI C57.12.00, Light & Power will either reject it, include it on these averages, or calculate losses using the Individual Transformer Losses Evaluation Form, whichever is most favorable to Light and Power. 16 368-120 City Order No. Manufacturer KVA/Unit LINE (1) (2) (3) INDIVIDUAL TRANSFORMER LOSS EVALUATION S/N Invoice No. DESCRIPTION Tested core losses Quoted core losses Excess core losses line (1) less line (2) but not less than zero (4) Percent difference line (3) ❑ line (2) x 100 (5) Tested total losses (6) Quoted total losses (7) Excess total losses line (5) less line (6) but not less than zero (8) Percent difference line (7) ❑ line (6) x 100 (9) Tested copper losses (10) Quoted copper losses (11)Excess copper losses (12) line (9) less line (10) but not less than zero (12) Penalty for excess core losses line (3) x $ (13) Penalty for excess copper losses line (11) x $ (14) Penalty to be assessed manufacturer line (12) plus line (13) Date Prepared By: Design Engineering AMOUNT REV. SYM: FF 17 368-120 Issued: 8/17/72 Revised: 1/21/94 Special Conditions and Supplemental Instructions to Bidders Applicable to Specification 368-120 A. Data to be Supplied with Bidder's Proposal The following data shall be supplied with the bidder's proposal in addition to that information required by the "Invitation to Bid." and the "Purchase Requisition". A typical list of users of 1 phase padmounted distribution class transformers manufactured by the bidder during the past five years. 2. A typical drawing of the transformers showing that they will meet the critical dimensions required by the Specification. 3. Impedance volts in % at full load, high voltage to low voltage at 850C. 4. No load and total losses at 850C. 5. Delivery in weeks. 6. A statement indicating compliance with our Specification without exception or a detailed list of exceptions. 7. Escalation is _.is not _applicable for the transformers bid. If escalation applies, the Bidder shall indicate in his bid the specific items or materials subject to escalation, and shall give the method and indices to be used in computing the amount thereof. Escalation occurring after the quoted delivery date will not be paid unless delays are the result of actions by the City. Escalation occurring after acceptance, if Purchaser exercises the option to delay shipment after manufacturing is completed, will not be paid. If the above information and compliance statement are not supplied, the proposal will not be evaluated. An alternate bid for the total order may be submitted in addition to the unit bids. B. Loss Evaluations Loss penalties and loss evaluations will be based on the following values: No load or excitation losses at $3.90/watt. 2. Load losses at $1.50/watt. C. Shipping Terms Ship F.O.B. point of destination, freight prepaid. D. Terms of Payment 1. If escalation applies, the City of Fort Collins shall not be billed for escalation occurring after the promised delivery date. 2. Test reports shall accompany the invoice. If test reports do not accompany the invoice, late payment penalty charges incurred due to delays in obtaining the test reports will not be paid. Certified copies of test reports shall be sent to the Design Section, Fort Collins Light and Power Utility. 3. Loss penalty credits and escalation charges shall be itemized on the invoice. Fort Collins Utilities Transformer Bid Loss Data Sheet # Units Bid # 7167 Preparer Name : Name Size Date: Preparer Contact Num: Number NL Loss Cost FL Loss Cost Escalation Base Bid Base Bid $ / Guar No Load Guar Full Load Meet Specs? (is / is not) Guar Total NIL Loss * NIL FL Loss * FL Evaluated Extended Cost Supplier Mfr / Mfr# Each Del/Wks Loss Loss Impedance (Yes / No) a factor Load Loss Loss Cost Loss Cost Bid (Total $) Westerm United GE $ 3,682.00 8 240 1378 1.82 y 1618 $ - $ - $ 3,682.00 $ 44,184.00 Howard $ 3,900.00 8 283 1339 2.50 y 1622 $ - $ - $ 3,900.00 $ 46,800.00 Hartigan Central Moloney $ 3,400.00 8 0 0 0.00 0 $ - $ - $ 3,400.00 $ 40,800.00 Stuart C. Irby COOPER $ 3,166.05 8 227 1575 2.28 1802 $ 3,166.05 $ 37,992.60 Wesco ABB $ 3,311.58 10 to 12 244 1621 2.52 y $ 3,311.58 $39,738.96 1) Fill out the information in the cells with blue text. 2) Save the file using your company name and the bid number and e-mail it to: purchasing@fcgov.com (Example: TransformerSales_Bid_58.xls) If you are concerned about security, you may password -protect this file after You have entered your data. To protect this file, take the following steps: 1) Select Tools, Options 2) Select Security Tab 3) Type your password in the 'Password to Open" field. 4) Re-enter your password to confirm it. Important! Please remember to include this password in the bid information that will be sealed in the envelope that will be unsealed at Bid Opening. This will secure your data until the time of the bid opening. 5) Save the file and e-mail it to: purchasing@fcgov.com gratuity, favor, entertainment, kickback or any items of monetary value from any person who has or is seeking to do business with the City of Fort Collins is prohibited. Freight terms: unless otherwise noted, all freight is F.O.B. Destination, Freight Prepaid. All freight charges must be included in prices submitted on proposal. Discounts: any discounts allowed for prompt payment, etc., must be reflected in bid figures and not entered as separate pricing on the proposal form. Purchasing restrictions: your authorized signature of this bid assures your firm's compliance with the City's purchasing restrictions. A copy of the resolutions are available for review in the Purchasing Office or the City Clerk's Office. Request Resolution 91-121 for cement restrictions. Collusive or sham bids: any bid deemed to be collusive or a sham bid will be rejected and reported to authorities as such. Your authorized signature of this bid assures that such bid is genuine and is not a collusive or sham bid. Bid results: for information regarding results for individual bids send a self-addressed, self -stamped envelope and a bid tally will be mailed to you. Bid results will be posted in our office 7 days after the bid opening. James B. O'Neill II, CPPO, FNIGP Director of Purchasing and Risk Management FIRM NAME: CITY OF FORT COLLINS BID PROPOSAL BID NO. 7167 167 kVA Pad -Mounted Compartmental -Type, Single -Phase Distribution Transformers BID DATE: 2:00 p.m. (Our clock) August 26, 2010 WE HEREBY ENTER OUR BID FOR THE CITY OF FORT COLLINS' REQUIREMENTS FOR 167 kVA PAD -MOUNTED COMPARTMENTAL -TYPE, SINGLE-PHASE DISTRIBUTION TRANSFORMERS, PER THE BID INVITATION AND ANY REFERENCED SPECIFICATIONS. QUANTITY: DESCRIPTION: 12 Ea. 167 kVA Pad -Mounted Compartmental -Type, Single -Phase Distribution Transformers with Separable Insulated Load Break High - Voltage Connectors. HIGH VOLTAGE RATING: 13200 GRDY/7620 VOLTS. LOW VOLTAGE RATING: 240/120. SERIAL NUMBER 180 TO BE IN ACCORDANCE WITH SPECIFICATION #368-120-180, REVISION FF PLEASE COMPLETE THE ATTACHED EXCEL SPREAD SHEET FOR BID SUBMITTAL. IF YOU ELECT TO PASSWORD PROTECT YOUR BID, PLEASE NOTE THAT PASSWORD BELOW. *Any surcharges or additional costs shall be noted & included in bid submittal. The transformers being bid meet or exceed the specifications. Yes No. If not, please list exceptions,(specifying paragraph reference number) on a separate sheet of paper and attach to your bid. Escalation is , is not applicable for the transformers bid. If escalation applies, the bidder shall indicate in his bid the specific items or materials subject to escalation, and shall give the method and indices to be used in computing the amount thereof. Escalation occurring after the quoted delivery date will not be paid unless delays are the result of actions by the city. Escalation occurring after acceptance if purchaser exercises the option to delay shipment after manufacturing is completed, will not be paid. Delivery may be a consideration of bid award. For purposes of warranty and service ONLY approved manufacturers or distributors authorized by an approved manufacturer to serve the Fort Collins area may bid. The City of Fort Collins reserves the right to split the bid in whatever percentages are most advantageous to the City. Future orders of Pad -Mounted Compartmental -Type, Single -Phase Distribution Transformers may be authorized, at the option of the City, from this bid for a period of five years after date of award. Satisfactory pricing and delivery is required for future orders based on this bid. SUPPLEMENTAL INSTRUCTIONS Prices quoted must remain firm for a 30 day period after the opening date. Freight terms: F.O.B. destination freight prepaid. All freight charges must be included in pricing submitted on proposal and not entered as separate pricing. Any discount allowed by Vendor for prompt payment, etc. must be reflected in quoted figure, and not entered as separate pricing. The City reserves the right to accept or reject any and all quotes. Bidder not responding to the services requested in this bid shall be removed from our automated listing for: Not Applicable Any questions or inquiries regarding this bid should be directed to: Opal F. Dick, CPPO, Senior Buyer (970)221-6778 SIGNATURE AND TITLE: TYPED OR PRINTED NAME AND TITLE COMPANY NAME: (AREA CODE) TELEPHONE NUMBER/FAX NUMBER ADDRESS: STREET, CITY, STATE, ZIP DATE EMAIL: Purchase Order Terms and Conditions 1. COSMERCTAL DETAILS. Tax exemptions. By stamen the City of Fort Collins is exempt from state and local taxes. Our Exemption Number is I L NONWAIVER 98-M502. Federal Excise Tax Exemption Cemf-re of Registry 846000597 is registered with the Collector of Failure of the Purchaser in insist upon strict performance of the terms and conditions hereof failure or delay to Internal Revenue. Dearer, Colorado (Ref. Colorado Revised Statures 1973, Chapter 39-26, 114 (a). exern a any, rights or remedies provided herein or by Law, failure to promptly notify the Seller in the event of a bread the acceptance ofor payment for goods hereunder or approval of the design, shall not release the Seller of Good.- k,;Krwd. GOODS RRMCTRD doe to failure to meet �pc cnri—, dd—wbm :Lipped oz doe m defeea of a^Y of rho warranties rc nNi�prirma of rhic pmrha.e nrdw .rod chap rot he dowmM a wars— of any tf eM of rho damage in rmnsit, may be returned to you for credit and ace not to be replaced except upon recaps of written Purchases` to insist ap= strict performance hereof or any of its rights or remedies as to any such goods, regardless instructions from the City of Fort Collins. of when shipped received or accepsd, as many. prior or subsequent default hereunder, nor shall nay purported oral modibratian car rescission of this purchase order by the Purchaser operate as a waiver of any of the terms Inspection. GOODS are subject to the Ctry of Fort Collins inspection an arrival. hereof Final Acceptance, Receipt of the merchandise, services or equipment in response to this order can result in 12 ASSIGNMENT OF ANTITRUST CLAMS. authorized payment on the pan of the City of Fort Collins. However, it is to be understood that FINAL Seller and the Purchaser recognise that in actual economic practise, overcharges resulting from antatu t ACCEPTANCE is dependent upon completion of all applicable required inspection procedures, violations are in fact borne by the Purchaser. Theretofore, for good cause and as consideration for executing this purchase order, the Seller hereby assigns m the Purchaser nay and all claims it may now have or bereafter Freight Tams. Shipments most be F.OB., City of Fort Collins, 700 Wood SL, Fort Collins, CO 80522. unless acquired under federal or state antimrst Laws for such overcharges relating to the particular bads or services otherwise specified on this order. If permission is, given to prepay freight and charge separately, the original freight purchased or acquired by the Purchaser pursuam m this purchase order. brill most accompany invoice. Additional chaps for parking will not be accepted Shipment Distance. Where-anfurmers have distributingpoints in various parts of the cottony, shipment is expected from the nearest distribution, point to destination, and excess freight will be deducted from Invoice when shipments are made from greater distance. Permits. Seller shall procure at sellers sole cost all necessary permits, certificates and licenses reganed by all applicable laws, regulations, ordinances and rules of the state, municipality, territory ar political subdivision where the work is performed, or regmmd by any other daily convarwed public authority having jmisdimon aver the walk of vendor: Seller further agrees to hold the City of Fort Collin harmless from and against all liability and loss incurred by them by reason of an asserted or established violation of any such laws, regolatiam, ordinances, roles and requirements. Audiatiutioa All parties to this contract agree that the representatives are, in fiat; bons fide and possess fall and complete authority to bind said panties. LMICATION OF TERMS. This Purchase Order expressly limits acceptance. to the corms wad comments stated beiem set forth and, any supplementary or additional term: and conditions maexed hereto or mccapotated herein by reference. Any additional a different terms and conditions proposed by seller we objected to and hereby rejected 2. DELIVERY. PLEASE ADVISE PURCHASING AGENT immediately if you canna make complete shipment to active on your promised dehvay dace as noted Time is of the essence. Delivery and performance mast be effected within the erne stated on. the purchase orderand the documents attached hereto. No acts of the Purchasers including, without limmation• acceptance of partial late deliveries, shall operate as a waiver of this "provision In the event of any delay: the Purchaser shall have, in addition to other legaland equitable remedies. the option ofphcing this order elsewhere and holding the Seller liable for damages. However, the Seller shall not be liable for damages as a result of delays due to causes no reasonably foreseeable which are beyond its ressanable control and without its fault of negligence such acts of God, acts of civil m military authorities, goveran rental priorities, fires, strflin, flood, epidemics, %— or riots provided that notice of the conditions cansfng inch delay is given to the Purchaser within five (5) days of the time when the Sella first received knowledge thereof In the event of any such delay, the dam of delivery shall be extended for the period equal to the time actually lost by reason of the decay. 3. WARRANTY-. The Seller transmits that all goods, articles, trumrials and work covered by this orderwill conform with applicable drawings, specifications, samples md'or otbu descriptions given. will be fit for the purposes intended, and performed with the highest degree of care and competence in accordance with accepted standards for work of a simile ast re. The Seller agrees to hold the purchaser harmless from any toss, damage or expense, which the Purchaser may suffer a mcm on accottm of the Sellers breach of warranty. The Seller shall replace, repair or make good, without cost to the pmdhaser. any defects or faults wising within one (1) year or within such longer period of time as may be prescribed by taw or by the terms of any applicable warmary provided by the .Sella after the date of accept -re of the goods f rr ushed hereunder (acceptance not m be raweasombly delayed), resutndg from imperfect or defective work dotter or materials famished by the Sella. Acceptance or use of goods by the Purchaser shall not constitute a warier of nay shim under this warrmry. Except. w otherwise provided in this purchase mdu. the Sellers liability hereunder shall emend to all damage proximately caused by the breach of my of the foregoing Warranries or goaramees, but such liability shall in no event include lam of profa s a loss of are. NO IMPLIED WARRANTY OR MERCHANTABILITY OR OF FITNESS FOR PURPOSE SHALL APPLY. 4. CHANGES IN LEGAL TER1fS. The Purchaser may make changes to legal terms by written chin— order. 5. CHANGES IN COMMERCIAL TMIS. The Purchases may make any changes to the terms. odia than legal terns, including additions to or deletions from the.gmntities originally ordered in the spedficatioas or drawings, by verbal or written change order. If any such change affects the amount deg or the time of performance hereunder, an equitable adjustment shall be made. 6: TERINM70.TIONS. The Porrhasa may at any tare by written change order, terminate this agreement as m nay or all portions of the goods rhea not slipped, subject to my equitable adjustment berween the parties as to sir wads or mareriaia then in progress provided that the Purchaser shall not be liable far my claims for anticipated profits on the uncompleted portion of the goods andtor work, for incidental or consequential damages, and that no such adjustment be made in favor of the Sella with respect to any goods which we die Sellers standard stock. No such termiavtion shallrelieve the Purchaser or the Seller of nay of their obligations as to my goods delivered hereunder. 7. CLAMS FOR ADIIISTNIENT. Any claim for adjustment mast be asserted within thirty (30) days from the dam the change at miminman is ordered S. COMPLIANCE WITH LAW. The Seller warrants that all goods wild hereunder shalt have been produced, sold, delivered and furnished in strict compliance with all applicable laws and regulations in which the good are mbiKL The Sella shall execate and deliversuch documents as may be requied to effect or evidence compliance. All laws and regulations required to be incorporated in agreemems of this character are hereby i rotpomted herein by dus reference. The Sella agrees to indemnify. and bold the Purchaser harmless from all costs and damages suffaed by the Pachsser as a result of the Sellers failure to comply with such law. 9. ASSIGNMENT. Neither patty shall assign, transfer, or convey this order, or my monies due or to become doe hereunder withtmt the prior written consent of the other parry. 10. TITLE. The Sella wsrrams fall, clear and unrestricted tide to the Purchaser for all equipment, tmtmW% and items banished in performance of this agreement, free and clew of my and all liens, restrictions, reservanans security interest encumbrmces and claims of others. 13. PURCHASERS PERFORt.L404CE OF SELLERS OBLIGATIONS. If the Purchase directs the Seller to correct nonconforming or defective goods by a dam to be agreed upon by the Pmchr and the Seller, and the Seiler ibeteafter indicates its mabRny or unwillingness to comply, the Purchaser may cause the work to be performed by the must expeditious merms available to a, and the Seller shall pay all costs associated with such work. The Seller shall release the Purchaser and its contractors of any tier from all liability and claims of any nature resulting from the performance of such work. This release shall apply -even in the event of fault of negligence of the parry released and shall extend to the directors, officers and employees of sash party. The Sellet's rocia-mal obligations, including warram y, sbatl not be deemed to be redwed in any way, because such cork is performed or caused to be performed by the Purchaser. 14_ PATENTS. Whimever the Seller. is required to use my design, device, material or process coveted by letter, patent trademad at copyright, the Seller shall indemnify and save harmless the Purchaser from any and all claims for infringement by reasons of the use of such patemed design, device, material or process in connection frith the couracf and shad indemnify the Purchaser, for mycost, expense ordamage which it may be obliged to pay.by reason of such infringement at any time daring. the prosecution a after the completion of the work. In case said egaipmem, or any pan thereof or the intended use ofthe goods, a in stiih suit held to constitute infringement and the use of said equipment or pan is eajoined the Seller shag at its own expense and at is "option, either procure for the Purchaser the. rightto comimme using said eq.4- rat "or parts, replace the same with mbstand lly equal but =,infringing equipment, or modify it so it becomes a infruq=g I5. INSOLVENCY_ If the Seller shall become insolvent or bankrupt, make an assignment for: the benefit of creditors, appoint a receuver m trustee for army of the. Sellers property or business, this order may forthwith be canceled by the Purchaser without liability. 16. GOVERNING LOW. The definitions of tends toed or the interpretation of the agreemert and the rights of all parties hereunder &half be canstrued under and governed by the laws of the State of Colorado, USA. The following Additional Conditions apply: only in cases where die Seiler is m perform work hereunder: mrlffiing the services of Sellers Represenmtive(s), on the premises of odien. 17. Sum t rue RESPONSIBILITY. The Sella shall carry on said wort at Seller% own itsk mail the same is filly completed and accepted, and shall, in case of any accident, destruction or im1my to the work andtor materials before Sell final completion and acceptance, complete the work at SeBets awn expense and to the satisfaction of due Purchaser. When materials and equipment are f=ished by others for installation or erection by the Sella, the Seller shall receive,milaad x and tmivIle an..••' m the site -d Laysrme reaykruulde wnetw as dvuaL arsb mk 1w h —d'- espkipr••e,.i were being famished by the Seller order the ardet. IS. INSURANCE_ The Sella shall at bus own expense, provide for the payment of workers compesatiou, including occupational disease benefits, to its Employees employed on or in counecnam with the wort coffered by this purchase order, anXw to then dependents in accordance with the laws of the state in which the work is to be done. The Seller shall also carry comprehensive general liability including, but not limited to, coaaacrosl and automobile public liabilityiasarence with bodily mjuiy and death limi,s of at least $300,000 for my one petsoo, $500,000 fm aay one accident andPropertydamage limit per accident of $400.000. The Sella shall likewise require his connectors, if ate, to provide for such compensation and mstnance. Before any of the Sellers or his contraRors employees shall do my work upon the premises of others, the Sella shall furnish the Puachas r with a certificate that such compensation and insurance have been provided Such certificates shall specify the dam 'when such compensation and insurance have been provided. Such certificates shall specify the date when such marpensation and insurance expares..The Sella agrees that such compensation and insurance shall be mainnined until alher the eaaie work is completed and accepted. 19. PROTECTION AGAINST ACCIDENTS AND DAMAGES. The Seller hereby assumes :he enure responsibility and liability for ate• and alldamage, loss or injury of my kind or nature whatsoever to persons or property caused by or resulting from the execution of the work provided for in this purchase order orin connection herewith The Sella will indemnify and hold harmless the Purchases and any or all of due Purchasers officers, agents and employees from and against any and all claims, losses, damages, charges a expenses, whether direct or indirect, and whether to persons or property to which the Purchaser may be put orsubject by reason of say act, action, neglect omission. or default on the pan of the Seller, any of bus contractors, or any of the Sellers or comractors officers, agents or employees. In case my sort or other proceedings shall be brought against the Purchaser,. or its officers, agents or employees at my time an account or by reason of any act, action, neglect, omission or default of the Seller of any of his contractors w my of its or their officers, agents or employees as aforesaid the Seller hereby agrees to assume the defense thereof and to defend the same at the Sellers own expense, to pay any and all costs, charges, attorneys fees and other expenses, my and all judgments that may be incurred by or obtained against the Purchaser or army of its or their officers, agents a employees in such suits a other proceedings, and incase judgment or other Lim be placed upon or obtained against the property of the Purchaser, or said parties in or as a result of such suits or other proceedings, the Sella will at once cause the same to be dissolved and discharged by giving bond or otherwise. The Sella and his contractors shall take all safety precautions, furnish and install all guards necessary for the prevention of students, comply with all laws and regulations with regard to safety including, but with" humastion, the Occupational Safety and Rea" Act of 1970 and all rules and regulations issued purstiat thereto. Revised 0312010 Fort Collins Utilities Transformer Bid Loss Data Sheet # Units Bid # 7167 Preparer Name : Name Size Date: Preparer Contact Num: Number NL Loss Cost $ FL Loss Cost $ Supplier Mfr/Mfr# Base Bid $1 Each DeIM1kS Guar No Load ILoss Guar Full Load Loss Impedance Meet Specs? (Yes I No) Escalation (is I is not) a factor Guar Total Load Loss NL Loss' NL Loss Cost FL LossFL Loss Cost Evaluated Bid Base Bid E)dended Cost (Total $) Supplier 1 Mfg 1 $ 0 0 0.00 - 0 $ $ $ $ Supplier 2 Mfr2 $ 0 0 0.00 0 $ $ $ $ Supplier 3 Mfr3 $ 0 0 0.00 0 $ $ $ $ Directions for Bidders: 1) Fill out the information in the cells with blue text. 2) Save the file using your company name and the bid number and e-mail it to: purchasing@fcgov.com (Example: TransformerSales_Bid_.xls) If you are concerned about security, you may password -protect this file after you have entered your data. To protect this file, take the following steps: A) Select Tools, Options B) Select Security Tab C) Type your password in the "Password to Open" field. D) Re-enter your password to confirm it. Important! Please remember to include this password in the bid information that will be sealed in the envelope that will be unsealed at Bid Opening. This will secure your data until the time of the bid opening. E) Save the file and e-mail it to: purchasing@fcgov.com THE CITY OF FORT COLLINS Light and Power Department P.O. Box 580 Fort Collins, CO 80522 SPECIFICATION NO: 368-120 TITLE: PAD -MOUNTED COMPARTMENTAL -TYPE, SINGLE-PHASE DISTRIBUTION TRANSFORMERS WITH SEPARABLE INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS APPROVED BY: Kraig E. ad Standards Engineering Manager ORIGINATED: 09/14/72 LAST REVISED: 7/21/2004 ITEMS COVERED BY THIS SPECIFICATION DESCRIPTION STOCK NO. SPECIFICATION NO. SERIAL 25 KVA, 120/240 ANSI Type 1 Transformer. 368-120 -130 50 KVA, 120/240 ANSI Type 1 Transformer. 368-120 -150 50 KVA, 120/240 ANSI Type 2 Transformer. 368-120 - 155 100 KVA, 120/240 ANSI Type 1 Transformer. 368-120 -170 167 KVA, 120/240 ANSI Type 1 Transformer. 368-120 -180 250 KVA, 120/240 ANSI Type 1 Transformer. 368-120 -190 REV. SYM: FF PREVIOUS REVISION DESCRIPTIONS ON FILE REVISION DESCRIPTION APPROVED REVISION DD: Sagen • Paragraph 3.2.2.7.5: Editorial 10/21/94 • Add paragraph 3.2.2.9.4 requiring pentahead locking bolts • Paragraph 3.2.2.13 add glossy to paint requirement • Paragraph 4.2.2: Clarify impedance requirement REVISION EE: Sagen • Paragraph 5.0: revised pallet size from 28 to 34 inches 2/25/98 REVISION FF Kraig Bader • Added 50kVA ANSI Type 2 Transformer (368-120-155) to Specification 7/21/2004 • Changed paint color to standard Munsell Green • Reorganized to consolidate impedance and fusing requirements into one table. • Consolidated secondary terminal requirements into one table. • Added maximum impedance requirement for 250kVA transformer (+/-7.5% from nominal for transformers with impedance greater than 2.5%) per ANSI/IEEE C57.12.00-2000. • Re-evaluated fusing requirements of all transformers in this specification. Went from dual sensing bay-o-net (expulsion) fuses to current sensing bay-o-net (expulsion) fuses. Fuse sizing was changed as follows: • Changed 25 kVA from 8A expulsion / 40 amp CL to 10A expulsion / 30A CL • Changed 50 kVA from 15A expulsion / 80 amp CL to 15A expulsion / 40A CL • Changed 100 kVA from 25A expulsion / 175 amp CL to 25A expulsion / 80A CL • Changed 167 kVA from 40A expulsion / 200amp CL to 40A expulsion / 125A CL • Changed 250 kVA from 65A expulsion / 350amp CL to 65A expulsion / 125A CL 368-120