Line Qty/Units Description Extended Price
1 6990-8841 7,500.00
79x56x6" 3-phase xfiner pad
YARD
TRANSFORMER PAD, PRECAST, 79"X56" X6", FOR 3 PHASE, 75-500 KVA,
FLAT TOP WITH NO RECESSED AREAS,
PER SPEC, DWG 368-400, SERIAL #01, REV.
AMCOR,
2 6990-8846 2,874.00
8473x6" 3-phase xfiner pad
YARD
TRANSFORMER PAD, PRECAST, 84"X73" X6", FOR 3 PHASE, 500-1000 KVA,
FLAT TOP WITH NO RECESSED AREAS,
PER SPEC. DWG 368-400, SERIAL #02, REV.
AMCOR,
Per quote dated 4/29/2008 (Wayne Bickford
Delivery: Five weeks
Total
$10,374.00
This order is rlig0alid over $5000 unless signed by James B. O'Neill Il, CPPO City of Fort Collins
Accounting Department
City of Fort Collins Purchasing, PO Box 580, Fort Collins, CO 80522-0580 PO Box 580
Fort Collins, CO 80522-0580
6"-1' (73')
7,_0•
<84')
52
PRIMARY SECt)N A/RY 16•
6'
Space requirements for pad and primary switching cabinet will
generally be 9'XI2'. Factors to be considered in locating the
pad include —
1. ACCESSIBILITY — The transformer pad shall be accessible
to the line boom trucks equipped for the installation and
removal of heavy transformers. Typically, the pad must
be placed within 10' of an all—weather surface where
a line boom truck can be driven. Such accessibility shall
not require intrusion on adjacent property.
2 PROXIMITY OF BUILDINGS, WALLS, AND/OR OVERHANGS —
In addition to the clearances required for installation and
removal, the minimum clearance in front of the transformer
pad shall be 8' and the minimum clearance from all other
sides shall be 3'. If the building has an overhang,
clearance to the edge of the transformer pod shall be
measured horizontally from the outer edge of the
overhang. Transformers through 300 KVA may be installed
under the overhang if the vertical clearance between the
pad and the overhang is at least 25' and the location
is accessible to line boom trucks.
3. CODES AND STANDARDS — In addition to the above, the
installation shall conform to the National Electric Code and
federal, state, and city codes and standards.
NOTE — This pad is typically used for a service total between 2000 amps
and 5000 amps at 120/208V 3—phase, or between 1200 amps and 2400
amps at 277/480V 3—phase.
M. Moore 03 12/16/1996 City of Fort Collins Utilities
Electric
CITY OF FORT COLLINS
UTILITIES
Drawn By: I Rev # Date ( Stds. Mgr. Appr. Transformer Pad Design 500 - 1000 KVA 3 Phase
r- I j_7__T__F__
I24 3/4"—
9 ,/4• L_1_J--)--1--t--1
,6
� I I
13 1/2-
T-
52-
Tv
#4 x 4'4' ® 12� C.C. (9 REO'D)
y4 x 6'3' ® 12 C.C. (6 REO'D)
/4- X 5 1/2- T-6A ANCHOR
LIFTING INSERT (2 REQ'0)
2- GLASS REINFORCED INSERT(4 REO'D)
7
13 1/2•
DESCRIPTION: 79' X 56" 6" PRECAST TRANSFORMER
REFERENCE SPECIFICATIONS:
PAD. TOP SHALL BE FLAT WITH
NO RECESSED AREAS.
ASTM A615
MATERIALS: TYPE III CEMENT
ASTM C33
GRADE 60 REINFORCING STEEL WITH YIELD STRENGTH
OF 60.000 psi
ASTM C39
3/4- AGGREGATE, AIR -ENTRAINING AGENT. WATER -REDUCING
AGENT. ACCELERATOR. SAND AND WATER
CONCRETE SHALL HAVE 28 DAY COMPRESSIVE STRENGTH
ASTM C136
OF 4.500 psi
ASTM C143
DUALITY CONTROL
ASTM C150
To assure proper quality contra and supervision, aonaete Pads shall be
produced of a Notional Precast Concrete Assxiotion (NPCA) certified ASTM C192
manufacturing facility. The manufacturer shall comply with the requirements
set by the NPCA's Quality Conlrai Manual far Precost Concrete Plants.
ASTM C291
ASTM C260
ASTM C494
ACI MI-89
Specification far Deformed and Plain Billet -Steel
Bars for Concrete Reinforcement
Specifications for Concrete Aggregates
Test Method for Compressive Strength of
Cylindrical Concrete Specimens
Method for Sieve Anclysis for Fine and Coarse
Aggregates
Test Method for Slump of Portland Cement Concrete
Specificotions far Portland Cement
Method of Making and Curing Concrete Test
Specimens o the Laboratory
Test Method of Air Content of Freshly Mixed Concrete
by the Pressure Method
Specfcaton for Air Entrainment Admixtures of
Concrete
Specification for Chemical Admixtures for Concrete
Specification for Design of Concert using Ultimata
Strength Methods
OITV OF FORT OOLLINIII
LIGHT and POWER
PRECAST TRANSFORMER PAD
for 75 — 500 KVA
Specification R 368-400, serial 01
ROL ENG X'PoBY SCALE
T. SAGEN G_10 NONE
1. BY DATE SVEET
S. CORAM 10/25/95 1 1 a 1