HomeMy WebLinkAbout102795 WESCO DISTRIBUTION INC - PURCHASE ORDER - 6604953Date: 08/04/06
City of Fort Collins
Page Number: 1
City of Fort Collins
Purchase Order Number: 6604953
Delivery Date: 03/16/07 Buyer: DICK,OPAL
Purchase Order number must appear on invoices, packing lists, labels, bills of lading, and all correspondence.
Note:
Line Qty UOM Description Unit Price Extended Price
1 10 EA T3000051; XMFMR
500 kVA; 480Y/277
T3000051
YARD
TRANSFORMER, 500 kVA PAD -MOUNTED
COMPARTMENTAL TYPE, THREE PHASE
DISTRIBUTION WITH SEPARABLE INSULATED
LOAD BREAK HIGH VOLTAGE CONNECTORS.
HIGH VOLTAGE RATING: 13200 GRDY/7620.
LOW VOLTAGE RATING: 480Y/277.
SERIAL NUMBER 051 TO BE IN ACCORDANCE
WITH SPECIFICATION #368-300-051, REVISION MM
MFR. ABB
ESCALATION IS APPLICABLE
ADJUSTMENTS WILL BE
REVIEWED BY CITY PRIOR
TO PRODUCTION AND IN
13, 376.000 133, 760.00
Opal Dick_ 368dash300.pdf Page
REV. SYM: MM
3.2 SPECIFIC REQUIREMENTS FOR DESIGN OF LOOP -FEED Units
3.2.1 FUNCTIONAL DESCRIPTION
The transformer shall be a three phase, pad mounted, loop feed -safe break, "deadfront" type for use on a
13.8 kV grounded "Y" distribution system.
3.2.2 DESIGN AND CONSTRUCTION
3.2.2.1 RATINGS
Table 1 - L000-Feed Transformer Ratinas
Stock No. WA Low Nominal
Voltage Impedance
Bushing T. a/Confi .
High Voltage
Low Voltage
368-300- 008
75
20BY/120
1.9%
c
of
368-300- 009
75
4BOY/277
1.7%
c
of
368-300- 015
150
208Y/120
2.1%
c
of
368-300- 016
150
480Y/277
2.1%
c
of
368-
300
20BY/120
25%
c
of
36-300-01 3
300
480Y/277
2.5%
c
of
368-300- 050
500
208Y/120
3.04%
c
e
368-300- 061
500
480Y1277
3.04%
c
of
368-300- 075
750
208Y/120
5.75%
c
ci
368-300- 076
750
480Y/277
5.75%
c
368-300- 100
1 1000
208Y/120
5.75%
c
368-300- 101
1 1000
1 480YI277
5.75%
c
368-300- 151
1500
480Y/277
5.75%
c
368-300- 201
2000
480Y/277
5.75%
c
368-300- 251
2500
480Y/277
5.75%
c
cFigure 1 (V-config.) of this specification
e Low -voltage line and neutral terminals shall be stud type bushings in accordance with ANSI C57.12.26-1992, Fig. 9(d)
and shall include a separate spade with NEMA standard drilling
f Figure 9(a) of ANSI C57.12.26 -1992 (4hole pad)
g Figure 9(b) of ANSI C57.12.26 -1992 (6-hole pad)
(<b�aF�Yq�Si[iL1fi4Ti�
3.2.2.2.1 The basic impulse level (BIL) of the comple lely assembled transformer, including high -voltage and
low -voltage terminals shall be 95 kV and 30 kV respectively.
3.2.2.2.2 Dielectric test levels shall be in accordance with the distribution levels in Paragraph 5.10 of ANSI
C75.12.002000
3.2.2.2.3 The unit shall withstand test voltages in accordance with ANSI C57.12.00 and impulse tests in
accordance with NEMA Standards for Transformers, Publications No. TR1.
3.2.2.3 TRANSFORMER CORE
A five -legged core -coil assembly or three separate core -cal assemblies shall be employed. The use of
three-legged designs is expressly prohibited.
7
368-300
Opal Dick- 368dash30O.pdf Page 8
REV. SYM: MM
3.2.2.4 HIGH VOLTAGE TAPS
A no-load tap changer with external operating handle shall provide two 2 Y2 full capacity taps above and
below normal. The operating handle shall be mounted in the primary compartment.
3.2.2.5 BUSHING WELLS AND TERMINALS
3.2.2.5.1 The number, location, and arrangement of bushing wells, terminals and parking stands shall be as
shown in Fig. 1 and Fig. 5 of this specification. All low -voltage bushings and higlrvoltage wells
shall be externally clamped and shall have leads of sufficient length to allow them to be changed
without removing he cover. Welded bushings and wells are expressly prohibited.
3.2.2.5.2 High -voltage bush ng wells shall be 200A load -break interface 8.N14.4 kV bushings in accordance
with ANSI/IEEE Sid. 386.
3.2.2.5.3 Low voltage bushing arrangement and spacing shall be "staggered', as shown in Fig. 5 of this
Specification.
3.2.2.5.4 The low -voltage neutral shall be a fully insulated bushing. A ground pad shall be provided on the
order surface of the tank and a removable copper ground strap shall be provided and connected
between the low -voltage neutra I bushing and the ground pad.
3.2.2.5.5 The high -voltage neutral shall be connected to the low -voltage neutral internally with provision for
opening this connection for testing.
3.2.2.6 ACCESSORY CABINET
3.2.2.6.1 The accessory cabinet shall consist of a high -voltage and low- voltage compartment generally
constructed in accordance with applicable ANSI specifications and dimensioned in accordance with
Fig.1 of this Specification.
3.2.2.6.2 Cabinet doors shall be hinged, removable, and lockable. Stainless hinge pins shall be provided.
3.2.2.7 ACCESSORY EQUIPMENT
Accessory equipment shall be provided in accordance with Table 1A and the following details:
3.2.2.7.1 Suitable jack bosses or equivalent jacking facilities shall be provided on the tank. Vertical
clearance for a jack shall be 11/2 inches minimum, 3Y= inches maximum.
3.2.2.7.2 The transformer base shall be arranged for rolling in two directions:
Parallel to and at right angles to the centerline of the higlrvoltage bushings.
3.2.2.7.3 Far lifting lugs shall be provided. These lugs shall be adequate strength and size and arranged on
the tank to provide a suitable lift for the completely assembled unit.
3.2.2.7.4 The base of the assembly shall be provided with suitable means for mounting the unit on the pad.
An internal flange shall be provided at the base of the accessory compartment to provide means for
mounting the unit on the pad. (Fig. 1).
3.2.2.7.5 Terminal designations are shown in Figure 1. The identification of terminal connection shall be
shown on the instruction nameplate. Instruction nameplate shall be corrosion resistant, located in
the low -voltage compartment, and shall be readable with cables in place. Where the nameplate is
mounted on a removable part, the manufacturer's name and transformer serial number shall be
pemnanerlly affixed to a non -removable part.
Instruction nameplate shall contain the informal ion specified in ANSI C57.12.00-2000, paragraph
5.12. In adddion, either on the nameplate or label affixed near it, the manufacturer shall indicate that
the dielectric fluid is nort-PCB.
8
368-300
Opal Dick- 368dash300.pdf Page 9
REV. SYM: MM
3.2.2.7.6 An automatic pressure relief device shall be located within the compartment. This device shall
meet the following requirements:
/:' NPT or larger male Inlet Pat.
Exposed pans of weather and corrosion resistant materials.
Non-deterioratin g gasket and o-ring material.
Manual pull ring able to withstand 25 pound force minimum.
Body able to withstand 100 pound force minimum.
Bug shield.
Cracking pressure of 10 t 2 psig.
Resealing pressure of 6 psig minimum.
Zero leak rate from resealing pressure to —8 psig.
Minimum flow rate of 35 SCFM at 15 psig.
3.2.2.8 OILPRESERVATION
Transformers shall be of sealed -tank construction. Sealed -tank construction is that which seals the interior
of the tank from the atmosphere, and in which the gas plus the oil volume remains constant. The
transformer will remain effectively sealed for a top -oil temperature range of —32°C to 105°C.
3.2.2.9 TANKS
The tank shall be domed or sloped to shed water and shall be of sufficient strength to support a minimum
of 500 lbs. Construction of the tank shall be in accordance with ANSI C57.12.26-1992, Section 7, except
bolted cover is preferred.
3.2.2.9.1 If main cover is welded, adequate handhole(s) shall be provided. Handholes shall be concealed.
Bolted -on covers shall be adequately gasketed and tamperproof. Main cover bolts may be
exposed; however, where cover bolts are exposed, the comer bolts shall be welted or otherwise
rendered tamperproof.
3.2.2.9.2 Tank grounding provision shall be in accordance with paragraph 7.6.4 of ANSI C52.12.26-1992.
3.2.2.9.3 Locking bolts shall be pentahead style.
3.2.2.10 OVERCURRENT PROTECTION
Overcurrent protection shall consist of a single element current sensing bay-o-net fuse link in series with
an ELSP currerlt limiting backup fuse. Fuses shall be sized as shown in Table 2:
Tahia 2 — Fusina Ranuiramantx
Expulsion 'Fuse Conttnuous
Current
Limiting Fuse
Stock
WA
Current Rating
Contlnudua<Current-Rating
Number
Ca acl
(Part Number*)
mart Nu bar'
36&304008
75kVA
"A
30A
36&30b009
4000353C06
354403OMi1M
I' V"
I
113544040M
368-30D-016
(4000353C0e)
ItA
368-300-030
300kVA
254
654
368-MG-031
4000353C10
3544065M61
368-300-D51
MVA
40A
10DA
4000353C12(3544100WIKM
368.30D 075
75OkVA
65A
125A
368-300-076
75MVA
(40DO353C 14)
(35441251V714
368-300-10D
1000kVA
368-300-101
1000kVA
120001NA
I14000353C17)
I(3544125M)1M1125A fuses
368-300-201
368-300-251
12500kVA
1125A Hi-Arrp OL Unk C05CB r
1250A : Parallel 1254 fuses
(3544125Mr1M)
Fuse shall be as specked in the table above or shall be an equivalent as approved in
writing by Electric Standards Engineering.
9
368-300
Opal Dick- 368dash300.pdf Page 10
REV. SYM: MM
3.2.2.11 COMPONENTS FOR LOOPED PRIMARY
The minimum current -carrying capability of components for the looped primary cable system shall be 200
amperes (continuous) and 10.000 amperes symmetrical (momentary).
3.2.2.12 AUDIBLE SOUND LEVEL
The audible sound level shall be in accordance with NEMA Standard TR1.
3.2.2.13 BASE PLAN
The base plan of a completely assembled unit shall be such that A can be installed on a pad of the
dimensions shown in Fig. 6 of this specification.
3.2.2.14 PAINT
3.2.2.14.1 Surfaces to be painted shall be blast cleaned (commercial blast) to provide a clean dry surface
free of dirt, dust, chalk, loose paint, rust, grease and any other contaminants.
3.2.2.14.2 EEI "Finishing Guidelines" specification shall apply. Finish coat shall be Desert Tan, Munsell
#10YR6.013.0, glossy.
3.2.2.15 SAFETY LABELS
The manufacturer shall not apply NEMA 260 Safety Labels. The Purchaser will apply custom warring
labels after delivery.
3.2.2.16 ANGULAR DISPLACEMENT:
Per Fig. 10(b) of ANSI C57.12.26-1992.
r
Opal Dick - 368dash300.pdf Page 1
L BELawd
a I I A's NIN
+ �+—V
+
r 4
I
27.0
FLANGE 31T MIN
1 11T MAX
KVARATINGS
LOWVOLTAGE
RATINGS
COMPARTMENT
UMEMIONS
(MINIMUM)
BUSHING
HEIGHT
A•
B
7blw
ALL
231M
27
T1S500
ALL
n
31
7561000
iaIYW7,Z8Y 11ID
R
4:1
15W.2500
ABOVlzz7
28
CB
NOTE:
D aed., insHe Amensbu.
See Fg.5
Al Sena n (inc8es�.
Mft m= gh,e lass shag al- arse bite dear a Iran edge M W (Fg. 6),
MIN'
Figure -Accessory compartment &Bushing Dimensions (Config. 1)
REV. SYM: MM
11
368300
Opal Dick - 368dash300.pdf Page 12]
-2.65 hit N.._..
TANK SFIRF. CE
r i. TANK SUR FACE
i 1 ,
ff I
1R c
I c 4 1-lie0
I0.79
_j
INSIDE
Cable Accessory Patkinj; Sty l
Figure I —Cable Accessory Parking Stand Detail
[: =2(Config.) - DELETED 7/92
Figures 3 & 4 - DELETED 11/00
Ref. now to: ANSI C57.12.26 - 1992 figures 9(a)
& 9(b)
REV. SYM: MM
12
368-300
Opal Dick- 368dash300.pdf Page 13
REV. SYM: MM
4.0" A A A 4.0" 6" RADIUS
IN MIN TYPICAL 3
PLACES
r CL
X1 X3 I
B
rr r rL
�\ XO ` k\ X2 �r
KVA RATINGS
LOWVOLTAGE
RATINGS
A
B
75-150
ALL
4.75
8
225-500
ALL
6
8
750-2500
480/277, 208Y/120
6
10
Figure 5- Staggered Low -Voltage Bushing Arrangement
(all dimensions minimum inches).
NOTE:
An area having a 6 inch radius around each bushing
shall remain clear of obstructions such as gauges, etc.
13
368-300
Opal Dick - 368dash300.pdf Page 14-1
REV. SYM: MM
KVA
I SERIAL
I PAD DIMENSIONS (inches)
A
I B
C
D
E
F
75
-M thru -M
75
55
40
21
15
61
150
-015
75
55
40
21
15
61
150
-016
75
55
40
21
15
61
300
-030
75
55
40
21
15
61
300
-031
75
55
40
21
15
61
500
-050
75
55
40
21
15
61
500
-051
75
55
40
21
15
61
750
-076, -075
85
72
49
23
15
67
1000
-101,-100
85
72
49
23
15
67
1500
-151
101
87
51
23
15
j 76
2000
-201
107
88
51
23
15
79
2500
-251
107
88
51
23
15
79
Fig.6 - Pad Dimensions
14
36&300
Opal Dick - 368dash30O.pdf rt Page 1
REV. SYM: MM
TABLE to
ACCESSORY EQUIPMENT
ACCESSORY I KVA
75450 300 500-2500
Tap changer handle in HV compartment
X
X
X
Irslruction nameplate in LV compartment
X
X
X
Jacking provisions
X
X
X
Provisions for rolling in two directions
X
X
X
Lifting lugs
X
X
X
Provisions for mounting on pad
X
X
X
Arrester moulting provisions
Grounding provisions in both compartments
X
X
X
1" oil drain plup
X
1"oil drain valve with sampling device
X
X
Upper filter press and filling plug (or cap) (f)
X
X
X
Provisions for oil gauge
X
Provisions for pressure -vacuum gauge
X
X
Oilgauge
X
Thennorneter
X
X
X
Secondary CT mounting holes
(4 holes on 4 318" x 5 5 8" centers)
X
X
X
Manual/automat is pressure relief valve
X
X
X
15
368-300
Opal Dick - 368dash300.pdf Page 16
REV. SYM: MM
3.3 SPECIFIC REQUIREMENTS FOR DESIGN OF RADIAL -FEED Units
3.3.1 FUNCTIONAL DESCRIPTION
The transformer shall be a three phase, pad mounted, radial feed safe break, "deadfrord" type for use on a
13.8 W grounded "Y" distribution system.
3.3.2 DESIGN AND CONSTRUCTION
The requirements for radial -feed transformers shall be the same as those of loop -feed with the following
exceptions:
3.3.2.1 RATINGS
Tahln 9 _ RaAhl_Pmd Transforrin o-e
Low
Stock No. WA Voltage Impedance
Bushin T e/Conft .
High Volta a Low Voltage
366-300- 006
75
208Y/120
1 9%
d f h
368-300- 007
75
1 480Y/277
1 9%
d I f h
d Per Figures 5A, & 7 of ANSI C57.12.26-1992 (In -Line) EXCEPTION: high voltage bushings shall be 32 .36 inches
above the base of the transformer
If Figures 9(a) & 9(d) of ANSI C57.12.26 -1992 (stud with 4-hole pad)
h Figure 8(a) of ANSI C57.12.26-1992 (Staggered)
3.3.2.2 ACCESSORY CABINET
The accessory cabinet shall be dimensioned in accordance with Fig. 7 of ANSI C57.12.26-1992.
4. QUALITY ASSURANCE
4.1 GENERAL
4.1.1 RESPONSIBILITY FOR INSPECTION
Unless otherwise specified, the vendor is responsible for the performance of all inspection requirements as
specked herein. Except as otherwise specified, the vendor may utilize his own facilities or any commercial
laboratory acceptable to the City of Fort Collins. The City reserves the right to perform or witness any of the
inspections set forth in this Specification where such inspections are deemed necessary.
4.1.2 TEST REPORT
The manufacturer shall furnish to the purchaser certified copies of the results of all tests prior to payment.
Copies shall be send to the Design Section as well as with the invoice. Unsigned copies are riot acceptable
even if accompanied by a signed cover letter. The Quality Control Manager shall review and sign each test
report.
4.2 TEST CONDITIONS
Unless otherwise specified, testing defined in Section 4.6 shall be conducted under the following conditions:
4.2.1 REFERENCE TEMPERATURE
The reference temperature to which losses, impedance, regulation, and efficiency are corrected shall be 850
C.
4.2.2 TOLERANCE ON IMPEDANCE VOLTAGE
Tolerance shall be as specified in ANSI C57.12.00.
16
368-300
Date: 08/04/06
I n
City of Fort Collins
Page Number: 2
City of Fort Collins
Purchase Order Number: 6604953
Delivery Date: 03/16/07 Buyer: DICK,OPAL
Purchase Order number must appear on invoices, packing lists, labels, bills of lading, and all correspondence.
Note:
Line Qty UOM Description Unit Price Extended Price
ACCORDANCEWITH STATED
INDICES IN PRICING.
ANY INDEX ESCALATION
(INCREASE) AFTER THE
QUOTED DELIEVERY DATE
WILL NOT BE ALLOWED.
NO LOAD LOSS - 924
FULL LOAD LOSS - 2346
TOTAL LOAD LOSS - 3270
IMPEDANCE 3.04%
DELIVERY: 32 WEEKS OR
CITY OF FORT COLLINS MAY
CONSIDER THE CAPACTIY
PLAN ARRANGEMENT AS
PROVIDED IN THE QUOTATION
FOR THESE UNITS WITH
SPECIFIC SHIPMENTS AND
QUANTITIES TO BE
STATED WITHIN THE NEXT
Opal Dick - 368dash300.pdf Page 177
REV. SYM: MM
4.2.3 TOLERANCE ON IMPEDANCE VOLTAGE ON A TAP
The percent departure of tested impedance voltage on any tap from tested impedance voltage at rated
voltage shall not be greater than the total tap voltage range expressed as a percentage of the rated voltage.
4.3 FUNCTIONAL TESTS
Functional tests shall consist of those tests and related requirements as cross referenced in Table 4 and shall be
performed on each unit, except Temperature and Noise Tests which shall be performed on one unit of each
design (KVA) per order.
Tn Mtn A C......N T
TEST
TEST PARAGRAPH
REQUIREMENT ;OR'REFERENCE
Examination Of Product
4.6
3.0 3.1 3.2 3.3 hisspecification)
Ratio
4.6
ANSI C57.12.00 Section 8
Polarity Arid Phase Relation
4.6
ANSI C57.12.00 Section 8
Excitation Loss
4.6
ANSI C57.12.00 Section 8
Excitation Current
4.6
ANSI C57.12.00 Section 8
Impedance & Load Loss
4.6
ANSI C57.12.00 Section 8
TemDerature Tests"
4.6
ANSI C57.12.00 Section 8
Dielectric Tests
4.6.1
is s cation
Impulse Tests
4.6.2
3.212.2 hiss ifrcation
Leak Testing
4.6.3 1
3.2.2.8 & 3.2.2.9 (This specification)
Noise Test .
4.6.4 1
3.2.2.12 hiss ifrcation
une urn per design per omer.
4.4 TEST METHODS -- FUNCTIONAL TESTS
Each completed unit shall be inspected to determine compliance with respect to dimensions, material,
workmanship, construction and marking, and routine tests on all units shall be made as specified in Section 8 of
ANSI Standard C57.12.00, and in ANSI Standard C57.12.90. In addition to rouline tests, the following test
requirements arKVor modifications shall apply.
4.4.1 DIELECTRIC TESTS
Induced and applied potential Dielectric Tests shall be performed in accordance with ANSI C57.12.00 and
C57.12.90. The low voltage windings shall have a test potential to ground of 10,000 volts for one minute.
The test potential between high voltage windings shall be 34,000 volts for one minute.
4.4.2IMPULSE TESTS
ANSI Standard Impulse Tests shall be performed. Full Wave Impulse Test shall use a 1.5 x 50 microsecond
wave.
4.4.3 LEAK TESTING
The transformer tank shall be filled with oil and tested for air and oil leaks under (1) 4 psig vacuum for % hour,
(2) 7 psig pressure for 24 hours in the sequence indiicated. An alternate method of leak testing may be
performed by iryecting halogen gas under 10 psig and detecting leaks through the use of a halogen detector.
(Note, the automatictmanual pressure relief device must be removed for this test).
4.4.4 NOISE TESTING
Noise testing shall be conducted in accordance with applicable NEMA Standards.
5. PREPARATION FOR DELIVERY
Transformers shall be prefilled with the appropriate amount of transformer oil and shall be shipped by open -bed trick. Units
shall be packaged in such a way as to provide for ease of handli rig and to protect units from shipping damage. Units shall be
fully palletized in four-way universal pallets with29' minimum openings to facilitate handling from any side. Pallets shall be
independent of the transformer. The Supplier shall give 24-hou notice prior to delivery for any shipments where an individual
transformer weighs over 4,000 pounds. In addition to these requdrements, the Supplier shall comply with any additional
requirements or modifications shown on the purchase order arKVor supplemental instructions.
17
3W300
Opal Dick - 368dash300.pdf Page 18_
REV. SYM: MM
6. DEFINITIONS AND ABBREVIATIONS
• Vendor or Supplier- The manufacturer andlor manufacturer's agent supplying or quoting on the specified article.
• Article, Unit, Assembly - All refers to the equipment defined by this specification.
DC or d.c.- Direct Current.
• AC or a.c. - Alternating Current.
• °C- Degree Celsius (Centigrade)
• OF - Degree Fahrenheit
• kV -1000 volts.
• CPS or Hz -Cycles per second.
psig -Pounds per square inch gauge.
• V ory -Volts.
• kVA -1000 Volt-amperes.
18
368-300
Opal Dick - 36-8dash300.pdf Page 19
REV. SYM: MM
APPENDIX A
Typical pad designs are shown in Figures 1A through 3,k
The dimensions in inches of Figures 1A through 3A Wil fit the mirdmum compartments on transformers covered by this
Specification as well as the maximum transformer envelope.
19
368-300
Opal Dick - 368dash300.pdf Page 20
REV. SYM: MM
_ I
I3" I PRIYNtY SEC.
3'
6' FRD r
' 27- 13• 19'
a3
LENLLEND fW NQ
fD wI WID7N
10" d0' — 3'
7 5T/9' Lr3.
}-
T T
Noted on Pad World —
I. Co+creb moot be3.ODD ver mninurn.
] Ir)aeinum coulee DgWeaote dra 1 1/2 idles
9page rewirements far Pad Cnd primary a ntnng cabinet Fill generally
be V X 12'. Faclars to he twmtacpt fdarmi In iq the Pod rock da —
1. Aeftseblity — Ina Udn l"er pod anal at aCCeeefaU to
line boon trucha eaufpped la the installation and removul of
heavy tranafarMoM $tads aeesddWlity shall not tegvia
mlrusmn a odj wt Prapeny.
2 Prosinity of Buadinga. dale. Darriea. and/or Ovarhmge —
m adaalm to the rtaarmrad raqured IS, Fdtdtaum and
nmoyd. the mninum elwwl w n front of the bonaformet pod
shot be eight (8) feat and the mhinum clearance from al
otrs ddm anal be tree (S) test If the aulldnq has on
e1411%en9, dwenae IS the alga of the bvinsformar Pad shah
be measured hurimntally from the wtar edge of the overhang.
Tronofarmss through 300 KVA may be installed undsd the
avemanq if the Yort"I dwanro bet✓bith ins Poe and the
ovfmohe is all le let 25 foot wA the faddtlun is weeesible to
line boom truohe
J. Codn and Standards — In uddtt'tm to the oboes. the
Installation dhrtl conform to the Notlm l Electric Cade and
hderut note arW ray mars are slu+mras.
2
S 25 93
REV NO.
DATE
OWN
D.E. APP
MO. ENG ADD
DIST ADP
CITY OF FORT COLLINS
DWG 3PHASEI
LIGHT AND POWER DEPARTMENT
TRANSFORMER PAD DESIGN
75 — 500 KVA
leeerr one �0�
3 PHASE
Figure IA- Pad Design (76 - 500 KVA)
20
368-300
Opal Dick - 368dash300.pdf Page 21
REV. SYM: MM
l I I I I
I I 72'
-
I—�----i--�-- I'
-mot.
3
17'
I PRINARY SEIbNS6tiY
8.
I
av— +IT 1 1 Tr
��— 1H' 26" or tir —+I
rotsw e7 otiva
49,3' L04GI. Mdl VtalY
7 3/0
—t—
47
Noted an Pro I,lotafnl —
1.
Crtt, mutt be 3,000 Per mrnrnum.
2.
o..um anoes oggepats sbe 1 112 novae
a requirements fdf pad and Pi.nory fowlehrnq edbnot 0111 q"aIr
M B' x 120. rectors to on, owzmweo fn facet rig the Pod InC1Yae —
f
ACcetaatity — the tmosiMmer pod snot ppe ecceatae 10
P
line boon trudm eauidaed far fnetolo4b,l ad removal of
heOty IrorMfoemsR. Such dec,"emy Mal not raep's
nt.an on odlownt FWCPWIy.
2.
Rotnnoty of B.rLatnyys. *thus Barriers, and//air Overr"s —
ti addition to the doaronced rew1 ed for ineluloUo, wet
remand, the Mn1hYM assrdles br front of the 1ra56farMw Pad
"I de dgnt (a) feet end Ina Mlnrmam oecrorce tam all
other tides shot ter four (1) test, If the "dilq hot on
aY,mom) eldoreneo to the edge of the transforms, Pod enrol
be mouslrrad horIzontolly ceva corn the outer adpe of the rhanp.
rrervformerd t rowel, 300 KVA moy be w0clied under the
onarnonq o the Ydltca clorwonae brelYolen tno Pod wo ins
onahod9 fs of host 25 feel and the lowbou is arcesalde to
lels boom trucks
31
Codes and Slondtrds - in odiiInn, to the above. the
neidfolydl "I Conform to the filit,431101 EIWIhC Code Ma
federal, state wd city Lodes and standorda.
1I 02 BO
REV NO.
OATE
D
D,E, APP
DS G E G APP
DIST, APP
CITY OF FORT COLLINS
DWG 3PHASE2
LIGHT AND PO ER QEPARNENT
TRANSFORWR P p OESIG
500 — 1000 KVA
3 PHASE
Figure 2A - Pad Design (500 -1000 KVA)
21
368-300
Opal Dick- 368dash300.pdf Page 22�
REV. SYM: MM
--I -1-4-� I-- �-
I�
15' PRIMARY WINDOW SC[WDARr
B" -- —� —
2B' 23' V. 29'
II FIVE ss REPAR
VI 31• L[NGIM AND Wl Dllp
3" AND
3'
7 5/9-
-F t
Not" on pad ildwo -
1,Sc,Ynalete marl no S.ODD psi minmum.
2, 1( nim cast" owegato Sao 1 1/2 inches,
space raqulhammm by POD end Primary lh+lchrg co%net *1 gmeroly
be 9' % 12'. Foekon to be coneidored in locotlrq the pod :+clods -
1. AenNl4ty - rha Lranafoi~ Pea Shop be oteouOY to
Nia boom trucks ewbped for the instalotim and raaaml of
a" Vpnilprerp'a Sum orcma ley snail rat ragbo
inkra9lm a odpcenk property.
2 Prodmily of Blr[dnge, l Whet Borriora, wd/w Overhangs -
In od3lion to the cleowcm reti.had for inetdlalion and
remow1, the mimmnu eMvorao in Iledt er the irOMlaimm pad
%boll tee light (8) 1wl and the mmraam doeronce from all
other sire Shall he 1" (4) feel If the baildbq has on
amain, r:MlanrJ to ME od" of me trenstermer Pad "I
be msosurod horirw,tely train the Dater edge 91 the overhong.
rrmrferrrlWE thiO qn 7W MVA may on y0141W under me
ovr"" it lea YrrdEal de>ereo Wtjam in$ Pod and Inn
ovsharq is of least 25 fist and the I=Von is occeedble to
Inr boom traate.
S. Cadn as stanryde - h addition to the asoye. the
matelelim shall twform to the Not End Deere ends and
fadrd, slots and ally codm and atomb
11/02/90
REV N0.
OATE
0 N
D.E. APP
DSNG. ENG APP
DIST. APP
CITY OF FORT COLLINS
DWC 3PHASE3
LIGHT AND POWERDEPARDEPARTIyIENT
11300 - 2500 KVA
w-�• ••�•••
gorses r �ar�
3 PHASE
Figure 3A- Pad Design (1000-2500 KVA)
22
368-300
Opal Dick - 368dash300.pdf Page 23
REV. SYM: MM
APPENDIX B
Transformers purchased under this Specification shall be of the make shown below. Manufacturers not listed below may
submit written proposals demonstrating compliance with these Specifications for consideration of addition to the accepted
manufacturer list prior to the next request for bids. In addition to inclusion on the list below, manufacturer's equipment must
also satisfy all requirements of this Specification to be acceptable.
TABLE 3B
MANUFACTURER SERIAL NO.
Cooper Power Systems
At
ASEA Brown-Bovari (ABB)
All
Howard Industries
All
Pawaels Transformers
All
The manufacturers in the following list have been conditionllyapproved and may bid as an aftemate. The definition and
intent of "Conditional Approval" of a manufacturer is to allow the City to gain some experience with the manufacturers product.
Should a conditionally approved manufacturer be the evaluated low bidder, the City reserves the right to award all, part, or
none of the order to them, dependant upon the current feeds of the City for that item or items.
23
368-300
Opal Dick - 368dash300.pdf Page 24]
REV. SYM: MM
APPENDIX C
The following fors for Individual and Average Transformer Losses are used by the City of Fort Collins to determine loss
pennies.
1) Transformer Loss Evaluation Average Losses For
2) Individual Transformer Loss Evaluation For
24
368-300
Opal Dick - 368dash300.pdf Page 25
REV. SYM: MM
TRANSFORMER LOSS EVALUATION -AVERAGE LOSSES
City Order No. SIN
Manufacturer Invoice No.
WA/Unit
LINE DESCRIPTION AMOUNT
(1) No. of units
(2) Average core losses
(3) Quoted core losses
(4) Excess average core losses:
line (2) less line (3)
(5) Penalty for excess average core losses:
line (1) x line (4) x $
(6) Average copper losses
(7) Quoted copper losses
(8) Excess average copper losses:
line (6) less line (7)
(9) Penalty for excess average copper losses:
line (1) x line (8) x $ _
(10) Penalty to be assessed manufacturer:
line (5) plus line (9) but not less
than zero
Date Prepared By:
Design Engineering
NOTE: If any unit(s) exceeds the loss tolerances of ANSI C57.12.00, Light & Power will either reject it, include it on these
averages, or calculate losses using the Individual Transformer Losses Evaluation Form, whichever is most favorable
to Light and Paver.
25
368-300
Opal Dick - 368dash300.pdf Page 26
INDIVIDUAL TRANSFORMER LOSS EVALUATION
City Order No.
Manufacturer
KVA/Unit
LINE
DESCRIPTION
(1) _
Tested core losses
(2)
Quoted core losses
(3)
Excess core losses
line (1) less line (2) but not less
than zero
(4)
Percent difference
Line (3)—line (2) x 100
(5)
Tested total losses
(6)
Quoted total losses
(n
Excess total losses
Line (5) less line (6) but not less
than zero.
(8)
Percent difference
Line (7) -a- line (6) x 100
(9)
_ Tested copper losses
(10)
Quoted copper losses
(11)
Excess copper losses
Line (9) less line (10) but not less
than zero.
(12)
Penalty for excess core losses
Line (3) x $
(13)
Penalty for excess copper losses
Line (11) x $
(14)
Penalty to be assessed manufacturer
Line (12) plus line (13)
SIN
Invoice No.
Date Prepared By:
Design Engineering
AMOUNT
REV. SYM: MM
26
368-300
Date: 08/04/06
City of Fort Collins
Page Number: 3
City of Fort Collins
Purchase Order Number: 6604953
Delivery Date: 03/16/07 Buyer: DICK,OPAL
Purchase Order number must appear on invoices, packing lists, labels, bills of lading, and all correspondence.
Note
Line Qty UOM Description Unit Price Extended Price
7 CALENDAR DAYS BY
WESCO
Total $133,760.00
City of Fort C1411ijs Director of Purchasing and Risk Management City of Fort Collins
This order is valid over $2000 unless signed by James B. O'Neill 11, CPPO, FNIGP Accounting Department
City of Fort Collins Purchasing, PO Box 580, Fort Collins, CO 80522-0580 PO Box 580
Fort Collins, CO 80522-0580
e
Opal Dick- 368dash300instructions.pdf Page 1
Revised 12/13/96
Special Conditions and Supplemental Instructions to Bidders
Applicable to Specification 368-300
A. Data to be supplied with Bidder's Proposal
The following data shall be supplied with the bidder's proposal in addition to that information required by
the "Invitation to Bid" and the "Purchase Requisition".
1. Impedance volts in percent (%) at full load, high voltage to low voltage at 85°C
2. No load and total losses at 85°C
3. Delivery in weeks
4. A statement indicating compliance with our Specification with exception or a detailed list of exceptions.
5. Escalation IS / IS NOT applicable for the transformers bid. If escalation applies, the Bidder
shall indicate in his bid, the specific items or materials subject to escalation and shall provide the method
and indices to be used in computing the amount thereof. Escalation occurring after acceptance, if Purchaser
exercises the option to delay shipment after manufacturing is completed, will not be paid.
If the above information and compliance statement are not supplied the proposal will not be evaluated
An alternate bid for the total order may be submitted in addition to the unit bids.
B. Loss Evaluations
Loss penalties and loss evaluations will be based on the following values:
1. No-load or excitation losses at $3.90/watt
2. Load losses at $2.30/watt
C. Shipping Terms
Ship F.O.B. point of destination, freight prepaid.
D. Terms of Payment
l . If escalation applies, the City of Fort Collins shall not be billed for escalation occurring after the promised
delivery date.
2. Test reports shall accompany the invoice. If test reports do no accompany the invoice, late payment penalty
charges incurred due to delays in obtaining the test reports will not be paid. Certified copies of test reports
shall be sent to the Standards Engineering Section, Fort Collins Utilities - Light & Power.
3. Loss penalty credits and escalation charges shall be itemized on the invoice.
Opai Dick - 368dash300.pdf Page 1
THE CITY OF FORT COLLINS
Light and Power Department
P.O. Box 580
Fort Collins, CO 80522
SPECIFICATION NO: 368-300
TITLE PAD -MOUNTED COMPARTMENTAL-TY PE,THREE-PHASE
DISTRIBUTION TRANSFORMERS
VNTH SEPARABLE
INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS
i
APPROVED BY:
Kraig Bader
Standards Engineering Division Manager -
ORIGINATION DATE: 8/12/83
REVISED: 2/2/2005
Opal Dick - 368dash300 pdf Pale 2
REV. SYM: MM
ITEMS COVERED BY THIS SPECIFICATION
DESCRIPTION
STOCK
NO.
SPECIFICATION NO.
SERIAL
75
KVA
20BY/120 RADIAL
368.300
-m
75
KVA 408Y/277 RADIAL
368-300
-007
75
KYA
208Y/120 LOOP
368-300
-008
75
KVA
480Y/277 LOOP
368-300
-009
150
KV&
208Y/120 LOOP
368-300
-015
150
KVA
480Y/277 LOOP
368-300
-016
300
KVA
208Y/120 LOOP
368-300
-030
300
KVA,
480Y/277 LOOP
368-300
-031
500
KV&
208Y/120 LOOP
368.300
-050
500
KVA
480Y/277 LOOP
368-300
-051
750
MA
20BY1120 LOOP
3W30D
-075
750
MA
480Y/277 LOOP
368-300
-076
1000
KVA
20BY1120 LOOP
368-300
-100
1000
MA
4BOY/277 LOOP
368-300
-101
15W
KVA
4BOY/277 LOOP
368 300
151
2000
KVA
480YI277 LOOP
368-300
-201
2TOO
KVA 480Y/277 LOOP
368-300
-251
2
368-300
Opal Dick - 368dash300.pdf Page 3
REV. SYM: MM
REVISION DESCRIPTIONS
REVISION DESCRIPTION Previous onflle
APPROVED
REVISION FF:
Tim Sagen
Add Paragraph 5.2.2.9.3: pentahead locking bolts
Susan Coram
Paragraph 3.2.2.13.1: add glossy requirement.
10-18-95
REVISION GG:
Susan Coram
Title page: Remove revised date
Tim Sagen
Paragraph 4.4 and Table 2A Change Temperature Tests and Noise Test from every
9-22-95
unit to one unit of design.
REVISION HH:
Opal Dick
GE removed from Appendix B
Tim Sagan
12-13-96
REVISION II
• Add paragraph 3.2.2.10 OVERCURRENT PROTECTION and renumber remaining
paragraphs in section 3.2
Opal Dick
• Revise Fig. 1 to reflect a "V" configuration for the primary bushing arrangement vs. an
Tim Sagen
in -line arrangement.
613199
• Revise Fig. 17 to remove requirement for CT mounting studs and increase drnansions
A from 5' and 5.5" to 6" on 225-25W WA sizes
REVISION JJ
Bill Bray
Reformat and converted to MS Word, delete List of Active Pages
Tim Sagan
911412000
REVISION KK
Kraig Bader
Added drawing la to describe cable accessory parking stand detail, revise to reflect
Tim Sagen
current editions of national standard s, change impedance on 368-300-009 from
9 / 11 / 2001
1.7% to 1.9%.
REVISION LL
Kraig Bader
• Charge fusing from oil -immersed cwrent sensing weak link cartridge to a current
4/212004
sensing bay-o-net fuse fink in series with an ELSP current limiting backup
fuse (clause 3.2.2.10).
• Charge column header for impedance table in 3.2.2.1 to clarify that impedance
numbers are nominal values. (Tolerance s are consistent with ANSI C.57.12.00-
2000)
• Charged wording from "Mr. Ouch" in 3.2.2.15 to "warring label"
Revision MM
Kraig Bader
Change clause 3.2.2.10 to specify current sensing bay-o-net fuse link by size and
212/2006
part number. Table 2 was added for this pupose.
Renamed table in 3.3.2.1 to from Table 2 to Table 3
Renamed table in 4.3. from Table 2A to Table 4
3
368-300
Opal Dick- 368dash300.pdf Page 4
REV. SYM: MM
TABLE OFCONTENTS
ITEMS COVERED BYTH IS SPECIFICATION ... ........... ............. ._........... ...... _.... ... ....._....... .........
...... ........ 2
REVISIONDESCRIPTIONS ...... _........ _... ....... ....... ...... . ............. .............. ............ ..... ......... ____ .............
.....__3
1. SCOPE ... .......... .............. .._.......... .............. ............... ... ....... .... ................ .............................. ... ........ ... ..............
............... ..5
2. APPLICABLE DOCUMENTS..._. ..... _ ._.. .............. .............. ..... ._....... _.___._... _.. __..._ ....__._... ... _ ..
.___ .. _.5
3. REQUIREMENTS ._......_.r. ___.._._... __._....._. ............ .. ............... ............... ............ ............... ............. .............. ..... _....... 5
3.1 GENERAL REQUIREMENTS FOR DESIGN .......... ................ ...... ... ...... ................-.............. ................ ................ ...............
.......5
3.2 SPECIFIC REQUIREMENTS FOR DESIGN OF LOOP -FEED UNITS ........................... ................ ................ ................
.............7
3.3 SPECIFIC REQUIREMENTS FOR DESIGN OF RADIAL -FEED UNITS ........... ................ ......... ................ ................
......16
4. QUALITY ASSURANCE ............ ............ ...... ............... ... ........... ............. .... ..... .... .... ... ....... _.....__.._
.............. .16
4.1 GENERAL ................ ............... ................................................ ................ ................
.....16
4.2 TEST CONDITIONS ................ ................ ................ ................ ................ ................ ................................................ ................
.....16
4.3 FUNCTIONAL TESTS ........... ................ ................ ............... ................ ................ ................ ............... _.............. ................
.......17
4.4 TEST METHODS - FUNCTIONAL TESTS ................ ................ _............. ................ ................ ................ ................
................ 17
5. PREPARATION FOR DELIVERY......_ _.___._.. .............. ............ ...... ....._..__. ._.._..... _.......__.._. ... ....
__. ._.._..17
6.DEFINITIONS AND ABBREVIATIONS _._.......... _...... ...... ............. .............. ..__.._._. ......... ... . .............. ......_..... ......18
APPENDIXA ...... _..___.... _____.... ........... .............. ............. ._........... ..... ..... _...._.._._.. ...... __..... ._.._._....
APPENDIXB_____.._. ........... ............... ....... _............ ........... ._........__ .__....__ .__..23
APPENDIXC.__.__.. _._._.w.. __....___ .__.._._. ....._._._... _..__...._.. ._. ....... ........... _. ......___. .__..___
_.....24
TRANSFORMER LOSS EVALUATION -AVERAGE LOSSES .......................... ................ ................ ................ ................
.......25
INDIVIDUAL TRANSFORMER LOSS EVALUATION ...................... ................ ................ ................ ................ ................
........26
4
368-300
Opal Dick - 368dash300.pdf Page 5
REV. SYM: MM
SPECIFICATION FOR
PAD -MOUNTED COMPARTMENTAL -TYPE, THREE-PHASE
DISTRIBUTION TRANSFORMERS WITH
SEPARABLE INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS
1.SCOPE
This Specification establishes the minimum electrical requirements and mechanical features of three phase, 60 HZ,
mineral al immersed, self -coded, pad -mounted, compartmen tal4ype distribution transformers rated 2500 WA and
smaller, high voltage 13,200 Grd Y17620 volts, with separab le insulated load break high voltage connectors. These
transformers are used for step down purposes from an underground primary cable supply.
This standard generally conforms to ANSI requirements for pad -mounted compartm ental-type, self -coded, three-phase,
distribution transformers for use with separable insulated high -voltage connectors, C57.12.26.
2.APPLICABLE DOCUMENTS
The following documents form a part of this Specification to the extent specified herein. The latest issue in effect on the
date of invitation for bids shall form a part of this Specification, undess otherwise rated.
• ANSI C57.12.00 - Distribution, power, and regulating transformers, and shunt reactors, general requirements for
• ANSI C57.12.26 - Pad mounted, comparl mental-ty pe, self -coded three phase, distribution transformers for use with
separable insulated high voltage connectors, high voltage 34,5W Grd Y/19,920 volts and below,
2500 WA and smaller, requirements for
• ANSI C57.12.70 - Temunal markings and connections for distribution and power transformers
• ANSI C57.12.80 - Terminology for power and distribution transformers
• ANSI C57.12.90 - Distribution, paver, and regulating transformers, and shunt reactors, test code for
• ANSMEEE 386 - Separable insulated connectors for pourer distribution systems above 600V
NEMA STANDARD TR1 -Transformers, regulators and reactors
3. REQUIREMENTS
3.1 GENERAL REQUIREMENTS FOR DESIGN
3.1.1 BASIC DESIGN STANDARDS
Transformers purchased under these Specifications shall be new and, unless otherwise specified, meet the
requirements of the applicable ANSI Standards and the modifications and additions given in the subsequent
paragraphs. In case of conflict, the requirements of the following documents shall apply in the priority shown:
a) This Specification.
b) ANSI C57.12.26
c) Other applicable ANSI and NEMA Standards.
3.1.2 KILOVOLT -AMPERE TEMPERATURE RATINGS
Kilovolt -ampere ratings are continuous and are based on not exceeding either a 65°C average winding
temperature or an 80°C hot spot temperature rise. The temperature rise of the insulating oil shall rat exceed
65°C when measured near the top of the tank. The temperature rise is based on an altitude of 3,300 feet.
3.1.3 GENERAL CONSTRUCTION
3.1.3.1 The pad -mounted compartmental-t ype transformers shall consist of the transformer tank, high -voltage
cable terminating compartment, and the law -voltage cable-terninatin g compartment. All three of these
components shall be assembled as an integral unit, tamperproof and weatherproof for mounting on a
pad. There shall be no exposed screws, bolts or other festering devices, which are externally
removable, except the main cover bolts may be exposed. Where the main cover bolts are exposed, the
5
368-300
Opal Dick - 368dash300.pdf Page 6
REV. SYM: MM
comer bolts shall be welded or otherwise render ed tamperproof. There shall be no opening through
which foreign objects such as sticks, rods, or wire s might be inserted to contact live parts. Suitable
means for padlocking the compartment door(s) shall be provided.
3.1.3.2 The high and low -voltage compartment shall be located side by side on one side of the transformer tank.
When facing the compartment, the low -voltage compartment shall be on the right.
3.1.3.3 Construction of the unit shall be such that it can be lifted, skidded, and slid into place on the mounting
pad without disturbing the entrance cables.
3.1.3.4 An undercoating over the regular finish or an equivalent treatment shall be applied to all surfaces that
are in contact with the pad to minimize corrosion.
3.1.3.5 Minimum dimensions shall be as shown in Fig. 1 of this Specification. Maximum transformer and
minimum pad dimensions are shown in Fig. 6 of this Specification.
3.1.4 LOSSES
The total losses of a transformer shall be the sum of the excitation losses and the load losses (12R losses).
Load loss tests shall be performed and reported on all tints regardless of whether or not a record of such
tests is available on duplicate units. Loss evaluation and loss costs will be based on the values shown in the
"Special Conditions and Supplemental Instructions s to Bidders." Transformers will be evaluated on excitation
losses and PR losses at the specified rates. If tested losses exceed quoted losses but are within the
tolerances of paragraph 9.3. ANSI C57.12.00-2000, the additional cost incurred from the differential of losses
will be calculated using the follawing equation and the above specified rates and will be deducted from the
original Purchase Order or back charged to the manufacturer. In Table 18 and the following equation "Units"
shall mean "Transforrmers of the same size and design on one order."
Excess loss $ _ [No. of units] [(No Load Loss Evaluat ion $) (Avg. No Load Losses — Quoted No Load Losses)
+ (Load Loss Evaluation $) (Avg. Load Losses — Quoted Load Losses)]. If this equation results in a negative
number no credit will be given the Supplier.
If any unit or units exceed the tolerances of paragraph 9.3, ANSI C57.12.OD-2000, that unit or units shall not
be shipped without express permission from the City. If accepted, the deduction for excess losses will be
based on the following equation: Excess loss $ _ (No Load Loss Evaluation $) (No Load Losses — Quoted No
Load Losses) But Not Less Than Zero + (Load Loss Evaluation $) (Load Losses —Quoted Losses) But Not
Less Than Zero.
3.1.5 SERVICE CONDITIONS
Service conditions shall be as defined in paragraph 4.1 of ANSI C57.12.00 except the ambient temperature
range shall be 40"C above to 32°C below zero. The transformer shall operate safely with starting
temperatures as low as 32"C below zero.
6
368-300