1 6 EA T1200180; 167kVA transformer
2401120; single phase padmount
T1200180
YARD
TRANSFORMER, 167 kVA
PAD -MOUNTED COMPARTMENTAL
TYPE, SINGLE PHASE
DISTRIBUTION WITH
SEPARABLEINSULATED
LOAD BREAK HIGH VOLTAGE
CONNECTORS. HIGH
VOLTAGE RATING: 13200 GRDY/7620.
LOW VOLTAGE RATING: 2401120.
SERIAL NUMBER 180 TO
BE IN ACCORDANCE
WITH SPECIFICATION
#368-120-180, REVISION FF
3,757.000 22,542.00
Opal Dick- 368dash120.pdf _Page 7
REV. SYM: FF
3.2.2.6 ACCESSORY CABINET
3.2.2.6.1 The accessory cabinet shall consist ofa compartment containing high -and low -voltage bushings
constructed in accordance with applicable ANSI spedficatons, including ANSI C57.12.28. Dimensions
shall be in accordance with Fig. 1 of this specification.
3.2.2.6.2 Cabinet doors shall be hinged, removable, lockable, and ofsu fident size to provide adequate working
space when removed or open. Unlocking the padlock shall permit access to both the high- and low -
voltage terminations. Stainless steel hinge pins shall be provided.
3.2.2.7 ACCESSORY EQUIPMENT
Accessory equipment shall be provided in accordance with the following details:
3.2.2.7.1 Deleted
3.2.2.7.2 The transformer base shall be arranged for rolling in two directions: Parallel to and at right angles to the
center line of the high -voltage bushings.
3.2.2.7.3 Lilting lugs or bosses for screw -in lift bolts shall be provided. These lugs or bosses shall be adequate
strength and size and arranged on the tank to provide a suitable balanced lift for the completely
assembled unit
3.2.2.7.4 The base of the assembly shall be provided with suitable means for mounting the unit on the pad. An
internal flange shall be provided atthe base ofthe accessory compartment to provide means for
mounting the unit on the pad. (Fig. land Figure 2, Appendix B).
3.2.2.7.5 Terminal designations are shown in Figure 1 and Figure 2, Appendix B. The identification of terminal
connections shall be shown on the instruction nameplate. Instruction nameplate shall be located in the
low -voltage side and shall be readable with cables in place. Where the nameplate is mounted on a
removable part, the manufacturer's name and transforms r serial number shall be permanently affixed to
a non -removable part
Instruction nameplate shall contain the information specified in 5.12 of ANSI C57.12.00-1987, Nameplate
A. Also, on the nameplate, or label affixed near it, the manufacturer shall indicate that the dielectric fluid
contains less than 1 ppm PCB.
3.2.2.7.6 A suitable marking inside ofthe tank shall indicate the correct oil level at 25•C.
3.2.2.7.7 An automatic pressure relief device shall be located within the compartment This device shall meet the
following requirements.
Y." NI'T or larger male Inlet Pat.
B(posed parts of weather and corrosion resistant materials.
Norrdeterioratin g gasket and o-ring material.
Manual pull ring able to withstand 25 pound force minimum.
Body able to withstand 100 pound shear force minimum.
• Bug shield.
Cracking pressure of 10 t 2 psig.
Resealing pressure of 8 t 2 psig.
Zero leak rate from 8 f 2 psig to -8 psig.
• Minimum flow rate of 35 SCFM at 15 psig.
3.2.2.7.8 An RTE BAY-O-NET current sensing fuse and internally vaunted partial range current limiting fuse shall
be furnished as shown in Table 1.
3.2.2.8 OIL PRESERVATION
Transformers shall be of sealed -tank constuction. Sealed -tank construction is that which seals the interior
ofthe tank from the atmosphere, and in which the gas plus the oil volume remains constant The
transformer will remain effectively sealed for a top -oil temperature range of-5•C to 105•C.
3.2.2.9 TANKS
The tank shall be domed or sloped to shed water. T he tank shall be of suffld ant strength to support a
minimum of 500 lbs. vertical load. Construction of the tank shall be in acoo rdance with ANSI C57.12.25-
1981, paragraphs 6.1 and 6.6.
7
3W120
Opal Dick - 368dash120.pdf Page g
REV. SYM: FF
3.2.2.9.1 The cover shall be welded construction.
3.2.2.9.2 Tank grounding provision shall consist oftwo steel pads, each with 'F inch - 13 NC tapped hole, 7l16
inch deep.
3.2.2.9.3 These ground pads shall be welded on the transformer base or on the tank wall near the base, one in
the high -voltage side and one in the low -voltage side. In cases where the transformer tank and
compartments are separate, provisions shall be made for electrically connecting them.
3.2.2.9.4 Looking bolts shall be pentahead.
3.2.2.10 COMPONENTS FOR LOOPED PRIMARY
The minimum current -carrying capability of components for the looped primary cable system shall be 200
amperes (continuous) and 10,000 amperes symmetrical (momentary).
3.2.2.11 AUDIBLE SOUND LEVEL
The audible sound level shall be in accordance with NEMA Standard TR1-1980.
3.2.2.12 BASE PLAN
The base plan of completely assembled unit shall be such that itcen be installed on a pad of the
dimensions shown in Fig. 1B.
3.2.2.13 PAINT
EEI "Finishing Guidelines" specification shall apply. Finish coat shall be Munsell Green, glossy.
3.2.2.14 LOSSES
The total losses of transformer shall be the su m of the excitation losses and the load losses (12R losses).
Load loss tests shall be performed and reported on all units regardless of whether or not a record of such
tests is available on duplicate units. Loss evaluations and loss costs will be based on the values shown in
the "Special Conditions and Supplemental Instruction to Bidders." Transformers will be evaluated on
excitation losses and FR losses at the specified rates. If tested losses exceed quote losses but are within
the tolerances of Table 18, ANSI C57.12.00-1987, the additional cost incurred from the differential of losses
Wit be calculated using the following equation and the above specified rates and will be deducted from the
original Purchase Order or back charged to the manufacturer. In Table 18 and the following equation "Units"
shall mean "Transformers of the as me sire and design on one order".
Excess loss $ = [No. of units] [(No Load Loss Evaluation $) (Avg. No Load Losses - Quoted No Load
Losses) +(Load Loss Evaluation $) (Avg. Load Losses - Quoted Load Losses)]. If this equation results in a
negative number, no credit will be given the Supplier.
9 any unit or units exceed the tolerances of Table 18, ANSI C57.12.00-1987, that unit or units shall not be
shipped without express permission from the City. If accepted, the deduction for excess losses will be based
on the followng equation: Excess loss $ = (No Load Loss Evaluation $) (No Load Losses - Quoted No Load
Losses) But Not Less Than Zero + (Load Loss Evaluation $) (Load Losses - Quoted Losses) But Not Less
Than Zero.
3.2.2.15 SAFETY LABELS
NEMA 1260 Safety Labels shall not be applied bythe manufacturer: Purchaser will applycustomer warning
labels after delivery.
8
368-120
Opal Dick - 368dash 120. pdf
Page
REV. SYM: FF
4 QUALITYASSURANCE
4.1 GENERAL
4.1.1 RESPONSIBILITY FOR INSPECTION
Unless otherwise specified, the vendor is responsible for the performance of all inspection requirements
as specified herein. Except as otherwise specified, the vendor may utilize his own facilities or any
commercial laboratory acceptable to the City of Fort Collins. The City reserves the right to perform or
witness any of the inspections set forth in this Specification where such inspections are deemed
necessary.
4.1.2 TEST REPORT
The manufacturer shall funish to the purchaser certified copies of the results of loss tests prior to
payment. Copies shall be sent to the Design Section as well as with the invoice. Unsigned copes are
not acceptable even if accompanied by a signed cover letter. The Quality Control Manager shall review
and sign each test report.
4.2 TEST CONDITIONS
Unless otherwise specified, testing required by Section 4.4 shall be conducted under the following
conditions:
4.2.1 REFERENCE TEMPERATURE
The reference temperature to which losses, impedanc e, regulation, and efficiency are corrected shall be
85°C.
4.2.2 TOLERANCE ON IMPEDANCE VOLTAGE
Impedance on competed units shall fall within the range specified herein.
4.2.3 TOLERANCE ON IMPEDANCE VOLTAGE ON A TAP
The percent departure of tested impedance voltage on any tap from tested impedance voltage at rated
voltage shall not be greater than the total tap voltage range expressed as a percentage of the rated
voltage.
4.3 Not used.
4.4 TESTS
The kinds of tests to be performed and the test procedur as shall be as specified in ANSI C57.12.20, ANSI
C57.12.00, and C57.12.90 except as specified herein.
4.4.1 DIELECTRIC TESTS
No applied potential test shall be made. The induced-potentia I test shall be made by applying between
the terminals of one winding a voltage which will develop from high -voltage line terminals to ground a
voltage of 1000 volts pus 3.46 times the rated transformer winding voltage.
4.4.2IMPEDANCE AND LOAD -LOSS TESTS
Impedance and load -loss tests shall be made on each unit and may not be omitted even if a record of
such tests made on a duplicate unit is available.
5 PREPARATION FOR DELIVERY
Transformers shall be preflled with the appropriate amount of transformer oil and shall be shipped by open -bed trick.
Units shall be packaged in such a way as to provide for ease of handling and to protect units from shipping damage.
9
368-120
Opal Dick - 368dash120.pdf Page 10
REV. SYM: FF
Units shall be packaged on four-way universal pallets with 34 inches minimum opening and loaded on the truck for
side removal. The Supplier shall give 24 hour notice prior to delivery for any shipments where an individual
transformer weighs over 5,000 pounds. In addition to these requirements, the Supplier shall comply with arry
additional requirerents or modifications shown on the purchase order andlor supplemental instructions.
6 DEFINITIONS AND ABBREVIATIONS
Vendor or Supplier - The manufacturer arKLor manufacturer's agent supplying or quoting on the specified article.
Article, Unit, Assembly - AN refer to the equipment defined by this Specification,
• DC or d.c. - Direct Current.
• AC or a.c. - Altercating Current.
• °C - Degree Celsius (Centigrade)
• OF -Degree Fahrenheit
• kV - 1000 volts.
• CPS or Hz- Cycles per second.
• psig - Pounds per square inch gauge.
• V or v- Volts.
• KVA - 1000 Volt-amperes.
10
368-120
Opal Dick - 368dash120.pdf Page 11�
REV. SYM: FF
APPENDIX A— Transformer Stock Number Coding
Below are examples that demonstrate the coding method used by City of Fort Collins to establish
transformer stock numbers.
I. SINGLE PHASE
Example #1:19--*
Trn mfnm
Single Phase
00 = 13.2Y/7620 &
7620/13.2Y x
2400/4160 outside
pole
05=13.2Y7620 ESNA pole
20 = 13.2Y/7620 ESNA pad
II. THREE PHASE
Example #2 E*
Transformer
3 Phase
Pad
3T68 -
f
368 -1
YZ
Other
KVA
0 = 5 5=50
1=10 6=75
2=15 7=100
3=25 8=167
4 = 37.5 9 = 250
1 = single voltage
2 = dual voltage
- XYZ
KVA
006 = 75 075 = 750
015 = 150 100 = 1000
030 = 300 150 = 1500
050 = 500
All suffixes indicate 208Y/120 sec.
For 480Y/277 sec., add 1 to XYZ
(ie. 007 would indicate a 75kVA with
480Y/477 sea)
11
368-120
Opal Dick - 368dash120.pdf Page 12�
APPENDIX B — DIMENSIONAL DRAWINGS
40' MAX
20" MIN
4VI
MIN
3e453k3IkN'
,
4j'�I MIN
IN
M
MMIN
MAIN"
NIA' HIB 'X3 'XI
CABLE ACCFSSORY
1
7*11` 32"max
PARKING STAND
1
X2
f
GROUND PAD --
18":2'
MAX.
OIM.
25 do 50 32. S"
100 -- 42`
1$7 42" 0'
23D 44' 55"
WITHOUT
WITH
MINIMUM OPENING
KV
RADIATORS
RADIATORS
YO IN ROTM OF COMPARTMENT
fOR CABLE ENTRANCE
Figure 1 - Type 1 Transformer Dimensions and bushing Designations (not to scale)
12
36&120
Opal Dick - 368dash120.pdf Page 13
�I - E
z° z
TANK SURFACE
DErAIL A
CABLE ACCESSORY
PARKING STAND
BOTTOM ► 1 10.E
FLANGE 4
MIN t--------_-_-
r 4 MAX is MAJ 60ftlua
ti MkN
7.
REV. SYM: FF
A
INSME
31TpAA*f POaJT
_ Zrl
2
i 3, MIN
MIN
8.1
PLANE
4
Stock Number Dimension A 1 Dimension $ I Dimension C I Dimension D I'Dimension E
368-120-155 1 13" 1 5" 1 4" 1 a, 1 3 Y,"
Figure 2 - Type 2 Transformer Dimensions and bushing Designations (not to scale)
13
36&120
Opal Dick - 368dash120.pdf Page 14
REV. SYM: FF
Pad Dimensions
This drawing is riot intended to dictate requirements for items purchased under Specification 368-120 but is included as
an aid to those users desiring a minimum of pad designs for the transformers covered by Specification 368-120.
The dimensions in inches of Figure 3 will fit the minimum compartments on transformers covered by this Specification as
well as the maximum transformer envelope.
01— FUUROREBW
LERGT MOWUTM
y L3
T 112'
T T
fax on Pad Material -
1. Concrete mmt W 3,Gg3 pi mnhum.
2 Maximum cear'e apprepate ... l 112.m..
Space ret,.k.eMs for it end Pknry.Mt Ng ceEnet .1 Bemraly
be 9 % 12. Factors to M comitleretl in bcetkg tits, pas! rcNds -
1. Accesslfkty- TM tmmformer pit shal M accessibe to
less born trucks equipetl forth. krtelM. eM remwel of
harry trensformers. Such accessNily shal not requke
ird.icn an e4went W wy.
2. P.Mkyef Bidengs, Wells, Berms, Moor Ovadrorp -
tneddiion to ihocbarerwes r,4W irnet.11M. ant
r ss,, the mnimum clearMkx n front of thetramfonmr pad
steel be oW (8) feat ant the mimmn cbamma from al
IXM'sees steel M two (2) feel. Iftm WIkMp has en
werMng, cle sewe to the odpe of tM Iramform W stud
be measured tw noisy frwntie outer edp of tMwedrrg
Tremfwmers though M KVA m W nstalbd under the
werhaw 8 the vestess cbamlwe between the ptl ant the
weVang is a bast 2b feet ant Vie bcalidn is accessible to
Me bops trucks.
3. Codes rid Standrde - Inaddkicn to tMaboae, the
imtatatorl sMl conform to tM National Ebctrn Code and
fedrel, elate end city code, erid staNerils.
Finure 3 - Pad Olmensions
14
368-120
Opal Dick - 368dash120.pdf Page 15]
REV. SYM: FF
APPENDIX C —Approved Manufacturers
Transformers purchased under this Specific ation shall be of the make shown below. Manufacturers not listed below may
submit written proposals demonstrating compliance with these Specifications for corsiderati on of addition to the accepted
manufacturers list prior to the next request for bids. In addition to inclusion on the list below, manufacturers equipment
must also satisfy all requirements of this Specification to be acceptable.
MANUFACTURER SERIAL NO.
ABB Ail
Cooper Power Systems All
General Bectric Al
Howard Industries Al
The manufacturers in the following list have been conditionally approved and may rid as an alternate. The definition and
intent of "Conditional Approval' of a maid acturer is to allow the City to gain some experience with the manufacturers
product. Should a conditionally approved manufacturer be the evaluated low bidder, the City reserves the right to award
all, part, or none of the order to them, dependant upon the current needs of the City for that item or dens.
15
368-120
Opal Dick- W8dash120.pdf Page 16�
REV. SYM: FF
TRANSFORMER LOSS EVALUATION - AVERAGE LOSSES
City Order No. SIN
Manufacturer Invoice No.
WA/Unit
LINE
DESCRIPTION A MOUNT
(1)
No. of units
(2)
Average core losses
(3)
Quoted core losses
(4)
Excess average care losses:
line (2) less fine (3)
(5)
Penalty for excess average core losses:
line (1) x line (4) x $
(6)
Average copper losses
(7)
Quoted capper losses
(8)
Excess average c r losses:
less
line (V6) Tine
(9)
IPe l�v)forl ramie Sj z $ e copper losses:
(10)
Penalty to be assessed manufacturer:
line (5) plus line (9) but not less
than zero
Date Prepared By:
Design Engineering
NOTE: If any, unit(s) exceeds the loss tolerances of ANSI C57.12.00, Light & Power will either reject it,
include it on these averages, or calculate losses using the Individual Transformer Losses Evaluation
Forth, whichever is most favorable to Light and Power.
16
368-120
0
a a
,
Citv of Fort Collins
Page Number: 2
City of Fort Collins
Date: 08/04/06
Purchase Order Number: 6604944
Delivery Date: 08/04/06 Buyer: DICK,OPAL
Purchase Order number must appear on invoices, packing lists, labels, bills of lading, and all correspondence.
Note:
Line Qty UOM Description Unit Price Extended Price
PREVIOUS QUOTE 23931
MFR. ABB
ESCALATION IS APPLICABLE
ADJUSTMENTS WILL BE
REVIEWED BYCITY PRIOR
TO PRODUCTION AND IN
ACCORDANCEWITH STATED
INDICES IN PRICING.
ANY INDEX ESCALATION
(INCREASE) AFTER THE
QUOTED DELIEVERY DATE
WILL NOT BE ALLOWED.
NO LOAD LOSS - 242
FULL LOAD LOSS - 1101
TOTAL LOAD LOSS - 1343
IMPEDANCE 2.51%
DELIVERY: 32 WEEKS OR
CITY OF FORT COLLINS MAY
CONSIDER THE CAPACTIY
Opal Dick - 368dash120.pdf Page 17
INDIVIDUAL TRANSFORMER LOSS EVALUATION
City Order No.
SIN
Manufacturer
Invoice No.
KVNUrd
LINE
DESCRIPTION AMOUNT
(1)
Tested core losses
(2)
Quoted con: losses
(3)
Excess core losses
line (1) less line (2) but rat less
than zero
(4) Percent difference %
line (3) D line (2) x 100
(5) Tested total losses
(6) Quoted total losses
() Excess total losses
line (5) less line (6) but not less
than zero
(8) Percent difference %
line (7) D line (6) x 100
(9) Tested copper losses
(10) Quoted capper losses
(11) Excess copper losses
(12) line (9) less line (10) but not less
than zero
(12) Penalty for excess core losses
line (3) x $
(13) Penalty for excess copper losses
line (11) x $
(14) Penalty to be assessed manufacturer
line (12) plus line (13)
Date Prepared By:
Design Engineering
REV. SYM: FF
17
368-120
Opal Dick - 368dashMinstructions.pdf Page I
Issued: 8/17/72
Revised: 1 /21 /94
Special Conditions and
Supplemental Instructions to Bidders
Applicable to
Specification 368-120
A. Data to be Supplied with Bidder's Proposal
The following data shall be supplied with the bidder's proposal in addition to that
information required bythe "Invitationto Bid" and the "Purchase Requisition".
1. Atypical listofusers of I phase padmounted distribution class
transformers manufactured bythe bidd erduring the past five years.
2. Atypical drawing of the transformers showing that they will meetthe
critical dimensions required by the Specification.
3. Impedance volts in% at full load, high voltage to low voltage at 850C.
4. No load and total losses at 85oC.
5. Delivery in weeks.
6. A statement indicating compliance with our Specification without
exception or detailed list of exceptions.
7. Escalation is _ is not _applicable for the transformers bid. Ifescalation
applies, the Bidder shall indicate inhis bid the specific items ormaterials
subject to escalation, and shall give the method and indices to be used in
computing the amount thereof. Escalation occurring afterthe quoted
delivery date will not be paid unless delays are the result of actions by the
C ity. Escalation occurring after acceptance, if Purchaser exercises the
option to delay shipment after manufacturing is completed, will not be
paid.
If the above information and compliance statement are not supplied, the proposal will not
be evaluated.
An alternate bid for the total order may be submitted in addition to the unit bids.
B. Loss Evaluations
Loss penalties and loss evaluations will be based on the
following values:
No load or excitation losses at $3.90/watt.
2. Load losses at $1.50/watt.
Opal Dick - 368dashl20instructions.pdf Page 21
Shipping Terms
Ship F.O.B. point of destination, freight prepaid.
D. Terms of Payment
If escalation applies, the City of Fort Collins shall not be billed for
escalation occurring after the promised delivery date.
2. Test reports shall accompany the invoice. If test reports do not accompany the
invoice, late payment penalty charges incurred due to delays in obtaining the test
reports will not be paid. Certified copies of test reports shall be sent to the Design
Section, Fort Collins Light and Power Utility.
Loss penalty credits and escalation charges shall be itemized on the
invoice.
Date: 08/04/06
City of Fort Collins
Page Number: 3
City of Fort Collins
Purchase Order Number: 6604944
Delivery Date: 08/04/06 Buyer: DICK,OPAL
Purchase Order number must appear on invoices, packing lists, labels, bills of lading, and all correspondence.
Note:
Line Qty UOM Description Unit Price Extended Price
PLAN ARRANGEMENT AS
PROVIDED IN THE QUOTATION
FOR THESE UNITS WITH
SPECIFIC SHIPMENTS AND
QUANTITIES TO BE
STATED WITHIN THE NEXT
7 CALENDAR DAYS BY
WESCO
Total
$22,542.00
City of Fort qllifis Director of Purchasing and Risk Management City of Fort Collins
This order is valid over $2000 unless signed by James B. O'Neill II, CPPO, FNIGP Accounting Department
City of Fort Collins Purchasing, PO Box 580, Fort Collins, CO 80522.0580 PO Box 580
Fort Collins, CO 80522-0580
Opal Dick - 368dash120.pdf Page
THE CITY OF FORT COLLINS
Light and Power Department
P.O. Box 580
Fart Collins, CO 80522
SPECIFICATION NO: 368420
TITLE PAD -MOUNTED COMPARTMENTAL -TYPE, SINGLE-PHASE
DISTRIBUTION TRANSFORMERS
WITH SEPARABLE
INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS
APPROVED BY:
Kraig E
Standards Engineering Manager
ORIGINATED: 09/14/72
LAST REVISED: 712112004
ITEMS COVERED BYTHIS SPECIFICATION
DESCRIPTION
STOCK NO.
SPECIFICATION
NO.
SERIAL
25 KVA 120/240 ANSI Type 1 Transformer.
368-120
-130
50 KVA 120/240 ANSI Type 1 Transformer.
368-120
-150
50 KVA 120/240 ANSI Type 2 Transformer.
368-120
- 155
100 KVA 1201240 ANSI Type 1 Transformer.
368-120
-170
167 KVA 1201240 ANSI Type 1 Transformer.
368-120
-180
250 KVA 120/240 ANSI Type 1 Transformer.
I 368-120
I -190
Opal Dick - 368dash12O pdf Page 2
REV. SYM: FF
PREVIOUS REVISION DESCRIPTIONS ON FILE
REVISION DESCRIPTION
APPROVED
REVISION DD:
Sagen
Paragraph 3.2.2.7.5: Editorial
10/21/94
• Acid paragraph 3.2.2.9.4 requiring pentahead locking bolts
• Paragraph 3.2.2.13 add glossy to paint requirement
• Paragraph 4.2.2: Cladfy impedance requirement
REVISION EE:
Sayan
• Paragraph 5.0: revised pallet size from 28 to 34 inches
2/25198
REVISION FF
Kraig Bader
• Added 50kVA ANSI Type 2 Transformer (368-120-155) to Specification
7/21/2004
• Changed paint color to standard Munsell Green
• Reorganized to consolidate impedance and fusing requirements into one table.
• Consolidated secondary terminal requirements into one table.
• Added maximum impedance requirement for 250kVA transformer (+/-7.5%from nominal for
transformers with impedance greater than 2.5%) per ANSI/IEEE C57.12.00-2000.
• Reevaluated fusing requirements of all transformers in this specification. Went from dual
sensing bay-o-net (expulsion) fuses to current sensing bay-o-net (expulsion) fuses. Fuse sizing
was charged as follows:
Changed 25 kVA from 8A expulsion / 40 amp CL to IOA expulsion 130A CL
Charged 50 WA from 15A expulsion 180 amp CL tol5A expulsion / 40A CL
Changed 100 kVA from 25A expulsion 1176 amp CL to25A expulsion / BOA CL
Charged 167 kVA from 40A expulsion 1200amp CL to40A expulsion / 125A CL
• Changed 250 kVA from 65A expulsion 1350amp CL to65A expulsion 1125A CL
2
368-120
Opal Dick - 368dash120.pdf Page
TABLE OF CONTENTS
PREVIOUS REVISION DESCRIPTIONS ON FILE .
1 SCOPE
REV. SYM: FF
............ ............. .2
.._....„._......._.._... ............. .._......... ............. ...4
2APPLICABLE DOCUMENTS_...._. ._.._._.._ .._„_.„..„ .._.._._... .._...._.._ ...... _..... ............. .._..„.._.. _.._.._..... ...„4
2.1 ANSI C57.12.00-DISTRIBUTION,POWER, AND REGULATINGTRANSFORMERS, AND SHUNT REACTORS, GENERAL REQUIREMENTS
FOR................. ................ ................ ................ ................ ................ ................ .............. .................. ................ ................ ................ ........4
2.2 ANSI C57.12.25 -PAD MOUNTEII COMPARTMENTAL -TYPE, SINGLE-PHASE, D19MBUTIONTRANSFORMERS WITH SEPARABLE H-V
CONNECTORS, STANDARD REQUIREMENTS FOR ................. ................ ................ ................ ................ ................ ................ .............. ........4
2.3 ANSI C57.12.28-SWITCHGEARANDTRANSFORMERS -PAD-MOUNTEDEQUIPMENT-ENCLOSUREINTEGRITY....................... _...... 4
2.4 ANSI C57.12.70 -TERMINAL MARKINGSAND CONNECTIONSFOR DISTRIBUTION AND POWER TRANSFORMERS .................... ...........4
2.5 ANSI C57.12.50-TERMINOLOGYFOR POWER AND DISTRIBUTIONTRANSFORMERS ................. ................ ................ ................ .......4
2.6 ANSI C57.12.90 - DISTRIBUTION, POWER, AND REGULATINGTRANSFORMERS , AND SHUNT REACTORS, TEST CODE FOR. ................ 4
2.7 IEEE C57.91 - GUIDEFOR LOADINGMINERAGOIL IMNMRSED OVERHEAD AND PAD-MOUNTEDDISTRIBUTIONTRANSFORMERS
RATED 500 KVA AND LESS WITH 65°C OR 550C AVERAGE W INDINGRISE................. ................ ................ ................ ................ ........A
3 REQUIREMENTS......_ ._„_ _._.._.._. ... _....... ._.._...... ........_... .._.._....... ...... .._.. ............... .._....„„..„ ... .......... ...........A
3.1 GENERAL REQUIREMENTS FOR DESIGN ................ ................ ................ ................ ................ ................ ................ ...............4
3.2 SPECIFIC DESIGN REQUIREMENTS .... ................ ................ ................ ................ ................ ................ ............... ................. ......5
4 QUALITY ASSURANCE___.. ............... ......._....... ............. _..... ........ .. ....9
4.1 GENERAL ......... ................ ._............. ................ ................ ................ ................ ............... ................. ................ ................ ..............9
4.2 TEST CONDITIONS ...... ................ ................ ................ ................ ................ ................ ............... ................. ................ ................ .9
4.3 NOT USED ................. ................ ................ ................ ................ ................ ................ .............. .................. ................ ................ ......_9
4.4 TESTS ........... ................ ................ ................ ................ ................ ................ ............... ................. ................ ................ ................ ...9
5PREPARATION FORDEUVERY_.._. ._._._.._. ._.._._..... ....___..__ ._...... .... ......... ..._..__. ....._._.„.._ ._.._.._.._. _..„.._.9
6 DEFINITIONS AND ABBREVIATIONS.....__._._ _..„._..„.. ............ _....___.. _. _.._.. _.._._...
APPENDIX A -TRANSFORMER STOCK NUMBER CODING...„._.. ..... _.._.. .„„_...__ .............
APPENDIX B- DIMENSIONAL DRAWINGS ... _...___......_. ............. „..„..„..... ........ _.. .......
PADDIMENSIONS ._..... _... ... ._..„._.._ ._.._.._.„. ._....__..... ............. .._........ ............. ....
APPENDIX C-APPROVED MANUFACTURERS .............. ...... ._...... _...... ....... _..... _...... ............
TRANSFORMER LOSS EVALUATION -AVERAGE LOSSES.„..... ............. ........... .„..„_......
INDIVIDUAL TRANSFORMER LOSS EVALUATION ......... _... .......... _.... ......... _... .............. ........
._......... _...10
_.._.___.. „........... _ ._...... 11
.............. _..... ...... _12
....... _ ..__...„„.. ............14
.............. _... ....... .. .....15
........ ._--------- .... „.... 16
.. ............. ............. .17
3
368-120
Opal Dick - 368dash120.pdf Page 4
REV. SYM: FF
SPECIFICATION FOR
PAD -MOUNTED COMPARTMENTAL -TYPE
SINGLE-PHASE DISTRIBUTION TRANSFORMERS
WITH SEPARABLE INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS
1 SCOPE
This Specification establishes the minimum electrical requirements and mechari cal features of single phase, 60 HZ,
mineral oil immersed, self -coded, pad -mounted, compar trnental-ty pe distribution transformers rated 250 WA and
smaller, high voltage 13,200 Grd Y/7620 volts, with separabl a insulated load break high voltage connectors. These
transformers are used for step doom purposes from an underground primary cable supply.
This standard generally conforms with ANSI requirements for pad -mounted compartmental-ty pe, self -coded, single-
phase, distribution trans farriers, C57.12.25.
2 APPLICABLE DOCUMENTS
The following documents of the issue shown form a part of this Specification to the extent specified herein. In those
cases when the document is note dated, the latest issue in effect on the date of invitation for bids shall form a part of
this Specification.
2.1 ANSI C57.12.00 - Distribution, power, and regulating transformers, and shunt reactors, general requirements for.
2.2 ANSI C57A2.25 - Pad mounted, compartmental-t ype, single-phase, distribution transformers with separable H-V
connectors, standard requirements for.
2.3 ANSI C57A2.28 - Switchgear and Transformers - Pad -Mounted Equipment-Enclos ire Integrity.
2.4 ANSI C57.12.70 -Terminal markings and connections for distribution and power transformers.
2.5 ANSI C57.12.80 - Terminology for power and distribution transformers.
2.6 ANSI C57.12.9 0 - Distribution, power, and regulating transformers, and shunt reactors, test code for.
2.71EEE C57.91 - Guide for Loading Mineral-Oil-Imme rsed Overhead and Pad -Mounted Distribution Transformers
Rated 500 WA and Less with 650C or 55°C Average Winding Rise.
3 REQUIREMENTS
3.1 GENERAL REQUIREMENTS FOR DESIGN
3.1.1 BASIC DESIGN STANDARDS
Transformers purchased under these Specifications shall be new and, url ess otherwise specified, meet
the requirements of the applicable ANSI Standards and the modifications and additions given in the
subsequent paragraphs. In case of conflict, the requirements of the following documents shall apply in
the priority shorn:
a) This Specification
b) Applicable ANSI Standards
Approved manufacturers are listed in Appendix C.
4
368-120
Opal Dick - 368dash120.pdf Page 5
I;1z3W1Yt W;I
3.1.2 KILOVOLT -AMPERE TEMPERATURE RATINGS
Kilovolt -ampere ratings are continuous and are based on not exceeding either a 65°C average winding
temperature or an 80°C hot spot temperature rise. The temperature rise of the insulating oil shall not
exceed WC When measured dear the top of the tank. The temperature rise is based on an altitude of
3,300 feet. The transformers shall be des igned for overloads based on IEEE C57.91.
3.1.3 GENERAL CONSTRUCTION
3.1.3.1 The pad -mounted compartmental-ly pe transformers shall consist of the transformer tank and high -and -low -
voltage cable terminating compartment constructed in accordance with ANSI C57.12.25 and ANSI C57.12.28.
The terminating compartment and tank shall be assembled as an integral unit tamperproof and weatherproof for
mounting on a pad. There shall be no exposed screws, bolts, or other fastening devices which are externally
removable. The cover shall be welded construction. There shall be no opening through which foreign object
such as sticks, rods, or wires might be inserted to contact live parts. Suitable means for padlocking the
compartment door(s) shall be provided.
3.1.3.2 The high -and low -voltage compartment shall be located side by si de on one side ofthe transformer tank When
facing the compartment, the low -voltage side shall be on the right
3.1.3.3 Construction of the unit shall be such that itcan be lifted, skidded, and slid into place on the mounting pad
without disturbing the entrance cables.
3.1.3.4 An undercoating over the regular finish or an equivalent treatment shall be applied to all surfaces that are in
contact with the pad to minimize corrosion.
3.1.3.5 Minimum dimensions for Type 1 transformers shall be as shown in Figure 1, Appendix B. Minimum dimensions
for Type 2transformers shall be as shown in Figure 2, Appendix B.
3.2 SPECIFIC DESIGN REQUIREMENTS
3.2.1 FUNCTIONAL DESCRIPTION
The transformer shall be a single phase, pad mounted, loop feed -safe break, "dead -from" type for use on
a 13.8 kV grounded "Y" distribution system.
3.2.2 DESIGN AND CONSTRUCTION
3.2.2.1 RATING
The transformer shall berated as follows:
a) High Voltage
13,200 Grd. Y17620 volts
b) Low Voltage
240/120
c) Taps
Two - 2Y2% FC above and below normal
d) Polarity
Additive
e) Capacity, Impedance values, and fusing for transformers in this specification shall conform to Table 1:
5
368-120
Opal Dick- 368dash120.pdf Page 6
REV. SYM: FF
Table 1 - Transformer Capacity, Impedance and Fuse Selection
kVA
I Min.
Max.
Bey-0-Net'
Current Limiting Fuse(s)
'l
I Capacity
j Impedance
I
ImpedanceFuse
I'
I
368-120-130
1 25
1.77%
2.16%
10 Amp
ELSP 3544030M IM (30 A)
4000353C06
368-120-150
5o
1.77%
2.16%
15 Anp
ELSP 3543040M61M (40 A)
4000353COB
36&120-155
50
1.77%
2.16%
15 Anp
ELSP 354304011A1M (40 A)
4000353C08
3611-120-170
100
1.95%
2.38%
25 Mp
ELSP 35430BOM71M (80 A)
4000353CIO
368-120-180
167
2.28%
2.79%
40 Amp
ELSP 3543125M71M (125 A)
3611-120-190
250
5.75%
6.61%
65 Arrp
ELSP 3543125M71M (125 A)
14
*The BAY-0-NET fuse shall be located in the high voltage side of the compartment.
3.2.2.2 INSULATION LEVEL
3.2.2.2.1 The basic impulse insulation level (BIL) of completely assembled high -voltage and low -voltage terminals
shall be 95 kV and 30 kV. respectively.
3.2.2.2.2 Dielectric test levels shall be in accordance with the distribution levels in Section 4 of ANSI C57.12 00.
3.2.2.3 HIGH -VOLTAGE TAPS
A no-load tap changer with external operating handle shall provide two - 21A% full capacity taps above and
below normal. The tap clanger operating handle shall be located within the high -voltage terminal side ofthe
terminal compartment
3.2.2.4 NOT USED
3.2.2.5 BUSHING WELLS AND TERMINALS
3.2.2.5.1 The number, location, and arrangement of bushing wells, terminals and parking stands shall be as
shown in Fig. 1 or Fig. 2 in Appendix B. All low -voltage bushings and high -voltage wells shall be
externally damped and shall have leads of sufid ent length to allow them to be changed without
removing the cover. Welded bushings and wells are expressly prohibited.
3.2.2.5.2 High -voltage terminals shall be universal flowerpot bushing wells in accordance with Figure 3 of
ANSIAEEE 386-1985. Two wells shall be provided and shall be connected in a feed -through
configuration. Loadbreak bushing inserts in accordance with Figure 5 of ANSIAEEE 386-1985 will be
owner furnished.
3.2.2.5.3 Low -voltage line and neutral terminals shall be sized as shown in Table 2 in acmrdance with ANSI
C57.12.25. Bushing arrangement and spacing shall be shown in Fig. 1 or Fig. 2 in Appendix B.
Table 2 - Low Voltage Terminal Sizes
Stock Number
I kVA Capacity
Low voltage Terminal Size
368-120.130
25
518" x 11" UNC-2A copper studs
368-120-150
50
5r8" x 11" UNC-2A copper studs
368-120-155
50
518" x 11" UNC-2A copper studs
368-120170
100
V x 1,V UNC-2A copper studs
368-120-180
167
1" x 14" UNC - 2A copper studs
368-120-190
250
1YV x 12 UNF - 2A copper studs.
3.2.2.5.4 The Im*voltage X2 bushing shall be a fully insulated bushing. A ground pad shall be provided on the
outer surface of the tank and an external removable copper ground strap shall be provided and
connected between the low -voltage X2 bushing and the ground pad.
3.2.2.5.5 The high -voltage neutral shall be securely grounded internally.
6
368-120