Note: Per Bid # 5775 (LP PVC Fittings)
Line Qty/Units Description Extended Price
1 6541-0625 / 300 @ 14.08 ea 4,224.00
4" x 45 x 36" PVC bend
65410625 13A2 BEND, PVC, 4", 45 DEGREES, TYPE DB, 36" RADIUS,
WALL THICKNESS 0.154", WITH CHAMFERED SPIGOT
END (45 DEGREE CHAMFER INSIDE EDGE, 50% OF
WALL THICKNESS) AND 4" MIN. DEPTH BELLED END
(COUPLING NOT ACCEPTABLE), PER ASTM F-512, DB-120
PICOMA, PER DESCRIPTION;
2 6541-0642 / 400 @ 17.99 ea 7,196.00
4" x 90 x 18" PVC bend
65410642 1362 BEND, PVC, SCHEDULE 40, 4", 90 DEGREE,
18" RADIUS, WALL THICKNESS 0.237", WITH
CHAMFERED SPIGOT END (45 DEGREE
CHAMFER INSIDE EDGE, 50% OF WALL
THICKNESS) AND 4" MIN. DEPTH BELLED END,
(COUPLING NOT ACCEPTABLE) PICOMA, PER DESCRIPTION;
Amended PO
Total $11,420.00
This order is slid over $2000 unless signed by City of Fort Collins James B. O'Neill II, CPPO, FNIGP Accounting Department
City of Fort Collins Purchasing, PO Box 580, Fort Collins, CO 80522-0580 PO Box 580
Phone: 970-221-6775 Fax: 970-221-6707 Email: purchasing@fcgov.com Fort Collins, CO 80522-0580
P. 01
TRANSACTION REPORT
Xt
JUN-02-06 FRI
02:44 PM
SEND(M)
DATE START RECEIVER
TX TIME PAGES TYPE
NOTE
M#
DP
JUN-02 02:43 PM WINLECTRIC
1'03" 1 SEND
( M) OK
031
TOTAL
1M 3S PAGES: 1
�
>K
City of Fort Collins
Page Number: 1
City of Fort Collins
Date: 06/02106
Purchase Order Number: 6603399
ueuvery uate: usluilub Buyer: DICK,OPAL
Purchase Order number must appear on Invoices, packing lists, labels, bills of lading, and all correspondence.
Note: Per Bid # 5775 (LP PVC Fittings)
4-1 r
t� �C
Line Qty/Units Description Extended Price
6541-06251 300 cet 14.08 ea
4" x 45 x 36" PVC bend
FG.11f16t9S i9A0 flC�11'1 ovr n" Ax ncrneee r nr.. no -, a•� nnnu m
4,224.00
CITY OF FORT COLLINS
Light and Power Department
P.O. Box 580
Fort Collins, CO 80522
SPECIFICATION NO: 366-200
PLASTIC CONDUIT FOR UNDERGROUND INSTALLATION
APPROVED BY:
Tim M. Sagen
Standards Engineering Manager
DATE: 3/20/87
REVISED: 5/5/99
ITEMS COVERED BY THIS SPECIFICATION
DESCRIPTION
ASTM REFERENCE
SERIAL
STORE'S NO.
2" P.V.C. Conduit
DB 120
02
6535-1081
4" P.V.C. Conduit
DB 120
04
6541-1120
5" P.V.C. Conduit
EB 35
05
6543-1142
Rev. Sym. G
PRFVIOl1S RFVISIC)N IIFRC:RIPTICINR C1N FII F
REVISION DESCRIPTION
CHANGE NOTICE
APPROVED
REVISION D: Add Appendix A, Approved
N/A
S. Coram
Manufacturers
Tim Sagen
3-12-92
REVISION E: Update Appendix A, Remove Condux
N/A
S. Coram
Tim Sagen
3-10-94
REVISION F: Update Appendix A, Change
N/A
O. Dick
Manufacturer (Quail Plastics to
NAPCO
Tim Sagen
314/97
REVISION G: Change 4" conduit to DB 120, wall
N/A
Tim Sagen 5/26/99
thickness 0.154
2
366-200
Rev. Sym. G
TABLE OF CONTENTS
PREVIOUS REVISION DESCRIPTIONS ON FILE................................................................................2
TABLEOF CONTENTS.........................................................................................................................3
1 SCOPE...............................................................................................................................................4
2 APPLICABLE DOCUMENTS...............................................................................................................4
3 REQUIREMENTS...............................................................................................................................4
3.1 GENERAL REQUIREMENTS FOR DESIGN.................................................................................4
3.2 SPECIFIC REQUIREMENTS FOR DESIGN.................................................................................5
4 QUALITY ASSURANCE......................................................................................................................6
4.1 RESPONSIBILITY FOR INSPECTION.........................................................................................6
4.2 REQUIREMENTS AND TEST METHODS....................................................................................6
5 PREPARATION FOR DELIVERY........................................................................................................7
APPENDIX A - APPROVED MANUFACTURERS..................................................................................8
3
366-200
SPECIFICATION FOR PLASTIC CONDUIT
SPEC. #366-200
1 SCOPE
Rev. Sym. G
This Specification establishes the minimum requirements for 2", 4", and 5" plastic conduit to be used with electric
power conductors and cables for aboveground use indoors or outdoors exposed to weather and sunlight at 5,000 feet
altitude, and for underground use by direct burial or encasement in concrete.
2 APPLICABLE DOCUMENTS
This Specification is in accordance with the requirements of ASTM F512, titled "Standard Specification for
Smoothwall Poly(vinyl Chloride) (PVC) Conduit and Fittings for Underground Installation", with exceptions as noted
in the following paragraphs.
3 REQUIREMENTS
3.1 GENERAL REQUIREMENTS FOR DESIGN
All conduit furnished under this Specification shall, unless otherwise specified, comply with ASTM F512. In
case of conflict, the requirements of the following documents shall apply in the priority shown:
This Specification,
ASTM F512.
Other referenced standards.
3.1.1 MATERIAL
Conduit furnished under this Specification shall be made of virgin polyvinyl -chloride (PVC) compound
conforming to ASTM D1784 with the minimum cell classification shown in Table I of this
Specification. Chemical resistance shall be in accordance with ASTM D1784, suffix A or B.
TABLE
Minimum ASTM
ASTM D1784
ASTM
D1784 Cell
Designation
Property and
Value
Test
Classification Cell
Order No.
Unit
Method
Limit No.
1
Base resin
Poly (vinyl
NA
1
homo of mer
chloride
Impact strength
2
(Izod)min ft-Iblin. of
0.65
D256
2
notch
Tensile strength, min
3
psi
5,000
D638
2
Modulus of elasticity
4
in tension, min psi
500,000
D638
>6
Deflection Tempera-
158
D648
4
5
ture under load, min
264 psi deg. F
Flexural strength min
psi
13,000
D790
-
4
366-200
Rev. Sym. G
3.1.2 COMPOUND
Virgin compound is defined as compound, which has not previously been used to make another
product. Reworked material is defined as clean reground or repelletized materials generated from a
manufacturer's own conduit extrusion, and used by the same manufacturer who generates it. Clean
is considered to exclude anything foreign to the specific compound designated by the manufacturer
for use under this Specification. Rework material may be used provided that the conduit or fittings
produced meet all of the requirements of this Specification.
3.1.3 CONDUIT TYPE
Conduit type shall be as specified in Specific Requirements for Design.
3.1.4 WORKMANSHIP
The conduit shall be homogeneous throughout and free from visible cracks, holes, foreign inclusions, or
other injurious defects. The conduit bore shall be smooth and free from blisters, nicks or other
imperfections which could mar conductors or cables.
3.1.5 SUNLIGHT RESISTANCE/COLOR
The conduit shall contain titanium dioxide pigment to produce a white color with a reflective factor of
greater than eighty percent to allow outdoor storage and/or installation at 5,000 feet altitude for an
indefinite period without deterioration.
3.1.6 LENGTH
Conduit shall be in lengths of twenty feet overall including integral bell. Tolerance of length shall be t
one inch (t 25 mm).
3.2 SPECIFIC REQUIREMENTS FOR DESIGN
3.2.1 CONDUIT DIMENSIONS AND TOLERANCES
Dimensions, tolerances and pipe stiffness shall be in accordance with Table II of this Specification.
Wall thicknesses shown in Table II are based on a minimum modulus of 500,000 psi.
TABLE II
Serial
Number
Nominal Size
in.
ASTM
Type
Wall Thickness
Min. In.
Average Outside
Dia. Inches
Out -of -Round
366-200-02
2
DB 120
0.077
2.375 t .006
0.038
366-200-04
4
DB 120
0.154
4.497 t.006
0.082
366-200-05
5
EB 35
0.126
5.563 t .010
0.082
Shaded items deviate trom AS I M F512
5
366-200
Rev. Sym. G
3.2.2 BELLED ENDS
Each length of conduit shall have an integral belled end. Glued couplings are specifically prohibited.
Belled end dimensions shall be based on the clearance fit system defined in Table 2 of ASTM F512
except socket depth and out -of -round requirements shall be in accordance with Table III of this
Specification. Belled ends shall be centered on the longitudinal axis to provide a visible shoulder
around the entire circumference of the conduit. Both ends of each length of the conduit shall be
perpendicular to the longitudinal axis of the conduit, i.e., both ends shall be square cut.
TABLE III
Nominal
Size
Inches
Socket Entrance
Inside Dia.
Inches
Socket Bottom
Inside Dia.
Inches
Socket Depth
Inches
Min. Max.
Out -of -Round
Tolerance
Inches
2
2.400 t 0.006
2.381 t 0.006
2,250 2.500
0,038'
4
4.544 t 0.009
4.509 t 0.009
4.000 4.250
0,082'
5
5.614 t 0.010
5.573 t 0.010
5.000 5.250
0.082
'Shaded items deviate from ASTM F512
4 QUALITY ASSURANCE
4.1 RESPONSIBILITY FOR INSPECTION
Unless otherwise specified, the vendor is responsible for the performance of all tests and inspection
requirements specified herein. Except as otherwise specified, the vendor may utilize his own facilities or any
commercial laboratory acceptable to the City of Fort Collins. The City reserves the right to perform or witness
any of the tests and inspections set forth in this Specification, where such inspections are deemed necessary.
If the City, upon receipt of the conduit, deems it necessary to have an independent laboratory perform tests
and inspections set forth in this Specification, the manufacturer shall be responsible for all fees incurred in
testing if any requirement of the specifications is not met and/or test results for that lot or shipment are not
consistent with the manufacturer's certified test results.
4.2 REQUIREMENTS AND TEST METHODS
4.2.1 COMPOUND TESTS
All the tests required by ASTM D1784, except the chemical resistance test, shall be made on a
compound sample from each new lot or batch. The average value for all the tests made on each batch
or lot shall comply with the requirements of paragraph 3.1.1 of this Specification and shall be reported in
the certified test report. The chemical resistance test shall be performed annually or when compound
suppliers are changed and test results shall be included in the certified test report.
4.2.2 SUNLIGHT RESISTANCE TESTS
Evidence that the compound being used has been qualified in accordance with all tests required by
Paragraph 17 of UL 651 shall be included in the certified test report.
4.2.3 PERFORMANCE TESTS
Conduit furnished under this Specification shall pass all tests required by and performed in accordance
with ASTM F512 except 2-inch conduit shall have a minimum impact resistance of 40-foot-pounds at
32°F (0°C).
6
366-200
Rev. Sym. G
4.2.4 EXTRUSION QUALITY TEST
The extrusion quality shall be determined by immersion in anhydrous acetone in accordance with ASTM
D2152. Finished duct shall not flake or disintegrate when subjected to this test.
4.2.5 CERTIFICATION
The manufacturer shall furnish to the purchaser certified copies of the results of the tests on each lot or
shipment and size of conduit ordered, prior to payment. The certified test report shall state the lot or
control number and manufacturer of compound used and shall give specific test values for compound
tests, stiffness test, and tests having other than a simple Pass/Fail result. Any conduit tested by the City
that does not yield results consistent with the certified test reports for that lot or shipment will be
sufficient reason for rejection of the entire lot or shipment. City of Fort Collins purchase order number
shall be noted on the first page of each report. Copies shall be sent to the Design section of Fort Collins
Light & Power. Unsigned copies are not acceptable even if accompanied by a signed cover letter.
5 PREPARATION FOR DELIVERY
Conduit shall be bundled by individual size into units suitable for shipping and stacked storage
To protect the bells from deformation caused by pressure from adjacent conduits, each bundle shall be assembled
such that bells are all at the same end of the bundle with the bell ends of alternating layers recessed at least the full
length of the bells in adjacent layers. The bundles shall be secured using two steel bands with 2" x 4" minimum
wooden boards under the bands, sets of bands and boards to be spaced appropriately along the length of the bundle
forming adequate crate frames to provide the vertical stacking, frame to frame, to minimize stacked storage
deformation with the stack height up to ten feet. Direct contact between the steel bands and the conduit anywhere on
the perimeter of the bundle is expressly prohibited.
Bundles shall be shipped on an open bed truck.
7
366-200
Rev. Sym. G
APPENDIX A
Conduit purchased under this Specification shall be of the manufacturers shown below. Manufacturers not listed
below may submit written proposals demonstrating compliance with these Specifications for consideration of addition