HomeMy WebLinkAbout113669 K V A SUPPLY - PURCHASE ORDER - 5507732Mkh
Ali
City of Fort Collins City of Fort Collins
Page Number: 1
Date: 11 /18/05
Purchase Order Number: 5507732
tsuyer: DICK,OPAL
Purchase Order number must appear on invoices, packing lists, labels, bills of lading, and all correspondence.
Vote:
Line
City
UOM Description
Unit Price
Extended Price
1
1500
EA 6764-8363
28.0000
42,000.00
200A, Loadbreak Elbow
08A3 TERMINAL, ELBOW, LOADBREAK, 200A CONTINUOUS,
200A SINGLE PHASE AND 3-PHASE LOADMAKE / LOADBREAK, 15KV
PER SPEC 367-200, REV S;
DELIVERY: STOCK - 2 WEEKS
Total
$42,000.00
City of Fort CiCilijs Director of Purchasing and Risk Management City of Fort Collins
This order is valid over $2000 unless signed by James B. O'Neill II, CPPO, FNIGP Accounting Department
City of Fort Collins Purchasing, PO Box 580, Fort Collins, CO 80522-0580 PO Box 580
Phone: 970.221-6775 Fax: 970-221-6707 Email: info@ci.fort-collins.co.us Fort Collins, CO 80522-0580
THE CITY OF FORT COLLINS - UTILITIES
Light and Power Department
P.O. Box 580
Fort Collins, CO 80521
SPECIFICATION NO: 367-200
SEPARABLE INSULATED LOADBREAK CONNECTORS
APPROVED BY:
Tim M.Sagen
Standards Engineering Manager
ORIGNATED: 6/23172
REVISION DATE: 6/14/02
REV: S
REV. SYM: S
REVISION DESCRIPTIONS
REVISION DESCRIPTION (previous descriptions on file)
CHANGE
APPROVED
NOTICE
Rev. P:
Sagen/Coram -- 2/8/91
Appendix A — added CS754 to indicate customer
N/A
special
Rev. Q:
Sagen/Coram — 6/12/92
. Appendix A — added Blackburn as approved
N/A
Rev. R:
Sagen/Coram — 2f7/94
Appendix A — removed Blackburn (purchased by
N/A
Elastimold
Rev. S:
N/A
Sagen/Bray -- 6/14/02
. Reformatted (electronic)
2
367-200
0
REV. SYM: S
TABLE OF CONTENTS
REVISIONDESCRIPTIONS.............................................................................................................................................2
TABLEOF CONTENTS....................................................................................................................................................3
1. SCOPE..............................................................................................................................................................................4
2. APPLICABLE DOCUMENTS.......................................................................................................................................4
3. DEFINITIONS.................................................................................................................................................................4
4. SERVICE CONDITIONS...............................................................................................................................................4
5. RATINGS AND CHARACTERISTICS........................................................................................................................4
5.1 VOLTAGE RATING.........................................................................................................................................................4
5.2 CONTINUOUS CURRENT RATING................................................................................................................................... 4
6. CONSTRUCTION...........................................................................................................................................................4
6.1 INSULATION.................................................................................................................................................................. 4
6.2 SHIELDING....................................................................................................................................................................4
6.3 TEST POINT.................................................................................................................................................................. 4
6.4 COMPRESSION CONNECTOR..........................................................................................................................................4
6.5 OPERATING MEANS...................................................................................................................................................... 5
6.6 INSULATION DIAMETER RANGE.................................................................................................................................... 5
7. QUALITY ASSURANCE / TESTING........................................................................................................................... 5
7.1 GENERAL......................................................................................................................................................................5
7.2 PRODUCTION (FUNCTIONAL) TESTS............................................................................................................................. 5
8. SUPPLIER REQUIREMENTS......................................................................................................................................5
8.1 GENERAL......................................................................................................................................................................5
8.2 PACKAGING.................................................................................................................................................................. 6
APPENDIXA.......................................................................................................................................................................7
3
367-200
REV. SYM: S
SPECIFICATION FOR
SEPARABLE INSULATED LOADBREAK CONNECTORS
1.SCOPE
This specification establishes the minimum requirements for separable insulated loadbreak connectors
rated 200 amperes, 8.3kV phase -to -ground / 14.4kV phase -to -phase @ 60 HZ.
2. APPLICABLE DOCUMENTS
Connectors purchased under this specification shall, unless otherwise specified, conform to IEEE Std.
386-1995, or latest revised edition, in its entirety. In the case of any conflict between City of Fort
Collins requirements (this specification) and IEEE Std. 386-1995, Fort Collins requirements shall
take precedence.
3. DEFINITIONS
IEEE Std. 386 definitions apply.
4. SERVICE CONDITIONS
No unusual service conditions apply.
5. RATINGS AND CHARACTERISTICS
5.1 Voltage Rating
8.3/14.4 kV rms phase-to-ground/phase-to-phase. The load -break connector shall be capable of
switching 14.4 kV across the open contacts.
5.2 Continuous Current Rating
200 amps rms (switching, fault -closure & short -time current ratings applicable to load -break
connectors having a 200 amp continuous current rating shall apply).
6. CONSTRUCTION
6.1 Insulation
Only peroxide cured EPDM shall be permitted.
6.2 Shielding
The connectors shall have a 1/8" minimum thick, molded peroxide cured semi -conductive exterior
shield meeting the requirements of IEEE Std. 592-1990 (or latest revision).
6.3 Test Point
All load -break elbows shall be furnished with a capacitively coupled voltage test point. In addition to
the requirements of IEEE Std. 386-1995, the test point shall be accurate within ±20% for an applied
test voltage range of 7kV — 11 kV when tested in accordance with paragraph 7.2 of this specification.
6.4 Compression Connector
The compression connector shall be suitable for use with 1/0 AWG, 19 strand, class "B" strand or
compressed strand, EC grade aluminum conductor. Connectors shall meet the requirements of EEI-
TDJ-162 for class "A" connectors, and shall have an aluminum compression barrel friction welded to
a threaded copper electrode connector. Each compression barrel shall be filled with an oxide -
inhibiting compound.
367-200
REV. SYM: S
6.5 Operating Means
An operating eye suitable for use with a hot stick shall be provided and the connector shall conform to
the operating force requirements specified in IEEE Std. 386-1995 for connectors without hold-down
bails.
6.6 Insulation Diameter Range
The connector shall be suitable for use over a cable insulation diameter range of 0.665 to 0.905
inches.
QUALITY ASSURANCE / TESTING
7.1 General
7.1.1 Responsibility for Inspection
Unless otherwise specified, the vendor is responsible for the performance of all inspection
requirements as specified herein. Except as otherwise specified, the vendor may utilize his own
facilities or any commercial laboratory acceptable to the City of Fort Collins. The City reserves the
right to perform or witness any of the inspections set forth in this specification where such inspections
are deemed necessary.
7.2 Production (Functional) Tests
In addition to the production tests required by IEEE 386 for 100% of production units, a 20% sampling
of all components having capacitive test points are required to be tested in accordance with the
following:
• Test points shall be tested for a maximum allowable variation between components of ±20% for
an applied test voltage range of 7kV —11 kV
• Test point measurements shall be taken with a Ross Hke (model VM 25-A) AC voltmeter fitted
with a VMP25-A high voltage probe (calibrated to 1.6-1.8 PF to 8-10 PF)
• The 7kV to 11kV test voltage shall be introduced to sample elbows via 110 AWG, class B stranded,
shielded cable with 220 mil thick XLP insulation (or a City of Fort Collins approved test mandrel).
• Results for this test shall accompany each shipment and shall, as a minimum, document those
values taken @ 7kV and 11 kV
8. SUPPLIER REQUIREMENTS
8.1 General
8.1.1 Approved Manufacturers
Product purchased under this specification shall be of the manufacturers listed in Appendix A.
Manufacturers not listed may submit written proposals demonstrating compliance with these
specifications for consideration of addition to the accepted manufacturer list prior to the next
request for bids. Acceptability of the listed manufacturer's will not be determined solely by
inclusion in this list. Listed manufacturers must satisfy all requirements of this specification to be
acceptable.
8.1.2 Approved Distributors
To avoid conflicts regarding warranty service, any distributor bidding must be an authorized
distributor appointed by an approved manufacturer to serve the Fort Collins area.
5
367-200
REV. SYM: S
8.2 Packaging
Packaging and marking of articles under this drawing shall be in accordance with the purchase order
and the following special requirements:
8.2.1 Each kit shall be individually packaged
8.2.2 Instruction sheets shall be included in each individual kit
8.2.3 Each kit shall contain all components required to produce a complete, functional assembly. This
may included but not be limited to connectors, arc probes, probe wrenches, silicone cable
lubricant, and cable cut back templates.
367-200
REV. SYM: S
APPENDIX A
Approved Manufacturers
Connectors purchased under this specification shall be of the make shown below. Manufacturers not listed below
may submit written proposals demonstrating compliance with these specifications for consideration of addition to
the approved manufacturer list prior to the next request for bids. Inclusion on the list below does necessarily
guarantee product approval. All products provided by an approved manufacturer must still fully satisfy all
requirements of this specification to be acceptable.
Manufacturer Catalog Number
Elastimold 166LR-B-5240
s67-200