City of Fort Collins
Page Number: 1
City of Fort Collins
Date: 09/26/05
Purchase Order Number: 5506506
Delivery Date: 12/20/05 Buyer: DICK,OPAL
Purchase Order number must appear on invoices, packing lists, labels, bills of lading, and all correspondence.
Note: vendor per drawing #368-110, revA
Line Qty UOM Description Unit Price Extended Price
1 4 EA T1100161; TRANSFORMER 3,332.0000 13,328.00
75kV single phase underground
T1100161 YARD TRANSFORMER, 75 kVA SUBMERSIBLE, SINGLE
PHASE WITH ONE COVER MOUNTED SEPARABLE
INSULATED LOAD BREAK HIGH VOLTAGE BUSHING
WELL, THREE COVER MOUNTED STUD SECONDARY
BUSHINGS, SUBMERSIBLE BAYONET FUSE. HIGH
VOLTAGE RATING: 13200 GRDY/7620, LOW VOLTAGE
RATING: 240/120. PER DRAWING #368-110-161, REVISION A
WITH TANK DIMENSIONS APPROVED BY KRAIG BADER
TO WAYNE SHARP ON 9-21-05
DELIVERY: 10-12 WEEKS
MFR - ABB
NO LOAD LOSS - 125
FULL LOAD LOSS - 550
TOTAL LOAD LOSS - 675
IMPEDANCE 2.05%
_ ^ n Total $13,328.00
City of Fort Ci6ififis Director of Purchasing and Risk Management City of Fort Collins
This order is valid over $2000 unless signed by James B. O'Neill II, CPPO, FNIGP Accounting Department
City of Fort Collins Purchasing, PO Box 580, Fort Collins, CO 80522-0580 PO Box 580
Phone:970-221-6775 Fax: 970.221-6707 Email: info@ci.fort-collins.co.us Fort Collins, CO 80522-0580
THE CITY OF FORT COLLINS
UTILITIES
Light and Power Department
P.O. Box 580
Fort Collins, CO 80522
SPECIFICATION NO: 368-11 U
TITLE: Single Phase Submersible Cover Mount Transformer
APPROVED BY:
Tim M. Sagen
Standards Engineer Manager
ORIGINATED: June 1999
LAST REVISED: December 15, 2000
REVISION DESCRIPTIONS
REVISION DESCRIPTION APPROVED
REVISION A Tim Sagen
Revised tank material in section 6 Bill Bray
12/15/2000
2
368-110
Specification for Single Phase Submersible Cover Mount Transformer
1 SCOPE
This specification and the accompanying drawing (368-110.dwa) establishes the minimum
requirements for an alternate design to City of Fort Collins Light and Power Specification 368-
105 for single phase 60 hertz mineral oil filled self cooled vault type distribution transformers.
The requirements of Specification 368-105 and applicable American National Standard
requirements for distribution transformers shall apply except where specifically altered by this
Specification.
2 PRIMARY
a. 13,200 GRDY/7620, No Taps, Single Voltage
b. Radial feed (1- HV bushing)
c. ESNA long shank wells welded to tank
d. "NO" inserts provided
3SECONDARY
a. 240/120 volt, 3-wire (3-bushing LV pattern) (exception to 368-105 Table I, cannot be
banked for 3phase 208Y/120 service)
b. X2 internally grounded (clarification to 368-105 paragraph 3.2.4.2)
c. Welded Central Moloney bushings with external epoxy (dia. <1.38 see 368-105 Fig. 1)
d. 5/8" threaded copper stud termination
e. Additive polarity
4 ELECTRICAL REQUIREMENTS
a. Frequency: 60 Hertz
a. KVA: 25, 50, or 75 as requested
b. BIL: 95 kV
c. Impedance Limits:
kVA
Impedance %Z
25
1.77 < %Z < 2.16
50
1.77<%Z<2.16
75
1.86 < %Z < 2.27
3
368-110
5 FUSING (EXCEPTION TO 368-105 TABLE 1)
a. Submersible type bayonet with overload dual sensing fuse element as shown below.
b. RTE ELSP 8.3 kV under oil partial range current limiting fuse as shown below.
c. "NO" low voltage under oil breaker
kVA
RTE Bayonet
RTE ELSP
25
358C05
40 amp 354304OM61 M
50
358C08
80 amp 354308OM51 M
75
358C10
125 amp 3543125M61M
6 TANK DESIGN
a. Tank material .105" (12 gauge) stainless steel (Tank - 400CB SST; Cover - 304L SST)
b. Tomko 1720K-1 pressure relief device located on cover
c. Tank drain 1.00" NPT flush coupling with brass pipe plug
d. (2) 1.00" NPT fill couplings located on cover with brass pipe plugs
e. (1) Tomko LG35 sight gauge/oil level coupling
f. (2) %" - 13 SST ground pads centered on tank below primary bushing 7" from top and 7"
from base respectively
g. (1) %2" - 13 SST ground pad on top near primary bushing
h. (1) SST loadbreak type parking stand
i. Cover to be welded to tank
j. Welded base runners
k. (2) Lifting hooks opposite each other welded on the front and backside of the tank near the
top
7 MARKINGS
a. X1, X2 & X3 SST identification tags with black lettering
b. "X2 Int Gnd" stenciled in black on cover
c. Bayonet warning decals located near bayonet fuse
d. SST nameplate in accordance with paragraph 3.2.5.6
e. Temporary serial/shipping card attached to tank lift -eye
8 MISC. DESIGN ISSUES
a. Cooling 650C AWR, average ambient 300C (55°C AWR and 400C ambient)
b. Final color ASA 70 Gray
c. All exposed parts shall be constructed of corrosion resistant material; e.g., SST, brass, or
plastic
d. Each unit shall be shipped on a two-way pallet with a minimum opening width of 34"
4
368-110