HomeMy WebLinkAbout103811 GLANZ ELECTRICAL CONTRACTING - CONTRACT - BID - 5874 ELECTRICAL FOR ALTERNATE FUEL BUILDING TRANSFSERVICES AGREEMENT
THIS AGREEMENT made and entered into this 12th day of August in the year 2004 and
between THE CITY OF FORT COLLINS, COLORADO, a Municipal Corporation, hereinafter
referred to as the "City" and Glanz Electrical Contracting, Inc., hereinafter referred to as
"Service Provider".
WITNESSETH:
In consideration of the mutual covenants and obligations herein expressed, it is agreed
by and between the parties hereto as follows:
1. Scope of Services. The Service Provider agrees to provide services in
accordance with the scope of services attached hereto as Exhibit "A", consisting of one (1)
page, and incorporated herein by this reference.
2. Time of Commencement and Completion of Services The services to be
performed pursuant to this Agreement shall be initiated within five (5) days following execution
of this Agreement. Services shall be completed no later than November 15, 2004. Time is of
the essence. Any extensions of the time limit set forth above must be agreed upon in a writing
signed by the parties.
3. Delay. If either party is prevented in whole or in part from performing its
obligations by unforeseeable causes beyond its reasonable control and without its fault or
negligence, then the party so prevented shall be excused from whatever performance is
prevented by such cause. To the extent that the performance is actually prevented, the Service
Provider must provide written notice to the City of such condition within fifteen (15) days from
the onset of such condition.
4. Early Termination by City/Notice. Notwithstanding the time periods contained
herein, the City may terminate this Agreement at any time without cause by providing written
notice of termination to the Service Provider. Such notice shall be delivered at least fifteen (15)
days prior to the termination date contained in said notice unless otherwise agreed in writing by
SA 0612004
1
SECTION 00615
PAYMENT BOND
Bond No.
KNOW ALL MEN BY THESE PRESENTS: that
(Firm)
(Address)
(an Individual), (a Partnership), (a Corporation), hereinafter referred to as the "Principal' and
(Firm)
(Address)
hereinafter referred to as "the Surety", are held and firmly bound unto the City of Fort Collins.
300 Laporte Ave., Fort Collins, Colorado 80522 a (Municipal Corporation) hereinafter referred to
as "the OWNER", in the penal sum of in lawful money of the United
States, for the payment of which sum well and truly to be made, we bind ourselves, successors
and assigns, jointly and severally, firmly by these presents.
THE CONDITIONS OF THIS OBLIGATION are such that whereas the Principal entered into a
certain Agreement with the OWNER, dated the day of , 20_, a copy of which is
hereto attached and made a part hereof for the performance of The City of Fort Collins project,
NOW, THEREFORE, if the Principal shall make payment to all persons, firms, subcontractors,
and corporations furnishing materials for or performing labor in the prosecution of the Work
provided for in such Agreement and any authorized extension or modification thereof, including
all amounts due for materials, lubricants, repairs on machinery, equipment and tools,
consumed, rented or used in connection with the construction of such Work, and all insurance
premiums on said Work, and for all labor, performed in such Work whether by subcontractor or
otherwise, then this obligation shall be void; otherwise to remain in full force and effect.
SA O6/2004
5
PROVIDED, FURTHER, that the said Surety, for value received, hereby stipulates and agrees
that no change, extension of time, alteration or addition to the terms of the Agreement or to the
Work to be performed thereunder or the Specifications accompanying the same shall in any way
affect its obligation on this bond; and it does hereby waive notice of any such change, extension
of time, alteration or addition to the terms of the Agreement or to the Work or to the
Specifications.
PROVIDED, FURTHER, that no final settlement between the OWNER and the CONTRACTOR
shall abridge the right of any beneficiary hereunder, whose claim may be unsatisfied.
PROVIDED, FURTHER, that the Surety Company must be authorized to transact business in
the State of Colorado and be acceptable to the OWNER.
IN WITNESS WHEREOF, this instrument is executed in three (3) counterparts, each one of
which shall be deemed an original, this _ day of 20_
IN PRESENCE OF: Principal
(Corporate Seal)
IN PRESENCE OF:
IN PRESENCE OF:
0
(Title)
(Address)
Other Partners
Surety
0-11
By:
(Surety Seal) (Address)
NOTE: Date of Bond must not be prior to date of Agreement.
If CONTRACTOR is Partnership, all partners should
execute Bond.
sn 06/2004
6
OD%
Western Surety Company
PERFORMANCE BOND
Bond Number: 69765785
KNOW ALL PERSONS BY THESE PRESENTS, That we Glanz Electrical Contracting, Inc.
of
1713 Lincoln Ave., Ste. A-1, Fort Collins, CO 80524 ,hereinafter
referred to as the Principal, and Western Surety Company
as Surety, are held and firmly bound unto City of Fort Collins
of 300 Laporte Ave., P. O. Box 580, Fort Collins, CO 80522 ,hereinafter
referred to as the Obligee, In the Sum of Thirty -Seven Thousand Four Hundred Fifty and 00/100
Dollars ($ 37, 450.00 ), for the payment of which we bind ourselves, our legal representatives, successors
and assigns, jointly and severally, firmly by these presents.
WHEREAS, Principal has entered into a contract with Obligee, dated the 12th day of August ,
2004 for Electrical Service For A Building at Transfort
NOW, THEREFORE, if the Principal shall faithfully perform such contract or shall indemnify and save harmless
the Obligee from all cost and damage by reason of Principal's failure so to do, then this obligation shall be null and
void; otherwise it shall remain in full force and effect.
ANY PROCEEDING, legal or equitable, under this Bond may be instituted in any court of competent jurisdiction in
the location in which the work or part of the work is located and shall be instituted within two years after Contractor
Default or within two years after the Contractor ceased working or within two years after the Surety refuses or fails
to perform its obligations under this Bond, whichever occurs first. If the provisions of this Paragraph are void or
prohibited by law, the minimum period of limitation available to sureties as a defense in the jurisdiction of the suit
shall be applicable.
NO RIGHT OF ACTION shall accrue on this Bond to or for the use of any person or corporation other than the
Obligee named herein or the heirs, executors, administrators or successors of the Obligee.
SIGNED, SEALED AND DATED this 24th day of August 1 2004 .
b�
r i l
k
Forth F4597
Glanz Electrical Contracting, Inc.
(Principal)
By res; d/e_,�eal)
?Ni�lh 4 S IT, C7lQ ry Z
Western Surety Company
(Surety)
By �, M. Bent, Asn't. Sec. (Seal)
Attorney -in -Fact
%1`�y
Western Surety Company
PAYMENT BOND
Bond Number: 69765785
KNOW ALL PERSONS BY THESE PRESENTS, That we Glanz Electrical Contracting Inc
1713 Lincoln Ave., Ste. A-1, Fort Collins, CO 80524
referred to as the Principal, and
Western Suret
as Surety, are held and firmly bound unto City of Fort Collins
of
, hereinafter
of 300 Laporte Ave. F. O. Box 580 Fort Collins CO 80522 ,hereinafter
referred to as the Obligee, in the Sum of Thirty -Seven Thousand Four Hundred Fifty and 00/100
Dollars ($ 37, 450. 00 ), for the payment of which we bind ourselves, our legal representatives, successors
and assigns, jointly and severally, firmly by these presents.
WHEREAS, Principal has entered into a contract with Obligee, dated 12th day of August
2004 ,for Electrical Service For A Building at Transfort
copy of which contract is by reference made a part hereof.
NOW, THEREFORE, if Principal shall, in accordance with applicable Statutes, promptly make payment to all
persons supplying labor and material in the prosecution of the work provided for in said contract, and any and all
duly authorized modifications of said contract that may hereafter be made, notice of which modifications to Surety
being waived, then this obligation to be void; otherwise to remain in full force and effect.
No suit or action shall be commenced hereunder
(a) After the expiration of one (1) year following the date on which Principal ceased work on said contract it
being understood, however, that if any limitation embodied in this bond is prohibited by any law controlling
the construction hereof such limitation shall be deemed to be amended so as to be equal to the minimum
period of limitation permitted by such law.
(b) Other than in a state court of competent jurisdiction in and for the county or other political subdivision of
the state in which the project, or any part thereof, is situated, or in the United States District Court for the
district in which the project, or any part thereof, is situated, and not elsewhere.
The amount of this bond shall be reduced by and to the extent of any payment or payments made in good faith
hereunder.
SIGNED, SEALED AND DATED this 24th day of August 2004
Glanz Electrical Contracting Inc
�(Principal)
'� � ��+^P' f (Seal)
W�; �By ��5� ��
,�..'$ _ CY7kCY laS j/ . (7'/qg�
Western Surety Company
(Surety)
l�
„ BY �Z.T� X Bent, M% Sec. _ (Seal)
e.
Attorney -in -Fact
;r
Western Surety Company
POWER OF ATTORNEY
KNOW ALL MEN BY THESE PRESENTS:
That WESTERN SURETY COMPANY, a corporation organized and existing under the laws of the State of South Dakota,
and authorized and licensed to do business in the States of Alabama, Alaska, Arizona, Arkansas, California, Colorado,
Connecticut, Delaware, District of Columbia, Florida, Georgia, Hawaii, Idaho, Illinois, Indiana, Iowa, Kansas, Kentucky,
Louisiana, Maine, Maryland, Massachusetts, Michigan, Minnesota, Mississippi, Missouri, Montana, Nebraska, Nevada, New
Hampshire, New Jersey, New Mexico, New York, North Carolina, North Dakota, Ohio, Oklahoma, Oregon, Pennsylvania,
Rhode Island, South Carolina, South Dakota, Tennessee, Texas, Utah, Vermont, Virginia, Washington, West Virginia,
Wisconsin, Wyoming, and the United States of America, does hereby make, constitute and appoint
M. Bent of Sioux Falls
State of South Dakota its regularly elected Assistant Secretary
as Attomey-in-Fact, with full power and authority hereby conferred upon him to sign, execute, acknowledge and deliver for
and on its behalf as Surety and as its act and deed, all of the following classes of documents to -wit:
Indemnity, Surety and Undertakings that may be desired by contract, or may be given in any action or proceeding in any court of law or
equity, polic4et�j mnifying employers against loss or damage caused by the misconduct of their employees; official, bail, and surety and
fidelity$ in all cases where indemnity may be lawfully given; and with full power and authority to execute consents and
waiN Wit 0 .F, ° ®or extend any bond or document executed for this Company, and to compromise and settle any and all claims or
de _ 'm*q IV; ist _. inst said Company.
jpgMrn Surety'40rb" further certifies that the following is a true and exact copy of Section 7 of the by-laws of Western Surety
cam"ny duly adopted aticlTij�[(er in force, to -wit:
oonsb
p wiolicies, undertakings, Powers of Attorney, or other obligations of the corporation shall be executed in the
co ® e"of• � pany by the President, Secretary, any Assistant Secretary, Treasurer, or any Vice President, or by such other
officers% 0 'bin
may authorize. The President, any Vice President, Secretary, any Assistant Secretary, or the Treasurer
may appoin itftbtHlys-in-Fact or agents who shall have authority to issue bonds, policies, or undertakings in the name of the Company. The
corporate seal is not necessary for the validity of any bonds, policies, undertakings, Powers of Attorney or other obligations of the corporation.
The signature of any such officer and the corporate seal may be printed by facsimile.
In Witness Whereof, the said WESTERN SURETY COMPANY has caused these presents to be executed by its
Senior Vice President with the corporate seal affixed this 24th day of August
2004
ATTEST
Assistant Secretary
STATE OF SOUTH DAKOTA
ss
COUNTY OF MINN[
WEST N SURET OMPANY
By
Paul T. Bruflat, Anior Vice President
On this 24th day of August 2004 before me, a Notary Public, personally appeared
Paul T. Bruflat and A. Vietor
who, being by me duly sworn, acknowledged that they signed the above Power of Attorney as Senior Vice President
and Assistant Secretary, respectively, of the said WESTERN SURETY COMPANY, and acknowledged said instrument to be
the voluntary act and deed of said Corporation.
}44444444444444444444444b }
a D. KRELL s'
s t3Ai NOTARY PUBLIC SE�AI s
s
�rSOUTH DAKOTA y�o 8
}bb 444444444444444444444 }
My Commission Expires November 30, 2006 Notary Public
Form 672-4-2002
EXHIBIT "D"
ALTERNATE FUELS STATION
SECT.
NO. SECTION TITLE
DIVISION 16 - ELECTRICAL
16050 BASIC ELECTRICAL MATERIALS AND METHODS
16060 GROUNDING AND BONDING
16130 RACEWAYS AND BOXES
16140 WIRING DEVICES
16145 NON -REVERSING CONTACTORS
16410 ENCLOSED SWITCHES
16442 PANELBOARDS
16461 DRY -TYPE TRANSFORMERS (1000 V AND LESS)
16491 FUSES
16511 LIGHTING
SA 06/2004
ALTERNATE FUELS STATION
SECTION 16050 - BASIC ELECTRICAL MATERIALS AND METHODS
PART] -GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1.
Building wire and connectors.
2.
Supporting devices for electrical components.
3.
Electrical identification.
4.
Electricity -metering components.
5.
Concrete equipment bases.
6.
Electrical demolition.
7.
Cutting and patching for electrical construction.
8.
Touchup painting.
1.3 SUBMITTALS
A. Product Data: For electricity -metering equipment.
1.4 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
B. Comply with NFPA 70.
1.5 COORDINATION
A. Coordinate chases, slots, inserts, sleeves, and openings with general construction work and
arrange in structure during progress of construction to facilitate the electrical installations that
follow.
1. Set inserts and sleeves in poured -in -place concrete, masonry work, and other structural
components as they are constructed.
B. Sequence, coordinate, and integrate installing electrical materials and equipment for efficient
flow of the Work.
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 1
SA oerzco4
8
ALTERNATE FUELS STATION
C. Coordinate electrical service connections to components furnished by utility companies.
1. Coordinate installation and connection of exterior underground and services, including
provision for electricity -metering components.
2. Comply with requirements of authorities having jurisdiction and of utility company
providing electrical power and other services.
D. Where electrical identification devices are applied to field -finished surfaces, coordinate
installation of identification devices with completion of finished surface. '
PART 2-PRODUCTS
2.1 CONDUCTORS
A. Conductors, No. 10 AWG and Smaller: Solid or stranded copper.
B. Conductors, Larger Than No. 10 AWG: Stranded copper.
C. Insulation: Thermoplastic, rated at 75 deg C minimum.
D. Wire Connectors and Splices: Units of size, ampacity rating, material, type, and class suitable
for service indicated.
2.2 SUPPORTING DEVICES
A. Material: Cold -formed steel, with corrosion -resistant coating acceptable to authorities having
jurisdiction.
B. Metal Items for Use Outdoors or in Damp Locations: Hot -dip galvanized steel.
C. Slotted -Steel Channel Supports: Flange edges turned toward web, and 9/16-inch- (14-mm-)
diameter slotted holes at a maximum of 2 inches (50 mm) o.c., in webs.
D. Pipe Sleeves: ASTM A 53, Type E, Grade A, Schedule 40, galvanized steel, plain ends.
E. Expansion Anchors: Carbon -steel wedge or sleeve type.
F. Toggle Bolts: All -steel springhead type.
G. Powder -Driven Threaded Studs: Heat -treated steel.
2.3 ELECTRICAL IDENTIFICATION
A. Identification Devices: A single type of identification product for each application category.
Use colors prescribed by ANSI A13.1, NFPA 70, and these Specifications.
B. Colored Adhesive Marking Tape for Raceways, Wires, and Cables: Self-adhesive vinyl tape,
not less than 1 inch wide by 3 mils thick (25 min wide by 0.08 min thick).
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 2
SA 0612004
9
ALTERNATE FUELS STATION
C. Underground Warning Tape: Permanent, bright -colored, continuous -printed, vinyl tape with
the following features:
1. Not less than 6 inches wide by 4 mils thick (150 mm wide by 0.102 mm thick).
2. Compounded for permanent direct -burial service.
3. Embedded continuous metallic strip or core.
4. Printed legend that indicates type of underground line.
D. Tape Markers for Wire: Vinyl or vinyl -cloth, self-adhesive, wraparound type with preprinted
numbers and letters.
E. Color -Coding Cable Ties: Type 6/6 nylon, self-locking type. Colors to suit coding scheme.
F. Engraved -Plastic Labels, Signs, and Instruction Plates: Engraving stock, melamine plastic
laminate punched or drilled for mechanical fasteners 1/16-inch (1.6-mm) minimum thickness
for signs up to 20 sq. in. (129 sq. cm) and 1/8-inch (3.2-mm) minimum thickness for larger
sizes. Engraved legend in black letters on white background.
G. Exterior Warning and Caution Signs: Comply with 29 CFR, Chapter XVII, Part 1910.145.
Weather -resistant, nonfading, preprinted, cellulose -acetate butyrate signs with 0.0396-inch (I-
mm), galvanized -steel backing, with colors, legend, and size appropriate to the application. 1/4-
inch (6-mm) grommets in corners for mounting.
H. Fasteners for Nameplates and Signs: Self -tapping, stainless -steel screws or No. 10/32 stainless -
steel machine screws with nuts and flat and lock washers.
2.4 EQUIPMENT FOR UTILITY COMPANY'S ELECTRICITY METERING
A. Current -Transformer Cabinets: Comply with requirements of electrical power utility company.
B. Meter Sockets: Comply with requirements of electrical power utility company.
2.5 CONCRETE BASES
A. Concrete Forms and Reinforcement Materials: As specified in Division 3 Section "Cast -in -
Place Concrete."
B. Concrete: 3000-psi (20.7-MPa), 28-day compressive strength as specified in Division 3 Section
"Cast -in -Place Concrete."
2.6 TOUCHUP PAINT
A. For Equipment: Equipment manufacturer's paint selected to match installed equipment finish.
B. Galvanized Surfaces: Zinc -rich paint recommended by item manufacturer.
PART 3 - EXECUTION
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 3
SA 06/2004
10
ALTERNATE FUELS STATION
3.1 ELECTRICAL EQUIPMENT INSTALLATION
A. Headroom Maintenance: If mounting heights or other location criteria are not indicated,
arrange and install components and equipment to provide the maximum possible headroom.
B. Materials and Components: Install level, plumb, and parallel and perpendicular to other
systems and components, unless otherwise indicated.
C. Equipment: Install to facilitate service, maintenance, and repair or replacement of components.
Connect for ease of disconnecting, with minimum interference with other installations.
D. Right of Way: Give to raceways and piping systems installed at a required slope.
3.2 WIRING METHODS FOR POWER, LIGHTING, AND CONTROL CIRCUITS
A. Feeders: Type THHN/THWN insulated conductors in raceway.
B. Underground Feeders and Branch Circuits: Type THWN or single -wire.
C. Branch Circuits: Type THHN/THWN insulated conductors in raceway.
D. Branch Circuits: Type THW or THHN/THWN insulated conductors in raceway where
exposed. Metal -clad cable where concealed in ceilings and gypsum board partitions.
E. Remote -Control Signaling and Power -Limited Circuits: Type THHN/THWN insulated
conductors in raceway for Classes 1, 2, and 3, unless otherwise indicated.
3.3 WIRING INSTALLATION
A. Install splices and taps that are compatible with conductor material and that possess equivalent
or better mechanical strength and insulation ratings than unspliced conductors.
B. Install wiring at outlets with at least 12 inches (300 mm) of slack conductor at each outlet.
C. Connect outlet and component connections to wiring systems and to ground. Tighten electrical
connectors and terminals, according to manufacturer's published torque -tightening values. If
manufacturer's torque values are not indicated, use those specified in UL 486A.
3.4 ELECTRICAL SUPPORTING DEVICE APPLICATION
A. Damp Locations and Outdoors: Hot -dip galvanized materials, U-channel system components.
B. Support Clamps for PVC Raceways: Click -type clamp system.
C. Selection of Supports: Comply with manufacturer's written instructions.
D. Strength of Supports: Adequate to carry present and future loads, times a safety factor of at
least four; minimum of 200-lb (90-kg) design load.
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 4
SA 06/2004
I1
the parties. All notices provided under this Agreement shall be effective when mailed, postage
prepaid and sent to the following addresses:
City:
Service Provider:
City: Service Provider:
City of Fort Collins, Purchasing Division Glanz Electrical Contracting Inc.
PO Box 580 1713 E. Lincoln Ave. Ste Al
Fort Collins, CO 80522 Fort Collins, CO 80524
In the event of early termination by the City, the Service Provider shall be paid for services
rendered to the date of termination, subject only to the satisfactory performance of the Service
Provider's obligations under this Agreement. Such payment shall be the Service Provider's sole
right and remedy for such termination.
5. Contract Sum. The City shall pay the Service provider for the performance of this
Contract, subject to additions and deletions provided herein, the sum of Thirty Seven Thousand
Four Hundred Fifty Dollars ($37,450).
6. City Representative. The City will designate, prior to commencement of the
work, its representative who shall make, within the scope of his or her authority, all necessary
and proper decisions with reference to the services provided under this agreement. All requests
concerning this agreement shall be directed to the City Representative.
7. Independent Service provider. The services to be performed by Service Provider
are those of an independent service provider and not of an employee of the City of Fort Collins.
The City shall not be responsible for withholding any portion of Service Provider's compensation
hereunder for the payment of FICA, Workmen's Compensation or other taxes or benefits or for
any other purpose.
8. Personal Services. It is understood that the City enters into the Agreement
based on the special abilities of the Service Provider and that this Agreement shall be
considered as an agreement for personal services. Accordingly, the Service Provider shall
SA 0612004
2
ALTERNATE FUELS STATION
3.5 SUPPORT INSTALLATION
A. Install support devices to securely and permanently fasten and support electrical components.
B. Support individual horizontal raceways with separate, malleable -iron pipe hangers or clamps.
C. Install 1/4-inch- (6-mm-) diameter or larger threaded steel hanger rods, unless otherwise
indicated.
D. Spring -steel fasteners specifically designed for supporting single conduits or tubing may be
used instead of malleable -iron hangers for 1-1/2-inch (38-mm) and smaller raceways serving
lighting and receptacle branch circuits for fastening raceways to slotted channel and angle
supports.
E. Install metal channel racks for mounting cabinets, panelboards, disconnect switches, control
enclosures, pull and junction boxes, transformers, and other devices unless components are
mounted directly to structural elements of adequate strength.
F. Install sleeves for cable and raceway penetrations of concrete slabs and walls unless core -drilled
holes are used. Install sleeves for cable and raceway penetrations of masonry and fire -rated
gypsum walls and of all other fire -rated floor and wall assemblies. Install sleeves during
erection of concrete and masonry walls.
G. Securely fasten electrical items and their supports to the structure, unless otherwise indicated.
Perform fastening according to the following unless other fastening methods are indicated:
1. Wood: Fasten with wood screws or screw -type nails.
2. Masonry: Toggle bolts on hollow masonry units and expansion bolts on solid masonry
units.
3. New Concrete: Concrete inserts with machine screws and bolts.
4. Existing Concrete: Expansion bolts.
5. Instead of expansion bolts, threaded studs driven by a powder charge and provided with
lock washers may be used in existing concrete.
6. Steel: Welded threaded studs or spring -tension clamps on steel.
a. Field Welding: Comply with AWS D1.1.
7. Welding to steel structure may be used only for threaded studs, not for conduits, pipe
straps, or other items.
S. Light Steel: Sheet -metal screws.
9. Fasteners: Select so the load applied to each fastener does not exceed 25 percent of its
proof -test load.
3.6 IDENTIFICATION MATERIALS AND DEVICES
A. Install at locations for most convenient viewing without interference with operation and
maintenance of equipment.
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 5
SA 06/2004
12
ALTERNATE FUELS STATION
B. Coordinate names, abbreviations, colors, and other designations used for electrical identification
with corresponding designations indicated in the Contract Documents or required by codes and
standards. Use consistent designations throughout Project.
C. Self -Adhesive Identification Products: Clean surfaces before applying.
D. Install continuous underground plastic markers during trench backfilling, for exterior
underground power, control, signal, and communication lines located directly above power and
communication lines. Locate 6 to 8 inches (150 to 200 mm) below finished grade. If width of
multiple lines installed in a common trench or concrete envelope does not exceed 16 inches
(400 mm), overall, use a single line marker.
E. Color -code 240/120-V system secondary service, feeder, and branch -circuit conductors
throughout the secondary electrical system as follows:
1. Phase A: Black.
2. Phase B: Red.
F. Color -code 480/277-V system secondary service, feeder, and branch -circuit conductors
throughout the secondary electrical system as follows:
1. Phase A: Yellow.
2. Phase B: Brown.
3. Phase C: Orange.
G. Install warning, caution, and instruction signs where required to comply with 29 CFR,
Chapter XVII, Part 1910.145, and where needed to ensure safe operation and maintenance of
electrical systems and of items to which they connect. Install engraved plastic -laminated
instruction signs with approved legend where instructions are needed for system or equipment
operation. Install metal -backed butyrate signs for outdoor items.
H. Install engraved -laminated emergency -operating signs with white letters on red background
with minimum 3/8-inch- (9-mm-) high lettering for emergency instructions on power transfer,
load shedding, and other emergency operations.
3.7 UTILITY COMPANY ELECTRICITY -METERING EQUIPMENT
A. Install equipment according to utility company's written requirements. Provide grounding and
empty conduits as required by utility company.
3.8 CONCRETE BASES
A. Construct concrete bases of dimensions indicated, but not less than 4 inches (100 mm) larger, in
both directions, than supported unit. Follow supported equipment manufacturer's anchorage
recommendations and setting templates for anchor -bolt and tie locations, unless otherwise
indicated. Use 3000-psi (20.7-MPa), 28-day compressive -strength concrete and reinforcement
as specified in Division 3 Section "Cast -in -Place Concrete."
3.9 DEMOLITION
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 6
SA O6/2004
13
ALTERNATE FUELS STATION
A. Protect existing electrical equipment and installations indicated to remain. If damaged or
disturbed in the course of the Work, remove damaged portions and install new products of equal
capacity, quality, and functionality.
B. Accessible Work: Remove exposed electrical equipment and installations, indicated to be
demolished, in their entirety.
C. Abandoned Work: Cut and remove buried raceway and wiring, indicated to be abandoned in
place, 2 inches (50 mm) below the surface of adjacent construction. Cap raceways and patch
surface to match existing finish.
D. Remove demolished material from Project site.
E. Remove, store, clean, reinstall, reconnect, and make operational components indicated for
relocation.
3.10 CUTTING AND PATCHING
A. Cut, channel, chase, and drill floors, walls, partitions, ceilings, and other surfaces required to
permit electrical installations. Perform cutting by skilled mechanics of trades involved.
B. Repair and refinish disturbed finish materials and other surfaces to match adjacent undisturbed
surfaces. Repair and refinish materials and other surfaces by skilled mechanics of trades
involved.
3.11 FIELD QUALITY CONTROL
A. Inspect installed components for damage and faulty work, including the following:
1. Building wire and connectors.
2. Supporting devices for electrical components.
3. Electrical identification.
4. Electricity -metering components.
5. Concrete bases.
6. Electrical demolition.
7. Cutting and patching for electrical construction.
8. Touchup painting.
3.12 REFINISHING AND TOUCHUP PAINTING
A. Refinish and touch up paint. Paint materials and application requirements are specified in
Division 9 Section "Painting."
1. Clean damaged and disturbed areas and apply primer, intermediate, and finish coats to
suit the degree of damage at each location.
2. Follow paint manufacturer's written instructions for surface preparation and for timing
and application of successive coats.
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 7
SA 06/2004
14
ALTERNATE FUELS STATION
3. Repair damage to galvanized finishes with zinc -rich paint recommended by
manufacturer.
4. Repair damage to PVC or paint finishes with matching touchup coating recommended by
manufacturer.
3.13 CLEANING AND PROTECTION
A. On completion of installation, including outlets, fittings, and devices, inspect exposed finish.
Remove burrs, dirt, paint spots, and construction debris.
B. Protect equipment and installations and maintain conditions to ensure that coatings, finishes,
and cabinets are without damage or deterioration at time of Substantial Completion.
END OF SECTION 16050
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 8
SA 0612004
15
ALTERNATE FUELS STATION
SECTION 16060 - GROUNDING AND BONDING
PART] -GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division I Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes methods and materials for grounding systems and equipment.
1.3 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
B. Comply with UL 467 for grounding and bonding materials and equipment.
PART 2-PRODUCTS
2.1 CONDUCTORS
A. Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by
applicable Code or authorities having jurisdiction.
B. Bare Copper Conductors:
I. Solid Conductors: ASTM B 3.
2. Stranded Conductors: ASTM B 8.
3. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor.
4. Bonding Jumper: Copper tape, braided conductors, terminated with copper ferrules; I-
5/8 inches (41 mm) wide and 1/16 inch (1.6 mm) thick.
2.2 CONNECTORS
A. Listed and labeled by a nationally recognized testing laboratory acceptable to authorities having
jurisdiction for applications in which used, and for specific types, sizes, and combinations of
conductors and other items connected.
B. Bolted Connectors for Conductors and Pipes: Copper or copper alloy, bolted pressure -type,
with at least two bolts.
GROUNDING AND BONDING
16060 - 1
SA 06/2004
16
ALTERNATE FUELS STATION
1. Pipe Connectors: Clamp type, sized for pipe.
C. Welded Connectors: Exothermic -welding kits of types recommended by kit manufacturer for
materials being joined and installation conditions.
2.3 GROUNDING ELECTRODES
A. Ground Rods: Copper -clad steel, sectional type; 3/4 inch by10 feet (19 mm by 3 m) diameter.
PART 3-EXECUTION
3.1 APPLICATIONS
A. Conductors: Install solid conductor for No. g AWG and smaller, and stranded conductors for
No. 6 AWG and larger, unless otherwise indicated.
B. Underground Grounding Conductors: Install bare copper conductor.
1. Bury at least 24 inches (600 mm) below grade.
C. Conductor Terminations and Connections:
1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors.
2. Underground Connections: Welded connectors, except at test wells and as otherwise
indicated.
3. Connections to Structural Steel: Welded connectors.
3.2 EQUIPMENT GROUNDING
A. Install insulated equipment grounding conductors with all feeders and branch circuits.
B. Install insulated equipment grounding conductors with the following items, in addition to those
required by NFPA 70:
1. Feeders and branch circuits.
2. Lighting circuits.
3. Receptacle circuits.
4. Single-phase motor and appliance branch circuits.
5. Three-phase motor and appliance branch circuits.
6. Flexible raceway runs.
3.3 INSTALLATION
A. Grounding Conductors: Route along shortest and straightest paths possible, unless otherwise
indicated or required by Code. Avoid obstructing access or placing conductors where they may
be subjected to strain, impact, or damage.
GROUNDING AND BONDING
16060 - 2
SA 0612004
17
ALTERNATE FUELS STATION
B. Common Ground Bonding with Lightning Protection System: Comply with NFPA 780 and
UL 96 when interconnecting with lightning protection system. Bond electrical power system
ground directly to lightning protection system grounding conductor at closest point to electrical
service grounding electrode. Use bonding conductor sized same as system grounding electrode
conductor, and install in conduit.
C. Ground Rods: Drive rods until tops are 2 inches (50 mm) below final grade, unless otherwise
indicated.
I. Interconnect ground rods with grounding electrode conductor below grade and as
otherwise indicated. Make connections without exposing steel or damaging coating, if
any.
2. For grounding electrode system, install at least two rods spaced at least one -rod length
from each other and connect to the service grounding electrode conductor.
D. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance,
except where routed through short lengths of conduit.
1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate
any adjacent parts.
2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install so
vibration is not transmitted to rigidly mounted equipment.
3. Use exothermic -welded connectors for outdoor locations, but if a disconnect -type
connection is required, use a bolted clamp.
E. Grounding and Bonding for Piping:
I. Bond each aboveground portion of gas piping system downstream from equipment
shutoff valve.
F. Ufer Ground (Concrete -Encased Grounding Electrode): Fabricate according to NFPA 70, using
a minimum of 20 feet (6 m) of bare copper conductor not smaller than No. 4 size> A WG.
1. If concrete foundation is less than 20 feet (6 m) long, coil excess conductor within base
of foundation.
2. Bond grounding conductor to reinforcing steel in at least four locations and to anchor
bolts. Extend grounding conductor below grade and connect to structure grounding grid
or to grounding electrode external to concrete.
3.4 FIELD QUALITY CONTROL
A. Perform the following tests and inspections and prepare test reports:
After installing grounding system but before permanent electrical circuits have been
energized, test for compliance with requirements.
B. Report measured ground resistances that exceed the following values:
1. Power and Lighting Equipment or System with Capacity 500 kVA and Less: 10 ohms.
GROUNDING AND BONDING
16060 - 3
SA 0612004
18
ALTERNATE FUELS STATION
C. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Architect
promptly and include recommendations to reduce ground resistance.
END OF SECTION 16060
GROUNDING AND BONDING
16060 - 4
SA 06/2004
19
ALTERNATE FUELS STATION
SECTION 16130 - RACEWAYS AND BOXES
PART1-GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical wiring.
1.3 DEFINITIONS
A. EMT: Electrical metallic tubing.
B. ENT: Electrical nonmetallic tubing.
C. FMC: Flexible metal conduit.
D. IMC: Intermediate metal conduit.
E. LFMC: Liquidtight flexible metal conduit.
F. LFNC: Liquidtight flexible nonmetallic conduit.
G. RNC: Rigid nonmetallic conduit.
1.4 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
B. Comply with NFPA 70.
1.5 COORDINATION
A. Coordinate layout and installation of raceways, boxes, enclosures and cabinets, with other
construction.
RACEWAYS AND BOXES
16130 - 1
SA 0612004
20
ALTERNATE FUELS STATION
PART2-PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where subparagraph titles below introduce lists, the following
requirements apply for product selection:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers
offering products that may be incorporated into the Work include, but are not limited to,
the manufacturers specified.
2.2 METAL CONDUIT AND TUBING
A. Manufacturers:
1. AFC Cable Systems, Inc.
2. Alflex Inc.
3. Anamet Electrical, Inc.; Anaconda Metal Hose.
4. Electri-Flex Co.
5. Grinnell Co./Tyco International; Allied Tube and Conduit Div.
6. LTV Steel Tubular Products Company.
7. Manhattan/CDT/Cole-Flex.
8. O-Z Gedney; Unit of General Signal.
9. Wheatland Tube Co.
B. Rigid Steel Conduit: ANSI C80.1.
C. Plastic -Coated Steel Conduit and Fittings: NEMA RN 1.
D. EMT and Fittings: ANSI C80.3,
1. Fittings: Compression type.
E. FMC: Zinc -coated steel.
F. LFMC: Flexible steel conduit with PVC jacket.
G. Fittings: NEMA FB l; compatible with conduit and tubing materials.
2.3 NONMETALLIC CONDUIT AND TUBING
A. Manufacturers:
1. American Intemational.
2. Anamet Electrical, Inc.; Anaconda Metal Hose.
3. Amco Corp.
4. Cantex Inc.
5. Certainteed Corp.; Pipe & Plastics Group.
6. Condux International.
RACEWAYS AND BOXES
16130 - 2
SA 06/2004
21
neither assign any responsibilities nor delegate any duties arising under the Agreement without
the prior written consent of the City.
9. Acceptance Not Waiver. The City's approval or acceptance of, or payment for
any of the services shall not be construed to operate as a waiver of any rights or benefits
provided to the City under this Agreement or cause of action arising out of performance of this
Agreement.
10. Warranty.
(a) Service Provider warrants that all work performed hereunder shall be
performed with the highest degree of competence and care in accordance
with accepted standards for work of a similar nature.
(b) Unless otherwise provided in the Agreement, all materials and equipment
incorporated into any work shall be new and, where not specified, of the
most suitable grade of their respective kinds for their intended use, and all
workmanship shall be acceptable to City.
(c) Service Provider warrants all equipment, materials, labor and other work,
provided under this Agreement, except City -furnished materials,
equipment and labor, against defects and nonconformances in design,
materials and workmanship/workwomanship for a period beginning with
the start of the work and ending twelve (12) months from and after final
acceptance under the Agreement, regardless whether the same were
furnished or performed by Service Provider or by any of its subcontractors
of any tier. Upon receipt of written notice from City of any such defect or
nonconformances, the affected item or part thereof shall be redesigned,
repaired or replaced by Service Provider in a manner and at a time
acceptable to City.
11. Default. Each and every term and condition hereof shall be deemed to be a
material element of this Agreement. In the event either party should fail or refuse to perform
according to the terms of this agreement, such party may be declared in default thereof.
12. Remedies. In the event a party has been declared in default, such defaulting
party shall be allowed a period of ten (10) days within which to cure said default. In the event
the default remains uncorrected, the party declaring default may elect to (a) terminate the
Agreement and seek damages; (b) treat the Agreement as continuing and require specific
performance; or (c) avail himself of any other remedy at law or equity. If the non -defaulting party
SA 0612004
3
ALTERNATE FUELS STATION
7. ElecSYS, Inc.
8. Electri-Flex Co.
9. Lamson & Sessions; Carlon Electrical Products.
10. Manhattan/CDT/Cole-Flex.
11. RACO; Division of Hubbell, Inc.
12. Spiralduct, Inc./AFC Cable Systems, Inc.
13. Thomas & Betts Corporation.
B. RNC: NEMA TC 2, Schedule 40 and Schedule 80 PVC.
C. RNC Fittings: NEMA TC 3; match to conduit or tubing type and material.
D. LFNC: UL 1660.
2.4 BOXES, ENCLOSURES, AND CABINETS
A. Manufacturers:
1. Cooper Crouse -Hinds; Div. of Cooper Industries, Inc.
2. Emerson/General Signal; Appleton Electric Company.
3. Erickson Electrical Equipment Co.
4. Hoffman.
5. Hubbell, Inc.; Killark Electric Manufacturing Co.
6. O-ZJGedney; Unit of General Signal.
7. RACO; Division of Hubbell, Inc.
8. Robroy Industries, Inc.; Enclosure Division.
9. Scott Fetzer Co.; Adalet-PLM Division,
10. Spring City Electrical Manufacturing Co.
11. Thomas & Betts Corporation.
12. Walker Systems, Inc.; Wiremold Company (The).
13. Woodhead, Daniel Company; Woodhead Industries, Inc. Subsidiary.
B. Cast -Metal Outlet and Device Boxes: NEMA FB 1, Type FD, with gasketed cover.
C. Nonmetallic Outlet and Device Boxes: NEMA OS 2.
D. Cast -Metal Pull and Junction Boxes: NEMA FB 1, cast aluminum with gasketed cover.
E. Cabinets: NEMA 250, Type 3R, galvanized steel box, finished inside and out with
manufacturer's standard enamel. Hinged door in front cover with flush latch and concealed
hinge. Key latch to match panelboards. include metal barriers to separate wiring of different
systems and voltage.
2.5 FACTORY FINISHES
A. Finish: For raceway, enclosure, or cabinet components, provide manufacturer's standard paint
applied to factory -assembled surface raceways, enclosures, and cabinets before shipping.
RACEWAYS AND BOXES
16130 - 3
SA 0612004
22
ALTERNATE FUELS STATION
PART 3 - EXECUTION
3.1 RACEWAY APPLICATION
A. Outdoors:
1. Exposed: Rigid steel.
2. Concealed: Rigid steel.
3. Underground, Single Run: RNC.
4. Underground, Grouped: RNC.
5. Connection to Vibrating Equipment (Including Transformers or Motor -Driven
Equipment: LFMC.
6. Boxes and Enclosures: NEMA 250, Type 4.
B. Hazardous Area:
1. Exposed: Rigid Steel.
2. Boxes and Enclosures: Suitable for Class 1 Division 1.
C. Minimum Raceway Size: 1/2-inch trade size (DN 16).
D. Raceway Fittings: Compatible with raceways and suitable for use and location.
I. PVC Extemally Coated, Rigid Steel Conduits: Use only fittings approved for use with
that material. Patch all nicks and scrapes in PVC coating after installing conduits.
3.2 INSTALLATION
A. Complete raceway installation before starting conductor installation.
B. Support raceways as specified in Division 16 Section "Basic Electrical Materials and Methods."
C. Install temporary closures to prevent foreign matter from entering raceways.
D. Protect stub -ups from damage where conduits rise through slabs. Arrange so curved portions of
bends are not visible above the finished slab.
E. Make bends and offsets so iD is not reduced. Keep legs of bends in the same plane and keep
straight legs of offsets parallel, unless otherwise indicated.
F. Install exposed raceways parallel or at right angles to nearby surfaces or structural members and
follow surface contours as much as possible.
1. Run parallel or banked raceways together on common supports.
2. Make parallel bends in parallel or banked runs. Use factory elbows only where elbows
can be installed parallel; otherwise, provide field bends for parallel raceways.
G. Join raceways with fittings designed and approved for that purpose and make joints tight.
RACEWAYS AND BOXES
16130 - 4
SA 0612004
23
ALTERNATE FUELS STATION
Use insulating bushings to protect conductors.
H. Terminations:
1. Where raceways are terminated with threaded hubs, screw raceways or fittings tightly
into hub so end bears against wire protection shoulder. Where chase nipples are used,
align raceways so coupling is square to box; tighten chase nipple so no threads are
exposed.
I. Install pull wires in empty raceways. Use polypropylene or monofilament plastic line with not
less than 200-lb (90-kg) tensile strength. Leave at least 12 inches (300 mm) of slack at each end
of pull wire.
Telephone and Signal System Raceways, 2-Inch Trade Size (DN 53) and Smaller: In addition
to above requirements, install raceways in maximum lengths of 150 feet (45 m) and with a
maximum of two 90-degree bends or equivalent. Separate lengths with pull or junction boxes
where necessary to comply with these requirements.
K. Install raceway sealing fittings at suitable, approved, and accessible locations and fill them with
UL-listed sealing compound.
Where otherwise required by NFPA 70.
L. Flexible Connections: Use maximum of 72 inches (1830 mm) of flexible conduit for equipment
subject to vibration, noise transmission, or movement; and for all motors. Use LFMC in damp
or wet locations. Install separate ground conductor across flexible connections.
M. Install hinged -cover enclosures and cabinets plumb. Support at each comer. Field install
weatherproof control devices mounted in cover.
3.3 PROTECTION
A. Provide final protection and maintain conditions that ensure coatings, finishes, and cabinets are
without damage or deterioration at time of Substantial Completion.
I. Repair damage to galvanized finishes with zinc -rich paint recommended by
manufacturer.
2. Repair damage to PVC or paint finishes with matching touchup coating recommended by
manufacturer.
3.4 CLEANING
A. After completing installation of exposed, factory -finished raceways and boxes, inspect exposed
finishes and repair damaged finishes.
END OF SECTION 16130
RACEWAYS AND BOXES
16130 - 5
SA O6I2004
24
ALTERNATE FUELS STATION
SECTION 16140 - WIRING DEVICES
PART] -GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
I. Duplex receptacles, ground -fault circuit interrupters.
2. Snap switches and dimmer switches.
3. Device wall plates.
1.3
DEFINITIONS
A.
EMI: Electromagnetic interference.
B.
GFCI: Ground -fault circuit interrupter.
C.
PVC: Polyvinyl chloride.
D.
RFI: Radio -frequency interference.
E.
TV SS: Transient voltage surge suppressor.
F.
UTP: Unshielded twisted pair.
1.4 SUBMITTALS
A. Product Data: For each type of product indicated.
1.5 QUALITY ASSURANCE
A. Source Limitations: Obtain each type of wiring device through one source from a single
manufacturer.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
C. Comply with NFPA 70.
WIRING DEVICES
16140 - 1
SA O6/2004
25
ALTERNATE FUELS STATION
PART2-PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Wiring Devices:
a. Bryant Electric, Inc./Hubbell Subsidiary.
b. Eagle Electric Manufacturing Co., Inc.
C. Hubbell Incorporated; Wiring Device-Kellems.
d. Leviton Mfg. Company Inc.
C. Pass & Seymour/Legrand; Wiring Devices Div.
2.2 RECEPTACLES
A. Straight -Blade -Type Receptacles: Comply with NEMA WD 1, NEMA WD 6, DSCC W-C-
596G, and UL 498.
B. Straight -Blade and Locking Receptacles: Heavy -Duty grade.
C. GFCI Receptacles: Straight blade, feed -through type, Heavy -Duty grade, with integral
NEMA WD 6, Configuration 5-20R duplex receptacle; complying with UL 498 and UL 943.
Design units for installation in a 2-3/4-inch- (70-mm-) deep outlet box without an adapter.
2.3 SWITCHES
A. Single -Pole Switches: Comply with DSCC W-C-89617 and UL 20.
B. Snap Switches: Heavy -Duty grade, quiet type.
2.4 WALL PLATES
A. Single and combination types to match corresponding wiring devices.
1. Plate -Securing Screws: Metal with head color to match plate finish.
2. Material for Wet Locations: Cast aluminum with spring -loaded lift cover, and listed and
labeled for use in "wet locations."
2.5 FINISHES
A. Color:
1. Wiring Devices Connected to Normal Power System: Brown unless otherwise indicated
or required by NFPA 70.
WIRING DEVICES
16140 - 2
SA 06/2004
26
ALTERNATE FUELS STATION
PART 3-EXECUTION
3.1 INSTALLATION
A. Install devices and assemblies level, plumb, and square with building lines.
B. Remove wall plates and protect devices and assemblies during painting.
3.2 CONNECTIONS
A. Ground equipment according to Division 16 Section "Grounding and Bonding."
B. Connect wiring according to Division 16 Section "Basic Electrical Materials and Methods."
C. Tighten electrical connectors and terminals according to manufacturer's published torque -
tightening values. If manufacturer's torque values are not indicated, use those specified in
UL 486A and UL 486B.
3.3 FIELD QUALITY CONTROL
A. Perform the following field tests and inspections and prepare test reports:
1. After installing wiring devices and after electrical circuitry has been energized, test for
proper polarity, ground continuity, and compliance with requirements.
2. Test GFCI operation with both local and remote fault simulations according to
manufacturer's written instructions.
B. Remove malfunctioning units, replace with new units, and retest as specified above.
END OF SECTION 16140
WIRING DEVICES
16140 - 3
SA 06/2004
27
ALTERNATE FUELS STATION
SECTION 16145 —NON-REVERSING CONTACTORS
PART1-GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following devices:
1. Multipole contactors.
B. Related Sections include the following:
I. Division 16 Section "Raceways and Boxes" for contactor housing.
1.3 SUBMITTALS
A. Product Data: For each type of product indicated.
1.4 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
PART 2-PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the
manufacturers specified.
2.2 MULTIPOLE CONTACTORS
A. Manufacturers:
NON -REVERSING CONTACTORS
16145 - 1
SA O6/2004
28
ALTERNATE FUELS STATION
l . Cutler -Hammer; Eaton Corporation.
2, GE Industrial Systems; Total Lighting Control.
3. Sq. D.
B. Description: Electrically operated and electrically held non -reversing 4-pole contactor. Sq. D
LCIF or equal.
l . Current Rating for Switching: 400-amp inductive, 420-amp resistive.
2. Control -Coil Voltage: 120-volt.
3. Voltage Rating for Switching: 480- volt.
4. Switching poles: 4-poles to switch 3-phase wire and neutral wire.
5. Additional parts:
a. Lug kit.
b. Control transformer
C. Weatherproof emergency shut off pushbutton. Large mushroom type, color red.
d. Weatherproof reset pushbutton.
e. Control relay
f. Weatherproof enclosure with hinged door.
g. Fuse protection of control circuits.
PART 3-EXECUTION
3.1 WIRING INSTALLATION
A. Wiring within Enclosures: Bundle, lace, and train conductors to terminal points. Separate
power -limited and nonpower-limited conductors according to conductor manufacturer's written
instructions.
B. Splices, Taps, and Terminations: Make connections only on numbered terminal strips in
junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures.
C. Tighten electrical connectors and terminals according to manufacturer's published torque -
tightening values. If manufacturer's torque values are not indicated, use those specified in
UL 486A and UL 486B.
3.2 IDENTIFICATION
A. Identify components and power and control wiring according to Division 16 Section "Basic
Electrical Materials and Methods."
B. Label contactors with a unique designation. Provide emergency and control labels on the
enclosure door by the pushbuttons as indicated on the plans.
3.3 FIELD QUALITY CONTROL
A. Perform the following field tests and inspections and prepare test reports:
NON -REVERSING CONTACTORS
16145 - 2
SA 0612004
29
ALTERNATE FUELS STATION
After installing equipment and after electrical circuitry has been energized, adjust and test
for compliance with requirements.
Operational Test: Verify actuation of each sensor and adjust time delays.
Remove and replace devices where test results indicate that they do not comply with specified
requirements.
END OF SECTION 16145
NON -REVERSING CONTACTORS
16145 - 3
SA 06/2004
30
ALTERNATE FUELS STATION
SECTION 16410 -ENCLOSED SWITCHES
PART 1-GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and other Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following individually mounted, enclosed switches and circuit
breakers:
1. Fusible switches.
2. Enclosures.
1.3 DEFINITIONS
A. GD: General duty.
B. GFCI: Ground -fault circuit interrupter.
C. HD: Heavy duty.
D. RMS: Root mean square.
E. SPDT: Single pole, double throw.
1.4 SUBMITTALS
A. Product Data: For each type of enclosed switch, accessory, and component indicated. Include
dimensioned elevations, sections, weights, and manufacturers' technical data on features,
performance, electrical characteristics, ratings, and finishes.
I. Enclosure types and details for types other than NEMA 250, Type 1.
2. Current and voltage ratings.
3. Short-circuit current rating.
1.5 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
ENCLOSED SWITCHES 16410- 1
SA 06/2004
31
commences legal or equitable actions against the defaulting party, the defaulting party shall be
liable to the non -defaulting party for the non -defaulting party's reasonable attorney fees and
costs incurred because of the default.
13. Binding Effect. This writing, together with the exhibits hereto, constitutes the
entire agreement between the parties and shall be binding upon said parties, their officers,
employees, agents and assigns and shall inure to the benefit of the respective survivors, heirs,
personal representatives, successors and assigns of said parties.
14. Indemnity/Insurance. a. The Service Provider agrees to indemnify and save
harmless the City, its officers, agents and employees against and from any and all actions,
suits, claims, demands or liability of any character whatsoever brought or asserted for injuries to
or death of any person or persons, or damages to property arising out of, result from or
occurring in connection with the performance of any service hereunder.
b. The Service Provider shall take all necessary precautions in performing the work
hereunder to prevent injury to persons and property.
c. Without limiting any of the Service Provider's obligations hereunder, the Service
Provider shall provide and maintain insurance coverage naming the City as an additional
insured under this Agreement of the type and with the limits specified within Exhibit B,
consisting of one (1) page, attached hereto and incorporated herein by this reference. The
Service Provider before commencing services hereunder, shall deliver to the City's Director of
Purchasing and Risk Management, P. O. Box 580 Fort Collins, Colorado 80522 one copy of a
certificate evidencing the insurance coverage required from an insurance company acceptable
to the City.
15. Entire Agreement. This Agreement, along with all Exhibits and other documents
incorporated herein, shall constitute the entire Agreement of the parties. Covenants or
representations not contained in this Agreement shall not be binding on the parties.
sn 06/2004
4
ALTERNATE FUELS STATION
B. Comply with NFPA 70.
C. Product Selection for Restricted Space: Drawings indicate maximum dimensions for enclosed
switches, including clearances between enclosures, and adjacent surfaces and other items.
Comply with indicated maximum dimensions.
1.6 PROJECT CONDITIONS
A. Environmental Limitations: Rate equipment for continuous operation under the following
conditions, unless otherwise indicated:
1. Ambient Temperature: Not less than minus 22 deg F (minus 30 deg C) and not
exceeding 104 deg F (40 deg Q.
2. Altitude: Not exceeding 6600 feet (2010 m).
1.7 COORDINATION
A. Coordinate layout and installation of switches, and components with other construction,
including conduit, piping, equipment, and adjacent surfaces. Maintain required workspace
clearances and required clearances for equipment access doors and panels.
PART2-PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers
offering products that may be incorporated into the Work include, but are not limited to,
manufacturers specified.
2.2 FUSIBLE AND NONFUSIBLE SWITCHES
A. Manufacturers:
1. Eaton Corporation; Cutler -Hammer Products.
2. General Electric Co.; Electrical Distribution & Control Division.
3. Siemens Energy & Automation, Inc.
4. Square D1Group Schneider.
B. Fusible Switch, 400 A and Smaller: NEMA KS 1, Type HD, with clips or bolt pads to
accommodate specified fuses, lockable handle with capability to accept two padlocks, and
interlocked with cover in closed position.
C. Accessories:
ENCLOSED SWITCHES
W-131( t]
SA asr2oc4
32
ALTERNATE FUELS STATION
i. Equipment Ground Kit: Internally mounted and labeled for copper ground conductors.
2. Neutral Kit: Internally mounted; insulated, capable of being grounded, and bonded; and
labeled for copper neutral conductors.
3. Secondary surge arrestor for 3 phase system, 650 Vac phase -to -ground maximum.
2.3 ENCLOSURES
A. NEMA AB 1 and NEMA KS I to meet environmental conditions of installed location.
I. Outdoor Locations: NEMA 250, Type 3R.
PART 3-EXECUTION
3.1 EXAMINATION
A. Examine elements and surfaces to receive enclosed switches for compliance with installation
tolerances and other conditions affecting performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Comply with applicable portions of NECA 1, NEMA PB 1.1, and NEMA PB 2.1 for installation
of enclosed switches.
B. Mount individual wall -mounting switches with tops at uniform height, unless otherwise
indicated.
3.3 IDENTIFICATION
A. Identify field -installed conductors, interconnecting wiring, and components; provide warning
signs as specified in Division 16 Section 'Basic Electrical Materials and Methods."
B. Enclosure Nameplates: Label each enclosure with engraved metal or laminated -plastic
nameplate as specified in Division 16 Section 'Basic Electrical Materials and Methods."
3.4 CLEANING
A. On completion of installation, vacuum dirt and debris from interiors; do not use compressed air
to assist in cleaning.
B. Inspect exposed surfaces and repair damaged finishes.
*END OF SECTION 16410
ENCLOSED SWITCHES
16410 - 3
SA osnoo4
33
ALTERNATE FUELS STATION
SECTION 16442 - PANELBOARDS
PART] -GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division I Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Distribution panelboards.
2. Lighting and appliance branch -circuit panelboards.
3. Load centers.
1.3 DEFINITIONS
A. EMI: Electromagnetic interference.
B. GFCI: Ground -fault circuit interrupter.
C. RFI: Radio -frequency interference.
D. RMS: Root mean square.
E. SPDT: Single pole, double throw.
1.4 SUBMITTALS
A. Product Data: For each type of panelboard, overcurrent protective device, transient voltage
suppression device, accessory, and component indicated. Include dimensions and
manufacturers' technical data on features, performance, electrical characteristics, ratings, and
finishes.
1.5 QUALITY ASSURANCE
A. Source Limitations: Obtain panelboards, overcurrent protective devices, components, and
accessories through one source from a single manufacturer.
B. Product Options: Drawings indicate size, profiles, and dimensional requirements of
panelboards and are based on the specific system indicated. Refer to Division 1 Section
"Product Requirements."
PANELBOARDS
16442 - 1
SA 06/2004
34
ALTERNATE FUELS STATION
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
D. Comply with NEMA PB 1.
E. Comply with NFPA 70.
1.6 PROJECT CONDITIONS
A. Environmental Limitations: Rate equipment for continuous operation under the following
conditions, unless otherwise indicated:
1. Ambient Temperature: Not exceeding 104 deg F (40 deg C).
2. Altitude: Not exceeding 6600 feet (2000 m).
B. Service Conditions: NEMA PB 1, usual service conditions, as follows:
1. Ambient temperatures within limits specified.
2. Altitude not exceeding 6600 feet (2000 m).
1.7 COORDINATION
A. Coordinate layout and installation of panelboards and components with other construction that
penetrates walls or is supported by them, including electrical and other types of equipment,
raceways, piping, and encumbrances to workspace clearance requirements.
1.8 EXTRA MATERIALS
A. Furnish extra materials described below that match products installed and that are packaged
with protective covering for storage and identified with labels describing contents.
I. Keys: Six spares for each type of panelboard cabinet lock.
PART2-PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Panelboards, Overcurrent Protective Devices, Controllers, Contactors, and Accessories:
a. Eaton Corporation; Cutler -Hammer Products.
b. General Electric Co.; Electrical Distribution & Protection Div.
c. Siemens Energy & Automation, Inc.
d. Square D.
PANELBOARDS
16442 - 2
SA 0612004
35
ALTERNATE FUELS STATION
2.2 MANUFACTURED UNITS
A. Enclosures: Surface -mounted cabinets. NEMA PB 1, Type 1.
1. Rated for environmental conditions at installed location.
a. Outdoor Locations: NEMA 250, Type 3R.
2. Front: Secured to box with concealed trim clamps. For surface -mounted fronts, match
box dimensions.
3. Hinged Front Cover: Entire front trim hinged to box and with standard door within
hinged trim cover.
4. Finish: Manufacturers standard enamel finish over corrosion -resistant treatment or
primer coat.
5. Directory Card: With transparent protective cover, mounted in metal frame, inside
panelboard door.
B. Phase and Ground Buses:
1. Material: Hard -drawn copper, 98 percent conductivity.
2. Equipment Ground Bus: Adequate for feeder and branch -circuit equipment ground
conductors; bonded to box.
C. Conductor Connectors: Suitable for use with conductor material.
1. Main and Neutral Lugs: Mechanical type.
2. Ground Lugs and Bus Configured Terminators: Compression type.
D. Service Equipment Label: UL labeled for use as service equipment for panelboards with main
service disconnect switches.
E. Future Devices: Mounting brackets, bus connections, and necessary appurtenances required for
future installation of devices.
2.3 PANELBOARD SHORT-CIRCUIT RATING
A. Fully rated to interrupt symmetrical short-circuit current available at terminals.
2.4 DISTRIBUTION PANELBOARDS
A. Doors: Secured with vault -type latch with tumbler lock; keyed alike-
B. Main Overcurrent Protective Devices: Circuit breaker.
C. Branch Overcurrent Protective Devices:
1. For Circuit -Breaker Frame Sizes 125 A and Smaller: Plug-in circuit breakers.
2. For Circuit -Breaker Frame Sizes Larger Than 125 A: Bolt -on circuit breakers; plug-in
circuit breakers where individual positive -locking device requires mechanical release for
removal.
PANELBOARDS
16442 - 3
SA 06l2004
36
ALTERNATE FUELS STATION
2.5 LIGHTING AND APPLIANCE BRANCH -CIRCUIT PANELBOARDS
A. Branch Overcunent Protective Devices: Plug-in circuit breakers, replaceable without disturbing
adjacent units.
B. Doors: Concealed hinges; secured with flush latch with tumbler lock; keyed alike.
2.6 LOAD CENTERS
A. Overcurrent Protective Devices: Plug-in, full -module circuit breaker.
B. Conductor Connectors: Mechanical type for main, neutral, and ground lugs and buses.
2.7 OVERCURRENT PROTECTIVE DEVICES
A. Molded -Case Circuit Breaker: UL 499, with interrupting capacity to meet available fault
currents.
1. Thermal -Magnetic Circuit Breakers: Inverse time -current element for low-level
overloads, and instantaneous magnetic trip element for short circuits.
B. Molded -Case Circuit -Breaker Features and Accessories: Standard frame sizes, trip ratings, and
number of poles.
I . Lugs: Mechanical style, suitable for number, size, trip ratings, and conductor materials.
2. Multipole units enclosed in a single housing or factory -assembled to operate as a single
unit.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install panelboards and accessories according to NEMA PB 1.1.
B. Mount top of trim 74 inches (1880 mm) above finished floor, unless otherwise indicated.
C. Mount plumb and rigid without distortion of box.
D. Install overcurrent protective devices.
E. Install filler plates in unused spaces.
3.2 IDENTIFICATION
A. Identify field -installed conductors, interconnecting wiring, and components; provide warning
signs as specified in Division 16 Section 'Basic Electrical Materials and Methods."
PANELBOARDs
16442 - 4
SA 06/2004
37
ALTERNATE FUELS STATION
B. Create a directory to indicate installed circuit loads. Obtain approval before installing. Use a
computer or typewriter to create directory; handwritten directories are not acceptable.
C. Panelboard Nameplates: Label each panelboard with engraved metal or laminated -plastic
nameplate mounted with corrosion -resistant screws.
3.3 CONNECTIONS
A. Ground equipment according to Division 16 Section "Grounding and Bonding."
B. Connect wiring according to Division 16 Section 'Basic Electrical Materials and Methods."
3.4 FIELD QUALITY CONTROL
A. Load Balancing:
1. Tolerance: Difference exceeding 20 percent between phase loads, within a panelboard, is
not acceptable. Rebalance and recheck as necessary to meet this minimum requirement.
3.5 CLEANING
A. On completion of installation, inspect interior and exterior of panelboards. Remove paint
splatters and other spots. Vacuum dirt and debris; do not use compressed air to assist in
cleaning. Repair exposed surfaces to match original finish.
END OF SECTION 16442
PANELBOARDS
16442 - 5
SA asr2004
38
ALTERNATE FUELS STATION
SECTION 16461 - DRY -TYPE TRANSFORMERS (600 V AND LESS)
PART1-GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following types of dry -type transformers rated 600 V and less, with
capacities up to 1000 kVA:
1. Distribution transformers.
2. Control and Signal transformers.
1.3 SUBMITTALS
A. Product Data Include rated nameplate data, capacities, weights, dimensions, minimum
clearances, installed devices and features, and performance for each type and size of
transformer indicated.
1.4 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
B. Comply with IEEE C 57.12.91.
C. Energy -Efficient Transformers Rated 15 kVA and Larger: Certified as meeting NEMA TP 1,
Class 1 efficiency levels when tested according to NEMA TP 2.
1.5 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor -bolt inserts into bases. Concrete,
reinforcement, and formwork requirements are specified in Division 3.
DRY -TYPE TRANSFORMERS (600 V AND LESS)
16461 - 1
SA 06/2004
39
ALTERNATE FUELS STATION
PART 2-PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
I . Acme Electric Corporation; Power Distribution Products Division.
2. Challenger Electrical Equipment Corp.; a division of Eaton Corp.
3. Computer Power Inc.
4. Controlled Power Co.
5. Cutler -Hammer.
6. Federal Pacific Transformer Company; Division of Electro-Mechanical Corp.
7. GE Electrical Distribution & Control.
g. Hammond Co.; Matra Electric, Inc.
9. Jefferson Electric, Inc.
10. Micron Industries Corp.
11. Siemens Energy & Automation, Inc.
12. Sola/Hevi-Duty Electric.
13. Square D/Groupe Schneider NA.
2.2 MATERIALS
A. Description: Factory -assembled and -tested, air-cooled units for 60-Hz service.
B. Cores: Grain -oriented, non -aging silicon steel.
C. Coils: Continuous windings without splices, except for taps.
l . Internal Coil Connections: Brazed or pressure type.
2. Coil Material: Copper.
2.3 DISTRIBUTION TRANSFORMERS
A. Comply with NEMA ST 20, and list and label as complying with UL 1561.
B. Provide transformers that are internally braced to withstand seismic forces specified in
Division 16 Section "Electrical Supports and Seismic Restraints."
C. Cores: One leg per phase.
D. Enclosure: Totally enclosed, nonventilated, with lifting eyes, NEMA 250, Type 3R.
1. Core and coil shall be encapsulated within resin compound, sealing out moisture and air.
E. Outdoor Transformer Enclosure Finish: Comply with NEMA 250 for "Outdoor Corrosion
Protection."
1. Finish Color. Gray.
DRY -TYPE TRANSFORMERS (600 V AND LESS) 16461 - 2
SA 06/2004
40
ALTERNATE FUELS STATION
F. Insulation Class: 220 deg C, UL-component-recognized insulation system with a maximum of
150 deg C rise above 40 deg C ambient temperature.
G. Taps for Transformers 7.5 to 24 kVA: One 5 percent tap above and one 5 percent tap below
normal full capacity.
H. Low -Sound -Level Requirements: Minimum of 3 dBA less than NEMA ST 20 standard sound
levels when factory tested according to IEEE C57.12.91.
2.4 CONTROL AND SIGNAL TRANSFORMERS
A. Description: Self -cooled, two -winding dry type, rated for continuous duty, complying with
NEMA ST 1, and listed and labeled as complying with UL 506.
B. Ratings: Continuous duty. If rating is not indicated, provide at least 50 percent spare capacity
above connected peak load.
2.5 SOURCE QUALITY CONTROL
A. Test and inspect transformers according to IEEE C57.12.91.
B. Factory Sound -Level Tests: Conduct sound -level tests on equipment for this Project.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine conditions for compliance with enclosure- and ambient -temperature requirements for
each transformer.
B. Verify that field measurements are as needed to maintain working clearances required by
NFPA 70 and manufacturer's written instructions.
C. Examine floors for suitable mounting conditions where transformers will be installed.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Install floor -mounting transformers level on concrete bases.[ Construct concrete bases not less
than 4 inches (100 mm) larger in both directions than supported unit and 4 inches (100 mm)
high.)
1. Anchor transformers to concrete bases according to manufacturer's written instructions.
DRY -TYPE TRANSFORMERS (600 V AND LESS)
16461 - 3
SA 06/2004
41
16. Law/Severability, The laws of the State of Colorado shall govern the construction
interpretation, execution and enforcement of this Agreement. In the event any provision of this
Agreement shall be held invalid or unenforceable by any court of competent jurisdiction, such
holding shall not invalidate or render unenforceable any other provision of this Agreement.
17. Special Provisions. Special provisions or conditions relating to the services to be
performed pursuant to this Agreement are set forth in Exhibit C, consisting of five (5) pages,
Exhibit D, consisting of forty two (42) pages, and Exhibit D, consisting of two (2) pages E1 and
E2 of the Construction Documents for Architect's Project No. 0337.15 dated May 18, 2004,
attached hereto and incorporated herein by this reference.
AT ST:
CORPORATE SECRETA
CITY OF FORT COLLINS, COLORADO
a municipal corporation
By
Ja es W O'Neill II, CPPO, FNIGP
Dire&6r of Purchasing and Risk Management
Date: Z 0
Glanz E!�iqtrical Contracting, Inc
:3l
PRINT NAME
Ncs ,'e-le
CORPORATE PRESIDENT OR VICE PRESIDENT
Date: 09 — /1� � e>o 5/
(Corporate Seal) '
SA O6/2004
ALTERNATE FUELS STATION
3.3 CONNECTIONS
A. Ground equipment according to Division 16 Section "Grounding and Bonding."
B. Connect wiring according to Division 16 Section "Basic Electrical Materials and Methods."
C. Tighten electrical connectors and terminals according to manufacturer's published torque -
tightening values. If manufacturer's torque values are not indicated, use those specified in
UL 486A and UL 486B.
3.4 ADJUSTING
A. Record transformer secondary voltage at each unit for at least 48 hours of typical occupancy
period. Adjust transformer taps to provide optimum voltage conditions at secondary terminals.
Optimum is defined as not exceeding nameplate voltage plus 10 percent and not being lower
than nameplate voltage minus 5 percent. Submit recording and tap settings as test results.
B. Output Settings Report: Prepare a written report recording output voltages and tap settings.
END OF SECTION 16461
DRY -TYPE TRANSFORMERS (600 V AND LESS)
16461 - 4
SA O612004
42
ALTERNATE FUELS STATION
SECTION 16491 - FUSES
PARTI- GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division I Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Cartridge fuses rated 600 V and less for use in switches and controllers
1.3 SUBMITTALS
A. Product Data: Include the following for each fuse type indicated:
1. Dimensions and manufacturer's technical data on features, performance, electrical
characteristics, and ratings.
2. Let -through current curves for fuses with current -limiting characteristics.
3. Time -current curves, coordination charts and tables, and related data.
4. Fuse size for elevator feeders and elevator disconnect switches.
1.4 QUALITY ASSURANCE
A. Source Limitations: Obtain fuses from a single manufacturer.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
C. Comply with NEMA FU 1.
D. Comply with NFPA 70.
1.5 PROJECT CONDITIONS
A. Where ambient temperature to which fuses are directly exposed is less than 40 deg F (5 deg C)
or more than 100 deg F (38 deg C), apply manufacturer's ambient temperature adjustment
factors to fuse ratings.
FUSES 16491-1
SA 0612004
43
ALTERNATE FUELS STATION
L6 COORDINATION
A. Coordinate fuse ratings with utilization equipment nameplate limitations of maximum fuse size.
1.7 EXTRA MATERIALS
A. Furnish extra materials described below that match products installed and that are packaged
with protective covering for storage and identified with labels describing contents,
I. Fuses: Quantity equal to 10 percent of each fuse type and size, but no fewer than 3 of
each type and size.
PART2-PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Cooper Bussman, Inc.
2. Eagle Electric Mfg. Co., Inc.; Cooper Industries, Inc.
3. Ferraz Shawmut, Inc,
4. Tracor, Inc.; Littelfuse, Inc. Subsidiary.
2.2 CARTRIDGE FUSES
A. Characteristics: NEMA FU 1, nonrenewable cartridge fuse; class and current rating indicated;
voltage rating consistent with circuit voltage.
PART 3-EXECUTION
3.1 EXAMINATION
A. Examine utilization equipment nameplates and installation instructions. Install fuses of sizes
and with characteristics appropriate for each piece of equipment.
B. Evaluate ambient temperatures to determine if fuse rating adjustment factors must be applied to
fuse ratings.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 FUSE APPLICATIONS
A. Service Entrance: Class T, fast acting.
FUSES
16491 - 2
SA 0612004
44
ALTERNATE FUELS STATION
B. Motor Branch Circuits: Class RK5, time delay.
C. Other Branch Circuits: Class RK5, time delay.
3.3 INSTALLATION
A. Install fuses in fusible devices. Arrange fuses so rating information is readable without
removing fuse.
3.4 IDENTIFICATION
A. Install labels indicating fuse replacement information on inside door of each fused switch.
END OF SECTION 16491
FUSES
16491 - 3
SA O6/2004
45
ALTERNATE FUELS STATION
SECTION 16511 -INTERIOR LIG14TING
PARTI- GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
l . Lighting fixtures, lamps, and ballasts.
1.3 DEFINITIONS
A. BF: Ballast factor.
B. CRI: Color -rendering index.
C. CU: Coefficient of utilization.
D. HID: High -intensity discharge.
E. LER: Luminaire efficacy rating.
F. Luminaire: Complete lighting fixture, including ballast housing if provided.
1.4 SUBMITTALS
A. Product Data: For each type of lighting fixture, arranged in order of fixture designation.
Include data on features, accessories, finishes, and the following:
1. Physical description of lighting fixture including dimensions.
2. Ballast.
3. Energy -efficiency data.
4. Life, output, and energy -efficiency data for lamps.
5. Photometric data, in IESNA format, based on laboratory tests of each lighting fixture
type, outfitted with lamps, ballasts, and accessories identical to those indicated for the
lighting fixture as applied in this Project.
a. For indicated fixtures, photometric data shall be certified by a qualified
independent testing agency. Photometric data for remaining fixtures shall be
certified by the manufacturer.
LIGHTING
16511 - 1
SA O6I2004
46
ALTERNATE FUELS STATION
b. Photometric data shall be certified by a manufacturer's laboratory with a current
accreditation under the National Voluntary Laboratory Accreditation Program
(NVLAP) for Energy Efficient Lighting Products.
1.5 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
B. Comply with NFPA 70.
1.6 COORDINATION
A. Coordinate layout and installation of lighting fixtures with other construction.
PART2-PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
2.2 LIGHTING FIXTURES AND COMPONENTS, GENERAL REQUIREMENTS
A. HID Fixtures: Comply with UL 1598. Where LER is specified, test according to
NEMA LE 5B.
B. Metal Parts: Free of buns and sharp corners and edges.
C. Sheet Metal Components: Steel, unless otherwise indicated. Form and support to prevent
warping and sagging.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage under
operating conditions, and designed to permit relamping without use of tools. Designed to
prevent doors, frames, lenses, diffusers, and other components from falling accidentally during
relamping and when secured in operating position.
E. Reflecting surfaces shall have minimum reflectance as follows, unless otherwise indicated:
1. White Surfaces: 85 percent.
2. Specular Surfaces: 83 percent.
3. Diffusing Specular Surfaces: 75 percent.
F. Plastic Diffusers, Covers, and Globes:
LIGHTING
16511 - 2
SA 06/2004
47
ALTERNATE FUELS STATION
1. Acrylic Lighting Diffusers: 100 percent virgin acrylic plastic. High resistance to
yellowing and other changes due to aging, exposure to heat, and UV radiation.
a. UV stabilized.
2.3 BALLASTS FOR HI) LAMPS
A. Electromagnetic Ballast for Metal -Halide Lamps: Comply with ANSI C82.4 and UL 1029.
Include the following features, unless otherwise indicated:
1. Ballast Circuit: Constant -wattage autotransformer or regulating high -power -factor type.
2. Minimum Starting Temperature: Minus 22 deg F (Minus 30 deg C) for single -lamp
ballasts.
3. Normal Ambient Operating Temperature: 104 deg F (40 deg Q.
4. Open -circuit operation that will not reduce average life.
5. Low -Noise Ballasts: Manufacturers' standard epoxy -encapsulated models designed to
minimize audible fixture noise.
B. High -Pressure Sodium Ballasts: Electromagnetic type, with solid-state igniter/starter. Igniter -
starter shall have an average life in pulsing mode of 10,000 hours at an igniter/starter-case
temperature of 90 deg C.
1. Minimum Starting Temperature: Minus 40 deg F (Minus 40 deg C).
2. Open -circuit operation shall not reduce average lamp life.
2.4 HB) LAMPS
A. High -Pressure Sodium Lamps: ANSI C78.42, CRI 21 (minimum), color temperature 1900 K,
and average rated life of 24,000 hours, minimum.
2.5 REQUIREMENTS FOR INDIVIDUAL LIGHTING FIXTURES
A. Fixture Type CIA: See plans for schedule
PART 3-EXECUTION
3.1 INSTALLATION
A. Lighting fixtures: Set level, plumb, and square with ceilings and walls. Install lamps in each
fixture.
B. Connect wiring according to Division 16 Section "Basic Electrical Materials and Methods."
END OF SECTION 16511
LIGHTING
16511 - 3
SA O6/2004
48
_ '.,. ..... �..�. nr, ..:. C "J,•�..� ."'^',^.^ern,• :,�...u.r r ....�,..rn'-m
'..i
1 1� TC INWDDIW)
.,.,+I. ,8/26/2004
pROp"¢"
THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION
ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE
"'
HOLDER THIS CERTIFICATE DOES NOT AMEND, EXTEND OR
Gregory insurance Group {
ALTER THE COVERAGE AFFORDED BY THE POLICIES BELOW.
1315 S. Clayton St., Ste 150 i:i j
,, COMPANIES AFFORDING COVERAGE
Dtauvex CO 00210 �' ++
r-nMPANY
_
A_
Farmer
IHBIIRED .. �
COMPANY
Glanx Electrical Contraol're
Inc s
1713 E . Lincoln Ave #A4111
CDMPANY
Fr Collins,CO 80524
C
(970) 482-521$ j
COMPANY
D
L'.I..,,,,...'
..,.
THIS IS TO CERTIFY THAT THE POLICIES OF INSURANCE
INDICATED,
STED BELOW HAVE BEEN ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD
NOTWITHSTANDING ANY REQUIREMENT ,'I'
CERTIFICATE MAY BE ISSUED OR MAY PERTAIN, TI F 9NSURANCE
F�M OR CONDITION OF ANY CONTRACT OR 01-HER DOCUMENT WITH RESPECT TO WHICH THIS
AFFORDED BY THE POLICIES DESCRIBED HEREIN
EXCLUSIONS AND CONDITIONS OF SUCH POLICIES. LIMU7$i
IS SUBJECT TO ALL THE TERMS,
SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS.
LTk
TYPE OF NSURANCL
,I!.
pp�a rytlM1�
�
' I.
�p
POLICY EFFECTNE
PCLICYCRVNAYION
LIMIT*
, I
DATE IM A)MYTI
DATE IINNIODIYYI
GENERAL
IJABLm'
GENERAL AGGREGATE
:
COMMERCIAL GENERAL LABILITY
"'
PRODUCTS-COMPJOP AGG
$
1p
CLAIM* NIAut ®iJCCUn
,i.• ;
rCROONAL & ADV INJUITY
A
OWNER'S& CONTRACTOR'S FROY
04596 9311; 1l
06/01/03
06/01/05
EACH OCCURRENCE
$
FIRE DAMAGE (Any arm fire)
S 100,000
ill !
MED EXP (Any am parmm)
$
I"
AUTOMOBILE
UUDUTT
k f
;:
ANY AUTO
i' I
I,
COMBINED SINGLE LIMIT
S
ALL OWNED AUTOS
p; I
.11000,000
SCHEDULED AUTOS
I'!
BODILY INJURY
(Par pmzm)
A
HIRED AUTOS
O4596 93i;
06/01/03
06/01/05
BODILY INJURY
NON -OWNED AUTOS
;b (
(Par ap6danq
S
,
i
PHOHhH I Y UAMAIitOARABE
m
LUV3ILITT
AUTO ONLY - EA ACCIOENT
S
ANY AUTO
I' 1
dl I
!
On IDR n IAN AUTO ONLY:
EACH ACCIDENT
$
EXCESS UABL17Y
AGGREGATE
S
n is
i'i
EACH OCCURRENCE
$
UMBRELLA FORM
�i',
AGGREGATE
$
OTI ICR n Wl UMDRCLLA rORM
�o' ;
wOIbiEA9 COAIPFNBATwN nND
Ce1P1.0YE11C LUtHILRY
II t..
!;I
--.,.,,.
TORY LIMITS ER
..... ....,.
::�....... .;,.; •."
EL EACH ACCIDENT
sloo -non
THE PROPRIETOW
PARTNERBIEXECUTIVE INCL
�I I
A0409 561:I:2
g
07/01/03
07/01/05
hL VI=Mt- YULIUY LIMIT
a
EL DISEASE • EA EMPLOYEE
$
OFFICERS ARE: EXCL
;;.
•
OTHER
1,
r; I
DEMORN'TION OF OPERATXXISILOCATIONEUnHICI MWINIECIAL ITEMS ,9
The Certificate Holder below ,4a':listed
as an Additional Insured with respects
to the above Liability policy'j!
garding Job #5874.
,.I��1T�nNO' n Gca u, I
;1 I
SHOULD ANY OF THE ABOVE DENCHNED POLICIES BE CANCELLED NCPOM THE
City of Fort yO11Yns i
SAPIAA7I0N DATE THEREOF. THE ISSUING COMPANY WILL %NCEAVOR 70 IMF
PO Boer 580
JO- DAYS WRITTEN NOTICE TO THti CERTIFICATE HOIAER NAmu TO THE LEFT,
Ft Collins CO 80522 it
OUT FAADJiE TO MAIL SUCH NOTICE SHALL IMPOSE NO OBLIGATION OR LIABILITY
Attn: John StephtanS
OF ANY.- UPON ANv, I CEN7B DR REPRESENTATIVES.
Farr 970 221-6707
AVTNOFI toA'
IIi i.
['"-':m„?'�""r..."dr-';[ _ •T___I r,,r '_.u., r ,.;;,..:, �Iil"'+f ,,,, ,;,(„1 r.:.1.�;�;L;; .. v7 .,�....::... .. .. ... ..... '. i; Aca�:u1iV G:LJ1iYURV4TTVH
1:0 39gd
da9 SNI AN09369 BOSLIP60ZL ZT:60 V00Z/9Z/80
EXHIBIT "A"
SCOPE
Electrical services for a building at Transfort per the attached specifications and drawings
titled: Alternate Fuels Station. Work may start as early as August 18, 2004 or as directed by
the Project Manager. Awarded contractor must sign the attached Service Agreement, provide
insurance per Exhibit "B" and provide performance and payment bonds per Exhibit "C".
Water, electrical power and sanitary facilities will be provided by the City at the site. Plans are
available at City of Fort Collins Purchasing Department, 215 N. Mason, 2"d floor and all
additional specifications are on the plans
7/96 Section 00610 Page 1
iXH
INSURANCE REQUIREMENTS
1. The Service Provider will provide, from insurance companies acceptable to the City,
the insurance coverage designated hereinafter and pay all costs. Before commencing
work under this bid, the Service Provider shall furnish the City with certificates of
insurance showing the type, amount, class of operations covered, effective dates and
date of expiration of policies, and containing substantially the following statement:
"The insurance evidenced by this Certificate will not be cancelled or materially altered,
except after ten (10) days written notice has been received by the City of Fort Collins."
In case of the breach of any provision of the Insurance Requirements, the City, at its
option, may take out and maintain, at the expense of the Service Provider, such
insurance as the City may deem proper and may deduct the cost of such insurance from
any monies which may be due or become due the Service Provider under this
Agreement. The City, its officers, agents and employees shall be named as additional
insureds on the Service Provider's general liability and automobile liability insurance
policies for any claims arising out of work performed under this Agreement.
2. Insurance coverages shall be as follows:
A. Workers' Compensation & Employer's Liability. The Service Provider shall
maintain during the life of this Agreement for all of the Service Provider's employees
engaged in work performed under this agreement:
1. Workers' Compensation insurance with statutory limits as required by
Colorado law.
2. Employer's Liability insurance with limits of $100,000 per accident,
$500,000 disease aggregate, and $100,000 disease each employee.
B. Commercial General & Vehicle Liability. The Service Provider shall maintain
during the life of this Agreement such commercial general liability and automobile
liability insurance as will provide coverage for damage claims of personal injury,
including accidental death, as well as for claims for property damage, which may
arise directly or indirectly from the performance of work under this Agreement.
Coverage for property damage shall be on a "broad form" basis. The amount of
insurance for each coverage, Commercial General and Vehicle, shall not be less than
$500,000 combined single limits for bodily injury and property damage.
In the event any work is performed by a subcontractor, the Service Provider shall be
responsible for any liability directly or indirectly arising out of the work performed under
this Agreement by a subcontractor, which liability is not covered by the subcontractor's
insurance.
7/96 Section 00610 Page 2
EXHIBIT "C°
SECTION 00610
PERFORMANCE BOND
Bond No.
KNOW ALL MEN BY THESE PRESENTS: that
(Firm)
(Address)
(an Individual), (a Partnership), (a Corporation), hereinafter referred to as the "Principal" and
(Firm)
(Address)
hereinafter referred to as "the Surety", are held and firmly bound unto City of Fort Collins. 300
Laporte Ave. Fort Collins. Colorado 80522 a (Municipal Corporation) hereinafter referred to as
the "OWNER", in the penal sum of in lawful money of the United
States, for the payment of which sum well and truly to be made, we bind ourselves,
successors and assigns, jointly and severally, firmly by these presents.
THE CONDITIONS OF THIS OBLIGATION are such that whereas the Principal entered into a
certain Agreement with the OWNER, dated the _ day of , 20_, a copy of which is
hereto attached and made a part hereof for the performance of The City of Fort Collins
NOW, THEREFORE, if the Principal shall well, truly and faithfully perform its duties, all the
undertakings, covenants, terms, conditions and agreements of said Agreement during the
original term thereof, and any extensions thereof which may be granted by the OWNER, with
or without Notice to the Surety and during the life of the guaranty period, and if the Principal
shall satisfy all claims and demands incurred under such Agreement, and shall fully indemnify
and save harmless the OWNER from all cost and damages which it may suffer by reason of
failure to do so, and shall reimburse and repay the OWNER all outlay and expense which the
OWNER may incur in making good any default then this obligation shall be void; otherwise to
remain in full force and effect.
7/96 Section 00610 Page 3
PROVIDED, FURTHER, that the said Surety, for value received, hereby stipulates and agrees
that no change, extension of time, alteration or addition to the terms of the Agreement or to
the Work to be performed thereunder or the Specifications accompanying the same shall in
any way affect its obligation on this bond; and it does hereby waive notice of any such
change, extension of time, alteration or addition to the terms of the Agreement or to the Work
or to the Specifications.
PROVIDED, FURTHER, that no final settlement between the OWNER and the
CONTRACTOR shall abridge the right of any beneficiary hereunder, whose claim may be
unsatisfied.
PROVIDED, FURTHER, that the Surety Company must be authorized to transact business in
the State of Colorado and be acceptable to the OWNER.
IN WITNESS WHEREOF, this instrument is executed in three (3) counterparts, each one of
which shall be deemed an original, this _ day of 20_.
IN PRESENCE OF: Principal
(Title)
(Address)
(Corporate Seal)
IN PRESENCE OF: Other Partners
By:
By:
IN PRESENCE OF: Surety
By:
By:
(Address)
(Surety Seal)
NOTE: Date of Bond must not be prior to date of Agreement.
If CONTRACTOR is Partnership, all partners should execute
Bond.
7/96 Section 00610 Page 4