Loading...
HomeMy WebLinkAboutBID - 17284 5814 LP TRANSFORMERS 100KVA (2)' • Box 580 Fort Collins,CO ;l.. •0. * •ERS x APPROVED 8Y: 3.2.2.5,2 High -voltage terminals shall be universal flowerpotbushing wells in accordance with figure 3 of ANSI/IEEE 385-1985. Two wells shall be provided and shall be connected In a feed -through configuration, toadbreak bushing inserts in accordance with Figure 5 of ANSI/IEEE 384-1985 will be owner furnished, 3.2,2,5,3 tow -voltage line and neutral terminals shall be Iw x 14" UNC-2A capper studs in accordance with ANSI C57.12.25. Bushing arrangement and spacing shall be shown in Fig. I of this Specification. 3.2,2.5.4 the low -voltage x bushing shall be a fully insulated bushing. A 6 ground pad shall provided on the outer surface of the tank and an external removable co r ground strap shall be provided and connected between the low -voltage %z bushing and the ground pad. 3.2,2.5.5 The high -voltage neutral shall be securely grounded internally, 3.2.2.E ACCESSORY CABINET 3.2.2.6.1 The accessary cabinet shall consist of a compartment containing high- and low -voltage bushings constructed in accordance with applicable ANSI specifications, including ANSI C57.12.28, tlimensions shall bo in accordance with Fig, I of this specification. 3.2.2.5.2 Cabinet doors shall be hinged, removable, lockable„ and of sufficient size to provide adequate working space when r ved or open. Unlocking the padlock shall peml t access to both the high - and low -voltage temfnations.. StainTess steel hinge pins shall be provided. 3,2.2,7 MtESSORY EgUiPMEXT Accessory equipment shall be provided in accordance with the following details: 3.2.2.7.I Deleted 3.2.2.7.2 The transformer base shall be arranged For rolling in two directions: Parallel 'to and at right angles to the center line of the high - voltage bushings. 3.2.2.1.3 lifting 'lugs or bosses for screw -in lift bolts shall be provided. These lugs or bosses shall be adequate strength and size and arranged on the tank to provide a suitable balanced lift for the compTetelp assembled unit„ 368- I2D 3.2.2.5.2 High -voltage terminals shall be universal flowerpot bushing wells In accordance with Figure 3 of ANSI/IEEE 386-1985. Two wells shall be provided and shall be connected in a feed -through configuration. Loadbreak bushing inserts in accordance with Figure 5 of ANSIJIEEE 385-1985 will be oar furnished. 3_2,2.5.3 Low -voltage line and neutral terminals shall be V x 14" U11C-21% capper studs in accordance with ANSI C57.12.25. Bushing arrangement and spacing shall be shown In Fig. 1 of this Specification. 3,2.2.5.4 The low -voltage X, bushing shall be a fully insulated bushing. A ground pad shall be provided on the outer surface of the tank and an external removable eo er ground strap shall be provided and connected between the lows -voltage %a bushing and the ground pad. 3.2.2.5.5 The hagh-voltage neutral shall he securely grounded internally. 3.,2.2.6 ACCESSORY CABiNEi 3,1.2.6.1 The accessory cabinet shall consist of a compartment containing high-- and low -voltage bushings constructed in accordance with applicable ANSI specifications, including ANSI C57.12.28, Dimensions :shall be in accordance with Fig. I of this specification. 3,2.2.5.2 Cabinet doors shall be hinged, retsovable, lockable, and of sufficient size to provide adequate winking space when removed or open. Unlocking the padlock ahall permit access to both the high - and low -voltage terminations, Stainless steel ivinge pins shall be provided, 3,2.2.7 ACCESSORY EQUIPMENT Accessory equipment shall be provided in accordance with the following details: 3.2.2.7.1 Deleted 3.2.2.7.2 The transforoer base shall he arranged for rolling in two directions; Parallel to and at right angles to the center line of the high voltage bushings, 3.2.2.1,3 Lifting lugs or bosses For serew-in lift bolts shall be provided., These lugs or bosses shall be adequate strength and size and arranged on the tank to provide a writable balanced lift for the completely assembled unit. ME REV. SYN: CC y ♦0' MAX f 2e lulu .".,:.».........m..,,. E #Ye AIIM WNiW MIN still t MRJ MiN 3��keN "f GABLE. ACCESSORY 32'mnK PAR0#G STAND m.... ... .... GROUND PAD s wNimvm GPEWNC, V aOnOM OF COVP,hRTMUT FAG. t OWNSQNS AN} 9USHING OGSIGNAMONS (Act to acwla) 4 368-I20 3, 2, 2, 7 4 The base of the assembly s ha I I be Pruq I (Wd with sui tabl e means for rmunting the unit or, the pad, An -Internal flange shall be provided at the base of the accessory C001part-Tent to provide means for mounting the unit on the pad. fFfq l), J-2,2 7-5 lerWral designaticns, are shown in Figure 1, 7)e identification Of te,mllnal connections shall be shown on the Instruction namplate, Instruction nameplate shall be located in the IN -voltage side and shall be readable with cables in place. Where the namepCate is wwrted on a rm=vable part, themanufartoner's name and transformer serial number shall be permanently affixed to a non-refnDvabie part instruction nw.plate shal I contain the -vnforrwt)or Specified in 5.12 of ANSI gameplate A Also, m thr rarreplate, or label affiKpd near it, tMe maniffacturer shall Indicate that the dielectric fluid contains less than I ppm PCB. 3.2.2,76 A suitable mark^ni3 Inside of the tank, shall indicate the C(i•rrect oil level at 25,,r i k 1 3.2.2 An asjtcmattc pressure rol"ot device, shall he locatro withfn the compartuent. This devilce shall neet the following re;uirewnts: NPT or larger -ale "rilet Port I sed parts at weather and corrosiar� resistant %at-e-rials, lion -deteriorating gasket and o-ring llarua 1,yLOI Pinq abl(, to withstand !� pound for--r? rjoitum, 606Y able to w',thstaid IC;0 pound shear' fierce m,rAwm. M shield. Cracking lessors of 10 t 2 iisi ' 9 Resealing pressure at' 8 ± 2 psil. Zero leak rate from 8 It 2 pstq to -8 prig. Minimum flow rate cat` 35 SUM at 15 psjg. M RJE 1lM-0-1*1' overload sensirjg base and internally wunted partial rarge current limiting fuso 0all he furnlsr,*d as follows: BAYQ,NFT FUSE orv. 354317FM51M (175,a7) or The W-0-KET fuse shall be located in the high voltage ,js� of the coMartwot. 3.2Z8 OIL PRESERVATION TransforFw,rs shall be of se.alj�,j tart: Cor,,,StrnCtjon. Sealed,tank corstrixtion is that which seals the +,ntprior of the tank frM 1,bp atmosphere, and in which the 9iis, plus the oil vo;une rtrains constant. The transformer will resin effectively reajeo for a top -oil temperature range- of I$C to 10hQC Iz 368-1,241 3.2 . 2.9 TAWS the tank shall be do or sloped to shed water. The tank shall be of sufficient strength to support a minimum of roo JbS, vertical !,oad. Constrixticnof the taro shall be in a,-cOFddnr-e witn ANSI C57, -12.25-1911t. paragraphs 6.1 and 6,6 3.2,2-9 1 Tt* cover Shall be welded Construction 3, ? D I 2 Tank nd i q � ha I I cors i i it of to steel pads , each with ine provi sic 13 P1C tapped hole. 716 irch deep. 31,2,9,3 These ground pads Shall be welded on the transforuter tase Or eii th°* tank oa)l near the base, one in the high -voltage S'de arrd one in the, low -voltage side. Ire cases where the transforwr 'Lark aM coapartments are separate, provisions shall bemade frkr electrically connecting thy, 3-2.2,4-4 LoCkirk) ecl-,!; shall be peritahead. 12.2.10 CORPOMENTS FOR LMD PRIMARY their,intm.Lo current -carrying capabtlit,yotcompoats for thie looped pryMary cable system shall ba, PilC amperes (cmtlnuous) and 10,M0 amperes sy".)etrical (momentaryl, 2 . 2, 11 AUDIBLE SOUND LEVEL the A;JdTblP sound level Sh,811 L-e it dCCrwrdance witr NF?,f,,Vk 1-,tandar(j TR t %0 3-19.2,12 BASE PLAN the base plar of a complist,ely aszPmbled UnIt Shd7l be such Utial. It Carl be installed on a pad Of the r is Shown in Fig 111, PAINT EFT "Flotshing &uidelirec" specification Shall aipply Flnj5h Coat shall be S;lver Green, W;nsol I f,,yjY 7iglossy, 2 3 " ,2,14 LOSSES ,h e total losses of transformer shall ie the som of &,e excjtat)orr losses and the load losses tYR 'osses). Load loss test: shall be porforTed and reported on all urits regardless of whether -r not I record of such tests is available or duplicate snits. Loss eVdIUdtiGrIS and loss casts will be based oa the values sno4rt jrj the 'Special Coflditim5 and Supplemental Instr),ictiorr to Bidders." Transformers will be, evaluated on excl ' tatior losses er,� I k losses at the, specified rates, It tested lasses exceed (11jote lasses but are, within tine tolerances of fable lkl, ANSi C57 the REV. Stm: D-D 3 2.2,14 (Cont.) additional cost incurred from the different'al of losses wjjl be calculated using the fallowing equation and the above spe-Ifled rates and will be deducted f'roithF, original P-,irchi5e 01rdCr o'back I charged to the manufacturer, In Table 18 and the fol](yong eomiation "Url'W shall Mean "Transformers of the same SiZL and design on one ruder ", Excess loss S [NO, of units? [Mo Load L055 Evaluation s) (Av9. NO Load Losses Ouoted No tiiad Lasses) + (Load Loss FValUatIM $) fkg, Load Losses - Noted Load, Losses)], If this equation results in a regative number, no credit will be given the SupDTiFr. If any unit or units exceed the tolerances Gf T,5ble Ill. ANSI C57 12 M-1987, that unit or units shall not he Shipped without express perrmis,.00n from the City. If accepted. the dedixtion for Qxcess hisses wi I I be based on the fal I oul no equal. I orl: Excess Sass Z = (No Lead Loss i-valuatim S) (No Load tosses - hooted No Load Losses) 54t Not Less Than Zero + (Load 1 - oss EvaIL6,atfiy, s) (1-jad Losses - Cuoted Losses) But Not Less Than Zero 31 2,15 SAFETY LABEtS NE?Pli 1260 Safety Labels shall not be applied fay the mdny.acWrer Purr-,haser will apply ousts r "Mr. OuLh" labels after doljver� SPECIFIC REMIRMNTS FOR OCSISU Or 368-120.180 'file requirements for 3tr8,1?10-180 trarsforrer shall bc- the same as the -117,01 with the following iweptlors; 3.13t i RATING The transfcrmpr shall be rateO, as follor4s' .13 KVA Capacity W b) Tinpedanrp 2 M imin. - 2 79t max 3. j , "I PUS I NG An RTF HAY-O-NET overload sensing fuse and internally mountpd EI-SP partial range current limit,,-inq fuse shall be furnished as fp7lows: 3SOC12 ante F13P 35432(1X51M (200 &ap) or two C-1 - 1. SP 83PIWS (?Or A) The BAY-O•NET fie shall be IoCaLtd 111 "�e high VOlt-49e side ;ff the compartment, 14 36R 120 LTA .13,3 LOW VOLTAGE BUSHING TERMINAL$ The ow -voltage bushings shall be I' x 14 IAC - 2A copper studs In accordance with ANSI C67 12,25, 3.4 SPECIFIC REQUIREMENTS FOR DESIGN OF 368.1,20-190 The riulrevnts for 3R-120-190 transformer shall be the sap* as the -1 0 with the foliowlN exceptIC415, 3,4.1 RATING The transfor7,p-r shall be f1tited as foliows: a) KVA Capacity 250 b) Impedance 5,751, 3.4.2 FUSING An RTE BAY,f)-NET fault sensing fuse and internally mounted I'tLSP partial rang ,e current limiting fuse shd'11 be furnished as follows; P1--Q-Wj-f 1,15—F LL—ILISLL51 353CI4 two ELSP 31&41175M51A.M [350 app) or two C,TA SP83PI50-S I300A) The PkY-0-NLT fuse shall be located in the high vDItage VIde of the compartment. 3.4.3 LOW VOLTAGE BUSHING TERMINALS The `ow -voltage bushings shall be 114" x 12 OiF , 2.4 cspper studs. 35 SPECIFIC REQUIREMENTS, FOR DESIGN OF 368-120-130 The rquirewents for, 368-120-130 trdrsformew s1rall be the same as the -170 with the following exception$ - RATING The transformer shall he rated as foil-ows; a) KVA Capaclty 25 b) Lmpedance I f1 Win - 2,16% max 2.5.2 LOW VOLTAGE BUSHING TERMIKAI.S, The LOA-voltage buShIrlijS S10all be 518' x 11 LILAC-bCooper StUd$ MMEMEM.- 3.5.3 FUSING An Ric BAY-0-NET overload sensingorited ttisfuse and internally m partial, range current liffl-ring shall be furnishpo as vj,cws. flAY,:Q.ALLfME I- r A-RU-SE151 359C5 orP ELSP 3543GA115IM 06 amp) or one CJ. SP 013P50-5 (50 amp) The [!Xf-O-W fue shall be localled in the higr voltage side of the coripartment, 3,6 SPECIFIC REQUIREMENTS FOR DESIGN OF 368.120-150 The requirenerts for 368-120-160 tran.5formar shall be the same as the 170 with the fol3owiN exceptim: 1,6,1, RATING a) KVA Capacity „dG t) Impedance 1.77% mil to 3,I6A any, 3,6 2 LOW VOLTAGE TERMINALS The l� -tolnige terminals shall he 5iR' ); 11 (Wl`-2A copor s7uds. 3,6,3 FUSING An RTZ ,Wi-O-NET overliwd neri$im use and -nterrally mounted U-SP partial range current limil."pq fUSe 9401 be I`UrrlShed as fIJTIPMS, 8AY_4:fjj 3158CR are FLSP 3543H.OMHM +,60 airp) or arm C.f,1. SP 83P80's (80 amp) The BAY -O,NET fuse shall be located Ir, 0e Hglt 4a)Itdge side f)f the cormart-mmt, 16 369 - 170 n 4, 1, J RESPONSIBILM FOR INSPEMON Unless othprAIse specified, t'he vendor Is responsible for the perforlildnce of all irspection rv( �rwprts as specified herein. Except as atlierwisf �I7,e vendor may utilize his ow facilities or arty commerci . a) laboratory acceptable to the City of Fort col 1 i� ns, The City reserves uhe right ght to perform or wi triess any of than inspections set forth in this Specification where such inspections are deemed freces&ar�), 4.1,2 TEST REPORT The manufacturer shall furnish to the purchaser certified coples, of the resalts of 'lass tests prior to paywrit, Copies shall be sent to the Design Svectior as Will oss with the invoice Unsigned copies are not acre table even if ac(arr anied by a signed cover lotter. The 0.jallty table Manager Oia'T rpOpw and sign each te,� t ,,t report, 4.2 TEST CONDITIONS Jnless otherwise specific-d, tes tirg required by 5cctton 4,4 shall be conducted kinder true tollowinq conditions: 4.2.1 RUEJREK� TEMPERAURE, "hie reference t erature to whia losses, iffpkarr'e, regulation, and efficitaricy are corrected shay be 85%'. 4 2,? TOLERANCE ON IMPEDANCE VOLTAGt ImpMarce on corpleted units stall fal I witAlIlln the NflgO specified here'{ n The percent, iJeparturo of tested impedance wc)ltagr. -nn any tap from tested impedance voltage at rated voltage shall riot be greater than the total tap voltage range expressed as a percentage of the rated wel td9e . 43 Not used. 4 4 TESTS 7bo kinds of tests to tip wrfarmc�d and thp tesr; prrcPdkirP,,; shall be as specifted in ANSI C57J2.20, ANSI C57,12,W and C57 12,90 except as specified herein. 0 kM SM Ail 4.4.1 DIELECTRIC TESTS No applied potential test shall be nade. The Induced -potential test shall be made by applying between the terminals of one winding a voltage which will develop from high -voltage line terminals to ground a voltage of 1000 volts plus 3.46 times the rated transformer winding voltage. 4.4.2 IMPEDANCE AND LOAD -LOSS TESTS Impedance and load -loss tests shall be made on each unit and nay not be omitted even if a record of such tests made on a duplicate unit is available. A 368-120 REV, SYM; AA ITEMS COVERED BY THIS SPECIFICATION OESCRIPTIOH STOCK 140. SPECIFICATION NO. SE'PIAE 25 KVA 120 240 X'frm. 368-120 -130 50 KVA., 120 240 3°frm. 368-I20 -150 100 KYA, 120 240 X'frm. 368-I20 -170 I2O 2401['fr�n. JgB_120 -180 t1lolKVA, KFA I20t240 X'fro. 368-120 -I90 2 368-120 REV. : EE REV. SM AA 6.0 DEFINITIONS AND ABBREVIATIONS 6.1 Vendor or Supplier - The manufacturer ,andjor manufacturer's agent supplying or quoting on the specified article. 6.7 Article, Unit, Assembly . All refer to the equipment defined by this Specification. 6.3 K or d.c. - Direct Current. 6,4 AC or ax. - Alternating Current. 63 °C - Degree Celsius (Centigrade) 6,6 OF - Degree Fahrenheit L l kv - 1000 vol t.s� 5.6 CPS or Hz - Cycles per secend. 63 psig - Pvupds per square inch gauge. 6.10 V or v - Volts. fill KVA - 1000 volt-amperes. APPEND!% A ftgures IA demonstrates the coding method used to establish City of fort Gotlins stock numbers for transformers. 3 FlGl1RE 1A REV. SYII1; AA TRANSFORM{ R STOCK NUMSER CDD; HG I , SINGLE PHASE I [C xY L 1 T P ----, OTHER 11. THREE "ASE �xo 0 m 5 KVA 5 .t 50 KVA 1 ft 10 KVA 6 n 75 KVA Z = 15 KVA 7 . 100 KVA 3 . 25 KVA 8 . 167 KVA 6 w 37.5 KVA 4 - a+tn eva 1 g single voltage 13,2Y/7620 and 7620/13.2Y X 2400/4160 mutsldao {axle = 13..2Y/7620 E'SNA We - 1 .2YI 620 E511A ad Ingle Phaaa Transformer Class 006 * 75 KVA 015 # 1,50 KVA 030 - 300 KVA 050 * 500 KVA 075 a 750 KVA 100 * 1000 KVA 150 1500 KYA xrz .r, 1 R 490Y)277 fiAa- phase load Transformer Class U/20BY/120 set, BE APPENDIX B (This Appendix is not intended to dictate rvquireaents for items purchased under Specification 368-120 but is included as an aid to those users desiring a minimum of pad designs for the transformers coveredby Specifications 368-120.) the dimensions in inches of figure 1B will fit the mWOOM compartments on transformers covered by this Specification as well as the Maximum transformer envelope. - - 36B -120 REV. S� 31 4 M!' --- -- 2e�v - -- LS* 21 IL It, 1p*4 t 1, 3 AMC A, �v IV, 'M H Notes on Pad Katergaq COnrrBtk Ook4cit la# 3,UQkl psi rir(jm, Ko-Imum Coarse oqgrRQ'�te 5iirp 1 :icy vncbe5" Space ro"'.Mantx PP"' pad and pro,ary uwtolmg .4' ganera';ly e* T X FAC"tor5 to be bon%bot,ed in to"Axq tt7e ".d W--bele ncid te)aU be bdOm ti-ocks Mll)"4 fat- A.w flSlaqttium and rcmavAi of traneFDr"ri- Surh arresmbwtySho,N qg+, reqre InCru;swin on adjacent property. Prswoity of Fisl*iga. Voils, 8r criers, cod/0', 1n Addit" to the 10,1§6+oftCP.5 lqrT-e'vfur frQftt of k;me t'MnVftev' pool thaLl Ipe, alght (D) Felt and the 1�t4wllll rita'stnce rrcre all other vcwx Ozh be two C?) +eot- 1, the oeizJ;oq has an avvrhto!3. vArarance -to the vd9v ot' Thl 1wn5FOr-ner Pool bhaBt be, neawwrad from the rna+,'Qr adage 1?F 'the overhan Trar,aforncrs theoo,�,b 100 XIVA may be iisiutlpd dpa'vo, oet-rh" 0' the vpnical k:ilt.ran the pad 5)d -,he Oueehbmg e; at leo5t r"!l f'"t aloi the k,+Lutpom it acrvsllkll' to I," dc" trsclo;-, 3 Codes and Standatds •, to aoVit-cn lz thv ab.reC, the estaltwtlon V16MU Cumfo,-' lu the qatomi FLtr. Lllr Codr elol 4�edkrAl' State and C&ty Cakips t'4 stiiedii'm' Uly OF fuicl cul'�'414S TRt"O�iFFRPZR PAF� J)CSa,7,N LEGHT AND POWER' 'ta & 1('� v K--MON DAML Nnv� -�. 1990 — 24 368-]ZO REY, S Mr. AA a The following forms for individual and Average Transformer Losses are used by the City of Fort Collins to determine lass penalties. 1) transformer Loss Evalvatton Average Losses Form 2) Individual Transfor r Loss Evaluation farm UEEK031M, City Order #a, Manufacturer KVA/Unit Date S/N __— Invoice No, Average core losses Quoted core losses Excess average core losses: line (2) less line (3) Penalty for excess average core losses: line (1) x1ine (4) Average copper losses Hunted copper losses Excess average copper lose$: lime, (6) less line )7) Penalty for excess average copper losses: line (1) x line i$) x P'eAAItY to be assessed manufacturer; line (5) plus line (9) but not less than Zero Prepared. Ry: Fes—ign �Enqifleerinq t0l'rf: If any UAit(s) exceeds the 105s tolerances of ANS 07,12.0G. tight & Power wit) either reject it, include it on these averages, or calculatp lasses using the individual Transformer Losses Evaluation Form, whichever is most favorable to Light and Power, M REV. SYM: AA INDIVIDUAL TRANSFORMER LOSS EVALUATION 6ity Order No, S Manufacturer invoice No, KVA/Unit Lm DESCRIPI10 (1) Tested core losses (2) Quoted core losses (11) Excess care lasses line (1) less line (2) but not. less than zero (4) Percent difference yy line (3) .4. lies@ (2) x ICO (5) Tested total lasses (6) Quoteii total lasses. (2) Excess total lasses lane (5) less line (6) but not less -..- . than zero (0) Percent difference line (1) -i- lime (6) "" (9) Tested copper lasses (IO) Quoted copper losses (11) Excess copper lasses line (V) less line (10) but not less than zero (12) Penalty for excess care lasses line (3) x $ (13) Penalty for excess copper losses line (11) x $ (14) Penalty to be assessed Manufacturer line (12) plus line (13) Nate _ _ Prepared By: Oesi�n Engineering Transformers purchased under this Specification shall be of the make shown below. Manufacturers not listed below may submit written proposals demonstrating compliance with these Specifications for consideration of addition to the accepted manufacturers list prior to the next request for bids. In addition to inclusion on the list below, maaufacturer's equipuent must also satisfy all requirements of this Specification to be acceptable. fAkLWER STRIAE tib. Alit Al Cooper Power Systems All General Electric All froward industries All The manufacturers in the following list have been conditionally approved :and may bid as an alternate. The definition and intent of "Conditional Approval" of a manufacturer is to allow the City to gain some experience with the manufacturer's product. Should a conditionally approved manufacturer be the evaluated low bidder, tile, City reserves the right to award all, part, or Wane of the order to them, dependant upon the current needs of the City for that item or items, REV. SYM, EE Issued: 8/17/72 Revised; 1/21/94 Special Conditions and SupplementalApplicable Instructions to Bidders Specification 368.120 A, Data to be Supplied with Bidder's Proposal The following data shall be supplied with the bidder's proposal in addition to that information required by the "Invitation to Bid" and the Turchase ReWisitionv, 1. A typical list of users of 1 phase padmount distribution class trarmformeP5 manufactured by the bidder during the past five years. 2. A typical drawing of the transformers showing that they will meet the critical dimensions rewired by the Specification, 8„ 1 dance volts in % at full Thad, high voltage to low vo3tage at WC. 4. No load and total losses at 85"C, 5, Delivery in weeks. 6. A statement indicating compliance with our Specification without exception or a detailed list of exceptions. 7, Escalation is is not applicable for the transformers bid. If escalation applies, the Bidder shall indicate in his bid the specific items or materials subject try escalation, and shall give the methgd and indices to be used in computing the amount thereof. Escalation occurring after the quoted delivery date will not be paid unless delays are the result of actions by the City Escalation occurring after acceptance, if Purchaser exercises the option to delay shipment after manufacturing is completed, will not be paid. If the above information and compliance statement are not supplied. the proposal will not be evaluated. An alternate bid for the total order say be submitted in addition to the unit bids, B. Loss Evaluations Loss penalties and loss evaluations will be based on the following values: I, No load or excitation losses at $3.90/watt, 2, Load losses at Si.SilJwatt. C- Shipping Terms D. Te s of Payment I. If escalation applies, the City of Fort Collins shall not be billed for escalation occurring after the promised delivery elate. 2. 'nest reports shall .ace rky the invoice. -If test reports do not accompany the invoice, late pa rit penalty charges incurred doe to belays in obtaining the test reports wilt not be paid. Certified copies of test reports shall be sent to the Design Section, Fort Collins Light and Rower utility. 3. Loss penalty credits and escalation charges shall he itemized on the invoice, REV, S: EE LIST OPACTIVE PAGES 1.0 2.0 3.0 3.1 3.2 3.3 3,4 3.5 3,6 4,0 4.1 4.Z 4.3 4.4 5.0 6.0 Titlepage .......................................... Items Cowered by this Specification........... Revision Recoril.,.,...... ............. ,............. List of Active pages ................................ Table of Contents .................................... Scope.............. ...........................»,... Applicable Doc eats ................................ Requirements.......,.. .............................. General Requirements for Design..... ....... ___ Specific Requirements for Design of 368-120-170,.... Specific Requirevents for Design of 368-120-180,,,.. Specific Requirements for design of 368-120-1g0..,.. Specific Requirements for lirsign of 368-120-130..... "specific Requirements fur Plesige of 366-120-150..... duality Assurance ...... »........ ., General q.c...................... Test Conditions.... ............. .......»,....,.,. RotUsed ............................................. lists.............................................. Preparation for Delivery. ............ Definitions—,.. ..... .............. Appendix A— ............... Appendix 8.... ........... ........... ....,.,....,.,,. AppendixC.......................................... Appendix 0.............. ..»...... ....»,...,.,,,,..,. 1 2 4 5 6 1 7 1a 14 15 15 16 17 1.7 1i 17 17 19 20 21 23 25 28 MM SPECIFICATION FOR PAD -MOUNTED CANPARTNEt'li`A,L-TYPE, SINGLE-PNRSE DISTRIBUTION TRANSFORMERS NITI4 SEPARABLE INSULATED LOAD BREAK NION-VOLTAGE CONNECTORS 1.0 SCOPE 1.1 This Specification establishes the minimum electrical requirements and mechanical features of a single phase, 60 NZ, mineral oil immersed, self -coaled, pad -mounted, compartmental -.type distribution transformers rated 250 KVA and smaller, high Voltage 13,200 Grd YJ7520 volts, with separable insulated load break high voltage connectors, These transformers are used for step down purposes from an underground primary cable supply, 1.2 This standard generally conforms with ANSI requirements for pad. mounted compartmental -type, self -cooled, single-phase, distribution transformers, C57.12.25. Z-o APPLICABLi DOCUMENTS The following documents of the issue shown form a part of this Specification to the extant specified herein, an those cases when the document is note dated., the latest issue in effect on the date of invitation fur bids shall form a part of this Specification. 2,1 ANSI C57,12.00 Distribution, power, and rOgulating transformers, and shunt reactors, general requirements for, 2,2 ANSI C57,I2,25 Para mounted, compartmental -type, single-phase, distribution traiisformors with separable H-V connectors, standard requirements for, 2.3 ANSI C57.12.28 Switchgoar and Transfor rs 11 Pad. -Mounted equipment -Enclosure Integrity, Z.4 ANSI C57.12.70 Terminal markings and cortnertlons for distribution and power trans, formers. 2.5 ANSI C67.12.80 Terminology for power and distribution transformers, M 2.6 ANSI C57.12.90 Distribution„ power, and regulating transformers, and shunt reactors, test code for. 2-7 IEEE C67.91 Guide for Loading Mineral -Oil-I rsed Overhead and Pad -Mounted Distribution Transformers Rated 500 kVA and Less with 65 % or 55 % Average Winding Rise. 3,O REQUIREMENTS 3,1 GENERAL REQUIREMENTS FOR DESIGN 3.1.1 BASIC DESIGN STANDAADS Transformers purchased under these Specifications shall be new and, unless otherwise specified, meet the requirements of the Applicable ANSI Standards and the 00difications and additions given in the subsequent paragraphs. In case of conflict, the requirements of the following documents shall apply in the priority shown. al This Specificatioim b) Applicable ANSI Standards Approved manufacturers are, listed in Appendix D. 3..2 KILOVOLT -AMPERE TEMPERATURE RATINGS 1400v01t-asapere ratings are continuous and are based on not exceeding either a 650C avierage winding temperature or an ao°C hot spot temperature rise. ThP temperature rise of the insulating all shall not exceed 650C when measured near the top of the tank, The temperature rise is based on an altitude of 3,300 feet, The transformers shall he designed for overloads based on IEEE C51,91. 3.1.3 GENERAL CONSTRUCTION S.I.3.1 The pad-sounted compare ntal-t,ype transformers shall consist of the transformer tank and high-and-liow-voltage cable terminating c0dipartment constructed in accordance with ANSI C57,12,25 and ANSI C:57.12,28. The terminating compartment and tank shall be assembled as an integral minit, tamporproof and weatherproof for mounting on a pad. There shall be no exposed screws, halts, or other fastening devices which are externally removable, The cover shall be welded construct.iori. There shall be no opening through which foreign objects such as sticks, rods, or wires might be inserter) to contact live parts, Suitable moans for padlacking the cemapartment doorisl shall he provided. !REV, SYM, 80 1,1.3,2 The high- and low -voltage compartment Shall be located side by side on one side of the, transformer tank, When facing the compartftent, the tow -voltage side shall be on the right. 3.1,1,1 Gonstrtretioe of the unit shall be such that it can be lifted, skidded, and slid into place on the mounting pad without disturbing the entrance cables, 3.13.4 An undercoating over the regular finish or an equivalent treatment shall be applied to all surfaces that are in contact with the pad to minimize corrosion. 3A ,3,S hiinimus dimensions shall be as shown its fig. 4: i REV, SYM: BB 3.2 SPECIFIC REQUIREMENTS FOR DESIGN OF 368-120-170 3.2.1 FUNCTIONAL DESCRIPTION 'rho transformer shall be a single phase, pad mounted, loop feed -- safe break, *deadfront" type for use on a 13,8 kV grounded OY" distribu-tion system. 3.2.2 DESIGN AND CONSTRUCTION 3.2,2.1 RATING The transformier shall be rated as follows: a) KVA Capacity 1010 b) High Voltage 13,200 Grd, Y/762q volts c) Low Voltage 2401120 d) Taps Two - 216 % FC above and below normal e) Impedance 1.95`K min. - 2.341% max, f) polarity Additive 3.2.2.2 INSULATION LEVEL 3.2.2.2.1 The basis impulse lnsulatiun level )8IL) of completely assembled high -voltage and low -voltage terminals shall be 95 kV and 30 kV respectively, 3,2.2.2,2 Dielectric test levels shall be in accordance with the distribution levels in Section 4 of ANSI C57,12,00, 3.2.2,3 HIGH -VOLTAGE TAPS A no -dead tap changer with, external operating handle shall provide two, - 2Y2% full capacity taps above and below normal. The tap changer operating handle shall be located within the high -voltage terminal side of the terminal compartment. 3.2.2.4 NOT USED 3.2,2,5 BUSHING WELLS AND TERNINALS 3.2.Z.5.1 The number,, location, and arrangement of bushing *dells, terminals and parking stands shall be as shown in Fig. 1, All low -voltage bushings and high -voltage wells shall be externally clamped and shall have leads of sufficient 'length to allow them to be changed without removing the cover. Welded bushings and wells are expressly prohibited. [w A