Loading...
HomeMy WebLinkAbout102795 WESCO DISTRIBUTION INC - PURCHASE ORDER - 3305524 (2)THE CITY OF FORT COLLINS UTILITIES Light and Power Department P.O. Box 580 Fort Collins, CO 80522 SPECIFICATION NO: 368-1 1 U TITLE: Single Phase Submersible Cover Mount Transformer APPROVED BY: Tim M. Sagen Standards Engineer Manager ORIGINATED: June 1999 LAST REVISED: December 15, 2000 REVISION DESCRIPTIONS REVISION DESCRIPTION APPROVED REVISION A Tim Sagen • Revised tank material in section 6 Bill Bray 12/15/2000 2 368-110 Specification for Single Phase Submersible Cover Mount Transformer 1 SCOPE This specification and the accompanying drawing (368-110.dwg) establishes the minimum requirements for an alternate design to City of Fort Collins Light and Power Specification 368-105 for single phase 60 hertz mineral oil filled self cooled vault type distribution transformers. The requirements of Specification 368-105 and applicable American National Standard requirements for distribution transformers shall apply except where specifically altered by this Specification. 2 PRIMARY a. 13,200 GRDY/7620, No Taps, Single Voltage b. Radial feed (1- HV bushing) c. ESNA long shank wells welded to tank d. "NO" inserts provided 3 SECONDARY a. 240/120 volt, 3-wire (3-bushing LV pattern) (exception to 368-105 Table I, cannot be banked for 3phase 208Y/120 service) b. X2 internally grounded (clarification to 368-105 paragraph 3.2.4.2) c. Welded Central Moloney bushings with external epoxy (dia. <1.38 see 368-105 Fig. 1) d. 5/8" threaded copper stud termination e. Additive polarity 4 ELECTRICAL REQUIREMENTS a. Frequency: 60 Hertz a. KVA: 25, 50, or 75 as requested b. BIL: 95 kV c. Impedance Limits: kVA Impedance %Z 25 1.77<%Z<2.16 50 1.77 < %Z < 2.16 75 1.86 < %Z < 2.27 3 368-110 5 FUSING (EXCEPTION TO 368-105 TABLE 1) a. Submersible type bayonet with overload dual sensing fuse element as shown below. b. RTE ELSP 8.3 kV under oil partial range current limiting fuse as shown below. c. "NO" low voltage under oil breaker kVA RTE Bayonet I RTE ELSP 25 358C05 40 amp 354304OM61 M 50 358C08 80 amp 354308OM51 M 75 358C10 125 amp 3543125M61 M 6 TANK DESIGN a. Tank material .105" (12 gauge) stainless steel (Tank - 400CB SST; Cover - 304L SST) b. Tomko 1720K-1 pressure relief device located on cover c. Tank drain 1.00" NPT flush coupling with brass pipe plug d. (2) 1.00" NPT fill couplings located on cover with brass pipe plugs e. (1) Tomko LG35 sight gauge/oil level coupling f. (2) V - 13 SST ground pads centered on tank below primary bushing 7" from top and 7" from base respectively g. (1)'/2" - 13 SST ground pad on top near primary bushing h. (1) SST loadbreak type parking stand i. Cover to be welded to tank j. Welded base runners k. (2) Lifting hooks opposite each other welded on the front and backside of the tank near the top 7 MARKINGS a. X1, X2 & X3 SST identification tags with black lettering b. "X2 Int Grid" stenciled in black on cover c. Bayonet warning decals located near bayonet fuse d. SST nameplate in accordance with paragraph 3.2.5.6 e. Temporary serial/shipping card attached to tank lift -eye 8 MISC. DESIGN ISSUES a. Cooling 650C AWR, average ambient 30°C (55°C AWR and 40°C ambient) b. Final color ASA 70 Gray c. All exposed parts shall be constructed of corrosion resistant material; e.g., SST, brass, or plastic d. Each unit shall be shipped on a two-way pallet with a minimum opening width of 34" 4 368-110 ITEM 01 HIGH VOLTAGE BUSHING WELL 02 LOW VOLTAGE BUSHING (5/9-fi UNC STUM 03 PARKING STAND (LOADBREAK TYPE) 05 STAINLESS STEEL TANK (Tank - 400CB SSTt Cover - 304L SST) 06 LIFTING HOOK 08 SST NAMEPLATE 11 PRESSURE RELIEF DEVICE (TOMCO 1720K-1) 12 1.00-NPT DRAIN PLUG 14 OIL LEVEL GAUGE (TOMCP LG35) 16 1/2-13 UNC SST GROUND PAD 18 SST I.D, TAGS FOR ALL BUSHINGS 21 TRANSFORMER SUPPORT RAILS 31 SUBMERSIBLE BAYONET IN SERIES WITH UNDER OIL PARTIAL RANGE CURRENT LIMITING FUSE Post -it® Fax Note 7671 Date pages) To ,'^fV-/ From Co./Dept. Co. Phone # Phone Fax # 3 L 55 2 v Fax # 1.7a Ku