Loading...
HomeMy WebLinkAbout131436 METRON INC - CONTRACT - CONTRACT - 15876SERVICES AGREEMENT THIS AGREEMENT made and entered into February 10, 2003 by and between THE CITY OF FORT COLLINS, COLORADO, a Municipal Corporation, hereinafter referred to as the "City" and Tecknit, Inc. Doing Business As Metron, Inc., hereinafter referred to as "Service Provider". WITNESSETH: In consideration of the mutual covenants and obligations herein expressed, it is agreed by and between the parties hereto as follows: 1. Scope of Services. The Service Provider agrees to provide services in accordance with the scope of services attached hereto as Exhibit "A", consisting of sixteen (16) pages and three (3) drawings, and incorporated herein by this reference. 2. Time of Commencement and Completion of Services The services to be performed pursuant to this Agreement shall be initiated upon signing of this Agreement. Services shall be completed no later than 60 days after Notice of Award. Time is of the essence. Any extensions of the time limit set forth above must be agreed upon in a writing signed by the parties. 3. Delay. If either party is prevented in whole or in part from performing its obligations by unforeseeable causes beyond its reasonable control and without its fault or negligence, then the party so prevented shall be excused from whatever performance is prevented by such cause. To the extent that the performance is actually prevented, the Service Provider must provide written notice to the City of such condition within fifteen (15) days from the onset of such condition. 4. Early Termination by City/Notice. Notwithstanding the time periods contained herein, the City may terminate this Agreement at any time without cause by providing written notice of termination to the Service Provider. Such notice shall be delivered at least fifteen (15) days prior to the termination date contained in said notice unless otherwise agreed in writing by SA 10/01 VFD pump can no longer maintain pressure while at maximum speed, the second VFD driven pump (60 hp pump) will be started, and the 20 hp pump retired. As flow continues to increase, the first VFD driven pump (20 hp pump) be started resulting in both VFD driven pumps to be operating. C. An algorithm shall be included for accurately reducing the VFD pump speed as the next sequential pump is started so that no pressure surges are generated during the transition (even with across the line starting). If the user prefers to switch the VFD from pump to pump for sequential starting, he can select this option with the OID. d. As the flow begins to decrease, pumps will be sequentially turned off until only a single VFD driven pump is operating. When a no flow condition occurs, the VFD pump shall be turned off. e. The pump station shall be programmed to provide a discharge pressure of 100 psi, at a flow of 675 gpm. Note the maximum flow available at a discharge pressure of 100 psi in shop drawings to be submitted for review and approval. 2.32 ELECTRICAL CONTROL PANEL ASSEMBLY A. The control panel enclosure shall have a NEMA-3R rating. All external or door mounted operating devices shall be dust and weatherproof. All internal components shall be mounted on a removable back panel. All wiring involving internal power and control components shall be completed within this enclosure. No external cable trays or wiring thruways shall be permitted. No water line connections shall be permitted anywhere inside the enclosure. B. All wiring shall be 600 VAC rated, THW or THWN, stranded copper wire installed according to National Electrical Code standards. All wiring from the control panel to the motors shall be sized according to NEC requirements based on motor full load current. A grounding cable sized to NEC requirements shall be included in the liquid -tight conduit from each motor to the control panel. No splices shall be permitted between the motor starters and the motor connection boxes, except to the submersible pump motor. All control wiring carrying more than 24 volts, shall be 16 gauge minimum with wire numbers at all termination points. The wiring to all devices outside the control panel shall be contained in metal lined, liquid -tight conduit. C. All secondary control components shall be powered with 120 VAC or 24 VDC. Panel face indicating lights shall be transformer type using 6 volt bulbs. All control relays shall be plug in type for easy replacement. D. The complete control panel assembly shall be U.L. Listed as an industrial control panel to ensure operator safety. The pumping station manufacturer's serial numbered U.L. label shall appear inside the enclosure and all applicable components used to construct the assembly shall be U.L. Listed or Recognized. 2.33 CONTROL FEATURES A. A pressure start time delay, a stop time delay, on and off flow sequencing set points, and a minimum run timer with automatic and manual time out shall be provided. A 100 percent speed start time delay shall be provided. B. Automatic bypass of the PC shall be provided to permit operation of pumps in the HAND position if the PC fails. C. An auto -pressurizing mode with adjustable settings that gradually restores system pressure with the VFD shall be provided to protect the irrigation piping at station startup and after extended station shut downs. D. An energy saving mode with adjustable settings that reduces the system pressure at low flow rates where friction losses in the irrigation system are lower. E. A panel face indicator package shall be provided. The package shall include a general alarm indicating light, a running light (integral to the selector switches) for each pump and the inverter, and a non-resettable, weather proof, elapsed time meter for each motor with a 99999.9 hour range and a 0.1 hour resolution. F. An alarm package shall be provided which includes a low system pressure alarm with trip time delay and manual reset; a high system pressure alarm with trip time delay and manual reset; a low level alarm with trip time delay and manual reset; a high flow rate alarm with trip time delay and manual reset; an irregular power alarm with trip time delay, with manual and delayed automatic reset; individual motor overload alarms with manual reset; individual motor contactor fault alarms with manual reset; pressure transmitter failure alarm with manual reset; high panel temperature alarm with trip time delay and manual reset; and an inverter (VFD) fault alarm with a two attempt automatic reset, a third trip lockout function with timed rollover, and manual reset. Pump shall be shutdown with the appropriate alarm whether they are operating in HAND or AUTO mode. G. A HAND -OFF -AUTO selector switch shall be provided for each pump. A TEST - OFF -AUTO selector switch shall be provided to allow the VFD to be run without a motor load connected. A DISABLE -ENABLE selector switch shall be provided for the low system pressure and high flow rate alarms to prevent these alarms from shutting down the station. An alarm RESET push button shall be provided. H. Primary and secondary fuses in puller equipped fuse holders shall be provided for the control power transformer. Adjustable, ambient temperature compensated, bimetallic, inverse time, U.L. class 10 thermal overload relays shall be provided for each motor. 2.34 PROGRAMMABLE CONTROLLER A. Provide a programmable controller to control all functions of the station. Relays may be used for interface purposes only. B. The programmable controller shall include a non-volatile memory (no battery needed) that prevents loss of program or field adjustable settings during power failures; an EEPROM cartridge that allows program changes via cartridge replacement; a protected data area that retains field adjustable settings while the program cartridge is changed; POWER, RUN, BATTERY, ERROR, and 1/0 status lights; availability of rack mounted RS-422 or RS-232C communications modules; dry contact, 2 amp rated, outputs (Triac outputs shall not be accepted.); and a duty -rated design for locations where electro-magnetic noise, voltage spikes, high temperature, humidity, and mechanical shock exist. 2.35 OPERATOR INTERFACE: A. A NEMA-4 rated, 24 VDC powered operator interface shall be provided. 120 VAC powered interfaces are not acceptable. The interface shall include an alphanumeric keypad with audible key press feedback and a 2 line x 80 character, high visibility, backlit, LCD display. The interface shall also include 12 function keys with custom labels that clearly define frequently used functions such as, next and previous screen; increase and decrease speed; manual speed, etc. Function keys with generic labels such as F1, F2, etc., shall not be accepted. In the event that the interface fails, a signal shall be sent to the PLC, and the station will continue to run normally. The operator interface shall provide access to all appropriate system data, such as the flow rate and system pressure, set point, set point mode, inverter speed, total gallons pumped, total pump starts, manual speed control, operational settings, and alarm messages. The interface shall also provide protected access to changing all operational set points, flow rates, pressure, speed, and time delay settings 2.36 DC POWER SUPPLY: A. A 115 VAC to 24 VDC power supply shall be provided to supply power to the operator interface and other 24 VDC powered devices. The use of the programmable controllers on -board power supply for this purpose is not acceptable. The power supply shall have a 2.1 amp output rating, a voltage adjustment, a run light, a built in noise filter, and built in over current protection with automatic reset. 2.37 VARIABLE FREQUENCY DRIVE (VFD): A. The variable frequency drive shall be an AC powered, IGBT power transistor based, variable -torque, pulse width modulation type inverter. The inverter shall use a high carrier frequency for low drive noise and motor sing. A digital readout shall be included that displays all adjustment settings, fault conditions, diagnostic codes, status, and speed. The inverter shall be able to be run normally without a load connected so that it may be tested. A set of high speed, current limiting fuses and MOV's shall be provided to protect the inverter from faults. B. Provide a separate drive for each vertical turbine pump (two are required, one 20 hp, and one 60 hp). 2.38 COOLING UNIT: A. An air -conditioner shall be provided to cool the inside of the control panel. The cooling unit shall be mounted outside the control panel on the side nearest the VFD with the cool air exhaust vent located below the VFD and the hot air intake vent located above the VFD. Mounting the cooling unit on the rear of the control panel with its intake and exhaust ports blocking the sub -panel is not acceptable. An air deflector shall be placed inside the control panel above the exhaust port to ensure proper air circulation throughout the panel and to the VFD heat sink fans. The cooling unit enclosure shall be air and water tight with a gasketed mounting flange to maintain a NEMA 4 rating on the control panel. The cooling unit enclosure shall be steel with a baked on, epoxy coating. An adjustable thermostat shall be located directly above the VFD heat sinks. The cooling unit shall run whenever the temperature exceeds the thermostat setting. 2.39 FULL FUNCTION VARIABLE SPEED POWER STRUCTURE: A. A full function VFD motor control power structure shall be provided. The VFD may be used to start each main motor successively or to start the first main motor only. Automatic alternation and pump failure sequence shifting of the main pumps shall be provided by this power structure. Each main pump shall have VFD contactors that are mechanically and electrically interlocked with their respective Line contactors. A VFD line side contactor shall be provided for safe transferring of the VFD between main motors, to disconnect the drive from the line during periods of no use for lightning protection, and to serve as an automatic disconnect when an atmospheric lightning detection system is being used with the pump station. 2.40 MAIN DISCONNECT: A. A main disconnect switch shall be provided. The disconnect shall have a NEMA 4 rated, through -the -door, rotary operated, disconnect handle. Refer to the data sheet for fuse type and ratings. 2.41 MOTOR FUSES: A. Motor fuses shall be provided in each motor circuit for fault protection and motor isolation. Motor fuses shall be dual element, time delay, class R rejection type. Fuses shall be provided for each motor circuit for fault protection. The fuses shall be installed in fuse holders equipped with rejection type clips. 2.42 FLOW SENSOR: A. A paddlewheel flow sensor shall be located in the discharge manifold meter run. It shall be rated for a maximum of 400 psig and it shall be accurate to plus or minus 1 percent of full scale. The body shall be made of brass and bronze and the impeller shall be glass reinforced nylon. The sensor shall be 24 VDC powered with a maximum voltage of 34 VDC. The internal electronic package shall included short circuit and reverse polarity protection; and a noise filter for RF and transient protection. The sensor shall provide a direct digital input to the programmable controller for maximum accuracy. The use of signal converters or analog signals for flow rate, is not acceptable. B. Provide a 6-inch diameter pipe of adequate length to accurately control the pumps. This section of pipe must be installed within the existing pump house. Provide three (3) 1-inch diameter threaded outlets, with plugs, downstream of the flow sensor. These outlets are provided for future fertilizer injection points. C. Provide a NEMA 4X digital flow meter readout compatible with flow sensor for monitoring the flow rate, totalizing gallons used, and for shifting the flow sequencing set point range. The display shall be a black character, LCD type. Adjustable settings for pipe diameter and pulse output shall be provided. The totalizer shall be capable of counting to 2 billion gallons and it must be resetable. Both settings and the gallons total shall be held in non-volatile memory (no battery required) and protected by a user defined password with a hidden override key 2.43 FLOW SENSOR OUTPUT INTERFACE: A. Provide interface package (optical isolator) for access of square wave signal of pump system flow sensor for the connection to a future fertigation and/or irrigation central control system. The pump manufacturer shall provide the interface in order that the manufacturer's warranty is not voided due to connection of external systems. 2.44 PRESSURE TRANSDUCER: A. A digital pressure transducer shall be provided to accurately read system pressure for input into the programmable controller. The pressure range shall be 0-200 psig, the proof pressure rating shall be 400 psig, and burst pressure rating shall be 2000 psig. All wetted parts shall be stainless steel. The transducer shall be bulkhead mounted inside the control panel with the water connection remaining outside. 2.45 LEVEL PROBES: A. The existing level probes for the well will be used. The control panel will be provided with terminals for connection to the existing probe assemblies. 2.46 POWER MONITOR: A. The main power supply in the pumping station shall be equipped with a 3 phase power monitor. It shall detect phase loss, reversal, shift, or improper sequence. It shall also detect abnormally low voltage. A voltage adjustment, normal status light, and line side fuses mounted in puller equipped fuse holders, shall be provided. 2.47 LIGHTNING ARRESTOR: A. The main power supply in the pumping station shall be equipped with a 3 phase, 600 volt rated, watertight, silicon oxide varistor type, lightning arrestor. It shall have a current rating of no less than 100,000 amps, a sparkover voltage rating of 1000, and a clamping voltage of 2,400 volts at 20,000 amps (NEMA standard 8x20 USEC. wave). It shall be mounted near the main disconnect device inside the control panel. 2.48 Auxiliary Electrical Power Circuits: A. Provide a separately mounted transformer to provide a 120 Volt, single phase circuit for pump station lighting and incidental use. In addition, provide a 480 V, 3 phase circuit for connection to existing electrical circuit supplying power to the pump house heater and pond aeration system. B. The primary and secondary circuit breakers shall be all located within a NEMA- 3R enclosure. The primary circuit breaker shall be connected to the incoming power line so that the auxiliary power supply can remain on independently of the pumping station. 2.49 Motors: A. As a bid alternate, provide and install new electric motors for the vertical turbine pumps. One 20 hp and one 60 HP motor will be required. B. Each pump motor shall be 1800-RPM nominal, squirrel cage induction vertical hollow shaft type with a WP-1 enclosure and a 1.15 service factor. The temperature rise of the motor shall be to NEMA Standard MG-1-12.42 for Class B or Class F insulation. C. For 40 HP motor or greater, furnish "Premium Efficiency" US Electric motors Type RUS that are rated for continuous inverter duty with variable frequency drive and are designated NEMA MGI-31. For less than 40 HP motors, furnish "High Efficiency / Energy Efficient" US Electric motors Type AUE that are rated for continuous inverter duty with variable frequency drive. D. Furnish motors of proper size to drive the pump at any point on its operation curve without exceeding motor horsepower nameplate rating. E. Furnish motor thrust bearings of ample capacity to accommodate the weight of all rotating parts plus the hydraulic thrust of the pump at shutoff conditions. Furnish motor bearings rated for a minimum service life not less than five years continuous operation at the design rating point. F. The pump shaft shall be connected to the motor by a bolted down coupling at the top of each motor. All couplings shall be equipped with non -reversing ratchets. G. Furnish motors manufactured in the U.S.A. 2.50 Pressure Maintenance Pump: A. Furnish a pressure maintenance pump, a 50 GPM, multistage, submersible type, well pump. Pump shall be equipped with a motor shroud for proper cooling of submersible motor and stainless steel suction screen. 10 B. Furnish a pump with a Franklin submersible motor and Subtrol motor protection controls. Pump furnished shall be a Goulds, Grundfos or engineer approved equal. C. Furnish an overall pump length to within 12-inches of the bottom of the wet well. Field measure and verify depth required. 2.51 PIPING: A. Fabricated Piping: All fabricated piping shall conform to ASTM specifications A53 for Grade B welded or seamless pipe. Piping 16" and smaller shall be Schedule 40. All welding flanges shall be forged steel with slip-on or welding neck type. All welding fittings shall be seamless, conforming to ASTM Specification A234, with pressure rating not less that 150 psi. All pressurized tube fittings shall be copper or brass. B. Winterization Connection: Provide 2-inch ball valve and capped threaded nipple in pump system discharge manifold for compressed air winterization of the irrigation system. C. Discharge pipe: Provide an 6-inch steel pipe section to be connected down stream of the pump station discharge pipe to connect to the below grade, 8-inch ductile iron irrigation mainline pipe. The pipe shall have two 90 degree flanged els. Below grade steel pipe shall be wrapped with pipe tap. All below grade fittings shall be ductile iron. A 6-inch flanged x 8-inch flanged or mechanical pipe fitting shall be installed to transition from steel pipe to ductile iron mainline pipe. Provide a thrust block at the below grade el. The thrust block shall have minimum area of 17 square ft. against undisturbed soil. Field verification of the mainline pipe depth will be required. Discharge pipe to existing the north facing wall of the existing building, approximately 3 to 4 feet in from the east wall. The discharge pipe orientation shall be closely coordinated with the installation of the below grade mainline pipe to the pump station. The below grade mainline pipe will be installed by others. 2.52 VALVES: A. Air/Vacuum Release Valve: Provide a continuous -acting, combination air release/vacuum valve to release excess air from the pump discharge manifold. The valve must be capable of releasing air during filling and pump operation and also open in a vacuum condition to allow air to enter the manifold when piping is drained. Valve shall have a cast iron body rated for 300 PSI, stainless steel trim and float ball, Buna N and viton seats. 2. In lieu of an air/vacuum release valve, provide an Engineer approved equal device to release air from the system. 11 B. Drain Valves: Drains are to be provided from any possible low point in the system and are to consist of 1/4" brass angle valves unless otherwise noted. Drain piping is to be furnished so that no drain water runs out on top of the deck plate, but either under deck plate, or directly into the trench drain or wet well. They include, but are not limited to, the following: Provide drain in the pump discharge manifold between pump check valves and control valve. 2. Provide 3/4" brass hose bib in the discharge piping to function as a washdown connection and also function as a drain. C. Check Valves: Pump check valves shall be of the silent operating, non -slam type, cast iron bodied with bronze and stainless steel trim. Sealing surfaces shall utilize resilient Buna N rubber. The valve design shall incorporate a center guided, spring, loaded poppet, guided at opposite ends and having a short linear stroke that generates a flow area equal to the pipe diameter. Valves shall be sized to permit full pump capacity to discharge through them without exceeding a pressure drop of 2.5 PSI. Furnish check valves on the discharge of each pump. D. Isolation Valves: Valves shall be butterfly type with the position lever or gear hand wheels and rated at 200 psi WOG working pressure. Trim shall include stainless steel stem, bronze streamlined disc, and full faced resilient seat. Isolation valves shall be installed on the discharge side of each pump. The pump system shall also be furnished with a main station isolation valve located in the discharge manifold. E. Pressure Relief Valve: Furnish pressure relief valve and bypass piping to wet well installed on the discharge. Size pressure relief valve to bypass sufficient water to avoid operating pumps at or near shut off head conditions. 2.53 GAUGES: A. Gauges and switch gauges shall be isolated from all electrical switch gear and control panels. Gauges shall be provided at appropriate locations to read inlet pressure and discharge manifold pressure. Switch gauges shall be 4" diameter vibration/pulsation dampened. Pressure gauges shall be 2.5" diameter, glycerin filled, with ANSI Class B accuracy. Install ball valves to provide total isolation of all pressure gauges. 2.54 AUTOMATIC BACKWASHING WYE-STRAINER: A. Provide an 8-inch, 125 class flanged, 200 psig rated wye-strainer. The strainer body shall be ASTM A126 cast iron and the screen shall be 304 stainless steel. The Wye -Strainer shall have a 40 mesh screen. B. Provide a 2-inch, 115 VAC, electric motor operated, ball valve for automatic blow down of the wye-strainer. The valve shall be rated for 400 psig working pressure and have a bronze body, 316 stainless steel ball with 1-1/2 inch port, and Teflon seats. The actuator shall have an 8 second cycle time, a NEMA-4 enclosure, a manual override, and a position indicator. Provide an illuminated "OFF-AUTO- 12 MAN" strainer blowdown selector switch on the control panel that lights up whenever the blowdown valve is open. C. Filter backwash pipe shall be steel pipe inside the pump house, and transition to Class 200 PVC pipe below grade. Pipe shall discharge filter backwash into the pond just east of the pump station building. Coordinate routing of pipe with Owner's Representative. Filter must be capable of an automatic backwash cycle based on pressure differential and time interval. 2.55 STANDARDS: A. All wiring shall conform to the National Electrical Code Standards. Flexible conduit sections shall be under 5' in length to meet code. All conduit to devices shall be attached securely to avoid trip hazards. B. A wiring schematic shall be provided by the manufacturer. The schematic shall show all devices, connections and wire numbers. C. All controls and electrical equipment shall be thoroughly inspected and tested before shipment. 2.56 PAINTING: A. Painting of the entire control panel shall consist of a multi -step coating system which includes metal preparation, rust inhibitive prime coat, and a two part polyurathane finish having a total dry film thickness of not less that 4 mils. Pump station components shall be painted the manufacturer's standard color. All electrical enclosures, tank, and accessory panels shall be painted to a minimum thickness of 3 mils and baked at 160-180 F. B. Painting of field fabricated pipe will be required. Use an epoxy based paint to coat all exterior pipe and fitting surfaces. Prepare the surface to be painted as recommended by the paint manufacturer. Paint color to be as approved by Owner's Representative. PART 3: EXECUTION 3.08 INSPECTIONS AND REVIEWS: A. Site Inspections: Verify site conditions and note irregularities affecting work of this section. Report irregularities to the Owner's Representative prior to beginning work. 2. Beginning work of this section implies acceptance of existing conditions. 3.09 CONTROL PANEL INSTALLATION: A. Provide technical start up procedures by the pump station manufacturer including: 13 Station start up and pressurization and pressure, flow, and programming adjustments 2. Monitoring of park irrigation cycle when possible. Technician will instruct operations personnel as to the operation, adjustment and maintenance of the pump station. 3. Provide one day of training to City staff on the operation and maintenance of the pump control system. 3.10 DISCHARGE MANIFOLD PIPE AND COMPONENTS INSTALLATION: A. Install improvements as outlined in approved shop drawings. B. Provide scaled shop drawing of proposed discharge manifold with all components specified for review and approval prior to construction. 3.11 OPERATION AND MAINTENANCE MANUALS: Operation and maintenance manuals shall be furnished at time of start up. A. Tools and Spare Parts: Prior to the Pre -Maintenance Review, supply to the Owner operating keys, servicing tools, test equipment, and any other items indicated. B. Other Materials: Install other materials or equipment to be part of the pumping system, even though such items may not have been referenced in these specifications. 3.12 PROJECT RECORD (AS -BUILT) DRAWINGS: A. The contractor is responsible for documenting changes to the design. Maintain on site and separate from the documents used for construction, one complete set of contract documents as Project documents. Keep documents current. Do not permanently cover work until as -built information is recorded. B. Record pumping system alterations. Record work which is installed differently than shown on the construction drawings. C. Prior to Final Review, obtain from the Owner's Representative a reproducible mylar copy of the drawings. Using technical drafting pen, duplicate information contained on the project drawings maintained on site. Label each sheet "Record Drawing". Completion of the Record Drawings will be a prerequisite for the Final Review. 14 the parties. All notices provided under this Agreement shall be effective when mailed, postage prepaid and sent to the following addresses: City: City of Fort Collins, Purchasing P.O. Box 580 Ft. Collins, CO 80522 Attn: John Stephen Service Provider: Metron, Inc. 1505 W. 3Id. Ave. Denver, CO 80223 Attn: David Haynes In the event of early termination by the City, the Service Provider shall be paid for services rendered to the date of termination, subject only to the satisfactory performance of the Service Provider's obligations under this Agreement. Such payment shall be the Service Provider's sole right and remedy for such termination. 5. Contract Sum. The City shall pay the Service provider for the performance of this Contract, subject to additions and deletions provided herein, the sum of Fifty Thousand Seven Hundred Thirty -One Dollars ($50,731.00), $45,798.00 Base Bid plus $4,933.00 Add Alternate, per Cost Breakdown attached as Exhibit "C". 6. City Representative. The City will designate, prior to commencement of the work, its representative who shall make, within the scope of his or her authority, all necessary and proper decisions with reference to the services provided under this agreement. All requests concerning this agreement shall be directed to the City Representative. 7. Independent Service provider. The services to be performed by Service Provider are those of an independent service provider and not of an employee of the City of Fort Collins. The City shall not be responsible for withholding any portion of Service Provider's compensation hereunder for the payment of FICA, Workmen's Compensation or other taxes or benefits or for any other purpose. 8. Personal Services. It is understood that the City enters into the Agreement based on the special abilities of the Service Provider and that this Agreement shall be considered as an agreement for personal services. Accordingly, the Service Provider shall SA 10/01 2 Attachment A The following information is provided for information only. All information provided shall be field verified by inspection and pump testing. A complete review of the existing pump station is required prior to development of shop drawings. The following information is attached. • Pump curve for existing 20 HP pump • Pump curve for existing 60 HP pump • Shop drawing of existing pump station. IN EXHIBIT B INSURANCE REQUIREMENTS The Service Provider will provide, from insurance companies acceptable to the City, the insurance coverage designated hereinafter and pay all costs. Before commencing work under this bid, the Service Provider shall furnish the City with certificates of insurance showing the type, amount, class of operations covered, effective dates and date of expiration of policies, and containing substantially the following statement: "The insurance evidenced by this Certificate will not be cancelled or materially altered, except after ten (10) days written notice has been received by the City of Fort Collins." In case of the breach of any provision of the Insurance Requirements, the City, at its option, may take out and maintain, at the expense of the Service Provider, such insurance as the City may deem proper and may deduct the cost of such insurance from any monies which may be due or become due the Service Provider under this Agreement. The City, its officers, agents and employees shall be named as additional insureds on the Service Provider's general liability and automobile liability insurance policies for any claims arising out of work performed under this Agreement. 2. Insurance coverages shall be as follows: A. Workers' Compensation & Employer's Liability. The Service Provider shall maintain during the life of this Agreement for all of the Service Provider's employees engaged in work performed under this agreement: 1. Workers' Compensation insurance with statutory limits as required by Colorado law. 2. Employer's Liability insurance with limits of $100,000 per accident, $500,000 disease aggregate, and $100,000 disease each employee. B. Commercial General & Vehicle Liability. The Service Provider shall maintain during the life of this Agreement such commercial general liability and automobile liability insurance as will provide coverage for damage claims of personal injury, including accidental death, as well as for claims for property damage, which may arise directly or indirectly from the performance of work under this Agreement. Coverage for property damage shall be on a "broad form" basis. The amount of insurance for each coverage, Commercial General and Vehicle, shall not be less than $500,000 combined single limits for bodily injury and property damage. In the event any work is performed by a subcontractor, the Service Provider shall be responsible for any liability directly or indirectly arising out of the work performed under this Agreement by a subcontractor, which liability is not covered by the subcontractor's insurance. EXHIBIT C CITY OF FORT COLLINS BID PROPOSAL BID #5762 BID OPENING: FEBRUARY 3, 2003, 3:00 p.m. (our clock) WE HEREBY ENTER OUR BID FOR THE CITY OF FORT COLLINS' REQUIREMENTS FOR PUMPING PLANT RENOVATION AT CITY PARK PER THE BID INVITATION AND ANY REFERENCED SPECIFICATIONS AND DRAWINGS: The City of Fort Collins Parks Department is requesting bids for retrofitting an existing pumping station with a variable speed drive system. Work at City Park must be completed 60 days after receiving notice to proceed. The successful bidder must enter into the attached services agreement and supply proof of insurance "Exhibit B" as requested. Any technical questions should be directed to Eileen Scholl, Project Manager at (970) 566-1342. Any Purchasing questions should be directed to John Stephen, CPPB, Senior Buyer at (970) 221-6775. A Mandatory pre -bid meeting will be held at City Park, 1500 W. Mulberry, Fort Collins on January 21, 2003 at 10:00 am. Meet at the City Park Pool located at intersection of Bryan and City Park Drive. BID SCHEDULE Supply all materials and labor required including installation for retrofitting an existing pumping station with a variable speed drive system. LUMP SUM $45,798.00 Add alternate $ 4,933.00 motors for vertical turbine pumps. Provision and installation of new premium efficiency FIRM NAME:=•Ietron, Inc. ' (Are you a corporation, DBA, Partnership, LLC, or PC) -ADDRESS: 1505 W. 3rd Ave. Denver, CO 80223 TELEPHONE # 303/592-1903 FAX # 303/592-1969 BY: Signature Printed . Tecknit, Inc. dba Metron, vu iFOR _17% BOWL EFFICIENCY FIELD PERFORMANCE DEDUCT FEET COLUMN FRICTION LL 500 1 f 1 Y��i n�N1119 { C 02118,'05 TUE 09:04 FAX 9089799059 MEEKER SHARKEY Client#: 78305 — I wrllv�, Z 002 ACORD,. CERTIFICATE OF LIABILITY INSURANCE a218�03D"Ym PRODUCER THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION Fleet Insurance Services (03) ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE HOLDER. THIS CERTIFICATE DOES NOT AMEND, EXTEND OR Cr anfordNJ 07016 Commerce Drive ALTER THE COVERAGE AFFORDED BY THE POLICIES BELOW. Cr, 908 272-8100 TWP Inc. 1505 West 3rd Ave. Denver, CO 80223 COVERAGES INSURERS AFFORDING COVERAGE NAIC # INSURERA: Federal INSURER e: National Union Flre/American Intl Gr INSURER C: INSURER D: INSURER E THE POLICIES OF INSURANCE LISTED BELOW HAVE BEEN ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD INDICATED. NOTWITHSTANDING ANY REQUIREMENT, TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WHICH THIS CERTIFICATE MAY BE ISSUED OR MAY PERTAIN, THE INSUP.ANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS, EXCLUSIONS AND CONDITIONS OF SUCH POLICIES. AGGREGATE LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS. IN POLICY EFFECTIVE POLICY E PIRATION LTR N R TYPE OF INSURANCE POLICY NUMBER DA MMIDDIYY OATE MMIDD/ Y) LIMITS A X GENERAL LIABILITY 35799356FPO 10/U1/02 10/01/03 EACH OCCURRENCE s 1 OOO OOO X COMMERCIAL GENERAL LIABILITY CLAIMS MADE 7 OCCUR DQFIMG ES RPf ITEO ra S1,000,000 MED EXP (Any one person) $10 000 x BF Vendors PERSONAL & AOV INJURY $1 00O 000 GENERAL AGGREGATE $2 OOO OOO GEN'L AGGREGATE LIMIT APPLIES' PER: POLICY PRO• LOC JECT UCTS - COMPIOP AGG $2.000 000 A AUTOMOBILE LIABILITY ANY AUTO 0274992184 10/01/02 10/01103 INED SINGLE LIMIT cidcnl) $1,000,000 X Y INJURY ALL OWNED AUTOS SCHEDULED AUTOS rson! HIRED AUTOS NON-OVvNED AUTOS X Y INJURY eldenc) !PRC)PERI"TY S X RTY DAMAGEdlen[I $GARAGE UABILITY ONLY • En ACCIDENT $ANY THnN EA ACC $NLY: AUTO S AGG B X EXCESSIUMBRELLA LIABILITY X OCCUR L7CLAIMS MADE BE2195656 10/01/02 10/01/03 EACH OCCURRENCE $10 000 000 AGGREGATE S10,000,000 S ' S DEDUCTIBLE X RETENTION S 10000 WORKERS COMPENSATION AND G'✓C SrnrU- OTH. EMPLOYERS' LIABILITY E.L. EACH ACCIDENT S ANY PROPRIETOR(PARTNERIEXECUTIVE E.L. DISEASE - EA rMPLOYEE S OFFICER/MEMBER EXCLUDED? It yera. dreribe under E.L. DISEASE • POLICY LIMIT S SPECIAL PROVISIONS below OTHER DESCRIPTION OF OPERATIONS I LOCATIONS I VEHICLES I EXCLUSIONS ADDED BY ENDORSEMENT I SPECIAL PROVISIONS Additional named Insureds: Metron Inc. Tecknit Inc. Young Electric & Manufacturing Inc. (See Attached Descriptions) HOLDER CANCELLATION SHOULD ANY OFTHE ABOVE DESCRIBED POLICIES BE CANCELLED BEFORE THE EXPIRATION City of Fort Collins, DATE THEREOF, THE ISSUING INSURER WILL ENDEAVOR TO MAIL if) WRITTEN Attn: John Stephen NOTICE TO THE CERTIFICATE HOLDER NAMED TO THE LEFT, BUT FAILURE TD DO SO SHALL P.O. Box 580 IMPOSE NO OBLIGATION OR LIABILITY OF ANY KIND UPON THE INSURER, ITS AGENTS OR Fort Collins, CO 80522 REPRESENTATIVES. AUTHORIZED REPRESENTATIVE OLi18iO3 TUE 09:04 FAX 9082729059 MEEKER SHARKEY 0 003 DESCRIPTIONS (Continued from Page 1) Tecknit Shielding Systems Inc City of Fort Collins is additional insured with respect to job performed by Insured. :y .6 Stp �twr PUMPING STATION I JO T cl sED ,`^ I JOC r PUMP 1 ��lSLG.PM. FT HEAD 7-0 HP. RPM AA��M^� 2 PUAIP >,1.w/_sGPN�FT HEAD •�DZt ►DR ►ram.-ny. ►_w L THIS FOUNDAT 00% ►LA'. Is r0R USE I►7H 169&XWI M S' WALL TPCWWESS tUR.004 STRUCTURE. W STATION IR TO s( UkINppSm. AND A SMALLER ►W"TON O "Mato. CoN%C`T KC.t Corr I. ALL DIMENSIONS AM "SW ON A 6'-0' ONA WET WELL MR WET WELLS OF OWrtKNT K PAWURS ONCTANOUTAR WET CONTACT KO-CORKNT twaimim a no MafED DRAEN7D.0 —CONTROL PAIL gSNOLTS HERTZ II r- DISCHARGE VALVE 14'-0' NOTICE" ' THIS DRAWN-0 /S CEteT/G/EO FOR CONSTRUCTION PURPOSES. CONCRETE AN04ORS SUPPLIED A OKENSOI USWO .K CONTINENT RIVs. Rt/EA 10 MIO CONTKNT [NORit[RNIIO IF ryM1 Or Or HER ✓ON. ARE TO K USED NO SCALE /gjAf. CONDUIT S12E FOUNDATION BASE GRADE -\ (CLKTGMER ESTABLISHED) \ TLsr 6'-7' 2'- 6' ACss L 0 12 -yS 5-0 . 1 V y/OUTLN[ I b' I 1 I O 3'-2• i ( 1 1 I STATION CRSCxAIIOC 1 S'AT*% CowTNCL CABINETS ' 6- 16'-0' STATIO14 WITHOUT STRAINER 20'-O' STATION WITH STRAINER 0 "I'lTOH r0R USE WITH AOK/S3 THEN LE•/RRT-WMpµ3 FOUNDATION r'�r-lN 00 W�'t - DELTA MOTOR STARTERS-RrT* To MO CO/m NT IFOTHER Tr►C STARTERS ANC TO st VKb PJMPNG STATION cONNt CTION TO STSTEM ICvs—'.'zm SI/REoI CTO st INSTALL[O AFTER RM7q STATION H.s sttN at T I. RACE. SYSTEM CONNECTION SIZE {o r-6. "—EXPANSION JOINT DETECTOR PROKS/ • Z. :'�Ifillilililili� ���111.11 ��1 �� •�� �`�1: � �� �� ••�.Ij1111111�111jljlj'�i �����1�� �"�_, - � r RESERVER TILL STOP WATER LEVEL I RESERVOIR FILL START WATER LEVEL --.- MESHAr � Il Al YAT. 7E0 SUE IY4 t38�r PLARP START ( _ LOW WATER LEVEL PUMP STOP .A LOW WATER LEVEL — RESERVOIR INLET SCREEN OUJOTE NO R�Iy/O/ZS,4 (DATE //��0�� �Br. J. /eZMAE MID-CONTINENT ENGINEERING CORP. TELEX 454-307 TELEPHONE (303) 466.1677 11936 WADSWORTH BLVD PO BOX 40 BROOMFIELO.COLORADO 80020 USA neither assign any responsibilities nor delegate any duties arising under the Agreement without the prior written consent of the City. 9. Acceptance Not Waiver. The City's approval or acceptance of, or payment for any of the services shall not be construed to operate as a waiver of any rights or benefits provided to the City under this Agreement or cause of action arising out of performance of this Agreement. 10. Warranty. (a) Service Provider warrants that all work performed hereunder shall be performed with the highest degree of competence and care in accordance with accepted standards for work of a similar nature. (b) Unless otherwise provided in the Agreement, all materials and equipment incorporated into any work shall be new and, where not specified, of the most suitable grade of their respective kinds for their intended use, and all workmanship shall be acceptable to City. (c) Service Provider warrants all equipment, materials, labor and other work, provided under this Agreement, except City -furnished materials, equipment and labor, against defects and nonconformances in design, materials and workmanship/workwomanship for a period beginning with the start of the work and ending twelve (12) months from and after final acceptance under the Agreement, regardless whether the same were furnished or performed by Service Provider or by any of its subcontractors of any tier. Upon receipt of written notice from City of any such defect or nonconformances, the affected item or part thereof shall be redesigned, repaired or replaced by Service Provider in a manner and at a time acceptable to City. 11. Default. Each and every term and condition hereof shall be deemed to be a material element of this Agreement. In the event either party should fail or refuse to perform according to the terms of this agreement, such party may be declared in default thereof. 12. Remedies. In the event a party has been declared in default, such defaulting party shall be allowed a period of ten (10) days within which to cure said default. In the event the default remains uncorrected, the party declaring default may elect to (a) terminate the Agreement and seek damages; (b) treat the Agreement as continuing and require specific performance; or (c) avail himself of any other remedy at law or equity. If the non -defaulting party SA 10/01 91 commences legal or equitable actions against the defaulting party, the defaulting party shall be liable to the non -defaulting party for the non -defaulting party's reasonable attorney fees and costs incurred because of the default. 13. Binding Effect. This writing, together with the exhibits hereto, constitutes the entire agreement between the parties and shall be binding upon said parties, their officers, employees, agents and assigns and shall inure to the benefit of the respective survivors, heirs, personal representatives, successors and assigns of said parties. 14. Indemnity/Insurance. a. The Service Provider agrees to indemnify and save harmless the City, its officers, agents and employees against and from any and all actions, suits, claims, demands or liability of any character whatsoever brought or asserted for injuries to or death of any person or persons, or damages to property arising out of, result from or occurring in connection with the performance of any service hereunder. b. The Service Provider shall take all necessary precautions in performing the work hereunder to prevent injury to persons and property. c. Without limiting any of the Service Provider's obligations hereunder, the Service Provider shall provide and maintain insurance coverage naming the City as an additional insured under this Agreement of the type and with the limits specified within Exhibit B, consisting of one (1) page, attached hereto and incorporated herein by this reference. The Service Provider before commencing services hereunder, shall deliver to the City's Director of Purchasing and Risk Management, P. O. Box 580 Fort Collins, Colorado 80522 one copy of a certificate evidencing the insurance coverage required from an insurance company acceptable to the City. 15. Entire Agreement. This Agreement, along with all Exhibits and other documents incorporated herein, shall constitute the entire Agreement of the parties. Covenants or representations not contained in this Agreement shall not be binding on the parties. SA 10/01 4 16. Law/Severability. The laws of the State of Colorado shall govern the construction interpretation, execution and enforcement of this Agreement. In the event any provision of this Agreement shall be held invalid or unenforceable by any court of competent jurisdiction, such holding shall not invalidate or render unenforceable any other provision of this Agreement. CITY OF FORT COLLINS, COLORADO a municipal oration By: �- John Fischbach City Manager By. Ja s B. O'Neill II, CPPO, FNIGP Dire of Purchasing and Risk Management Date: S �TTEST:' 4� City ` Jerk AP�'f C3 �ORM: r Assistant City Attorney Tecknit, Inc. doingk u ' as -- Metron, Inc. r By: PRINT NAME rnRPORATE PRESIDENT OR VICE PRESIDENT te: ,-2 '�� ' Q 3 (Corporate Seal) SA 10/01 5 EXHIBIT A SCOPE OF WORK PUMP CONTROL SYSTEM SPECIFICATIONS SECTION 02815- PUMP CONTROL SYSTEM PART 1: GENERAL 1.07 SCOPE: It is the intention of this specification to describe a variable speed control system and other improvements for the existing landscape irrigation pump station located at City Park in Fort Collins, Colorado. This is to be accomplished by replacing the existing control system with a new a prefabricated pump control panel, manifold piping, and other appurtenances. The existing pumps are to remain in place. A new steel discharge manifold with wye- strainer shall be provided. A new submersible pressure maintenance pump will also be added as part of this scope of work. The existing pump station consists of a 20 hp vertical turbine pump, and a 60 hp vertical turbine pump. The existing pump station was designed to provide a flow of 675 gpm at a discharge pressure of 140 psi. The pump curves are provided as an attachment to these specifications. The existing pump station was installed in 1978. Furnish all labor, materials, supplies, equipment, tools, and transportation, and perform all operations in connection with and reasonably incidental to the complete installation of the pump system improvements, and guarantee/warranty as shown on the drawings, the installation details, and as specified herein. Items of work specifically included are: A. Procurement of all applicable licenses, permits, and fees as required by local utilities. B. Removal and salvage of the existing pump station control panel. C. Provision of prefabricated pump control panel. D. Removal and salvage of the existing discharge manifold within the pump house including the isolation valves and check valves at the discharge of each turbine pump, manifold pipe, manifold filter screen, pressure relief valves, 6-inch pump control valve, and other miscellaneous pressure gauges, switches, etc. E. Installation and connection of electrical power supply to the new control panel and vertical turbine pumps, new pressure maintenance pump, 120V lighting circuit, and 480V circuit for the pump house electric heater and pond aeration system. F. Provision and installation of new pressure relief valve, flow sensor, pressure transducer, discharge manifold, isolation valves, check valves, conduit, and wiring as required. G. Provision and installation of submersible sustaining pump. H. Provision and installation of new premium efficiency motors for vertical turbine pumps (Add Alternate). Start-up, testing, and demonstration of the performance of the system. Maintenance period. 1.08 SUBMITTALS: E. Deliver four (4) copies of all submittal to the Owner's Representative within 15 days from the Notice to Proceed. F. Materials List: Include pipe, fittings, pumps and motors, control system components, and electrical equipment. Quantities of materials need not be included. G. Manufacturers' Data: Submit manufacturers' catalog cuts, specifications, and operating instructions for equipment shown on the materials list. H. Shop Drawings: Submit shop drawings of proposed pump system improvements. Show products required for proper installation, their relative locations, and critical dimensions. Submit technical data sheets, electrical schematics, sequence of operation, UL listing authorization form. The shop drawings shall show the system layout, elevation view, and critical dimensions for the pump system, building, wet well, etc. Pump system manufacturer is responsible for layout and design of the pump system supplied, and any special coordination issues that affect the critical dimensions, layout, or orientation of the pump system improvements. 1.09 RULES AND REGULATIONS: A. Work and materials shall be in accordance with the latest edition of the National Electric Code, the Uniform Plumbing Code as published by the Western Plumbing Officials Association, and applicable laws and regulations of the governing authorities. B. When the contract documents call for materials or construction of a better quality or larger size than required by the above -mentioned rules and regulations, provide the quality and size required by the contract documents. 1.10 TESTING: A. Notify the Owner's Representative three days in advance of testing. B. On completion of assembly, hydrostatically test all piping at the maximum pump shutoff head. C. Contractor shall bump manual motor starter controls to prove correct rotation and secure local inspection/approval. D. Control and safety shut off devices shall be tested and verified operational. E. Flow and discharge pressure shall be verified with specified values. 1.11 REVIEWS: The purpose of on -site reviews by the Owner's Representative is to observe the Contractor's interpretation of the construction documents and to address questions with regards to the pump installation. A. Scheduled reviews such as those for testing should be scheduled with the Owner's Representative as required by these specifications. B. Impromptu reviews may occur at any time during the project. C. Final review will occur at the completion of the pumping system installation and Record (As -Built) Drawings. 1.12 GUARANTEEIWARRANTY AND REPLACEMENT: The purpose of this guarantee/warranty is to insure that the Owner receives materials of prime quality, installed and maintained in a thorough and careful manner. A. The manufacturer shall warrant the new pump control panel and VFD drive to be free of defects and product malfunctions for a period of one year from date of start up or eighteen months after shipment, whichever occurs first. B. Failures caused by lighting strikes, power surges, vandalism, flooding, operator abuse, or acts of God are excluded from warranty coverage. C. Repair damage to the premises caused by a defective item. Make repairs within seven days of notification from the Owner's Representative. D. Contract documents govern replacements identically as with new work. Make replacements at no additional cost to the contract price. PART 2: MATERIALS 2.29 QUALITY: A. Materials used in the system shall be new and without flaws or defects of any type, and shall be the best of their class and kind. 2.30 MANUFACTURER REQUIREMENTS: A. All pump station components shall be supplied by and be the responsibility of one manufacturer, even though others manufactured some components. B. Provide a factory -trained technician to supervise the installation of the pump station, pumps, and motors. In addition to the time required for installation supervision, the technician shall provide a minimum of 1 day of training for the Owner's staff in the operation, maintenance, and programming of the pumping system. C. Acceptable Manufacturers: FLOWTRONEX PSI Ltd., 10717 Harry Lines Blvd., Dallas, Texas 75220, (214) 357-1320. Local Representative: Jay Folk, Arapahoe Pumping Systems, P.O. Box 3482, Littleton, Colorado 80161. 2. SYNCHROFLO, 6700 Best Friend Rd., Norcross, Georgia, 30071, (770) 447-4443. Local Representative: John Macintyre, Munro Supply, 1271 Elmwood Court, Broomfield, Colorado 80020, (303) 439-2600. 3. WATERTRONICS, 525 Industrial Drive, Hartland, Wisconsin 53029, (800)356-6686, (414)367-5000, F: (414) 367-5551. Local Representative: Torry Roesch, Watertronics,7574 Jellison Court, Arvada, CO 80005 (720) 898-0540 4. METRON, INC., 1505 West 3rd. Avenue, Denver, Colorado 80223, 303- 592-2903, F: 534-1947. 2.31 GENERAL REQUIREMENTS: A. Furnish a prefabricated VFD pump control panel for the existing submersible well pump as shown on the drawings and details. B. The panel shall be completely wired and electrically tested before shipment to the job site. C. The power supply to the panel shall be the existing 480 V, 3 phase power supply to the existing pump station control panel. The control panel manufacturer shall verify the existing service is compatible with the new control panel as specified. D. All components shall be supplied by and be the responsibility of one manufacturer, even though some components were manufactured by others. E. Operation: a. During non -irrigation times, the pressure maintenance pump (PM) will cycle on and off as required to maintain irrigation system pressure. The cycling pressures can be user selected and can be set substantially below normal set point pressure, if desired. If the PM pump cannot maintain the desired pressure, then the VFD will start the first pump (20 hp pump) and will gradually ramp the pressure up to desired irrigation pressure. b. The pump speed will be modulated to hold a constant discharge pressure regardless of flow. As the flow rate increases and the