Line: Qty: Units: Description: Unit Price: Extended Price:
1 3000 FT 7503-1036 1.2010 3,603.00
500MCM, AL U.G. SINGLE COND
YARD
CABLE, U.G. BOOV, AL, COMPRESSED,
500MCM, 37 STRD., SINGLE CONDUCTOR,
PER SPEC. 369-100, SERIAL #08, REV. R,
SHIP ON N/R REELS, STD. PKG.
MFR: SOUTHWIRE
DELIVERY: 4-8 WEEKS
PRICE AND DELIVERY PER CHARLIE
CABLE SUPPLEMENTAL INSTRUCTIONS FOR SHIPPING:
'THE CABLE SHALL BE PLACED ON REELS SUITABLE FOR PROTECTING IT FROM DAMAGE DURING SHIPMENT. EACH END OF THE CABLE SHALL BE FIRMLY AND
PROPERLY SECURED TO THE REEL. CARE SHALL BE TAKEN TO PREVENT LOOSNESS OF THE REELED CABLE.
'EACH END OF EACH LENGTH OF CABLE SHALL BE DURABLY SEALED TO PREVENT ENTRANCE OF MOISTURE.
'THE REELS SHALL BE COVERED WITH SUITABLE MATERIAL TO PROVIDE PHYSICAL PROTECTION FOR THE CABLE DURING TRANSIT AND DURING ORDINARY STORAGE
AND HANDLING OPERATIONS.
'REELS SHALL BE SHIPPED ON OPEN -BED TRUCK(S) WITH REELS IN THE UPRIGHT POSITION; I.E., ON FLANGES, AND BLOCKED TO PREVENT MOVEMENT DURING
SHIPPING.
'ACCURATE GROSS REEL AND TARE WEIGHTS ARE CRITICAL
'PLEASE WEIGH EMPTY REEL, AND VERIFY WEIGHTS PRIOR TO SHIPPING.
-AVERAGED WEIGHTS ARE UNACCEPTABLE SINCE SPECIFIC CABLE IS
Date: 02/04/03
City of Fort Collins
Page Number: 2 Of 2
City of Fort Collins
PURCHASE ORDER NUMBER: 3300857
UTILITY SERVICE CENTER'- WAREHOUSE
CITY OF FORT COLLINS i
700'WOOD ST
FORT COLLINS ICID 80621'
Delivery Date: 03/14/03 Buyer: DICK,OPAL
Purchase Order number must appear on invoices, packing lists, labels, bills of lading and all correspondence
NOTE:
Line: Description: Extended Price:
ISSUED BY FOOT PER POUND UNITS.
'REFUSAL TO COMPLY WITH THESE TERMS MAY RESULT IN REMOVAL
FROM THE BIDDER'S LIST FOR FUTURE ORDERS.
City of For C Ilins Director of Purchasing and Risk Management
This order b4iot valid over $2000 unless signed by James B. O'Neill II, CPPO
City of Fort Collins Purchasing, PO Box 580, Fort Collins, CO 80522-0580
Phone: 970-221-6775 Fax: 970-221-6707 Email: info@ci.fort-collins.co.us
Total: 3,603.00
Mail Invoices in duplicate to:
City of Fort Collins
Accounting Department
PO Box 580
Fort Collins, CO 80522-0580
THE CITY OF FORT COLLINS
Light and Power Department
P.O. Box 580
Fort Collins. CO 80521
SPECIFICATION NO: 369-100
Single and Multiconductor Cross -Linked
Polyethylene 600 Volt Secondary Power Cable
APPROVED BY:
Tim M. a
Standards
PREPARED BY:
Standards Engineer
ORIGNATED: 3/22/73
Revised: 4/11/2002
Manager
REV. SYM: R
REVISION DESCRIPTIONS
REVISION DESCRIPTION (Previous on file)
CHANGE NOTICE
APPROVED
Revision N:
N/A
Tim M. Sagan
• Page 6. para. 3.2.1: Add quadruplex
Susan Coram
assembly:
5-23-90
• Page 10. para. 5.0: Add open -bed truck
Requirement
• Repaginate
Revision O:
N/A
Susan Coram
• Update Appendix A, Alcoa Now ACPC, remove
7-26-93
Kaiser & Reynolds
Tim M. Sagan
7-26-93
Revision P: Reissue
N/A
Tim M. Sagan
• Page 1, add filename
6-9-94
• Update Appendix A: Remove ACPC
Susan Coram
Revision O:
N/A
Tim M. Sagan
• Page 1, add "prepared by'
7-21-95
Susan Coram
• Page 7, para 3.2.3.1;
• Update Heat distortion test to Hot Creep and
Set
• Page 11, Update Cablec to BICC
Revision R:
April 11, 2002
Kraig Bader
• Reformated, converted to MS Word and
4/11/2002
delete List of Active Pages
Tim Sagan
• Page 6 Updated Table 1 - Added 350kcmil
4/11/2002
single conductor cable (7503-1038).
• Updated BICC to General Cable.
• Grammar correction in Section 3.2.1
2
369-100
REV. SYM: R
TABLE OF CONTENTS
REVISION DESCRIPTIONS.............................................................................................................................................2
TABLEOF CONTENTS....................................................................................................................................................3
1 SCOPE...............................................................................................................................................................................4
2 APPLICABLE DOCUMENTS........................................................................................................................................4
3 REQUIREMENTS........................................................................................................................................................... 4
3.1 GENERAL REQUIREMENTS...................................................................................................................................4
3.2 SPECIFIC REQUIREMENTS....................................................................................................................................4
3.3 IDENTIFICATION..................................................................................................................................................... 6
4 QUALITY ASSURANCE................................................................................................................................................6
4.1 RESPONSIBILITY FOR INSPECTION.................................................................................................................... 6
4.2 TESTS......................................................................................................................................................................... 6
5 PREPARATION FOR DELIVERY................................................................................................................................6
TABLE1.....................................................................................................................................6
APPENDIXA......................................................................................................................................................................7
3
369-100
REV. SYM: R
SPECIFICATION FOR
SINGLE AND MULTICONDUCTOR CROSS -LINKED
POLYETHYLENE 600 VOLT SECONDARY POWER CABLE
7 SCOPE
This specification establishes the minimum requirements for 600 volt, cross -linked polyethylene insulated,
secondary power cables suitable for direct burial, installation in ducts, or aerial applications.
2 APPLICABLE DOCUMENTS
The following documents of the issue shown form a part of this specification to the extent specified herein.
In those cases when the document is not dated, the latest issue in effect on the date of invitation for bids
shall form a part of this specification.
2.1 ICEA S-66-524
Cross -Linked -Thermosetting -Polyethylene -Insulated Wire and Cable for the Transmission and
Distribution of Electrical Energy.
2.2 ASTM B-230
3 REQUIREMENTS
3.1 GENERAL REQUIREMENTS
Cable purchased under this specification shall meet all applicable requirements of the Insulated Cable
Engineers Association (ICEA) Standard Publication S-66-524 with additions or deletions as detailed
herein.
3.1.1 APPROVED MANUFACTURERS
Cable purchased under this specification shall be of the manufacturers listed in Appendix A.
Manufacturers not listed may submit written proposals demonstrating compliance with these
specifications for consideration of addition to the accepted manufacturer list prior to the next
request for bids. Acceptability of the listed manufacturer's cable will not be determined solely by
inclusion in this list. Listed manufacturers must satisfy all requirements of this specification to be
acceptable.
3.2 SPECIFIC REQUIREMENTS
3.2.1 CABLE ASSEMBLY
When multi -conductor cable is required the assembly shall be as follows:
• Two conductor cables shall consist of two black insulated single conductors duplexed. The
length of lay shall not be less than 30 nor more than 60 times the insulated conductor diameter.
• Three conductor cables shall consist of two black phases and one yellow or yellow striped
neutral insulated single conductors triplexed. The length of lay shall not be less than 35 nor
more than 60 times the larger single insulated conductor diameter.
• Four conductor cables shall consist of three black phases and one yellow or yellow striped
neutral insulated single conductors quadruplexed. The length of lay shall not be less than 40
nor more than 60 times the larger single insulated conductor diameter.
3.2.2 CONDUCTOR
The conductor shall be "EC" grade aluminum, compressed stranding, in applicable sizes, as
required in Table 1. Stranding shall be in accordance with ICEA S-66-524 Part 2. Tensile strength
shall be 12,000 to 20,000 psi for solid conductors. Conductor diameters for the various cable sizes
purchased under this specification shall be in accordance with Table 1.
369-100
REV. SYM:R
3.2.3 INSULATION
Insulation shall be extruded cross -linked polyethylene (XLP) applied as an integral insulation -jacket
in accordance with ICEA S-66-524. In triplexed assemblies, phased conductors shall be black and
neutral conductor shall be either solid yellow or have three (3) equally spaced extruded yellow
stripes. Minimum insulation thickness at any point shall be not less than 90 percent of the minimum
average thickness values shown in Table 1. The insulation shall be applied in a manner which
prevents inclusions of insulation in the interstices of the conductor. If a mylar separator is used, it
must be opaque. Insulation properties shall be as required by ICEA S-66-524 and the following
paragraphs.
3.2.3.1 PHYSICAL AND AGEING REQUIREMENTS
Tensile strength (minimum).......................................................1,800psi
Elongation at rupture (minimum)...................................................250%
After air oven test at 121 °Cf1 °C for 168 hours — tensile
strength and elongation at rupture,
minimum percentage of un-aged value.......................................75%
Hot creep, 150' C ± 2' C maximum percent:
Unfilled....................................................................................175%
Filled........................................................................................ 100%
Hot creep set maximum percent:
Unfilled...................................................................................... 10%
Filled............................................................................................ 5%
Solvent extraction, maximum percent, after 20 hours
drying time (referee test): ............................................................. 30%
3.2.3.2 ELECTRICAL REQUIREMENTS
Insulation resistance constant (k) at 15.6°C (60°F),
minimum....................................................... ..... ...................... 10,000
SIC at 75°C, 80 VPM, 60 cycle, maximum........................................6.0
3.2.3.3 WATER ABSORPTION
Electrical Method
Dielectric constant after 1 day, maximum..........................................6.0
Increase in capacitance, maximum percent:
1 to 14 days.............................................................................. 3.0%
7 to 14 days.............................................................................. 1.5%
Stability factor after 14 days, maximum.............................................1.0
Alternate to stability factor -- stability factor difference, 1 to 14 days,
maximum............................................................................................0.5
5
369-100
REV. SYM: R
3.2.4 INDIVIDUAL CABLE REQUIREMENTS
The following table shows the catalogue numbers and the various requirements for insulation
thickness, compressed stranding, and assembly, for cable purchased under this specification.
Tahla 1 • (:ahlp Rimini irarnpntG
art �I {� 'li
I�fl„'+g�n
?
F�
�i �n i1� .
7503-0982
03
1
v ,H�i2;
1I0
19
.361
80
#2 7
.283
60
7503-1021
04 3
tri lex 1/0
19 .361
80
7503-1027
05
3
tri lex
4/0
19
.512
80
2/0 19
.406
80
7503-0993
06
1
4/0
19
.512
80
f,
4/0 19
.512
80
7503-1032
07 3
triplex 350
37 .661
95
7503-1036
08
1
"
500
37
.789
95
.�'�':
I,+++`
.f '•i�
7503-1034
09
4
uadIx
350
37
.661
95
1
.512 1
80
7503-1038
1 10
1
- `,
350
37 1
.661
95
I
11,
'Compressed wire
3.3 IDENTIFICATION
Each conductor shall have a durable continuous marking showing the manufacturer's name or
trademark, voltage rating, and conductor size. The separate phase conductors shall be individually
identified. Marking shall not cause surface irregularities.
4 QUALITY ASSURANCE
4.1 RESPONSIBILITY FOR INSPECTION
Unless otherwise specified, the vendor is responsible for the performance of all inspection
requirements as specified herein. Except as otherwise specified, the vendor may utilize his own
facilities or any commercial laboratory acceptable to the City of Fort Collins. The City reserves the right
to perform or witness any of the inspections set forth in this specification where such inspections are
deemed necessary. If required by the Purchase Order, representatives of an independent test
laboratory acceptable to the City of Fort Collins shall witness or perform all tests required therein and
shall certify all test reports.
4.2 TESTS
All cable manufactured under this specification shall be tested according to the applicable paragraphs
of ICEA specification S-66-524. If required by the Purchase Order, certified test reports shall be
furnished to the City of Fort Collins.
5 PREPARATION FOR DELIVERY
Packaging and marking of articles procured under this specification shall be in accordance with the
Purchase Order and the following: Each reel shall be legibly tagged with type, voltage, and length of the
cable, the purchase order number and the name and address of the manufacturer. Each reel shall be
weighed and marked with actual tare, gross and net weights. Average weights are NOT acceptable.
Reels shall be shipped on open -bed truck(s) with reels in the upright position; i.e., on flanges, and blocked
to prevent movement during shipping.
369-100
APPENDIX A
Approved Manufacturers
• Alcan Cable
• General Cable
• Pirelli Cable
• Southwire
369-100