ADDENDUM No. 1
SPECIFICATIONS AND CONTRACT DOCUMENTS
Description of Bid: Cable, Underground, 15KV, 750KCM
OPENING DATE: 2:00 p.m. (our clock ) February 7, 2002
To all prospective bidders under the specifications and contract documents described above, the
following changes are hereby made.
The diameter over shield (DOS) in the description for the cable on Bid #5761 has been
revised from 1.500+/-50 mils to 1.560+/_50 mils. The complete description follows:
QUANTITY: DESCRIPTION:
109,200 ft. Cable, underground, 15KV, 750 KCM, 61 strd., Blocked
strd. Compressed AL. conductor, min. 20 mils semi-
conducting XLP conductor shield, 220 mils nominal
TRXLPE insulation, 1.460"+/-30 mils DOI, min. 40 mils
semi -conducting black XLP insulation shield,
1.560"+/750 mils DOS, 12-#12 AWG untinned copper
concentric neutral, per Specification No. 367-102,
Rev. E, Serial 03 except 220 mils insulation
thickness, 12 #12 neutral, and no jacket. Ship on
lagged N/R reels meeting the following requirements:
max. flange dia. 70", Max. o/A Width 37", Min. drum
dia. 28" min. rim clear 2", 1400+/-25'
ATTENTION is also directed to the Exception of 220 mils insulation
thickness, 12#12 neutral, and no jacket in the description.
RECEIPT OF THIS ADDENDUM MUST BE ACKNOWLEDGED BY A WRITTEN STATEMENT
ENCLOSED WITH THE BID/QUOTE STATING THAT THIS ADDENDUM HAS BEEN RECEIVED.