Loading...
HomeMy WebLinkAboutAddenda - BID - 5671 CABLE UNDERGROUND 15KV 750KCM (2)CITY OF FORT COLLINS ADDENDUM No. 1 SPECIFICATIONS AND CONTRACT DOCUMENTS Description of Bid: Cable, Underground, 15KV, 750KCM OPENING DATE: 2:00 p.m. (our clock ) February 7, 2002 To all prospective bidders under the specifications and contract documents described above, the following changes are hereby made. The diameter over shield (DOS) in the description for the cable on Bid #5761 has been revised from 1.500+/-50 mils to 1.560+/_50 mils. The complete description follows: QUANTITY: DESCRIPTION: 109,200 ft. Cable, underground, 15KV, 750 KCM, 61 strd., Blocked strd. Compressed AL. conductor, min. 20 mils semi- conducting XLP conductor shield, 220 mils nominal TRXLPE insulation, 1.460"+/-30 mils DOI, min. 40 mils semi -conducting black XLP insulation shield, 1.560"+/750 mils DOS, 12-#12 AWG untinned copper concentric neutral, per Specification No. 367-102, Rev. E, Serial 03 except 220 mils insulation thickness, 12 #12 neutral, and no jacket. Ship on lagged N/R reels meeting the following requirements: max. flange dia. 70", Max. o/A Width 37", Min. drum dia. 28" min. rim clear 2", 1400+/-25' ATTENTION is also directed to the Exception of 220 mils insulation thickness, 12#12 neutral, and no jacket in the description. RECEIPT OF THIS ADDENDUM MUST BE ACKNOWLEDGED BY A WRITTEN STATEMENT ENCLOSED WITH THE BID/QUOTE STATING THAT THIS ADDENDUM HAS BEEN RECEIVED.