HomeMy WebLinkAboutBID - 5400 LP TRANSFORMERS 50KVAAdministrative Services
Purchasing Division
City of Fort Collins
INVITATION TO BID
Sealed bids will be received and publicly opened at the office of The Director of Purchasing and Risk
Management, 258 West Mountain Avenue, Fort Collins, Colorado 80521, ( P O Box 580, 80522) at
the time and date noted on the bid proposal and/or contract documents
Bids must be received at the Office of the Director prior to the opening time (our clock)
SPECIAL INSTRUCTIONS
All bids must be signed by an authorized representative of the company with the legal capacity to
bind the company to the agreement Bids may be withdrawn up to the date and hour set for opening
Once bids have been accepted by the City and opening time has passed, failure to enter into
contract or honor the purchase order will be cause for removal of supplier's name from the city of
Fort Collins' bidders list for a period of twelve months from the date of the opening The City may
also pursue any remedies available at law or in equity Bid prices must be held firm for a period of
forty-five days after bid openings
Submission of a bid is deemed as acceptance of all terms, conditions and specifications contained
in the City's specifications initially provided to the bidder Any proposed modification must be
accepted in writing by the City prior to award of the bid
Only bids properly received by the Purchasing Department will be accepted
No proposal will be accepted from, or any purchase order awarded, to any person, firm or
corporation in default on any obligation to the City
All bids must be labeled with both the project name and bid number indicated on the bid proposal
Bids must be furnished exclusive of any federal excise tax, wherever applicable
Bidders must be properly licensed and secure necessary permits wherever applicable
Vendors not responding to requests for bid shall be removed from our automated listing for the
requested commodities/services
The City may elect where applicable, to award bids on an individual item/group basis or on a total
bid basis, whichever is most beneficial to the City The City reserves the right to accept or reject any
and all bids, and to waive any irregularities or informalities
Sales Prohibited/Conflict of Interest No officer, employee, or member of City Council, shall have a
financial interest in the sale to the City of any real or personal property, equipment, material, supplies
or services where such officer or employee exercises directly or indirectly any decision -making
authority concerning such sale or any supervisory authority over the services to be rendered This
rule also applies to subcontracts with the City Soliciting or accepting any gift, gratuity favor,
entertainment, kickback or any items of monetary value from any person who has or is seeking to
do business with the City of Fort Collins is prohibited
256 W Mountain Avenue • PO Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6775 • FAX (970) 221-6707
REV SYM: II
TABLE OF CONTENTS
Title Page
Revision Record
List of Active Pages
Table of Contents
1 0
Scope
2.0
Applicable Documents
3.0
Requirements
3.1
General Requirements for Design
3.2
Specific Requirements for Design
21.0
Quality Assurance
4.1
General Quality Assurance
4 2
Test Conditions
4.3
Not Used
4 4
Tests
5.0
Preparation for Delivery
Table I
Figure 1
Figure 2
Appendix A
Appendix B
Appendix C
Appendix D
1
2
3
4
5
5
5
5
6
11
11
11
12
12
12
13
15
16
17
19
20
21
PAGE
4
368-105
REV SYM: II
SPECIFICATION 368.105
FOR
OVERHEAD -TYPE, SINGLE PHASE
DISTRIBUTION TRANSFORMERS WITH SEPARABLE
INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS
1.0 SCOPE
This Specification establishes the minimum requirements for single
phase, 60 hertz, mineral -oil -filled sell' cooled (0 I S C.)
overhead -type distribution transformers with separable insulated
load break high voltage connectors, rated 250 kilovolt- amperes
(KVA) and smaller, high -voltage 7620/13200Y and dual voltage
7620/13200Y x 2400/4160Y; low voltage 120/240, 240/480, 277 volts,
and 4160Y/2400.
2.0 APPLICABLE DOCUMENTS
The following American National Standards (ANSI) for Distribution,
Power, and Regulating Transformers and Shunt Reactors form a part
of this Specification.
General Requirements C57 12.00
Overhead -Type Distribution Transformers C57 12 20
Terminal Marking and Connections C57 12.70
Terminology C57.12.80
Test Code C57 12 90
Appendix to ANSI C57.12 20 C57.91
Separable Insulated Connectors ANSI/IEEE 386
3.0 REQUIREMENTS
3.1 GENERAL REQUIREMENTS FOR DESIGN
Unless otherwise stated in this Specification, all transformers
shall be new and shall conform to the American National Standard
Requirements for Overhead -Type Distribution Transformers, ANSI
C57.12.20 - latest revision In case of conflict, the
requirements of the following documents shall apply in the
priority shown:
1. This Specification.
2 Referenced ANSI Standards.
5
368-105
REV SYM. II
Approved manufacturers are listed in Appendix C. For purposes of
warranty and service, any distributor bidding must be an
authorized distributor appointed by an approved manufacturer to
serve the Fort Collins area.
3.2 SPECIFIC REQUIREMENTS FOR DESIGN
3.2.1 FUNCTIONAL DESCRIPTION
Transformers of this design are for installation on an underground
power system utilizing separable insulated connectors and may be
installed in underground vaults subject to submersion. They may
also be padmounted under an enclosure, or pole mounted. The
transformer tank, cover, and all external appurtenances shall be
of corrosion -resistant material, unless they are otherwise
rendered corrosion resistant.
3.2.2 RATINGS
3.2.2.1 KILOVOLT -AMPERE -RATINGS
3.2.2.1.1 NAMEPLATE RATING
Kilovolt -ampere ratings are continuous and based on not exceeding
either a 650C average winding temperature rise or an 80°C hot spot
temperature rise. The temperature rise of the insulating oil
shall not exceed 65' when measured near the top of the tank. The
KVA rating shall be regarded as a test rating which defines an
output which can be taken from the apparatus under the prescribed
conditions of test within the limitations of all applicable
standards KVA ratings shall be in accordance with Table I.
3.2.2.1.2 ADDITIONAL SUPPLEMENTAL LOADING
Additional supplemental loadings may be carried as recommended by
ANSI C57.91.
3.2.2.2 VOLTAGE RATINGS
Secondary and primary voltage ratings shall be in accordance with
Table I.
6
368-105
REV. SYM: II
3.2.2.3 IMPEDANCE
Nominal impedance voltage shall be in accordance with Table I of
this specification. Completed units may vary from the specified
nominal up to the tolerance specified in ANSI C57 12 00.
3.2.2.4 BASIC IMPULSE INSULATION LEVELS
The high voltage BIL shall be 95 kV. The low voltage BIL shall
be 30 kV
3.2.3 BUSHINGS AND TERMINALS
All internal leads and connections, on both high and low voltage,
shall be sized to carry full ampere rating, including overload
rating of transformer.
3.2.3.1 HIGH VOLTAGE TERMINALS
The number of high voltage terminals required is specified in
Table I. High voltage terminal(s) shall consist of cover mounted
universal type flowerpot bushing well(s) conforming to ANSI/IEEE
386-1985 Fig. 3.
3.2.3.2 LOW VOLTAGE TERMINALS
Terminal type and number shall be in accordance with Table I of
this specification Eyebolt and spade terminals shall be singly
mounted sidewall type. Stud type terminals shall be singly
mounted on the sidewall, internally or externally clamped, with
dimensions in accordance with Figure 1 of this specification. All
non-metallic components of the terminals shall be of a material
resistant to ultra -violet degradation Transformers with
secondary voltages above 480V require cover mounted bushing
well(s) having interfaces conforming to ANSI/IEEE 386-1985 Fig.
3.
3.2.4 NEUTRAL TERMINATION
3.2.4.1 On transformers having one high voltage bushing, the HZ end of the
winding shall be securely grounded internally.
7
368-105
® a REV. SYM II
3.2.4.2 On units having three external eyebolt or spade type low -voltage
terminals, the XZ connection of the winding shall be isolated and
an adequate external copper ground strap shall be provided from
the neutral bushing to a standard tank ground pad.
On units having lead type low -voltage terminals, the XZ
connections of the winding shall be connected to the tank
internally and such connection shall be indicated on a label next
to the XZ lead as well as on the nameplate.
Ground connections shall be suitably sized for the short-circuit
rating of the transformer as defined in ANSI C57.12.00
3.2.4.3 An adequate stainless steel connection shall provide electrical
continuity between the tank and the cover.
3.2.5 ACCESSORY EQUIPMENT
In addition to the requirements of ANSI, accessory equipment shall
be provided in accordance with Table I and the following details.
3.2.5.1 Current -protecting (CP) when specified in Table I shall include
internal weaklink primary fuse, secondary breaker, signal light,
and emergency control handle Internal fusing (internal) when
specified in Table I shall include an internal partial range
current limiting fuse in conjunction with an internal eutectic
(temperature sensitive) weak link fuse.
3.2.5.2 When required by Table I, an RTE Bay-o-net fuse and internally
mounted ELSP partial range current limiting fuse(s) shall be
furnished Bay-o-net fuses shall be top mounted or sidewall
mounted as required in Table I.
3.2.5.3 When the transformer is specified as a dual voltage unit, an
externally operated dual voltage switch shall be provided.
8
368.105
Ask
® REV. SYM II
3.2.5.4 Taps, when required, shall be full capacity above and below normal
and shall be provided with an externally operated tap changer
switch. On dual voltage transformers, taps shall be furnished on
the top voltage only
3.2.5.5 Cover mounted pocket type cable accessory parking stand for a
loadbreak stand off device shall be provided.
3.2.5.6 Cover mounted instruction nameplate conforming to 5 12 of ANSI
C57.12.00-1987, Nameplate A, shall be provided. Also, on the
nameplate or label affixed near it, the manufacturer shall
indicate that the dielectric fluid contains less than 1 ppm PCB.
3.2.6 TANK
3.2.6.1 An adequate tank coating for underground vault application shall
be provided. Appendix B is provided as a reference for comparing
coating requirements. The Light and Power Department, Engineering
Division, is the only authority regarding the adequacy of proposed
coatings Figure 2 shows outside dimensions
3.2.6.2 PRESSURE
The tank shall be equipped with a Qualitrol #202-014-01 or 202-
030-01 pressure relief device or a pressure relief cover. If a
pressure relief cover is used, the cover assembly shall remain
effectively sealed for overloads and external secondary short
circuits of the magnitude and duration allowed by industry
standards and loading guides, but shall relieve pressure at a
minimum of 8 psi gauge if designed to reseal; or at a minimum of
20 psig if designed for pressure relief without resealing. If a
pressure relief cover is used, a manual means of venting the tank
before removal of the cover shall be provided Regardless of
which means of pressure relief is provided, the tank and other
components of the tank shall be of sufficient strength to
withstand, without damage or permanent distortion, the pressures
occurring prior to pressure relief, as well as pressures occurring
due to normal overloads and external secondary short circuits.
9
368-105
El
REV SYM. II
3.2.6.3 GROUNDING PROVISIONS
A minimum of two tank mounted ground nuts fitted with a solderless
type connector for AWG conductor size No. 8 solid to No. 2
stranded shall be provided One ground connector shall be on the
tank sidewall, near the top of the tank, below the primary bushing
and the other shall be near the base, below the primary bushing.
3.2.7 LOSSES
The total losses of a transformer shall be the sum of the
excitation losses and the load losses (IZR losses). Load loss
tests shall be performed and reported on all units regardless of
whether or not a record of such tests is available on duplicate
units Loss evaluations and loss costs will be based on the
values shown in the "Special Conditions and Supplemental
Instructions to Bidders " Transformers will be evaluated on
excitation losses and I2R losses at the specified rates If
tested losses exceed quoted losses but are within the tolerances
of Table 18, ANSI C57.12 00-1987, the additional cost incurred
from the differential of losses will be calculated using the
following equation and the above specified rates and will be
deducted from the original Purchase Order or back charged to the
manufacturer In Table 18 and the following equation "Units"
shall mean "Transformers of the same size and design on one
order."
Excess loss $ = [No of units] [(No Load Loss Evaluation $) (Avg.
No Load Losses - Quoted No Load Losses) + (Load Loss Evaluation
$) (Avg Load Losses - Quoted Load Losses)]. If this equation
results in a negative number, no credit will be given the
Supplier
If any unit or units exceed the tolerances of Table 16, ANSI
C57.12.00-1980, that unit or units shall not be shipped without
express permission from the City If accepted, the deduction for
excess losses will be based on the following equation. Excess
loss $ = (No Load Loss Evaluation $) (No Load Losses - Quoted No
Load Losses) But Not Less Than Zero + (Load Loss Evaluation $)
(Load Losses - Quoted Losses) But Not Less Than Zero.
10
368-105
REV. SYM: II
4.0 QUALITY ASSURANCE
4.1 GENERAL
4.1.1 RESPONSIBILITY FOR INSPECTION
Unless otherwise specified, the vendor is responsible for the
performance of all inspection requirements as specified herein.
Except as otherwise specified, the vendor may utilize his own
facilities or any commercial laboratory acceptable to the City of
Fort Collins. The City reserves the right to perform or witness
any of the inspections set forth in this Specification where such
inspections are deemed necessary.
4.1.2 TEST REPORT
The manufacturer shall furnish to the purchaser certified copies
of the results of loss tests prior to payment Copies shall be
sent to the Design section as well as with the invoice. Unsigned
copies are not acceptable even if accompanied by a signed cover
letter.
4.2 TEST CONDITIONS
Unless otherwise specified, testing required by Section 4.4 shall
be conducted under the following conditions.
4.2.1 REFERENCE TEMPERATURE
The reference temperature to which losses, impedance, regulation,
and efficiency are corrected shall be 850C
4.2.2 TOLERANCE ON IMPEDANCE VOLTAGE
Impedance on completed units shall fall within the ranges
specified herein.
4.2.3 TOLERANCE ON IMPEDANCE VOLTAGE ON A TAP
The percent departure of tested impedance voltage on any tap from
tested impedance voltage at rated voltage shall not be greater
than the total tap voltage range expressed as a percentage of the
rated voltage.
11
368.105
REV SYM JJ
4.3 NOT USED
4.4 TESTS
The kinds of tests to be performed and the test procedures shall be as specified in
ANSI C57 12 20, ANSI C57 12 00, and C57 12 90 except impedance and load -loss
tests shall be made on each unit and may not be omitted even if a record of such tests
made on a duplicate unit is available
5.0 PREPARATION FOR DELIVERY
Transformers shall be prefilled with the appropriate amount of transformer oil and shall
be shipped by open -bed truck Units shall be packaged in such a way as to provide for
ease of handling and to protect them form shipping damage Units shall be packaged
on four-way universal pallets with 34 inch minimum opening and loaded on the truck for
side removal The Supplier shall give 24 hour notice prior to delivery for any shipments
where an individual transformer weighs over 5,000 pounds In addition to these
requirements, the Supplier shall comply with any additional requirements or
modifications shown on the purchase order and/or supplemental instructions
12
368-105
TABLE I
STOCK NO
HIGH VOLTAGE
LOW VOLTAGE
368-105
SERIAL
KVA
% Z
RATING
TERMINAL(S)
TAPS
RATING
TYPE AND
NUMBER OF
TERMINALS
PROTECTION
TYPE**
ABOVE
BELOW
-111
10
TBD
13200 GRDY/7620
One bushing well
-
120/240*
Three Eyebolt
CP
-131
25
1 77 to 2 16
13200 GRDY/7620
One bushing well
-
120/240*
Three CU stud
CP
-151
50
1 77 to 2 16
13200 GRDY/7620
One bushing well
-
-
120/240*
Three CU stud
CP
-155
50
TBD
7620/13200Y
Two bushing wells
2-2112%
2-2i%
120/240*
Three 4 hole "H"
S
-156
50
TBD
13200 GRDY/7620
One bushing well
-
240/480
Three Eyebolt
CP
-161
75
1 86 to 2 27
13200 GRDY/7620
One bushing well
120/240*
Three CU stud
Internal
-171
100
TBD
13200 GRDY/7620
One bushing well
120/240*
Three Eyebolt
Internal
-174
100
TBD
13200 GRDY/7620
One bushing well
2-2i%
2-2%%
1201240
Four 6 hole "J"
Internal
-175
100
TBD
7620/13200Y
Two bushing wells
2-2i%
2-2i%
120-240
Four 6 hole "J"
S
-176
100
TBD
13200 GRDY/7620
One bushing well
2-2%%
2-22%
277
Two 4 hole "H"
Internal
-177
100
TBD
7620/13200Y
Two cover mounted
bushing wells
2-2i%
2-2i%
2400/4160Y
Two cover mounted
bushing wells
S
-184
167
TBD
13200 GRDY/7620
One bushing well
2-22%
2-2i%
1201240
Four 6 hole "J"
Internal
-185
167
TBD
7620/13200Y
Two bushing wells
2-2112%
2-2i%
120/240
Four 6 hole "J"
S
-186
167
TBD
13200 GRDY/7620
One bushing well
2-2i%
2-22%
277
Two 4 hole "H"
Internal
* Reconnectable in field for 120/208 volt service
** CP refers to current -protecting (see para 3 2 5 1)
TBD = To be Determined
S refers to conventional
Internal refers to current limiting protection (see para 3 2 5 1)
m
C
(n
3
{
Freight Terms Unless otherwise noted, all freight is F O B destination, freight prepaid All freight
charges must be included in prices submitted on proposal
Discounts Any discounts allowed for prompt payment, etc , must be reflected in bid figures and not
entered as separate pricing on the proposal form
Purchasing Restrictions Your authorized signature of this bid assures your firm's compliance with
the City's purchasing restrictions on cement A copy of the Resolution 91-121 is available for review
in the Purchasing Division or the City Clerk's office
Collusive or Sham Bids Any bid deemed to be collusive or a sham bid will be rejected and reported
to authorities as such Your authorized signature of this bid assures that such bid is genuine and
is not a collusive or sham bid
Bid Results For information regarding results for individual bids send a self-addressed, self -stamped
envelope and a bid tally will be mailed to you.
<\ mes B O'N�IIOCPPO
erector of Purchasing & Risk Management
TARI E I (CONT
STOCK NO
LOW VOLTAGE
368-105
HIGH VOLTAGE
PROTECTION
TAPS
TYPE
SERIAL
KVA
% Z
RATING
TERMINAL(S)
RATING
TYPE AND
ABOVE
BELOW
NUMBER OFTERMINALS
-189
167
TBD
13200 GRDY/7620
One cover mounted
4160GRDY/
One cover mounted
S
bushing wells
2400
bushing well
-195
250
TBD
7620/13200Y
Two bushing wells
2-2i%
2-2i%
120/240
Four 6 hole "J"
S
-196
j 250
TBD
13200 GRDY/7620
One bushing well
2-2i%
2-2%%
277
Two 6 hole "J"
Internal
-231
25
TBD
13200 GRDY/7620x
One bushing well
120/240*
Three Eyebolt
CP
4160 GRDY/2400
-238
25
TBD
13200 GRDY/7620x
One bushing well
2-2/%
2-2i%
240/480
Three Eyebolt
CP
4160 GRDY/2400
-251
50
TBD
13200 GRDY/7620X
One bushing well
-
-
120/240*
Three Eyebolt
CP
4160 GRDY/2400
-258
50
TBD
13200 GRDY/7620X
One bushing well
2-22%
2-22%
240/480
Three Eyebolt
CP
4160 GRDY/2400
* Reconnectable in field for 120/208 volt service
** CP refers to current -protecting (see para 3 2 5 1)
TBD = To be Determined
7
J
�J
S refers to conventional
Internal refers to current limiting protection (see para 3 2 5 1)
m
C
(n
3
REV. SYM. II
kVa
Rating
Thread
Size
Min
Length
25 to 75
0 625"-11 UNC-2A
1.25"
100 to 167
1 0"-14 UNC-2A
1.75"
Figure 1
15
368-105
Cif
REV SYM: II
MAXIMUM CLEARANCE DIMENSIONS*
KVA
A
B
C**
75 and Below
27
33
44
100 and Above
36
36
50
* In Inches
** C dimension is to the top of the bushing well insert, (City
provided)
Figure 2
16
368-105
REV. SYM: II
APPENDIX A
Figure 1A demonstrates the coding method used to establish City
of Fort Collins Stock Numbers for transformers.
17
368.105
REV. SYM: II
I. SINGLE PHASE
II. THREE PHASE
FIGURE 1A
TRANSFORMER STOCK NUMBER CODING
OTHER
0 = 5
KVA
1 = 10
KVA
2 = 15
KVA
3 = 25
KVA
4 = 37.5
KVA
5 = 50
KVA
6 = 75
KVA
7 = 100
KVA
8 = 167
KVA
9 = 250
KVA
1 = Single Voltage
2 = Dual Voltage
00 = 13.2Y/7620 and 7620/13.2Y x 2400/4160
outside pole
05 = 13.2Y/7620 ESNA pole
20 = 13.2Y/7620 ESNA pad
Ingle Phase
former Class
006
= 75
KVA
015
= 150
KVA W/208Y/120 sec.
030
= 300
KVA
050
= 500
KVA
075
= 750
KVA
100
= 1000
KVA
150
= 1500
KVA
XYZ + 1 = 480Y/277 sec
3 phase pad
Transformer Class
18
368-105
REV SYM: II
APPENDIX B
This Appendix is not intended to dictate requirements for items
purchased under Specification 368-105, but is included as an aid
in comparing coatings for those manufacturers attempting to meet
the requirements of this design
Tank coatings listed here are for reference only and shall not be
considered as complete. Also, the City of Fort Collins shall not
be held responsible for patent infringements incurred through the
use of this information.
B.1 ARMORTEC, a fusion bonded vinyl resin having a minimum
coating thickness of 15 mils
B.2 Coal -tar Epoxy having a minimum thickness of 15 mils
applied in two coats over a zinc rich primer and
overcoated with flow coat applied black enamel paint
B.3 Electrostatically applied thermosetting polyester
applied as follows
1. Five Stage Wash - alkaline detergent, water
rinse, phosphate treatment, water rinse, and
sealing rinse.
2 Delay Line - dry and cool
3 Coat - Electrostatically coat with a thermoset-
ting polyester.
4 Bake - Heat as recommended by polyester
manufacturer to set polyester
5. Cool.
6. Repeat Process - Repeat applicable steps of above
process to obtain a minimum dry build of 6 mils.
B.4 Ceilcote Flakeline 252 (minimum thickness 35 mils)
19
368-105
REV. SYM II
APPENDIX C
Transformers purchased under this Specification shall be of the make
shown below. Manufacturers not listed below may submit written
proposals demonstrating compliance with these Specifications for
consideration of addition to the accepted manufacturers list prior
to the next request for bids. In addition to inclusion on the list
below, manufacturer's equipment must also satisfy all requirements
of this Specification to be acceptable
MANUFACTURER
Cooper Power Systems
Howard Industries
ABB
SERIAL NO
Al 1 except 196 & 195
All
All
The manufacturers in the following list have been conditionally
approved and may bid as an alternate. The definition and intent of
"Conditional Approval" of a manufacturer is to allow the City to
gain some experience with the manufacturer's product Should a
conditionally approved manufacturer be the evaluated low bidder, the
City reserves the right to award all, part, or none of the order to
them, dependant upon the current needs of the City for that item or
items.
20
368-105
0
REV. SYM: II
APPENDIX D
The following forms for Individual and Average Transformer Losses
are used by the City of Fort Collins to determine loss penalties
1) Transformer Loss Evaluation Average Losses Form.
2) Individual Transformer Loss Evaluation Form.
21
368-105
C)
REV. SYM: II
TRANSFORMER LOSS EVALUATION
AVERAGE LOSSES
City Order No
Manufacturer
KVA/Unit
LINE
(1) No. of units
(2) Average core losses
S/N
Invoice No,
DESCRIPTION
(3) Quoted core losses
(4) Excess average core losses
line (2) less line (3)
(5) Penalty for excess average core losses:
line (1) x line (4) x $
(6) Average copper losses
(7) Quoted copper losses
(8) Excess average copper losses
line (6) less line (7)
(9) Penalty for excess average copper losses:
line (1) x line (8) x $
(10) Penalty to be assessed manufacturer
line (5) plus line (9) but not less
than zero
AMOUNT
Date Prepared By:
Design Engineering '
NOTE: If any unit(s) exceeds the loss tolerances of ANSI C57.12 00,
Light & Power will either reject it, include it on these
averages, or calculate losses using the Individual Transformer
Losses Evaluation Form, whichever is most favorable to Light
and Power
22
368.105
REV SYM: II
INDIVIDUAL TRANSFORMER LOSS EVALUATION
City Order No
Manufacturer
KVA/Um t
S/N
Invoice No.
LINE DESCRIPTION
(1) Tested core losses
(2) Quoted core losses
(3) Excess core losses
line (1) less line (2) but not less
than zero
(4) Percent difference
line (3) — line (2) x 100
(5) Tested total losses
(6) Quoted total losses
(7) Excess total losses
line (5) less line (6) but not less
than zero
(8) Percent difference
line (7) _ line (6) x 100
(9) Tested copper losses
(10) Quoted copper losses
(11) Excess copper losses
line (9) less line (10) but not less
than zero
(12) Penalty for excess core losses
line (3) x $
(13) Penalty for excess copper losses
line (11) x $
(14) Penalty to be assessed manufacturer
line (12) plus line (13)
Date Prepared By:
Design Engineering
AMOUNT
23
368-105
FIRM NAME
CITY OF FORT COLLINS
BID PROPOSAL
BID NO 5400
BID DATE: 2:00 p m (our clock) July 6, 1999
WE HEREBY ENTER OUR BID FOR THE CITY OF FORT COLLINS' REQUIREMENTS
FOR TRANSFORMERS, 50 KVA PER THE BID INVITATION AND ANY REFERENCED
SPECIFICATIONS
QUANTITY DESCRIPTION
100 Ea Transformer, 50 KVA, modified over -head, single phase
distribution with one high -voltage bushing well, high voltage
rating 13200 GRDY/ 7620 Low voltage rating 120/240 Serial
number 151 to be in accordance with specification #368-105-151,
revision JJ
$ Ea $ Total
Delivery in Weeks
Mfr & Mfr #
Guaranteed No Load Loss
Guaranteed Full Load Loss
Guaranteed Total Load
Loss
Impedance (%)
The transformers being bid meet or exceed the specifications Yes_ No If not,
please list exceptions on a separate sheet of paper and attach to your bid
3
Page 1 of 2
qWP
Issued:
9/7/77
Revised•
9-4-97
Special Conditions and
Supplemental Instructions to Bidders
Applicable to Specification 368-105
A Data to be Supplied with Bidder's Proposal
The following data shall be supplied with the bidder's proposal
in addition to that information required by the "Invitation to
Bid" and the "Purchase Requisition"
1 Impedance volts in % at full load, high voltage to low
voltage at 850C
2. No load and total losses at 85°C
3. Protective tank coating specification
4. A statement indicating compliance with our Specification
without exception
5 Escalation is , is not applicable for the
transformers bid If escalation applies, the Bidder shall
indicate in his bid the specific items or materials subject
to escalation, and shall give the method and indices to be
used in computing the amount thereof. Escalation occurring
after the quoted delivery date will not be paid unless
delays are the result of actions by the City Escalation
occurring after acceptance, if Purchaser exercises the
option to delay shipment after manufacturing is completed.
will not be paid
Failure to supply the above data shall constitute a basis for
rejection of the bid
B Loss Evaluations
Loss penalties and loss evaluations will be based on the
following values
1 No load or excitation losses at'�3.9p/watt
2 Load losses at 'f/• 5o /watt
C Shipping Terms
Ship F 0 B point of destination, freight prepaid
D Terms of Payment
1 If escalation applies, the City of Fort Collins shall
not be billed for escalation occurring after the
promised delivery date Escalation charges shall be
itemized on the invoice
Page 2 of 2
Test reports shall accompany the invoice. If test
reports do not accompany the invoice, late payment
penalty charges incurred due to delays in obtaining the
test reports will not be paid Certified copies of test
reports shall be sent to the Design Section, Fort
Collins Light and Power Utility
Loss penalty credits and escalation charges shall be
itemized on the invoice
ALTERNATE 1 Afflk
IV MR
City of Fort Collins
Light and Power Department
Specification 368-110 - Revised I I-June-1999
Single Phase Submersible Cover Mount Transformer
1 Scope
This specification and the accompanying drawing establishes the minimum requirements for
an alternate design to City of Fort Collins Light and Power Specification 368-105 for single
phase 60 hertz mineral oil filled self cooled vault type distribution transformers The
requirements of Specification 368-105 and applicable American National Standard
requirements for distribution transformers shall apply except where specifically altered by this
Specification
2 Primary
a 13,200 GRDY/7620, No Taps, Single Voltage
b Radial feed (1- HV bushing)
c ESNA long shank wells welded to tank
d "NO" inserts provided
3 Secondary
a 240/120, 3-wire (3-bushing LV pattern) (exception to 368-105 Table I, cannot be banked
for 3phase 208Y/120 service)
b X2 internally grounded (clarification to 368-105 paragraph 3.2.4.2)
c Welded Central Moloney bushings with external epoxy (dia. <1.38 see 368-105 Fig. 1)
d 5/8" threaded copper stud termination
e Additive polarity
4 Electrical Requirements
a Frequency 60 Hertz
a KVA 25, 50, or 75 as requested
b BIL 95 kV
c Impedance Limits
KVA
Impedance
25
1 77% < %Z < 2 16%
50
1 77% < %7_ < 2 16%
75
1 86% < %Z < 2 27%
5 Fusing (exception to 368-105 Table 1)
a Submersible type bayonet with overload dual sensing fuse element as shown below
b RTE ELSP 8 3 kV under oil partial range current limiting fuse as shown below
c "NO" low voltage under oil breaker
KVA
RTE Bayonet
RTE EI.SP
25
358C05
40 amp 354304OM61M
50
358C08
80 amp 354308OM51 M
75
358C10
125 amp 3543125M61M
Ior2
3681 I0A DOC
Aim
City of Fort Collins
Light and Power Department
Specification 368-110 - Revised 11-June-1999
Single Phase Submersible Cover Mount Transformer
6 Tank Design
a Tank material 105" (12 gauge) stainless steel (304 SST)
b Tomko 1720K-1 pressure relief device located on cover
c Tank dram 1 00" NPT flush coupling with brass pipe plug
d (2) 1 00" NPT fill couplings located on cover with brass pipe plugs
e (1) Tomko LG35 sight gauge/oil level coupling
f (2) 1/2 - 13 SS1 ground pads centered on tank below primary bushing 7" from top and 7"
from base respectively
g (1) Y2 - I3 SST ground pad on top near primary bushing
h (1) SST loadbreak type parking stand
i Cover to be welded to tank
j Welded base runners
k (2) Lifting hooks opposite each othei welded on the front and back side of the tank near the
top
7 Markings
a XI, X2 & X3 SST identification tags with black lettering
b "X2 Int Grid" stenciled in black on cover
c Bayonet warning decals located near bayonet fuse
d SST nameplate in accordance with paragraph 3 2 5 6
e Temporary serial/shipping card attached to tank lift -eye
8 Misc Design Issues
a Cooling 65 Deg C AWR, average ambient 30 Deg C (55 Deg C AWR and 40 Deg C
ambient)
b Final color ASA 70 Gray
c All exposed parts shall be constructed of corrosion resistant material, e g , SST, brass, or
plastic
d Two-way pallet with mimmum width of 34"
2of 2
368110A DOC
I
I
I
I
I
I
I
I
�I
(
I
I
I
I
I
J1 00
�._ ?? nn MAX, r
j1 5
1 �s
— J--i
01
HIGH VOLTAGE BUSHING WELL
02
LOW VOLTAGE BUSHING (5/8 — 13 UNC STUD)
03
SST PARKING STAND (LOADBREAK TYDPE)
05
STAINLESS STEEL TANK (304 SST)
06
LIFTING HOOK
08
SST NAMEPLATE
11
PRESSURE RELIEF DEVICE (TOMCO 1720K-1)
12
1 00 — NPT DRAIN PLUG
14
OIL LEVEL GAUGE (TOMCO LG35)
16
'/2 - 13 UNC SST GROUND PAD
18
SST I D TAGS FOR ALL BUSHINGS
7 P9Ax. 21
31
TRANSFORMER SUPPORT RAILS
SUBMERSIBLE BAYONET IN SERIES WITH UNDER OIL
PARTIAL RANGE CURRENT LIMITING FUSE
I
CITY OF FORT COLLINS, LIGHT AND POWER
TITLE SINGLE PHASE VAULT TYPE TRANSFORMER
DES 1PH SUBMERSIBLE, 1-HV, 3-LV, 13200 GRDY/7620 X 240/120, 25,50, &75 kVA
DRAWING/SPECIFICATION NO 368-110 1 REV A
SCALE NTS I DRAWN BY TMS I APPD BY TMS I DATE 6/11/99
Purchase Order Term
1 COMMERCIAL DETAILS
Imoice Address To ensure prompt Payment mail invoices in duplicate to
City of Fort Collins Accounting Division
P 0 Box 580
Fort Collins, CO 80522
Tax exemptions By statute the City of Fort Collins is exempt from state and local
taxes Our Exemption Number is 98-04SO2 Federal Excise Tax Exemption
Certificate of Registry 84-6000587 is registered with the Collector of Internal
Revenue, Denver, Colorado (Ref Colorado Revised Statutes 1973, Chapter
39-26, 114 (a)
Goods Rejected GOODS REJECTED due to failure to meet specifications, either
when shipped or due to defects of damage in transit, may be returned to you for
credit and are not to be replaced except upon receipt of written instructions from
the City of Fort Collins
Inspection GOODS are subject to the City of Fort Collins inspection an arrival
Final Acceptance Receipt of the merchandise, services or equipment in response
to this order can result in authorized payment on the part of the City of Fort
Collins However, it is to be understood that FINAL ACCEPTANCE is dependent
upon completion of all applicable required inspection procedures
Freight Terms Shipments must be F 0 B , City of Fort Collins, 700 Wood St ,
Fort Collins, CO 80522, unless otherwise specified on this order If permission
is given to prepay freight and charge separately, the original freight bill must
accompany invoice Additional charges for packing will not be accepted
Shipment Distance Where manufacturers have distributing points in various parts
of the country, shipment is expected from the nearest distribution point to
destination, and excess freight will be deducted from Invoice when shipments are
made from greater distance
Permits Seller shall procure at sellers sole a ost all necessary permits, certificates
and licenses required by all applicable laws, regulations, ordinances and rules of
the state, municipality, territory or political subdivision where the work is
performed, or required by any other duly constituted public authority having
jurisdiction over the work of vendor Seller further agrees to hold the City of Fort
Collins harmless from and against all liability and loss incurred by them by reason
of an asserted or established violation of any such laws, regulations, ordinances,
rules and requirements
Authorization All parties to this contract agree that the representatives are, in
fact, bona fide and possess full and complete authority to bind said parties
LIMITATION OF TERMS This Purchase Order expressly limits acceptance to the
terms and conditions stated herein set forth and any supplementary or additional
terms and conditions annexed hereto or incorporated herein by reference Any
additional or different terms and conditions proposed by seller are objected to and
hereby rejected
2 DELIVERY
PLEASE ADVISE PURCHASING AGENT immediately if you cannot make complete
shipment to arrive on your promised delivery date as noted Time is of the
essence Delivery and performance must be effected within the time stated on
the purchase order and the documents attached hereto No acts of the
Purchasers including, without limitation, acceptance of partial late deliveries, shall
operate as a waiver of this provision In the event of any delay, the Purchaser
shall have, in addition to other legal and equitable remedies, the option of placing
this order elsewhere and holding the Seller liable for damages However, the
Seller shall not be liable for damages as d result of delays due to causes not
reasonably foreseeable which are beyond its reasonable control and without its
fault of negligence, such acts of God, acts of civil or military authorities,
governmental priorities, fires, strikes, flood, epidemics, wars or riots provided
that notice of the conditions causing such delay is given to the Purchaser within
five (5) days of the time when the Seller first received knowledge thereof In the
event of any such delay, the date of delivery shall be extended for the period
equal to the time actually lost by reason of the delay
3 WARRANTY
The Seller warrants that all goods, articles, materials and work covered by this
order will conform with applicable drawings, specifications, samples and/or other
descriptions given, will be fit for the purposes intended, and performed with the
highest degree of care and competence in accordance with accepted standards
for work of a similar nature The Seller agrees to hold the purchaser harmless
from any loss, damage or expense which the Purchaser may suffer or incur on
account of the Sellers breach of warranty The Seller shall replace, repair or make
good, without cost to the purchaser, any defects or faults arising within one (1)
year or within such longer period of time as may be prescribed by law or by the
terms of any applicable warranty provided by the Seller after the date of
acceptance of the goods furnished hereunder (acceptance not to be unreasonably
delayed), resulting from imperfect or defective work done or materials furnished
s and Conditions
by the Seller Acceptance or use of goods by the Purchaser shall not constitute
a waiver of any claim under this warranty Except as otherwise provided in this
purchase order, the Sellers liability hereunder shall extend to all damages
proximately caused by the breach of any of the foregoing warranties or
guarantees, but such liability shall in no event include loss of profits or loss of use
NO IMPLIED WARRANTY OR MERCHANTABILITY OR OF FITNESS FOR PURPOS
SHALL APPLY
4 CHANGES IN LEGAL TERMS
The Purchaser may make changes to legal terms by written change order
5 CHANGES IN COMMERCIAL TERMS
The Purchaser may make any changes to the terms, other than legal terms,
including additions to or deletions from the quantities originally ordered in the
specifications or drawings, by verbal or written change order If any such Chang
affects the amount due or the time of performance hereunder, an equitable
adjustment shall be made
6 TERMINATIONS '
The Purchaser may at any time by written change order, terminate this agreemen
as to any or all portions of the goods then not shipped, subject to any equitable
adjustment between the parties as to any work or materials then in progress
provided that the Purchaser shall not be liable for any claims for anticipated profit
on the uncompleted portion of the goods and/or work, for incidental or
consequential damages, and that no such adjustment be made in favor of the
Seller with respect to any goods which are the Sellers standard stock No such
termination shall relieve the Purchaser or the Seller of any of their obligations a
to any goods delivered hereunder
7 CLAIMS FOR ADJUSTMENT
Any claim for adjustment must be asserted within thirty (30) days from the dot
the change or termination is ordered
S COMPLIANCE WITH LAW
The Seller warrants that all good•, sold hereunder shall have been produced, sold
delivered and furnished in strict compliance with all applicable laws and
regulations to which the goods are subject The Seller shall execute and deliver
such documents as may be required to effect or evidence compliance All laws an
regulations required to be incorporated in agreements of this character are hereb
incorporated herein by this reference The Seller agrees to indemnify and hold th
Purchaser harmless from all costs and damages suffered by the Purchaser as a
result of the Sellers failure to comply with such law
9 ASSIGNMENT
Neither party shall assign, transfer, or convey this order, or any monies due or t
become due hereunder without the prior written consent of the other party
10 TITLE
The Seller warrants full, clear and unrestricted title to the Purchaser)) for all
equipment, materials, and items furnished in performance of this agreement, fre
and clear of any and all hens, restrictions, reservations, security interest
encumbrances and claims of others
11 NONWAIVER
Failure of the Purchaser to insist upon strict performance of the terms and
conditions hereof, failure or delay to exercise any rights or remedies provided
herein or by law, failure to promptly notify the Seller in the event of a breach, th
acceptance of or payment for goods hereunder or approval of the design, shall no
release the Seller of any of the warranties or obligations of this purchase order an
shall not be deemed a waiver of any right of the purchaser to insist upon strict
performance hereof or any of its rights or remedies as to any such )goods,
regardless of when shipped, received or accepted, as to any prior or subsequen
default hereunder, nor shall any purported oral modification or rescission of this
purchase order by the Purchaser operate as a waiver of any of the terms) hereof
12 ASSIGNMENT OF ANTITRUST CLAIMS
Seller and the Purchaser recognize that in actual AD. practice, overcharges
resulting fropi antitrust violations are in fact borne by the Purchaser Theretofore,
fongood cause and as consideration for executing this purchase order, the Seller
hereby assigns to the Purchaser any and all claims it may now have or hereafter
acquired under federal or state antitrust laws for such overcharges relating to the
particular goods or services purchased or acquired by the Purchaser pursuant to
this purchase order
13 PURCHASERS PERFORMANCE OF SELLERS OBLIGATIONS
If the Purchaser directs the Seller to correct nonconforming or defective goods
by a date to be agreed upon by the Purchaser and the Seller, and the Seller
thereafter indicates its inability or unwillingness to comply, the Purchaser may
cause the work to be performed by the most expeditious means available to it,
and the Seller shall pay all costs associated with such work
The Seller shall release the Purchaser and its contractors of any tier from all
liability and claims of any nature resulting from the performance of such work
This release shall apply even in the event of fault of negligence of the party
released and shall extend to the directors, officers and employees of such party
The Seller's contractual obligations, including warranty, shall not be deemed to
be reduced, in any way, because such work is performed or caused to be
performed by the Purchaser
14 PATENTS
Whenever the Seller is required to use any design, device, material or process
covered by letter, patent, trademark or copyright, the Seller shall indemnify and
save harmless the Purchaser from any and all claims for infringement by reason
of the use of such patented design, device, material or process in connection
with the contract, and shall indemnify the Purchaser for any cost, expense or
damage which it may be obliged to pay by reason of such infringement at any
time during the prosecution or after the completion of the work In case said
equipment, or any part thereof or the intended use of the goods, is in such suit
held to constitute infringement and the use of said equipment or part is enjoined,
the Seller shall, at its own expense and at its option, either procure for the
Purchaser the right to continue using said equipment or parts, replace the same
with substantially equal but non -infringing equipment, or modify it so it becomes
non -infringing
15 INSOLVENCY
If the Seller shall become insolvent or bankrupt, make an assignment for the
benefit of creditors, appoint a receiver or trustee for any of the Sellers property
or business, this order may forthwith be canceled by the Purchaser without
liability
16 GOVERNING LAW
The definitions of terms used or the interpretation of the agreement and the
rights of all parties hereunder shall be construed under and governed by the laws
of the State of Colorado, USA
The following Additional Conditions apply only in cases where the Seller is to
perform work hereunder, including the services of Sellers Representativelsl, on
the premises of others
17 SELLERS RESPONSIBILITY
The Seller shall carry on said work at Seller's own risk until the same is fully
completed and accepted, and shall, in case of any accident, destruction or injury
to the work and/or materials before Seller's final completion and acceptance,
complete the work at Seller's own expense and to the satisfaction of the
Purchaser When materials and equipment are furnished by others for installation
or erection by the Seller, the Seller shall receive, unload, store and handle same
at the site and become responsible therefor as though such materials and/or
equipment were being furnished by the Seller under the order
18 INSURANCE
The Seller shall, at his own expense, provide for the payment of workers
compensation, including occupational disease benefits, to its employees
employed on or in connection with the work covered by this purchase order,
and/or to their dependents in accordance with the laws of the state in which the
work is to be done The Seller shall also carry comprehensive general liability
including, but not limited to, contractual and automobile public liability insurance
with bodily injury and death limits of at least $300,000 for any one person,
$500,000 for any one accident and property damage limit per accident of
$400,000 The Seller shall likewise require his contractors, if any, to provide for
such compensation and insurance Before any of the Sellers or his contractors
employees shall do any work upon the premises of others, the Seller shall furnish
the Purchaser with a certificate that such compensation and insurance have been
provided Such certificates shall specify the date when such compensation and
insurance have been provided Such certificates shall specify the date when such
compensation and insurance expires The Seller agrees that such compensation
and insurance shall be maintained until after the entire work is completed and
accepted
19 PROTECTION AG ACCIDENTS AND DAMAGES
The Seller hereby assumes the entire responsibility and liability for any and all
damage, loss or injury of any kind or nature whatsoever to persons or property
caused by or resulting from the execution of the work provided fort in this
purchase order or in connection herewith The Seller will indemnify and hold
harmless the Purchaser and any or all of the Purchasers officers, agents and
employees from and against any and all claims, losses, damages, charges or
expenses, whether direct or indirect, and whether to persons or property to whit
the Purchaser may be put or subject by reason of any act, action, neglect,
omission or default on the part of the Seller, any of his contractors, or any of th
Sellers or contractors officers, agents or employees In case any suit or other
proceedings shall be brought against the Purchaser, or its officers, agents or
employees at any time on account or by reason of any act, action, neglect,
omission or default of the Seller of any of his contractors or any of its IIor then
officers, agents or employees as aforesaid, the Seller hereby agrees to assume th
defense thereof and to defend the same at the Sellers own expense, to pay any
and all costs, charges, attorneys fees and other expenses, any and all judgment
that may be incurred by or obtained against the Purchaser or any of its or then
officers, agents or employees in such suits or other proceedings, and Iin case
judgment or other lien be placed upon or obtained against the property of the
Purchaser, or said parties in or as a result of such suits or other proceedings, th
Seller will at once cause the same to be dissolved and discharged by giving bon
or otherwise The Seller and his contractors shall take all safety precautions,
furnish and install all guards necessary for the prevention of accidents, icomply
with all laws and regulations with regard to safety including, but without
limitation, the Occupational Safety and Health Act of 1970 and all rules and
regulations issued pursuant thereto
9/90
Revised 11/91
Firm Name
Alternate 1
QUANTITY DESCRIPTION
100 Ea Transformer, 50 KVA submersible, single phase with one cover
mounted separable insulated load break high voltage bushing
well, three cover mounted stud secondary bushings, submersible
bayonet fuse High voltage rating 13200 GRDY/7620, low
voltage rating 240/120 Per drawing #368-110, revision A
E
Delivery in Weeks
Mfr & Mfr #
Guaranteed No Load Loss
Guaranteed Full Load Loss
Guaranteed Total Load
Loss
Impedance (%)
Total
The transformers being bid meet or exceed the specifications Yes_ No _ If not,
please list exceptions on a separate sheet of paper and attach to your bid
4
Firm Name
Alternate 2:
QUANTITY DESCRIPTION
100 Ea Transformer, 50KVA underground -type, single phase with one
cover mounted separable insulated load break high voltage
bushing well, three low -voltage cable leads, submersible bayonet
fuse High voltage rating 13200 GRDY/7620, low voltage rating
240/120 Per ANSI C57 12 23
$ Ea $ Total
Delivery in Weeks
Mfr & Mfr #
Guaranteed No Load Loss
Guaranteed Full Load Loss
Guaranteed Total Load
Loss
Impedance (%)
The transformers being bid meet or exceed the specifications Yes_ No _ If not,
please list exceptions on a separate sheet of paper and attach to your bid
Escalation is _ , is not applicable for the transformers bid If escalation
applies, the bidder shall indicate in the bid specific items or materials subject to
escalation, and shall give the method and indices to be used in computing the amount
thereof Escalation occurring after the quoted delivery date will not be paid unless
delays are the result of actions by the City Escalation occurring after acceptance, if
purchaser exercises the option to delay shipment after manufacturing is completed, will
not be paid
For purposes of warranty and service, ONLY approved manufacturers or distributors
authorized by an approved manufacture to serve the Fort Collins area may bid
DELIVERY WILL BE AN EVALUATION FACTOR
City of Fort Collins reserves the right to purchase any combination of the proposed
transformers
City of Fort Collins reserves the right to evaluate best combination of design, delivery
and price
5
SUPPLEMENTAL INSTRUCTIONS
Prices quoted must remain firm for a 30 day period after the opening date
Freight terms F O B destination freight prepaid All freight charges must be included in
pricing submitted on proposal and not entered as separate pricing
Any discount allowed by Vendor for prompt payment, etc must be reflected in quoted
figure, and not entered as separate pricing
The City reserves the right to accept or reject any and all quotes
Bidder not responding to the services requested in this bid shall be removed from our
automated listing for Not applicable
Any questions or inquiries regarding this bid should be directed to
Opal F Dick, CPPO, Senior Buyer— (970) 221-6778
SIGNATURE AND TITLE TYPED OR PRINTED NAME AND TITLE
COMPANY NAME (AREA CODE) TELEPHONE NUMBER/FAX NUM
ADDRESS STREET, CITY, STATE, ZIP
DATE
REV SYM JJ
THE CITY OF FORT COLLINS
Light and Power Department
P 0 Box 580
Fort Collins, CO 80522
SPECIFICATION NO. 368-105
TITLE OVERHEAD -TYPE, SINGLE PHASE
DISTRIBUTION TRANSFORMERS
WITH SEPARABLE
INSULATED LOAD BREAK HIGH -VOLTAGE CONNECTORS
PREPARED BY.
rim M Sager, Design Engineer
ORIGINATED: March 3. 1973
REVISED September, 1997
Coram 19
1
368-105
REV SYM JJ
PREVIOUS REVISION DESCRIPTIONS ON FILE
I REVISION DESCRIPTION I APPROVED I
REVISION II
REVISION JJ
Table of contents- Update
Paragraph 3 2 2 1 1; 3 2 4 2 Editorial
Paragraph 3.2.3.1. update ANSI reference
to 1985
Paragraph 3 2 3 2 Change lead type
terminals to stud type, update ANSI
reference to 1985
Paragraph 3 2 5 2 Delete reference to
Table II
Paragraph 3 2.5 6 Update ANSI
reference to 1987, change "non -PCB" to
"contains < 1 ppm PCB"
Paragraph 3 2 6 1 Change Table III to
Figure 2
Paragraph 3 2 7. Delete ratio
requirement, update ANSI reference to
1987
Paragraph 4 2 2 Change Impedance
tolerance to within range specified
Table I Change lead type LV terminals
to stud type Add impedance ranges on
131, 151 and 156
Add Figure 1
Change Table III to Figure 2
Appendix C delete tank coating from
table
Paragraph 5 0 Add pallet requirements
2
368-105
MIN
REV SYM JJ
LIST OF ACTIVE PAGES
ORIGINAL PAGES
ADDED PAGES
REV SYM
SHEET NO
REV SYM
SHEET NO
REV SYM
1
JJ
2
JJ
7SHEET:NO
3
JJ
4
II
5
II
6
it
7
II
8
II
9
II
10
II
11
II
12
JJ
13
II
14
II
15
II
16
it
17
it
18
II
19
II
20
II
21
II
22
I I
23
II
3
368-105