INVITATION TO BID
PFA FIRE HOSE & EQUIPMENT
BID # 5279
BID OPENING: April 28, 1998, 2.30pm (our clock)
The City of Fort Collins is requesting bids for fire hose appliances and nozzles, miscellaneous fire
equipment, and fire hose
Sealed bids will be received and publicly opened at the office of the Director Of Purchasing and
Risk Management, PO Box 580, 256 West Mountain Avenue, Fort Collins, Colorado 80522, at the
time and date noted on the bid proposal and/or contract documents
Bids must be received at the Purchasing Office prior to April 28, 1998, 2.30pm (our clock).
A copy of the Bid may be obtained as follows:
Call the Purchasing Fax -line, 970-416-2033 and follow the verbal instruction to
request document # 5279
Download the Bid from the Purchasing Webpage, Current Bids page, at
www ci fort-collins co us\CITY HALL\PURCHASING then via the
Current Bids pushbutton
3 Come by Purchasing at 256 W Mountain Ave , Fort Collins, and request a copy of
the Bid
Special Instructions
All bids must be properly signed by an authorized representative of the company with the legal
capacity to bind the company to the agreement Bids may be withdrawn up to the date and hour
set for closing Once bids have been accepted by the City and closing has occurred, failure to
enter into contract or honor the purchase order will be cause for removal of supplier's name from
the City of Fort Collins' bidders list for a period of twelve months from the date of the opening The
City may also pursue any remedies available at law or in equity Bid prices must be held firm for
a period of forty-five (45) days after bid openings
Submission of a bid is deemed as acceptance of all terms, conditions and specifications contained
in the City's specifications initially provided to the bidder Any proposed modification must be
accepted in writing by the City prior to award of the bid
Only bids properly received by the Purchasing Office will be accepted All bids should be clearly
identified by the bid number and bid name contained in the bid proposal
No proposal will be accepted from, or any purchase order awarded, to any person, firm or
corporation in default on any obligation to the City
256 W Mountain Avenue • PO Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6775 • FAX (970) 221-6707
REINFORCEMENT
THE HOSE SHALL BE MANUFACTURED WITH A 100% SYNTHETIC REINFORCEMENT
ENCOMPASSED IN SYNTHETIC NITRILE RUBBER USING A THROUGH THE WEAVE
EXTRUSION PROCESS RESULTING IN ONE PIECE CONSTRUCTION THE HOSE SHALL BE
TOTALLY IMMUNE TO MILDEW
THE HOSE SHALL BE WOVEN OF 100% SYNTHETIC HIGH TENSILE YARN CIRCULAR PLAIN
WOVEN SO AS TO ELIMINATE TWIST
LINING AND COVER
THE LINING AND COVER SHALL CONSIST OF SYNTHETIC NITRILE COVER COMPOUND OF
IDENTICAL MATERIAL WITH BONDING AGENTS TO PREVENT POSSIBILITY OF
DELAMINATION
FINISHED HOSE
FINISHED HOSE SHALL COMBINE THE 100% SYNTHETIC REINFORCEMENT WITH THE
NITRILE RUBBER COMPOUND USING A THROUGH THE WEAVE EXTRUSION PROCESS
RESULTING IN A ONE PIECE CONSTRUCTION THE RUBBER SHALL BE BOTH CHEMICALLY
AND MECHANICALLY BONDED TO THE WOVEN REINFORCEMENT GLUED HOSE OR HOSE
NOT HAVING CHEMICAL ADHESION WILL NOT BE ACCEPTABLE
THE HOSE SHALL BE YELLOW IN COLOR
COUPLINGS
COUPLINGS TO BE 5 STORTZ QUICK CONNECTION WITH STREAMLINED FIELD
REPAIRABLE BINDINGS COLLAR SHALL BE DESIGNED TO PREVENT DAMAGE TO THE
HEADS OF THE BOLTS WHEN HOSE IS BEING LAID, USED OR LOADED COUPLINGS MUST
BE ASSEMBLED AND DISASSEMBLED USING AN ALLEN WRENCH ONLY SPECIAL
DISASSEMBLY TOOLS SHALL NOT BE REQUIRED
El
BID PROPOSAL
BID # 5279
BID OPENING- April 28, 1998, 2:30pm (our clock)
We hereby enter our bid for the City of Fort Collins' requirements for fire hose appliances and
nozzles, miscellaneous fire equipment and fire hose, per the bid invitation and any referenced
specifications
SUBSTITUTIONS FOR ITEMS SPECIFIED WITH AKRON, ELKHART, HARRINGTON,
PARATECH, SUPER VAC, OR TASK FORCE TIP NUMBERS WILL NOT BE ACCEPTED ALL
THREADS TO BE NST UNLESS OTHERWISE SPECIFIED
Pricing:
Qty
Description
Part #:
Price/Each
Extension
1
ADAPTER, 75" X 2 5", BRASS
AKRON 421
$
$
2
ADAPTER, 1 5" X 2 5"
AKRON 1422
$
$
2
ADAPTER, 4 5" FEMALE X 5"
HARINGTON
$
$
STORTZ
HSFS50-
45NHLH, WITH
STORTZ-LOK
2
BLIND CAP, 5" STORTZ
HARRINGTON
$
$
#HBC-50
1
BRESNAN DISTRIBUTOR, 2 5",
AKRON 535
$
$
BRASS
1
CAP, 1 5', BRASS, WITH CHAIN
AKRON 245
$
$
1
DOUBLE FEMALE, 1 5",
AKRON 335
$
$
PYROLITE
2
DOUBLE FEMALE, 2 5",
AKRON 335
$
$
PYROLITE
2
DOUBLE MALE, 2 5, PYROLITE
AKRON 336
$
$
1
GATE VALVE, 2 5", PYROLITE
AKRON 2285
$
$
5
NOZZLE HOLDER, 1 5",
AKRON E-Z LOK
$
$
STAINLESS STEEL
OR EQUIVALENT
15
NOZZLE HOLDER, 2 5",
AKRON E-Z LOK
$
$
STAINLESS STEEL
OR EQUIVALENT
1
SIAMESE, 2 5", CLAPPER,
AKRON 1262
$
$
PYROLITE
Qty
Description.
Part #
Price/Each
Extension
1
TRIPLE STACKED TIPS,
PYROLITE
AKRON 1420
$
$
2
WYE, 1 5" X 2 5", GATED
ELKHART B-100A
$
$
1
WYE, 2 5", GATED, PYROLITE
AKRON 1582
$
$
1
WYE, 2 5" X 5" STORTZ,
GATED
HARRINGTON
#200-50-25NH
$
$
3
NOZZLE, 1 5", TASK FORCE
TFT #HMD-VPGI
$
$
1
NOZZLE, 1 5", TASK FORCE
TFT #HMD-STO
$
$
1
PISTOL GRIP, TASK FORCE
TFT, #H-VOI
$
$
1
NOZZLE, 2 5", FOG, TASK
FORCE, WITH PLAYPIPE
TFT # H-213LITZ
$
$
1
PLAYPIPE, 2 5", TASK FORCE
TFT # H-2VPP(H)
$
$
1
TASK FORCE, #XFC-42
PACKAGE
See Bid List
Description
$
$
1
TASK FORCE, XFC-MOUNT
PACKAGE
See Bid List
Description
$
$
1
PRY AXE, WITH STANDARD
CLAW AND VEHICLE BRACKET
PARATECH #501
$
$
1
CLOSET HOOK, 36" PIKE POLE, FIBERGLASS
HANDLE WITH "D" RING
$
$
1
FLOOR RUNNER, TX 20', VINYL
$
$
1
HOSE CLAMP W/BRACKET
AKRON 588
$
$
6
HOSE TOOL, STRAP
AKRON 78
$
$
2
ADJUSTABLE HYDRANT
WRENCH
AKRON 15
$
$
1
PIKE POLE, 10', FIBERGLASS HANDLE
$
$
3
SALVAGE COVERS, 12' X 14', 10 OZ VINYL, RED,
GREEN & YELLOW
$
$
1
SMOKE EJECTOR, 16", STEEL
SUPER VAC #
P164SE
$
$
4
SPRINKLER SHUTOFF
AKRON 1078
$
$
8
SPANNER WRENCH, 5"
Is
$
ro
Qty
Description:
Part #:
Price/Each
Extension
4
SPANNER WRENCH HOLDER, 5
$
$
4
DUAL HOLDER WITH SPANNER
AKRON 448
$
$
WRENCHES, 2 5"
2
1" FIRE HOSE IN 100 FOOT
1" hose spec
$
$
LENGTHS (200 feet)
12
1 75 FIRE HOSE IN 50 FOOT
1.75" hose spec
$
$
LENGTHS (600 feet)
4
1 75 FIRE HOSE IN 50 FOOT
1.75" high rise
$
$
LENGTHS (200 feet)
hose spec
2
1 75 FIRE HOSE IN 100 FOOT
1.75" high rise
$
$
LENGTHS (200 feet)
hose spec
30
2 5" FIRE HOSE IN 50 FOOT
2.5" hose spec
$
$
LENGTHS (1500 feet)
4
5 FIRE HOSE IN 100 FOOT
5" hose spec
$
$
LENGTHS (400 feet)
Total
$
Delivery:
Delivery will be made within days after receipt of order Prices must be quoted FOB
Destination Fort Collins, CO
For questions concerning this bid, contact Jim Hume, Buyer, 970-221-6776
For questions concerning technical specifications, contact Mel Carlson, Poudre Fire Authority, 970-
221-6581
Signature
Title
Company
Date
Street
Phone #
City
Fax #
State/Zip
Email
$}pp}pp
1,75
EQUIPMENT BID LIST
APRIL 1, 1998
HOSE APPLIANCES
I ADAPTER, 75" X 2 5", BRASS, AKRON 421
2 ADAPTER, 1 5" X 2 5", PYROLITE, AKRON 1422
2 ADAPTER, 4 5" FEMALE X 5" STORTZ, HARINGTON #HSFS50-45NHRL, WITH
STORTZ-LOK
2 BLIND CAP, 5" STORTZ, HARRINGTON #HBC-50
1 BRESNAN DISTRIBUTOR, 2 5", BRASS, AKRON 535
1 CAP, 1 5", BRASS, WITH CHAIN, AKRON 245
2 CAP, 5" STORTZ, BLIND CAP, HARRINGTON #HBC-50
I DOUBLE FEMALE, 1 5", PYROLITE, AKRON 335
2 DOUBLE FEMALE, 2 5", PYROLITE, AKRON 335,
2 DOUBLE MALE, 2 5, PYROLITE, AKRON 336
1 GATE VALVE, 2 5", PYROLITE, AKRON 2285
5 NOZZLE HOLDER, 1 5", STAINLESS STEEL, AKRON E-Z LOK OR EQUIVALENT
15 NOZZLE HOLDER, 2 5", STAINLESS STEEL, AKRON E-Z LOK OR EQUIVALENT
1 SIAMESE, 2 5", CLAPPER, PYROLITE, AKRON 1262
1 TRIPLE STACKED TIPS, PYROLITE, AKRON, 1420
2 WYE, 1 5" X 2 5', GATED, ELKHART B-100A
I WYE, 2 5", GATED, PYROLITE, AKRON 1582
1 WYE, 2 5" X 5" STORTZ, GATED, HARRINGTON #200-50-25NH
IR
NOZZLES
3 NOZZLE, 1 5", TASK FORCE, (TFT #HMD-VPGI)
NOZZLE, 1 5", TASK FORCE, (TFT #HMD-STO)
PISTOL GRIP, TASK FORCE (TFT, #H-VOI)
NOZZLE, 2 5", FOG, TASK FORCE, WITH PLAYPIPE, (TFT # H-213LITZ)
PLAYPIPE, 2 5", TASK FORCE, (TFT # H-2VPP(H))
TASK FORCE, #XFC-42 PACKAGE, INCLUDING (1) SAFE-TEK 1250 PORTABLE
BASE WITH 5" STORTZ, WITH OUT SAFETY VALVE, (1) XFT-NJ CROSSFIRE
MONITOR TOP, (1) M-R MASTER STREAM NOZZLE, (1) MST-4NJ QUAD STACK
TIPS, (1) XF-SSIO STREAM STRAIGHTENER
TASK FORCE, XFC-MOUNT PACKAGE, INCLUDING (1) XFF-MPL 3" TRUCK
FLANGE BASE AND (1) XF-B COMPACT COMPARTMENT STORAGE BRACKET
MISC. EQUIPMENT
1 PRY AXE, PARATECH 4501 WITH STANDARD CLAW AND VEHICLE BRACKET
I CLOSET HOOK, 36" PIKE POLE, FIBERGLASS HANDLE WITH "D" RING
1 FLOOR RUNNER, Y X 20', VINYL
1 HOSE CLAMP W/BRACKET. AKRON 588
6 HOSE TOOL, STRAP, AKRON 78
2 ADJUSTABLE HYDRANT WRENCH, AKRON 15
1 PIKE POLE, 10', FIBERGLASS HANDLE
3 SALVAGE COVERS, 12' X 14', 10 OZ VINYL, RED, GREEN & YELLOW
I SMOKE EJECTOR, 16", STEEL, SUPER VAC # P 164SE
4 SPRINKLER SHUTOFF, AKRON 1078
8 SPANNER WRENCH, 5"
4 SPANNER WRENCH HOLDER, 5"
4 DUAL HOLDER WITH SPANNER WRENCHES, 2 5", AKRON 448
SUBSTITUTIONS FOR ITEMS SPECIFIED WITH AKRON, ELKHART, HARRINGTON,
PARATECH, SUPER VAC, OR TASK FORCE TIP NUMBERS WILL NOT BE ACCEPTED
FIRE HOSE BID
APRIL 1, 1998
ALL FIRE HOSE IN THIS SPECIFICATION MUST MEET OR EXCEED THE CURRENT
NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 1961.
THE HOSE SHALL NOT BE DEGRADED FROM EXPOSURE TO MOST CHEMICAL
SUBSTANCES SUCH AS HYDROCARBONS, OILS, ALKALI, AND GREASE.
COMPLETE DETAILED SPECIFICATIONS, ALONG WITH A 12" SAMPLE OF THE
HOSE PROPOSED TO MEET THIS SPECIFICATION, SHALL BE SUBMITTED WITH
THE HOSE BID.
THE FIRE DEPARTMENT RESERVES THE RIGHT TO FORWARD 3 FOOT SAMPLES,
CUT FROM LENGTHS OF DELIVERED HOSE, TO A NATIONALLY RECOGNIZED
LABORATORY FOR TESTING. THE TESTS SHALL COVER THE PHYSICAL
REQUIREMENTS OF THE LININGS AS WELL AS THE JACKETS AS OUTLINED IN
THESE SPECIFICATIONS. IF THE HOSE PASSES, THE COST WILL BE PAID BY
THE FIRE DEPARTMENT. IF THE HOSE FAILS THE COST SHALL BE PAID BY
THE SUPPLIER. FAILURE TO COMPLY WITH THESE SPECIFICATIONS WILL BE
CAUSE FOR ALL HOSE TO BE REJECTED.
THE MANUFACTURER SHALL GUARANTEE THE PROPOSED FIRE HOSE SHALL MEET
THE REQUIREMENTS AND SPECIFICATIONS AS HEREIN SET FORTH. THE
MANUFACTURER SHALL ALSO, AS PART OF THIS PROPOSAL, GUARANTEE SUCH
FIRE HOSE FOR A PERIOD OF TEN (10) YEARS OR MORE AGAINST FAILURE
DUE TO DEFECTS IN MATERIAL AND WORKMANSHIP, AND SHALL PROVIDE FOR
THE REPLACEMENT OF ANY SUCH HOSES AS MAY BE DEFECTIVE IN THIS
RESPECT AT NO ADDITIONAL COST TO POUDRE FIRE AUTHORITY.
INDIVIDUAL HOSE SECTIONS LESS THAN THE SPECIFIED LENGTH WILL BE
REJECTED.
EACH LENGTH OF HOSE SHALL BE INDELIBLY MARKED IN LETTERS AND
FIGURES AT LEAST 1" HIGH. MARKING SHALL BE ACCORDANCE WITH THE
LATEST EDITION OF NFPA STANDARD 1961 FIRE HOSE.
THE COUPLINGS SUPPLIED SHALL COMPLY WITH THE CURRENT NFPA 1963
STANDARD.
HOSE BID SPECIFICATIONS 1"
SCOPE:
THIS SPECIFICATION IS FOR 200 FEET OF 1" FIRE HOSE IN 100 FOOT
LENGTHS.
THE HOSE SHALL BE PREMIUM QUALITY, ABRASION RESISTANT, CHEMICAL
RESISTANT ATTACK GRADE FIRE HOSE DESIGNED FOR PROLONGED STORAGE AND
EASE OF MAINTENANCE.
LINING AND COVER:
THE LINING AND COVER SHALL CONSIST OF SYNTHETIC NITRILE RUBBER,
COMPOUNDED TO PROVIDE MAXIMUM ADHESION TO THE REINFORCEMENT WHEN
APPLIED BY A THROUGH THE WEAVE EXTRUSION PROCESS.
REINFORCEMENT:
THE HOSE REINFORCEMENT SHALL BE WOVEN OF 100% SYNTHETIC, HIGH
TENSILE YARN SO AS TO ELIMINATE TWIST.
THE REINFORCEMENT SHALL BE TOTALLY ENCAPSULATED IN THE NITRILE
RUBBER COMPOUND UTILIZING A THROUGH THE WEAVE PROCESS RESULTING IN
A ONE-PIECE CONSTRUCTION HOSE.
FINISHED HOSE:
THE FINISHED HOSE SHALL HAVE RIBBED PATTERNS ON THE OUTSIDE TO
REDUCE WEAR ON THE COVER.
THE HOSE SHALL NOT BE DEGRADED FROM EXPOSURE TO MOST CHEMICAL
SUBSTANCES SUCH AS HYDROCARBONS, OILS, ALKALI, AND GREASE.
THE HOSE SHALL BE YELLOW IN COLOR.
COUPLINGS:
THE COUPLINGS SUPPLIED SHALL BE HARD COATED, LIGHTWEIGHT ROCKER
LUG, AND COMPLY WITH THE CURRENT NFPA 1963 STANDARD. ONE MALE AND
ONE FEMALE COUPLING WITH 1" NST THREADS ARE TO BE PROPERLY
INSTALLED ON EACH LENGTH OF HOSE BY THE MANUFACTURER.
0
H_
HOSE BID SPECIFICATIONS 1.75"
SCOPE:
THIS SPECIFICATION IS FOR 600 FEET OF 1.75" FIRE HOSE IN 50 FOOT
LENGTHS.
THE FIRE HOSE SHALL BE PREMIUM QUALITY, ABRASION RESISTANT, DOUBLE
JACKET, LIGHT WEIGHT MUNICIPAL FIRE HOSE DESIGNED FOR EASE OF
HANDLING AND USE.
THE HOSE SHALL BE IN COMPLIANCE WITH NFPA 1961 (LATEST EDITION)
REQUIREMENTS FOR DOUBLE JACKET, 800 PSI PROOF TEST PRESSURE, ATTACK
GRADE FIRE HOSE.
LINING:
THE SYNTHETIC RUBBER LINING SHALL BE A SINGLE -PLY EXTRUDED TUBE
COMPOUNDED TO RESIST DETERIORATION BY OZONE. THE FINISHED FORM
SHALL BE FREE OF PITS AND OTHER IMPERFECTIONS AND SHALL HAVE A
SMOOTH INTERIOR FINISH.
JACKET:
THE WRAP YARNS AND FILER YARNS SHALL BE OF ADEQUATE NUMBER AND SIZE
TO MEET ALL OF THE HYDROSTATIC REQUIREMENTS THE NFPA 1961
SPECIFICATION. THE WRAP YARN OF BOTH JACKETS SHALL BE STRUCTURED OF
ENTANGLED FILAMENT GRADE (6-6) POLYAMIDE (DUPONT CORDURA) OR
EQUIVALENT. THERE SHALL BE NO KNOT SPLICING OF THE WRAP IN EITHER
JACKET. THE FILLER YARN SHALL BE HIGH STRENGTH, LOW ELONGATION
FILAMENT POLYESTER.
IMPREGNATION:
THE OUTSIDE JACKET SHALL BE THOROUGHLY IMPREGNATED WITH A HIGH
PERFORMANCE POLYMER. THE POLYMER COMPOUND SHALL BE HEAT SET IN THE
TEXTILE OF THE OUTSIDE JACKET. COATING APPLIED TO FINISHED HOSE AND
/OR SET WITH AMBIENT TEMPERATURE PROCESSES ARE NOT ACCEPTABLE.
THE HOSE SHALL BE YELLOW IN COLOR.
JACKET FIT:
THE OUTSIDE AND INSIDE JACKET FIT IS CRITICAL TO THE FINISHED HOSE.
AFTER THE INITIAL PROOF PRESSURE TEST, THEIR SHALL BE NO EXCESS
OUTER JACKET BAGGINESS. THE JACKETS MUST FIT SNUGLY INSIDE ONE
ANOTHER UNDER ZERO PRESSURE OR UNDER PROOF AND SERVICE TEST
PRESSURES.
91
Bids must be furnished exclusive of any federal excise tax, wherever applicable
Bidders must be properly licensed and secure necessary permits wherever applicable
Bidders not responding to this bid will be removed from our automated vendor listing for the subject
commodities
The City may elect where applicable, to award bids on an individual item/group basis or on a total
bid basis, whichever is most beneficial to the City The City reserves the right to accept or reject
any and all bids, and to waive any irregularities or informalities
Sales prohibited/conflict of interest no officer, employee, or their dependent or person residing in
and sharing the expenses of their household, shall have a financial interest in the sale to the City
of any real or personal property, equipment, material, supplies or services This rule also applies
to subcontracts with the City This shall not apply to members of any authority, board, committee
or commission of the city, other than the members of the City Council Soliciting or accepting any
gift, gratuity favor, entertainment, kickback or any items of monetary value from any person who
has or is seeking to do business with the City of Fort Collins is prohibited Any vendor knowing of
this type of activity is encouraged to report in confidence to the Director of Purchasing and Risk
Management, Director of Finance, City Attorney or City Manager so the matter can be dealt with
Freight terms unless otherwise noted, all freight is F O B Destination, Freight Prepaid All freight
charges must be included in prices submitted on proposal
Discounts any discounts allowed for prompt payment, etc , must be reflected in bid figures and
not entered as separate pricing on the proposal form
Purchasing restrictions your authorized signature of this bid assures your firm's compliance with
the City's purchasing restrictions A copy of the resolutions are available for review in the
Purchasing Office or the City Clerk's Office
Cement restrictions City of Fort Collins Resolution 91-121 requires that suppliers and producers
of cement or products containing cement to certify that the cement was not made in cement kilns
that burn hazardous waste as a fuel
Collusive or sham bids any bid deemed to be collusive or a sham bid will be rejected and reported
to authorities as such Your authorized signature of this bid assures that such bid is genuine and
is not a collusive or sham bid
Bid results for information regarding results for individual bids send a self-addressed, self -stamped
envelope and a bid tally will be mailed to you Bid results will be posted in our office 7 days after
the bid opening
a es B O Neill II, CPPO
D ector of Purchasing and Risk Management
COUPLINGS:
THE COUPLINGS SUPPLIED SHALL BE LIGHTWEIGHT ROCKER LUG, AND COMPLY
WITH NFPA 1963 STANDARD. ONE MALE AND ONE FEMALE COUPLING WITH 1.5"
NST THREADS ARE TO BE PROPERLY INSTALLED ON EACH LENGTH OF HOSE BY
THE MANUFACTURER. THE COUPLINGS SHALL BE HARD COATED.
HOSE BID SPECIFICATIONS 1.75" HIGH RISE
SCOPE:
THIS SPECIFICATION IS FOR 200 FEET OF 1.75" FIRE HOSE IN 50 FOOT
LENGTHS AND 200 FEET OF 1.75" FIRE HOSE IN 100 FOOT LENGTHS.
THE HOSE TO BE SUPPLIED UNDER THIS SPECIFICATION SHALL BE PREMIUM
QUALITY, ABRASION RESISTANT, DOUBLE JACKET, LIGHT WEIGHT MUNICIPAL
FIRE HOSE DESIGNED FOR EASE OF HANDLING AND USE.
THE HOSES SHALL BE IN COMPLIANCE WITH NFPA 1961 (LATEST EDITION)
REQUIREMENTS FOR DOUBLE JACKET, 800 PSI PROOF TEST PRESSURE, ATTACK
GRADE FIRE HOSE.
LINING:
THE THERMOPLASTIC LINING SHALL BE A SINGLE -PLY EXTRUDED TUBE
COMPOUNDED TO RESIST DETERIORATION BY OZONE. THE FINISHED FORM
SHALL BE FREE OF PITS AND OTHER IMPERFECTIONS AND SHALL HAVE A
SMOOTH INTERIOR FINISH.
JACKET CONSTRUCTION:
THE WRAP YARNS AND FILER YARNS SHALL BE OF ADEQUATE NUMBER AND SIZE
TO MEET ALL OF THE HYDROSTATIC REQUIREMENTS OF THE NFPA 1961
SPECIFICATION. THE WRAP YARN OF BOTH JACKETS SHALL BE STRUCTURED OF
ENTANGLED FILAMENT GRADE (6-6) POLYAMIDE (DUPONT CORDURA) OR
EQUIVALENT. THERE SHALL BE NO KNOT SPLICING OF THE WRAP IN EITHER
JACKET. THE INSIDE JACKET SHALL HAVE A REVERSE TWILL WEAVE TO
PRODUCE A SMOOTH WATERWAY. THE FILLER YARN SHALL BE HIGH STRENGTH,
LOW ELONGATION FILAMENT POLYESTER.
IMPREGNATION:
THE OUTSIDE JACKET SHALL BE THOROUGHLY IMPREGNATED WITH A HIGH
PERFORMANCE POLYMER. THE POLYMER COMPOUND SHALL BE HEAT SET IN THE
TEXTILE OF THE OUTSIDE JACKET. COATING APPLIED TO FINISHED HOSE AND
/OR SET WITH AMBIENT TEMPERATURE PROCESSES ARE NOT ACCEPTABLE.
THE HOSE SHALL BE ORANGE IN COLOR.
JACKET FIT:
THE OUTSIDE AND INSIDE JACKET FIT IS CRITICAL TO THE FINISHED HOSE.
AFTER THE INITIAL PROOF PRESSURE TEST, THEIR SHALL BE NO EXCESS
OUTER JACKET BAGGINESS. THE JACKETS MUST FIT SNUGLY INSIDE ONE
ANOTHER UNDER ZERO PRESSURE OR UNDER PROOF AND SERVICE TEST
PRESSURES.
COUPLINGS:
THE COUPLINGS SUPPLIED SHALL BE HARD COATED, LIGHTWEIGHT ROCKER
LUG, AND COMPLY WITH NFPA 1963 STANDARD. ONE MALE AND ONE FEMALE
COUPLING WITH 1.5" NST THREADS ARE TO BE PROPERLY INSTALLED ON EACH
LENGTH OF HOSE BY THE -MANUFACTURER.
HOSE BID SPECIFICATIONS 2.5"
SCOPE:
THIS SPECIFICATION IS FOR 1500 FEET OF 2.5" FIRE HOSE IN 50 FOOT
LENGTHS.
THE HOSE TO BE SUPPLIED UNDER THIS SPECIFICATION SHALL BE PREMIUM
QUALITY, ABRASION RESISTANT, DOUBLE JACKET, LIGHT WEIGHT MUNICIPAL
FIRE HOSE DESIGNED FOR EASE OF HANDLING AND USE.
THE HOSES SHALL BE IN COMPLIANCE WITH NFPA 1961 (LATEST EDITION)
REQUIREMENTS FOR DOUBLE JACKET, 800 PSI PROOF TEST PRESSURE, ATTACK
GRADE FIRE HOSE.
LINING:
THE THERMOPLASTIC LINING SHALL BE A SINGLE -PLY EXTRUDED TUBE
COMPOUNDED TO RESIST DETERIORATION BY OZONE. THE FINISHED FORM
SHALL BE FREE OF PITS AND OTHER IMPERFECTIONS AND SHALL HAVE A
SMOOTH INTERIOR FINISH.
JACKET CONSTRUCTION:
THE WRAP YARNS AND FILER YARNS SHALL BE OF ADEQUATE NUMBER AND SIZE
TO MEET ALL OF THE HYDROSTATIC REQUIREMENTS OF THE NFPA 1961
SPECIFICATION. THE WRAP YARN OF BOTH JACKETS SHALL BE STRUCTURED OF
ENTANGLED FILAMENT GRADE (6-6) POLYAMIDE (DUPONT CORDURA) OR
EQUIVALENT. THERE SHALL BE NO KNOT SPLICING OF THE WRAP IN EITHER
JACKET. THE INSIDE JACKET SHALL HAVE A REVERSE TWILL WEAVE TO
PRODUCE A SMOOTH WATERWAY. THE FILLER YARN SHALL BE HIGH STRENGTH,
LOW ELONGATION FILAMENT POLYESTER.
IMPREGNATION:
THE OUTSIDE JACKET SHALL BE THOROUGHLY IMPREGNATED WITH A HIGH
PERFORMANCE POLYMER YELLOW IN COLOR. THE POLYMER COMPOUND SHALL BE
HEAT SET IN THE TEXTILE OF THE OUTSIDE JACKET. COATING APPLIED TO
FINISHED HOSE AND /OR SET WITH AMBIENT TEMPERATURE PROCESSES ARE
NOT ACCEPTABLE.
JACKET FIT:
THE OUTSIDE AND INSIDE JACKET FIT IS CRITICAL TO THE FINISHED HOSE.
AFTER THE INITIAL PROOF PRESSURE TEST, THEIR SHALL BE NO EXCESS
OUTER JACKET BAGGINESS. THE JACKETS MUST FIT SNUGLY INSIDE ONE
ANOTHER UNDER ZERO PRESSURE OR UNDER PROOF AND SERVICE TEST
PRESSURES.
COUPLINGS:
THE COUPLINGS SUPPLIED SHALL BE HARD COATED, LIGHTWEIGHT ROCKER
LUG, AND COMPLY WITH NFPA 1963 STANDARD. ONE MALE AND ONE FEMALE
COUPLING WITH 2.5" NST THREADS ARE TO BE PROPERLY INSTALLED ON EACH
LENGTH OF HOSE BY THE MANUFACTURER.
HOSE BID SPECIFICATIONS 5"
SCOPE:
THIS SPECIFICATION IS FOR 400 FEET OF 5" FIRE HOSE IN 100 FOOT
LENGTHS.
THE HOSE SHALL BE PREMIUM QUALITY, ABRASION RESISTANT, CHEMICAL
RESISTANT ATTACK GRADE FIRE HOSE DESIGNED FOR PROLONGED STORAGE AND
EXTENDED SERVICE LIFE.
REINFORCEMENT:
THE HOSE SHALL BE MANUFACTURED WITH A 100% SYNTHETIC REINFORCEMENT
ENCOMPASSED IN SYNTHETIC NITRILE RUBBER USING A THROUGH THE WEAVE
EXTRUSION PROCESS RESULTING IN ONE PIECE CONSTRUCTION. THE HOSE
SHALL BE TOTALLY IMMUNE TO MILDEW.
THE HOSE SHALL BE WOVEN OF 100% SYNTHETIC HIGH TENSILE YARN
CIRCULAR PLAIN WOVEN SO AS TO ELIMINATE TWIST.
LINING AND COVER:
THE LINING AND COVER SHALL CONSIST OF SYNTHETIC NITRILE COVER
COMPOUND OF IDENTICAL MATERIAL WITH BONDING AGENTS TO PREVENT
POSSIBILITY OF DELAMINATION.
FINISHED HOSE:
FINISHED HOSE SHALL COMBINE THE 1000 SYNTHETIC REINFORCEMENT WITH
THE NITRILE RUBBER COMPOUND USING A THROUGH THE WEAVE EXTRUSION
PROCESS RESULTING IN A ONE PIECE CONSTRUCTION. THE RUBBER SHALL BE
BOTH CHEMICALLY AND MECHANICALLY BONDED TO THE WOVEN REINFORCEMENT.
GLUED HOSE OR HOSE NOT HAVING CHEMICAL ADHESION WILL NOT BE
ACCEPTABLE.
THE HOSE SHALL BE YELLOW IN COLOR.
COUPLINGS:
COUPLINGS TO BE 5" STORTZ QUICK CONNECTION WITH STREAMLINED FIELD
REPAIRABLE BINDINGS. COLLAR SHALL BE DESIGNED TO PREVENT DAMAGE TO
THE HEADS OF THE BOLTS WHEN HOSE IS BEING LAID, USED OR LOADED.
COUPLINGS MUST BE ASSEMBLED AND DISASSEMBLED USING AN ALLEN WRENCH
ONLY. SPECIAL DISASSEMBLY TOOLS SHALL NOT BE REQUIRED.
13
BID #5279, EQUIPMENT LIST
SUBSTITUTIONS FOR ITEMS SPECIFIED WITH AKRON, ELKHART, HARRINGTON,
PARATECH, SUPER VAC, OR TASK FORCE TIP NUMBERS WILL NOT BE ACCEPTED ALL
THREADS TO BE NST UNLESS OTHERWISE SPECIFIED
HOSE APPLIANCES
1 ADAPTER, 75" X 2 5, BRASS, AKRON 421
2 ADAPTER, 1 5 X 2 5, PYROLITE, AKRON 1422
2 ADAPTER, 4 5 FEMALE X 5 STORTZ, HARINGTON #HSFS50-45NHLH, WITH
STORTZ-LOK
2 BLIND CAP, 5 STORTZ, HARRINGTON #HBC-50
1 BRESNAN DISTRIBUTOR, 2 5, BRASS, AKRON 535
1 CAP, 1 5", BRASS, WITH CHAIN, AKRON 245
1 DOUBLE FEMALE, 1 5", PYROLITE, AKRON 335
2 DOUBLE FEMALE, 2 5', PYROLITE, AKRON 335,
2 DOUBLE MALE, 2 5, PYROLITE, AKRON 336
1 GATE VALVE, 2 5, PYROLITE, AKRON 2285
5 NOZZLE HOLDER, 1 5", STAINLESS STEEL, AKRON E-Z LOK OR EQUIVALENT
15 NOZZLE HOLDER, 2 5, STAINLESS STEEL, AKRON E-Z LOK OR EQUIVALENT
1 SIAMESE, 2 5, CLAPPER, PYROLITE, AKRON 1262
1 TRIPLE STACKED TIPS, PYROLITE, AKRON, 1420
2 WYE, 1 5 X 2 5, GATED, ELKHART B-100A
1 WYE, 2 5", GATED, PYROLITE, AKRON 1582
1 WYE, 2 5" X 5' STORTZ, GATED, HARRINGTON #200-50-25NH
ys.
NOZZLES
3 NOZZLE, 1 5", TASK FORCE, (TFT #HMD—VPGI)
1 NOZZLE, 1 5", TASK FORCE, (TFT #HMD—STO)
1 PISTOL GRIP, TASK FORCE (TFT, #H—VOI)
1 NOZZLE, 2 5", FOG, TASK FORCE, WITH PLAYPIPE, (TFT # H-2BLITZ)
1 PLAYPIPE, 2 5", TASK FORCE, (TFT # H-2VPP(H))
1 TASK FORCE, #XFC-42 PACKAGE, INCLUDING (1) SAFE—TEK 1250 PORTABLE BASE
WITH 5" STORTZ, WITH OUT SAFETY VALVE, (1) XFT—NJ CROSSFIRE MONITOR TOP,
(1) M—R MASTER STREAM NOZZLE, (1) MST-4NJ QUAD STACK TIPS, (1) XF—SS10
STREAM STRAIGHTENER
1 TASK FORCE, XFC—MOUNT PACKAGE, INCLUDING (1) XFF—MPL 3" TRUCK FLANGE
BASE AND (1) XF—B COMPACT COMPARTMENT STORAGE BRACKET
MISC. EQUIPMENT
1 PRY AXE. PARATECH #501 WITH STANDARD CLAW AND VEHICLE BRACKET
1 CLOSET HOOK, 36" PIKE POLE, FIBERGLASS HANDLE WITH "D" RING
1 FLOOR RUNNER, TX 20', VINYL
1 HOSE CLAMP W/BRACKET, AKRON 588
6 HOSE TOOL, STRAP, AKRON 78
2 ADJUSTABLE HYDRANT WRENCH, AKRON 15
1 PIKE POLE, 10', FIBERGLASS HANDLE
3 SALVAGE COVERS, 12' X 14', 10 OZ VINYL, RED, GREEN & YELLOW
1 SMOKE EJECTOR, 16", STEEL, SUPER VAC # P164SE
4 SPRINKLER SHUTOFF. AKRON 1078
8 SPANNER WRENCH. 5"
4 SPANNER WRENCH HOLDER, 5"
4 DUAL HOLDER WITH SPANNER WRENCHES, 2 5", AKRON 448
ll
FIRE HOSE
ALL FIRE HOSE IN THIS SPECIFICATION MUST MEET OR EXCEED THE CURRENT
NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 1961
THE HOSE SHALL NOT BE DEGRADED FROM EXPOSURE TO MOST CHEMICAL
SUBSTANCES SUCH AS HYDROCARBONS, OILS, ALKALI, AND GREASE
COMPLETE DETAILED SPECIFICATIONS, ALONG WITH A 12" SAMPLE OF THE HOSE
PROPOSED TO MEET THIS SPECIFICATION, SHALL BE SUBMITTED WITH THE HOSE BID
THE FIRE DEPARTMENT RESERVES THE RIGHT TO FORWARD 3 FOOT SAMPLES, CUT
FROM LENGTHS OF DELIVERED HOSE, TO A NATIONALLY RECOGNIZED LABORATORY
FOR TESTING THE TESTS SHALL COVER THE PHYSICAL REQUIREMENTS OF THE LININGS
AS WELL AS THE JACKETS AS OUTLINED IN THESE SPECIFICATIONS IF THE HOSE
PASSES, THE COST WILL BE PAID BY THE FIRE DEPARTMENT IF THE HOSE FAILS THE
COST SHALL BE PAID BY THE SUPPLIER FAILURE TO COMPLY WITH THESE
SPECIFICATIONS WILL BE CAUSE FOR ALL HOSE TO BE REJECTED
THE MANUFACTURER SHALL GUARANTEE THE PROPOSED FIRE HOSE SHALL MEET THE
REQUIREMENTS AND SPECIFICATIONS AS HEREIN SET FORTH THE MANUFACTURER
SHALL ALSO, AS PART OF THIS PROPOSAL, GUARANTEE SUCH FIRE HOSE FOR A PERIOD
OF TEN (10) YEARS OR MORE AGAINST FAILURE DUE TO DEFECTS IN MATERIAL AND
WORKMANSHIP, AND SHALL PROVIDE FOR THE REPLACEMENT OF ANY SUCH HOSES AS
MAY BE DEFECTIVE IN THIS RESPECT AT NO ADDITIONAL COST TO POUDRE FIRE
AUTHORITY
INDIVIDUAL HOSE SECTIONS LESS THAN THE SPECIFIED LENGTH WILL BE REJECTED
EACH LENGTH OF HOSE SHALL BE INDELIBLY MARKED IN LETTERS AND FIGURES AT
LEAST 1" HIGH MARKING SHALL BE ACCORDANCE WITH THE LATEST EDITION OF NFPA
STANDARD 1961 FIRE HOSE
THE COUPLINGS SUPPLIED SHALL COMPLY WITH THE CURRENT NFPA 1963 STANDARD
HOSE SPECIFICATIONS 1"
THIS SPECIFICATION IS FOR 200 FEET OF 1" FIRE HOSE IN 100 FOOT LENGTHS
THE HOSE SHALL BE PREMIUM QUALITY, ABRASION RESISTANT, CHEMICAL RESISTANT
ATTACK GRADE FIRE HOSE DESIGNED FOR PROLONGED STORAGE AND EASE OF
MAINTENANCE
LINING AND COVER
THE LINING AND COVER SHALL CONSIST OF SYNTHETIC NITRILE RUBBER, COMPOUNDED
TO PROVIDE MAXIMUM ADHESION TO THE REINFORCEMENT WHEN APPLIED BY A
THROUGH THE WEAVE EXTRUSION PROCESS
REINFORCEMENT
THE HOSE REINFORCEMENT SHALL BE WOVEN OF 100% SYNTHETIC, HIGH TENSILE
YARN SO AS TO ELIMINATE TWIST
THE REINFORCEMENT SHALL BE TOTALLY ENCAPSULATED IN THE NITRILE RUBBER
COMPOUND UTILIZING A THROUGH THE WEAVE PROCESS RESULTING IN A ONE-PIECE
CONSTRUCTION HOSE
FINISHED HOSE
THE FINISHED HOSE SHALL HAVE RIBBED PATTERNS ON THE OUTSIDE TO REDUCE
WEAR ON THE COVER
THE HOSE SHALL NOT BE DEGRADED FROM EXPOSURE TO MOST CHEMICAL
SUBSTANCES SUCH AS HYDROCARBONS, OILS, ALKALI, AND GREASE
THE HOSE SHALL BE YELLOW IN COLOR
COUPLINGS
THE COUPLINGS SUPPLIED SHALL BE HARD COATED, LIGHTWEIGHT ROCKER LUG, AND
COMPLY WITH THE CURRENT NFPA 1963 STANDARD ONE MALE AND ONE FEMALE
COUPLING WITH 1" NST THREADS ARE TO BE PROPERLY INSTALLED ON EACH LENGTH
OF HOSE BY THE MANUFACTURER
HOSE SPECIFICATIONS 1.75"
THIS SPECIFICATION IS FOR 600 FEET OF 1.75" FIRE HOSE IN 50 FOOT LENGTHS
THE FIRE HOSE SHALL BE PREMIUM QUALITY, ABRASION RESISTANT, DOUBLE JACKET,
LIGHT WEIGHT MUNICIPAL FIRE HOSE DESIGNED FOR EASE OF HANDLING AND USE
THE HOSE SHALL BE IN COMPLIANCE WITH NFPA 1961 (LATEST EDITION) REQUIREMENTS
FOR DOUBLE JACKET, 800 PSI PROOF TEST PRESSURE, ATTACK GRADE FIRE HOSE
LINING
THE SYNTHETIC RUBBER LINING SHALL BE A SINGLE -PLY EXTRUDED TUBE
COMPOUNDED TO RESIST DETERIORATION BY OZONE THE FINISHED FORM SHALL BE
FREE OF PITS AND OTHER IMPERFECTIONS AND SHALL HAVE A SMOOTH INTERIOR
FINISH
JACKET
THE WRAP YARNS AND FILER YARNS SHALL BE OF ADEQUATE NUMBER AND SIZE TO
MEET ALL OF THE HYDROSTATIC REQUIREMENTS THE NFPA 1961 SPECIFICATION THE
WRAP YARN OF BOTH JACKETS SHALL BE STRUCTURED OF ENTANGLED FILAMENT
GRADE (6-6) POLYAMIDE (DUPONT CORDURA) OR EQUIVALENT THERE SHALL BE NO
KNOT SPLICING OF THE WRAP IN EITHER JACKET THE FILLER YARN SHALL BE HIGH
STRENGTH, LOW ELONGATION FILAMENT POLYESTER
IMPREGNATION
THE OUTSIDE JACKET SHALL BE THOROUGHLY IMPREGNATED WITH A HIGH
PERFORMANCE POLYMER THE POLYMER COMPOUND SHALL BE HEAT SET IN THE
TEXTILE OF THE OUTSIDE JACKET COATING APPLIED TO FINISHED HOSE AND /OR SET
WITH AMBIENT TEMPERATURE PROCESSES ARE NOT ACCEPTABLE
THE HOSE SHALL BE YELLOW IN COLOR
JACKET FIT
THE OUTSIDE AND INSIDE JACKET FIT IS CRITICAL TO THE FINISHED HOSE AFTER THE
INITIAL PROOF PRESSURE TEST, THEIR SHALL BE NO EXCESS OUTER JACKET
BAGGINESS THE JACKETS MUST FIT SNUGLY INSIDE ONE ANOTHER UNDER ZERO
PRESSURE OR UNDER PROOF AND SERVICE TEST PRESSURES
COUPLINGS
THE COUPLINGS SUPPLIED SHALL BE LIGHTWEIGHT ROCKER LUG, AND COMPLY WITH
NFPA 1963 STANDARD ONE MALE AND ONE FEMALE COUPLING WITH 1 5" NST THREADS
ARE TO BE PROPERLY INSTALLED ON EACH LENGTH OF HOSE BY THE MANUFACTURER
THE COUPLINGS SHALL BE HARD COATED
HOSE SPECIFICATIONS 1.75" HIGH RISE
THIS SPECIFICATION IS FOR 200 FEET OF 1.75" FIRE HOSE IN 50 FOOT LENGTHS AND 200
FEET OF 1.75" FIRE HOSE IN 100 FOOT LENGTHS
THE HOSE TO BE SUPPLIED UNDER THIS SPECIFICATION SHALL BE PREMIUM QUALITY,
ABRASION RESISTANT, DOUBLE JACKET, LIGHT WEIGHT MUNICIPAL FIRE HOSE
DESIGNED FOR EASE OF HANDLING AND USE
THE HOSES SHALL BE IN COMPLIANCE WITH NFPA 1961 (LATEST EDITION)
REQUIREMENTS FOR DOUBLE JACKET, 800 PSI PROOF TEST PRESSURE, ATTACK GRADE
FIRE HOSE
LINING
THE THERMOPLASTIC LINING SHALL BE A SINGLE -PLY EXTRUDED TUBE COMPOUNDED
TO RESIST DETERIORATION BY OZONE THE FINISHED FORM SHALL BE FREE OF PITS
AND OTHER IMPERFECTIONS AND SHALL HAVE A SMOOTH INTERIOR FINISH
JACKET CONSTRUCTION
THE WRAP YARNS AND FILER YARNS SHALL BE OF ADEQUATE NUMBER AND SIZE TO
MEET ALL OF THE HYDROSTATIC REQUIREMENTS OF THE NFPA 1961 SPECIFICATION
THE WRAP YARN OF BOTH JACKETS SHALL BE STRUCTURED OF ENTANGLED FILAMENT
GRADE (6-6) POLYAMIDE (DUPONT CORDURA) OR EQUIVALENT THERE SHALL BE NO
KNOT SPLICING OF THE WRAP IN EITHER JACKET, THE INSIDE JACKET SHALL HAVE A
REVERSE TWILL WEAVE TO PRODUCE A SMOOTH WATERWAY THE FILLER YARN SHALL
BE HIGH STRENGTH. LOW ELONGATION FILAMENT POLYESTER
IMPREGNATION
THE OUTSIDE JACKET SHALL BE THOROUGHLY IMPREGNATED WITH A HIGH
PERFORMANCE POLYMER THE POLYMER COMPOUND SHALL BE HEAT SET IN THE
TEXTILE OF THE OUTSIDE JACKET COATING APPLIED TO FINISHED HOSE AND /OR SET
WITH AMBIENT TEMPERATURE PROCESSES ARE NOT ACCEPTABLE
THE HOSE SHALL BE ORANGE IN COLOR
JACKET FIT
THE OUTSIDE AND INSIDE JACKET FIT IS CRITICAL TO THE FINISHED HOSE AFTER THE
INITIAL PROOF PRESSURE TEST, THEIR SHALL BE NO EXCESS OUTER JACKET
BAGGINESS THE JACKETS MUST FIT SNUGLY INSIDE ONE ANOTHER UNDER ZERO
PRESSURE OR UNDER PROOF AND SERVICE TEST PRESSURES
COUPLINGS
THE COUPLINGS SUPPLIED SHALL BE HARD COATED, LIGHTWEIGHT ROCKER LUG, AND
COMPLY WITH NFPA 1963 STANDARD ONE MALE AND ONE FEMALE COUPLING WITH 1 5"
NST THREADS ARE TO BE PROPERLY INSTALLED ON EACH LENGTH OF HOSE BY THE
MANUFACTURER,
HOSE SPECIFICATIONS 2.5"
THIS SPECIFICATION IS FOR 1500 FEET OF 2.5" FIRE HOSE IN 50 FOOT LENGTHS
THE HOSE TO BE SUPPLIED UNDER THIS SPECIFICATION SHALL BE PREMIUM QUALITY,
ABRASION RESISTANT, DOUBLE JACKET, LIGHT WEIGHT MUNICIPAL FIRE HOSE
DESIGNED FOR EASE OF HANDLING AND USE
THE HOSES SHALL BE IN COMPLIANCE WITH NFPA 1961 (LATEST EDITION)
REQUIREMENTS FOR DOUBLE JACKET, 800 PSI PROOF TEST PRESSURE, ATTACK GRADE
FIRE HOSE
LINING
THE THERMOPLASTIC LINING SHALL BE A SINGLE -PLY EXTRUDED TUBE COMPOUNDED
TO RESIST DETERIORATION BY OZONE THE FINISHED FORM SHALL BE FREE OF PITS
AND OTHER IMPERFECTIONS AND SHALL HAVE A SMOOTH INTERIOR FINISH
JACKET CONSTRUCTION
THE WRAP YARNS AND FILER YARNS SHALL BE OF ADEQUATE NUMBER AND SIZE TO
MEET ALL OF THE HYDROSTATIC REQUIREMENTS OF THE NFPA 1961 SPECIFICATION
THE WRAP YARN OF BOTH JACKETS SHALL BE STRUCTURED OF ENTANGLED FILAMENT
GRADE (6-6) POLYAMIDE (DUPONT CORDURA) OR EQUIVALENT THERE SHALL BE NO
KNOT SPLICING OF THE WRAP IN EITHER JACKET THE INSIDE JACKET SHALL HAVE A
REVERSE TWILL WEAVE TO PRODUCE A SMOOTH WATERWAY THE FILLER YARN SHALL
BE HIGH STRENGTH, LOW ELONGATION FILAMENT POLYESTER
IMPREGNATION
THE OUTSIDE JACKET SHALL BE THOROUGHLY IMPREGNATED WITH A HIGH
PERFORMANCE POLYMER YELLOW IN COLOR THE POLYMER COMPOUND SHALL BE
HEAT SET IN THE TEXTILE OF THE OUTSIDE JACKET COATING APPLIED TO FINISHED
HOSE AND /OR SET WITH AMBIENT TEMPERATURE PROCESSES ARE NOT ACCEPTABLE
JACKET FIT
THE OUTSIDE AND INSIDE JACKET FIT IS CRITICAL TO THE FINISHED HOSE AFTER THE
INITIAL PROOF PRESSURE TEST, THEIR SHALL BE NO EXCESS OUTER JACKET
BAGGINESS THE JACKETS MUST FIT SNUGLY INSIDE ONE ANOTHER UNDER ZERO
PRESSURE OR UNDER PROOF AND SERVICE TEST PRESSURES
COUPLINGS
THE COUPLINGS SUPPLIED SHALL BE HARD COATED, LIGHTWEIGHT ROCKER LUG, AND
COMPLY WITH NFPA 1963 STANDARD ONE MALE AND ONE FEMALE COUPLING WITH 2 5"
NST THREADS ARE TO BE PROPERLY INSTALLED ON EACH LENGTH OF HOSE BY THE
MANUFACTURER
HOSE SPECIFICATIONS 5"
THIS SPECIFICATION IS FOR 400 FEET OF 5" FIRE HOSE IN 100 FOOT LENGTHS
THE HOSE SHALL BE PREMIUM QUALITY, ABRASION RESISTANT, CHEMICAL RESISTANT
ATTACK GRADE FIRE HOSE DESIGNED FOR PROLONGED STORAGE AND EXTENDED
SERVICE LIFE