Line Qty UOM Description Unit Price Extended Price
1 50 EA 6550-8640 1,270 000 63,500 00
Small Oval Vault
YARD
VAULT, COMPLETE, SMALL OVAL PRIMARY, TX 6' WITH QUEEN OLIVE COLOR COVER,
UNASSEMBLED, WITHOUT ASSEMBLING HARDWARE,
WITH LOCKING HARDWARE INSTALLED,PER SPEC #366-103
FIBERGLASS STRUCTURES,
Delivery 12-14 Weeks
Total $63,500 00
City of Fort Cl6lhs Director of Purchasing and Risk Management City of Fort
This order is Collins
valid over $2000 unless signed by James B O'Neill II, CPPO, FNIGP AccountingFrt Department
City of Fort Collins Purchasing, PO Box 580, Fort Collins, CO 80522-0580 PO Box 580
Fort Collins, CO 80522-0580
THE CITY OF FORT COLLINS
Light and Power Department
P O Box 580
Fort Collins, CO 80521
SPECIFICATION NO 366-103
Fiberglass Utility Vault
i
APPROVED BY
Kraig Aader
Standards Engineering Manager
PREPARED BY Kraig Bader
Date September 22, 1992
Revision Date February 4, 2005
REV C
REV SYM C
REVISION DESCRIPTIONS
DESCRIPTION (previous revision descriptions on file)
CHANGE
APPROVED
NOTICE
Revision A
N/A
Sagen/Coram
Paragraph 3 4 — deleted requirement for "queen olive gel coat' on all
9128192
vault parts
Revision B
Paragraph 21 — Edited the testing paragraph to clarify the test
N/A
methods and results desired for the vault lid This is a clarification of
10/4/2002
the intended test method only and no test values were changed
Revision C
Kraig Bader
• Paragraph 2 1 — Specified that load rating shall be an ultimate
2/17/2005
load rating Amend load rating from 14,100 pounds -force to
10,000 pounds -force The reduced load rating is selected as
a compromise between strength rating and lid weights that
will allow safe operation (Line Crew Foreman lifting limit from
floor to knuckle is 52 pounds)
• Paragraph 3 3 - Cover weights for oval vaults changed from
minimum of 58 pounds to a range between 60 and 80
pounds
• Paragraph 4 - Modified "Qualification Testing" requirements
to include more specific language that requires testing for any
design or process changes on both the covers and the vaults
2
366-103
TABLE OF CONTENTS
REVISION DESCRIPTIONS ...... ...................... .... ... ........... ... ... ... .......2
TABLE OF CONTENTS ............... .............. .... ... .............. ... .... 3
1 GENERAL DESCRIPTION........... .......... ........... ... ... ... ..... ..4
2 PERFORMANCE REQUIREMENTS .............. .... ... ... ......... .. ... .. .... .... 4
3 CONSTRUCTION REQUIREMENTS .... .......... ............ ...... ..... .. .. ... ....4
4 QUALIFICATION TESTING ... ........ ..... ... ... .. 4
3
366-103
SPECIFICATION FOR
FIBERGLASS UTILITY VAULT
7 GENERAL DESCRIPTION
REV SYM C
This specification covers large fiberglass utility vaults for sub -surface installation of electric equipment
Vaults purchased under this Specification shall be in accordance with drawing no 366-103 and the
following requirements
2 PERFORMANCE REQUIREMENTS
2 1 Covers shall support a minimum ultimate load of 10,000 pounds -force when tested with a point load
applied to a 12" diameter steel plate placed at the center of the lid Covers shall be tested with the
lids in place on the vault housing
2 2 Sidewalls shall have a minimum ultimate strength of 3,000 pounds -force when tested with a point
load applied to a 10" x 10" plate placed in the middle of the sidewall
2 3 The structural properties of the vault shall remain stable over a temperature range of -50°F to +200°F
3 CONSTRUCTION REQUIREMENTS
31 The vault and cover shall be constructed of fiberglass reinforced polyester (FPR) with a minimum of
30% glass, the balance being isophthalic polyester resin The resin shall include ultraviolet
inhibitors
3 2 The side panels and half round end sections shall be a minimum of 210 mils thick Side panels shall
be a minimum weight of 36 Ibs each End panels shall be a minimum weight of 46 Ibs each
3 3 The cover shall be constructed with reinforcing ribs as shown on drawing 366-103 The top of the
cover shall be a minimum of 474 mils thick, shall have a non-skid surface, and shall be impregnated
with a queen olive color
3 31 Round covers shall have a minimum weight of 30 pounds
3 3 2 Oval covers shall have a weight between 60 pounds and 80 pounds
3 4 Deleted
3 5 Dimensional integrity shall be such that parts can be randomly selected for development of either an
oval or round vault
3 6 All hardware shall be stainless steel
4 QUALIFICATION TESTING
Manufacturers shall be required to provide certified test reports prior to placing an order and on at least
one vault and cover from the first production run following any design or process change Test reports
shall verify that the glass content and ultimate strength of the covers and the vault sections
manufactured under the manufacturer's process conform to this specification
:Stitt-1 W