ADDENDUM No. 1
SPECIFICATIONS AND CONTRACT DOCUMENTS
Description of Bid 6010: SouthRidge Irrigation Pump Replacement
OPENING DATE: 2:30 P.M. (Our Clock) December 5, 2006
To all prospective bidders under the specifications and contract documents described above,
the following changes are hereby made.
1. Section 1.01 (1) Delete. There is no maintenance requirement, other than that required
during initial 30 days of system operation, as specified in Section 3.05 Maintenance.
2. Section 3.04 Project Record Drawings. There are no mylar or CAD drawings of the existing
pump stations. All references in Section 3.04 refer to as -built drawings to be supplied by the
contractor when project is complete.
3. Bid Proposal page, Bid Submittals. Bidders do not need to provide drawings of the proposed
system. Exact details will be worked out with the awarded vendor. Bidders may submit any
pump or equipment drawings they feel will add detail to their bid.
Please contact James R. Hume, CPPO, Senior Buyer at (970) 221-6776 with any questions
regarding this addendum.
RECEIPT OF THIS ADDENDUM MUST BE ACKNOWLEDGED BY A WRITTEN STATEMENT
ENCLOSED WITH THE BID/QUOTE STATING THAT THIS ADDENDUM HAS BEEN
RECEIVED.
215 North Mason Street • 2H' Floor • P.O. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6775 • Fax (970) 221-6707 wwwALov.eon
CITY OF FORT COLLINS
INVITATION TO BID
Bid 6010
SouthRidge Irrigation Pump Replacement
BID OPENING: 2:30 p.m. (our clock), December 5, 2006
Sealed bids will be received and publicly opened at the office of the Director of Purchasing and Risk
Management, PO Box 580, 215 North Mason St., 2nd floor, Fort Collins, Colorado 80522, at the
time and date noted on the bid proposal and/or contract documents. If delivered, they are to be
sent to 215 North Mason Street, 2" Floor, Fort Collins, Colorado 80524. If mailed, the address is
P.O. Box 580, Fort Collins, 80522-0580.
Bids must be received at the Purchasing Office prior to 2:30 p.m. (our clock), December 5,
2006.
Questions concerning the scope of the bid should be directed to Project Manager Randy
Bonneville, (970) 416-2787.
Questions regarding bid submittal or process should be directed to James R. Hume, CPPO, Senior
Buyer (970) 221-6776.
A pre -bid conference will be held on November 21, 2006, 10:00am, at SouthRidge Golf
Course, SouthRidge Clubhouse, 5750 South Lemay Avenue, Fort Collins, CO 80525.
A copy of the Bid may be obtained as follows:
1. Download the Bid from the Purchasing Webpage, Current Bids page, at:
hftr)s://secure2.fcciov.com/bso/login.psr).
2. Come by Purchasing at 215 North Mason St., 2nd floor, Fort Collins, and request a
copy of the Bid.
Special Instructions
All bids must be properly signed by an authorized representative of the company with the legal
capacity to bind the company to the agreement. Bids maybe withdrawn up to the date and hour set
for closing. Once bids have been accepted by the City and closing has occurred, failure to enter
into contract or honorthe purchase orderwill be cause for removal of supplier's name from the City
of Fort Collins' bidders list for a period of twelve months from the date of the opening. The City may
also pursue any remedies available at law or in equity. Bid prices must be held firm for a period of
forty-five (45) days after bid openings.
Submission of a bid is deemed as acceptance of all terms, conditions and specifications contained
in the City's specifications initially provided to the bidder. Any proposed modification must be
accepted in writing by the City prior to award of the bid.
Only bids properly received by the Purchasing Office will be accepted. All bids should be clearly
identified by the bid number and bid name contained in the bid proposal.
No proposal will be accepted from, or any purchase order awarded, to any person, firm or
corporation in default on any obligation to the City.
Bids must be furnished exclusive of any federal excise tax, wherever applicable.
Bidders must be properly licensed and secure necessary permits wherever applicable
215 North Mason Street • 2"d Floor 9 P.O. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6775 • Fax (970) 221-6707 wwwAilov.com
Bidders not responding to this bid will be removed from our automated vendor listing for the subject
commodities.
The City may elect where applicable, to award bids on an individual item/group basis or on a total
bid basis, whichever is most beneficial to the City. The City reserves the right to accept or reject
any and all bids, and to waive any irregularities or informalities.
Sales prohibited/conflict of interest: no officer, employee, or member of City Council, shall have a
financial interest in the sale to the City of any real or personal property, equipment, material,
supplies or services where such officer or employee exercises directly or indirectly any decision -
making authority concerning such sale or any supervisory authority over the services to be
rendered. This rule also applies to subcontracts with the City. Soliciting or accepting any gift,
gratuity, favor, entertainment, kickback or any items of monetary value from any person who has or
is seeking to do business with the City of Fort Collins is prohibited.
Freight terms: unless otherwise noted, all freight is F.O.B. Destination, Freight Prepaid. All freight
charges must be included in prices submitted on proposal.
Discounts: any discounts allowed for prompt payment, etc., must be reflected in bid figures and not
entered as separate pricing on the proposal form.
Purchasing restrictions: your authorized signature of this bid assures your firm's compliance with
the City's purchasing restrictions. A copy of the resolutions is available for review in the Purchasing
Office or the City Clerk's Office. Request Resolution 91-121 for cement restrictions.
Collusive or sham bids: any bid deemed to be collusive or a sham bid will be rejected and reported
to authorities as such. Your authorized signature of this bid assures that such bid is genuine and is
not a collusive or sham bid.
Bid results: for information regarding results for individual bids send a self-addressed, self -stamped
envelope and a bid tally will be mailed to you. Bid results will be posted in our office 7 days after
the bid opening.
James B. O'Neill II, CPPO, FNIGP
Director of Purchasing and Risk Management
BID PROPOSAL
BID 6010
SouthRidge Irrigation Pump Replacement
BID OPENING: December 5, 2006, 2:30pm (our clock)
We hereby enter our bid for the City of Fort Collins' requirements for SouthRidge Irrigation Pump
Replacement, per the bid invitation and any referenced specifications:
Pre -Bid Conference:.
A pre -bid conference will be held on November 21, 2006, 10:00am, at SouthRidge Golf Course,
SouthRidge Clubhouse, 5750 South Lemay Avenue, Fort Collins, CO 80525.
Specifications:
IRRIGATION PUMP SYSTEM
PART 1: GENERAL
1.01 SCOPE:
Furnish all labor, materials, supplies, equipment, tools, and transportation, and perform
all operations in connection with and reasonably incidental to the complete
manufacturing and installation of two pumping systems, and guarantee/warranty as
specified herein.
Any existing conditions provided herein are for information only. It is the contractor's
responsibility to confirm existing conditions on site prior to submitting bid. Items of work
specifically included are:
A. Procurement of all applicable licenses, permits, and fees as required by local
utilities and regulations.
B. Services of a factory field service person to supervise the assembly, installation,
and start-up of the pumping system, and the training of maintenance staff.
C. Furnishing and installing two prefabricated, vertical turbine type pumping
systems including pumps, motors, electrical controls, and other items as
specified.
D. Electrical Improvements:
1. Verify that existing conductors between existing electric meter and
electrical panels are of sufficient size.
2. Protect existing electric meter and phone line into pump building. Make all
necessary connections to existing electric meter.
3. Remove existing electrical panels.
4. Furnish and install new electrical panels meeting UL listing for hose
directed water. Existing location may not be appropriate based on layout
of new pump station. Install new electrical panels in locations meeting
NEC requirements and approved by Owner. Provide all necessary
electrical conduit and conductors if electrical panel locations are not
appropriate. Coordinate exact location of panels and routing of conduit
and conductors with the Owner on site prior to construction.
5. Furnish and install new conductors between new electrical panels and
pump station control panel and complete all necessary connections.
E. Install pump station using existing 5-foot inside diameter concrete wet well in
existing pump buildings.
F. Connect new pump station discharge pipe to existing flanged steel pipe
approximately 30-40-inches from inside wall. The new discharge piping cannot
be routed through the existing pump station building walls.
G. Complete mandatory site visit prior to submission of bid. It is the contractor's
responsibility to accurately record existing wet well location and discharge piping
point -of -connection inside building. The contractor must provide accurate, to
scale, shop drawing for each pump station installation with their bids. Contractor
must ensure that there is adequate maintenance room around control panels and
filter assembly
H. Repair any damage to existing turf grass on site in either transporting or installing
pump station.
Maintenance period.
1.02 WORK NOT INCLUDED:
Items of work specifically excluded or covered by the City of Fort Collins:
A. Provision and installation of electrical transformers on site,
B. Demolition and removal of existing pumping station and piping inside of existing
pump buildings.
C. A new concrete pad will be poured inside the existing pump buildings.
D. The existing pump building roofs will be removed and replaced in order to install
the new pump station skids.
E. Installation of new insulation and interior finish of existing pump buildings.
F. Remove existing Naiad wetting agent injection assembly from #10 pump station
on south side of course and mount on new pump skid.
G. Provide new Naiad wetting agent injection assembly on #5 pump station on north
side of course.
1.03 SUBMITTALS:
A. Deliver four (4) copies of all submittals to the Owners Representative within 21
days from the date of Notice To Proceed. Deliver Maintenance Manual prior to
start-up.
Materials List: Include pipe, valve, fittings, pumps and motors, control system
components, and electrical equipment. Quantities of materials need not be
included.
C. Manufacturers' Data: Submit manufacturers' catalog cuts, performance curves,
specifications, and operating instructions for equipment shown on the materials
list. Submit complete instructions for installation, operation, and recommended
maintenance of the pump system.
D. Maintenance Manual: Submit four copies of a bound maintenance manual that
includes all manufacturer's data listed above and recommended operating
procedures and preventive maintenance procedures. Include guide for
troubleshooting operational problems with the pump station and complete
documentation for programming, recommended settings and adjustments.
E. Shop Drawings: Submit shop drawings of proposed pump system. Show
products required for proper installation, their relative locations, and critical
dimensions. Submit technical data sheets, electrical schematics, sequence of
operation, UL listing authorization form.
Pump system manufacturer is responsible for layout and design of the pump
system supplied, and any special coordination issues that affect the critical
dimensions, layout, or orientation of the pump system.
The layout of the existing pump building, location of discharge pipe connection
must be shown, and relative dimension of the pump station are required.
1.04 RULES AND REGULATIONS:
A. Work and materials shall be in accordance with the latest edition of the National
Electric Code, the Uniform Plumbing Code as published by the Western
Plumbing Officials Association, and applicable laws and regulations of the
governing authorities.
All electrical control panels with controls shall be built in accordance to N.E.C.,
U.L. and E.T.L. standards. The electrical components and enclosure shall be
labeled as a complete U.L. listed assembly with manufacturer's U.L. label applied
to the door. All equipment and wiring shall be mounted within the enclosure and
labeled for proper identification.
1.05 TESTING:
A. Notify the Owner's Representative three days (72 hours) in advance of testing.
B. On completion of assembly of the pumping station, all discharge pipe and valves
shall be hydrostatically tested at 150% of the maximum pump shutoff head.
C. Bump manual motor starter controls to prove correct rotation and secure local
inspection/approval.
D. Test, verify, and demonstrate to the Owner's Representative the proper operation
of all control and safety shut off devices.
E. Verify flow and discharge pressure from the pump system and demonstrate to
the Owner's Representative system performance based on the specified values.
1.06 REVIEWS:
The purpose of on -site reviews by the Owner's Representative is to observe the
Contractor's interpretation of the construction documents and to address questions with
regards to the pump installation.
A. Scheduled reviews such as those for testing should be scheduled with the
Owner's Representative as required by these specifications.
B. Impromptu reviews may occur at any time during the project.
C. Final review will occur at the completion of the pumping system installation and
Record Drawings.
1.07 GUARANTEE/WARRANTY AND REPLACEMENT:
The purpose of this guarantee/warranty is to insure that the Owner receives materials of
prime quality, installed and maintained in a thorough and careful manner.
A. The manufacturer shall warrant the pumping system to be free of defects and
product malfunctions for a period of one year from date of start up or eighteen
months after shipment, whichever occurs first.
B. The programmable controller shall be unconditionally warranted for 5 years from
the date of shipment. The pumping system manufacturer shall be responsible for
all warranties, pass through warranties are not acceptable.
C. Failures caused by lightning strikes, power surges, vandalism, flooding, operator
abuse, or acts of God are excluded from warranty coverage.
D. Repair damage to the premises caused by a defective item. Make repairs within
seven days of notification from the Owner's Representative.
E. Contract documents govern replacements identically as with new work. Make
replacements at no additional cost to the contract price.
PART 2: MATERIALS
2.01QUALITY:
Materials used in the system shall be new and without flaws or defects of any type, and
shall be the best of their class and kind.
2.02 SUBSTITUTIONS:
A. Make complete submittals of all manufacturer's data showing compliance with
the Contract Documents.
B. In making a request for a substitution, the Contractor represents that he:
Has investigated the proposed substitution and found that it is the same
or better quality, level, capacity, function, or appearance than the
specified product, and can demonstrate that to the Owner.
2. Will coordinate the installation and make all modifications to the work,
which are required for the complete installation and operation of the
system.
C. The Owner's Representative will determine acceptability of the proposed
substitution and will notify Contractor of acceptance or rejection.
D. Pipe sizes referenced in the construction documents are minimum sizes, and
may be increased at the option of the Contractor.
2.03 GENERAL REQUIREMENTS:
A. Each prefabricated pumping station shall have a capacity of 1,000 GPM at a
discharge pressure of 125 PSI downstream of all pump system components,
using two equally sized main pumps. Provide a submersible pump as a pressure
maintenance pump. The station shall be completely piped, wired, hydraulically
and electrically tested on a structural steel skid before shipment to the job site.
B. All components of the pumping system shall be designed to function in an
outdoor environment exposed to all of the elements. Furnish protective
enclosures and covers as required for proper operation of the system.
C. Use a static lift of 10-feet when calculating the total dynamic head (TDH)
requirements of the pump system.
D. The existing wet well depths are 11-feet. Pump station intake must be 12-inches
off of the bottom of the wet well.
E. Construction shall include skid assembly to support all components during
shipping and to serve as the installed mounting base. Base shall be of sufficient
size and strength to resist twisting and bending from hydraulic forces and support
the full weight of pumps and motors.
The pump station and related equipment shall meet all the general and technical
specifications; shall be designed, fabricated and installed in a workmanlike
manner; and shall be delivered within the negotiated schedule.
G. Provide a factory -trained technician to supervise the installation of the pump
station, pumps, and motors.
In addition to the time required for installation supervision, the technician shall
provide a minimum of 1 day of training for the Owner's staff in the operation,
maintenance, and programming of the pumping system.
H. All pump station components shall be supplied by and be the responsibility of
one manufacturer, even though others manufactured some components.
Acceptable Manufacturers:
FLOWTRONEX PSI Ltd., 10717 Harry Lines Blvd., Dallas, Texas 75220
214-357-1320.
2. RAIN BIRD, 6991 East Southpoint Rd, Bldg #1, Tucson, AZ 85706
520-741-6145
SYNCROFLO, 6700 Best Friend Rd., Norcross, Georgia, 30071
770-447-4443
WATERTRONICS, 525-industrial Drive, Hartland, Wisconsin 53029
800-356-6686, 414-367-5000, Fax: 414-367-5551
2.04 PUMPS:
A. Furnish two main vertical turbine type pumps, electric motor driven, 1800 nominal
RPM, complete with the required length of threaded column assembly,
galvanized steel basket type suction strainer, and cast iron discharge head.
B. Bowl assemblies including the suction, intermediate, and discharge bowls shall
be furnished in cast iron, enamel lined with flanged connections. Furnish bronze
statically balanced impellers that are adjustable vertically by an adjusting nut
located at the top of the hollowshaft motor.
C. Pump efficiency shall be minimum 80% at the specified operating point. The
performance curve of each pump selected shall be continuously rising as the
shutoff condition is approached. The impeller diameter selected shall be less
than the maximum diameter available.
D. Furnish each pump with a flanged, cast iron or fabricated steel discharge head
complete with a cast iron adjustable packing gland, gland plate, grease seal,
packing bushing, packing and water slinger. Provide a continuous bypass flush
line from the stuffing box of each pump to the wet well.
E. All bowl bearings shall be constructed of bronze, all column bearings shall be
fluted rubber. Each pump shaft, column line shaft, and pump motor shaft shall
be turned, ground and polished 416 stainless steel sized to transmit full
nameplate HP of the motor. Minimum acceptable shaft size is 1-inch.
All shaft couplings shall be threaded and machined from 300 series stainless
steel. Furnish two piece headshaft assembly. Each motor shaft shall be
removable and couple to the pump head shaft between the bottom of the motor
and the packing gland with sufficient clearance to allow removal of the packing
gland assembly without motor removal.
G. Furnish a pressure maintenance pump, a multistage, submersible type, well
pump. Pump shall be equipped with a motor shroud for proper cooling of
submersible motor and stainless steel suction screen.
Furnish a pump with a Franklin submersible motor and Subtrol motor protection
controls. Pump furnished shall be a Goulds, Grundfos or approved equal.
2.05 MOTORS:
A. Each main pump motor shall be 1800-RPM nominal, squirrel cage induction
vertical hollow shaft type with a WP-1 enclosure and a 1.15 service factor. The
temperature rise of the motor shall be to NEMA Standard MG-1-12.42 for Class
B or Class F insulation.
B. For 40 HP motor or greater, furnish "Premium Efficiency" US Electric motors
Type RUS that are rated for continuous inverter duty with variable frequency
drive and are designated NEMA MGI-31.
C. Furnish motors of proper size to drive the pump at any point on its operation
curve without exceeding motor horsepower nameplate rating.
D. Furnish motor thrust bearings of ample capacity to accommodate the weight of
all rotating parts plus the hydraulic thrust of the pump at shutoff conditions.
Furnish motor bearings rated for a minimum service life not less than five years
continuous operation at the design rating point.
The pump shaft shall be connected to the motor by a bolted down coupling at the
top of each motor. All couplings shall be equipped with non -reversing ratchets.
F. Furnish motors manufactured in the U.S.A.
2.06 PIPING:
A. Fabricated Pioinq: All fabricated piping shall conform to ASTM specifications
A53 for Grade B welded or seamless pipe. Piping 16" and smaller shall be
Schedule 40. All welding flanges shall be forged steel with slip-on or welding
neck type. All welding fittings shall be seamless, conforming to ASTM
Specification A234, with pressure rating not less that 150 psi. All pressurized
tube fittings shall be copper or brass.
Bid Proposal: Bid #6010, SouthRidge Irrigation Pump System Replacement
Qty.
Description:
Extension
1
Replace Pump Station at SouthRidge Golf Course,
as specified below.
$
Bid Submittals:
Bidders must submit a complete written description and drawings of their proposed system. System
and component descriptions must be listed in the same order as they appear in Specifications,
Irrigation Pump System, Sections 2.03 through 2.18, as applicable.
Each bidder must also provide a written description of their proposed installation process and ability
to comply with the requirements set forth in Specifications, Irrigation Pump System, Sections 3.03
through 3.05.
Bidders may include a separate list of optional items, including descriptions and prices.
Delivery:
Prices must be quoted FOB Destination: SouthRidge Golf Course, Fort Collins, CO
Installation: AfPAPX !d EJOAKIPJA QAYY
Installation of new pump station will begin days after notice of award.
4,i''A$R1 LAPON
Fortechnical questions regarding the pump station, contact Randy Bonneville, Golf Superintendent,
970-416-2787.
For questions concerning bid procedures, contact Jim Hume, Buyer, 970-221-6776.
Signature:
Title: C
Print Name:
Company: �> 7��/Vi jNG_
Date: 17,1W 04
Street �Jl s �f, 3�U _
Phone 3 —5912-/VS
City: 'a VEk
Fax#:
State/Zip: c v, Dz-?3
Email: 94ULS6 °" M Itlln%e. Cd
M
B. Winterization Connection:
system discharge manifold
system.
2.07 VALVES:
Provide 2-inch capped threaded nipple in pump
for compressed air winterization of the irrigation
A. Air/Vacuum Release Valve:
Provide a continuous -acting, combination air release/vacuum valve to
release excess air from the pump discharge manifold. The valve must be
capable of releasing air during filling and pump operation and also open
in a vacuum condition to allow air to enter the manifold when piping is
drained. Valve shall have a cast iron body rated for 300 PSI, stainless
steel trim and float ball, Buna N and viton seats.
In lieu of an airtvacuum release valve, provide an approved equal device
to release air from the system.
B. Drain Valves: Drains are to be provided from any possible low point in the system
and are to consist of 1/4" brass angle valves unless otherwise noted. Drain
piping is to be furnished so that no drain water runs out on top of the deck plate,
but either under deck plate, or directly into the trench drain or wet well. They
include, but are not limited to, the following:
1. Provide drain in the pump discharge manifold between pump check
valves and control valve.
2. Provide 3/4" brass hose bib in the discharge piping to function as a
washdown connection and also function as a drain.
C. Check Valves: Pump check valves shall be of the silent operating, non -slam type,
cast iron bodied with bronze and stainless steel trim. Sealing surfaces shall
utilize resilient Buna N rubber. The valve design shall incorporate a center
guided, spring, loaded poppet, guided at opposite ends and having a short linear
stroke that generates a flow area equal to the pipe diameter. Valves shall be
sized to permit full pump capacity to discharge through them without exceeding a
pressure drop of 2.5 PSI. Furnish check valves on the discharge of each pump.
D. Isolation Valves: Valves shall be butterfly type with the position lever or gear
hand wheels and rated at 200 psi WOG working pressure. Trim shall include
stainless steel stem, bronze streamlined disc, and full faced resilient seat.
Isolation valves shall be installed on the discharge side of each pump. The pump
system shall also be furnished with a main station isolation valve located in the
discharge manifold.
E. Pressure Relief Valve: Furnish pressure relief valve and bypass piping to wet
well installed on the discharge piping upstream of the pressure regulating valve.
Size pressure relief valve to bypass sufficient water to avoid operating pumps at
or near shut off head conditions.
2.08 GAUGES:
Gauges and switch gauges shall be isolated from all electrical switch gear and control
panels. Gauges shall be provided at appropriate locations to read inlet pressure and
discharge manifold pressure. Switch gauges shall be 4" diameter vibration/pulsation
dampened. Pressure gauges shall be 2.5" diameter, glycerin filled, with ANSI Class B
accuracy. Install ball valves to provide total isolation of all pressure gauges.
2.09 ELECTRICAL:
A. Electrical Suooly: The power supply to the station shall be three phase, 460 volt,
60 hertz, for full voltage across the line motor starting.
B. Enclosures:
The pumping station electrical controls shall be mounted in a self
contained NEMA 3S (minimum NEMA rating) enclosure with a drip lip
fabricated from not less that 14 gauge steel. Door gasket seals shall be
neoprene sponge, sufficient to protect interior components from weather
and dust. The electrical panel doors shall be constructed from 12-gauge
steel with integral locking screws and latches.
2. Provide operating handle for the main station power disconnect on the
front of the panel. Furnish weatherproof and dust proof external
operating devices.
3. All internal components of the enclosures shall be mounted on removable
back panels. Mounting screws for components shall not be tapped in the
panel enclosure.
4. All internal wiring within, and interconnecting between, the panels shall be
complete and no field wiring within the panels shall be required. Wiring
troughs and cable raceways shall be self-contained within the enclosures
and no external cable trays or wiring troughs are permitted.
5. No pressure gauges, pressure switches, water activated devices, or water
lines of any sort shall be installed in any electrical control panel. All
adjustments and maintenance shall be able to be done from the front of
the control enclosure. A complete wiring circuit and legend with all
terminals, components, and wiring identification shall be provided. Main
disconnect shall be interlocked with door.
6. All electrical starter and control panels shall be assembled from
components that are U.L. listed and each completed panel shall be U.L.
listed as an Industrial Control Panel,
7. A closed type cooling system shall be included to cool the enclosure and
reject heat from the VFD. Open type cooling systems allowing outside
ambient air to enter the panel are not acceptable.
C. Pump Motor Starters. Disconnect. and Electrical Switch Gear:
1. The pump motor starters shall be contained within a single NEMA 12
enclosure with a single access door and main disconnect. Each starter
shall be protected on each power leg by a time delay fuse of the
appropriate amperage. Motor starter coils shall be 120 volt operated.
2. Overload relays shall be ambient -compensating type installed on each
power leg and shall be set to trip at 105% of motor full -load current rating.
D. Variable Soeed Master Controls and Display:
Provide complete instrumentation and controls to automatically start, stop and
modulate pump speed(s) to smoothly, efficiently and reliably pump variable flow
rates at a constant discharge pressure. Provide full alarms and safety features
needed to protect the equipment and irrigation piping system.
Variable Freauencv Drive: Provide a digital, pulse width modulation
(PWM) variable frequency drive (VFD) with IGBT transistors.
a. Provide VFD with a minimum wire to wire efficiency of 98.5%, and
shall be rated up to 550-volt operation In order to eliminate
nuisance tripping at marginally high voltage conditions.
b. Provide VFD with the front end protected by fast acting
semiconductor fuses. Any VFD error messages shall be
displayed on a 40-character LCD readout in English or any one of
8 other languages.
C. Include the following fault protection circuits: Over -current (200%),
over -voltage (130%), under -voltage (60%), over -temperature (700
C), ground fault, and motor overload.
d. Provide VFD capable of starting into a rotating load and
accelerate or decelerate to setpoint without safety tripping.
e. Provide VFD with an automatic extended power loss ride through
circuit, which will utilize the inertia of the pump to keep the drive
powered. The minimum power loss ride -through shall be one
cycle based on full load and no inertia.
f. Provide VFD optimized for a 3 kHz carrier frequency to reduce
motor noise and employing three current limit circuits to provide
"tripless" operation.
g, The following operating information shall be displayed on the VFD
LCD: KWH, elapsed time, Output frequency (Hz), motor speed
(RPM), motor current (amps), and voltage. Line reactor will be
installed on input of VFD to protect against voltage transients.
h. Provide VFD as manufactured by Allen Bradley, ABB, Toshiba,
Siemens, or approved equal.
2. Pressure Transducer: Pressure transducer shall be utilized for providing
all pressure signals for the control logic.
a. Provide a solid-state bonded strain gauge type pressure
transducer with an accuracy of plus/minus 0.20%. Housing shall
be stainless steel NEMA 4X with 304L stainless steel wetted
parts. Plastic transducer housings are not acceptable.
b. Furnish a transducer rated for station discharge pressure as
shown on technical data sheet, that will provide gauge pressure
output, rather than an absolute.
3. Controls: All control logic shall be handled by an industrial grade
programmable logic controller (PLC) with a 40 character LED industrial
operator interface providing data entry and read-out capabilities.
a. Provide PLC with LED indicators for input, output, and four (4)
diagnostic read-outs showing PC Run, CPU Fault, 1/0 Fault, and
communication. Provide an LED visual status light for each 1/0 to
indicate on/off status.
b. Provide PLC with a built in EEPROM, capacitor, and battery for
memory backup. A surge suppressor shall be mounted on input
of PLC for power transient suppression.
C. All logic for system control, timing, and control of VFD speed shall
be handled by the PLC. No external relay logic and/or timers are
permitted. A separate set point controller is not acceptable.
d. PLC shall have a built in clock calendar. The PLC shall be of the
type manufactured by Toshiba, Siemens, Allen Bradley,
Mitsubishi, or approved equal,
4. Alarms and shutdowns:
a. Low discharge pressure (with override switch)"
b. High discharge pressure
C. Low lake level (Attempts restart)*
d. Phase loss (Attempts restart)*
e. Low voltage (Attempts restart)"
f. Phase unbalance (Attempts restart)'
g. Individual motor ovedoad/phase loss (indicates which individual
motor was shut down)
h. VFD fault (shutdown VFD pump only and attempts restart).*
*Three failed restarts in 15-minute period will give hard shutdown.
A red general alarm light will indicate all alarms. Specific alarm conditions along
with procedures for correction will be displayed in English on the operator
interface display (OID).
5. Panel face switches and li-ghts:
a. Individual pump run lights and pump on/off switches
b. System Hand/Off/Automatic switch
C. Mode Select switch -- allows automatic bypass mode of operation
that can be used if VFD should fail.
d. VFD selector switch -- in manual mode, allows user to select
which pump will be run off the VFD.
e. Reset — Acknowledges pump station alarms
Speed potentiometer -- in manual mode allows user to adjust VFD
pump speed
g. Low discharge pressure override switch -- disables low discharge
pressure alarm
h. PLC bypass switch mounted inside panel allows user to manually
operate pumps should PLC fail.
6. Software:
a. Software will be included to automatically and gradually ramp up
irrigation system pressure to the desired operating pressure (i.e.,
1 PSI every 3 seconds) without overshooting design pressure.
This feature operates whenever pressure drops below set point
pressure. This ramp up time is fully adjustable by the operator.
This control feature is based on an increase in pressure over a
pre -defined time period. The acceleration control on the VFD is
NOT an acceptable means of adjusting pressure ramp up speed.
b. Software will be included for optionally maintaining a lower
irrigation system pressure when not irrigating. Reduced pressure
values will be shown in the technical data sheet. Controls will
cycle the PM pump at these reduced pressures during non-
irrigation times and pressure will gradually increase to design
pressure when the irrigation periods begin.
C. Neither flow meter nor VFD output frequency shall be used for
shutting down last VFD driven pump. Controls and software shall
incorporate a method to eliminate excessive cycling of VFD pump
at very low flow conditions, yet not run the pump excessively at no
flow conditions.
d. Provide automatic alternation of VFD driven pumps accomplished
by incorporating dual mechanically and electrically interlocked
contactors allowing alternation of the VFD between pumps.
e. Real time clock calendar allows PLC to internally provide all date
and time functions used above.
f. Two separately adjustable PID control loops for both low flow and
high flow pressure stability.
Provide system that allows user to Feld select either two modes of
VFD operation. Auto switch VFD option allows VFD to
sequentially start each pump. The standard mode of operation
starts the first main pump on the VFD and the remaining pump
starts across the line as required.
Shutoff algorithm for fixed speed pumps to minimize pump cycling
while also remaining responsive to sudden flow reductions.
Minimum run timers alone for minimizing fixed speed pump cycling
is not acceptable. Discharging through relief valve during pump
transitions is not acceptable.
Full manual operation capability with panel face mounted speed
potentiometer for manually adjusting VFD speed.
System can be immediately and directly switched from manual to
automatic mode of operation. This allows for manual
pressurization and immediate switching capability to automatic.
k. Light test sequence. Pressing the reset button for 5 seconds
illuminates all lights.
Rate of pressure change algorithm to rapidly determine if there is
an irrigation demand and immediately cycle on the VFD pump, in
lieu of waiting for pressure to drop to a predetermined start
pressure.
M. All pump station shutdowns shall be of the controlled type which
sequentially phase pumps off at user selectable internals to
reduce water hammer within the irrigation system.
Operator Interface Device (OID):
a. The pump station shall include a NEMA 4, 40 character LED
display and keypad mounted on the control panel door. This
device will allow the operator to view and selectively modify all
registers in the PLC. The unit shall store its messages in non-
volatile memory. The operator interface device shall incorporate
password protection for protecting data integrity. The device will
allow for display and modification of all timers, set points, lockout
times, etc. The device shall communicate with the PLC through
the programming port, and shall include an RS232
communications port allowing a printer to be attached for real time
station status logging.
b. The OID shall be an information system only and not required for
pump station operation. No switches, reset buttons, general alarm
light, run lights or speed potentiometers are included within this
unit. This pump station will be fully functional in the event the OID
unit should fail.
C. In addition to normal data entry keys, the device shall include a
minimum of the following function keys labeled:
(1) Event. Displays one of three data logging functions.
(a) Operator can scroll through the historical pump
station flows and pressures for up to the last 7
days. The operator can change sampling time
periods (from 1 to 60 minutes). Averages are taken
over the sample period and the average recorded
with time stamp.
(b) The last 128 sequential pump station events with
time of occurrence. Events shall include but not be
limited to: all alarms, starting of individual pumps,
stopping of individual pumps and changing of
selector switches.
(c) Station flow and pressure are shown every second
for the previous 60 seconds and every minute for
the previous 30 minutes. If a shutdown occurs, the
flow and pressure tables are locked in so that the
operator may view how the pump station was
performing immediately before the shutdown
occurred.
(2) Status. Will display the current operating status. When
the station is running, the display will show the setpoint
pressure, actual pressure, flow, and pump rpm.
(3) Alarm Info. It will display detailed information on the
alarm, time of occurrence, pumps operating at time of
alarm and how to correct the alarm condition.
(4) Daily Log. It will display the following: Last time of log
reset, individual pump run times, run times since last reset,
pump starts, pump starts since last reset, total flow, total
flow since last reset, highest flow rate with time of
occurrence, alarm conditions, and times since last reset.
(5) Scroll Key. Used to scroll up and down through data.
8. Operation:
a. During non -irrigation times, the pressure maintenance pump (PM)
will cycle on and off as required to maintain irrigation system
pressure. The cycling pressures can be user selected and can be
set substantially below normal set point pressure, if desired. If the
PM pump cannot maintain the desired pressure, then the VFD will
start the first pump and will gradually ramp the pressure up to
desired irrigation pressure.
b. The pump speed will be modulated to hold a constant discharge
pressure regardless of flow. As the flow rate increases and the
VFD pump can no longer maintain pressure while at maximum
speed, the next sequential pump will be started and the VFD
driven pump will accordingly reduce its speed and modulate.
C. An algorithm shall be include for accurately reducing the VFD
pump speed as the next sequential pump is started so that no
pressure surges are generated during the transition (even with
across the line starting). If the user prefers to switch the VFD from
pump to pump for sequential starting, he can select this option
with the OID.
d. As the flow continues to increase, pumps will sequentially be
started until all pumps are operating. As the flow begins to
decrease, pumps will be sequentially turned off until only a single
VFD driven pump is operating. When a no flow condition occurs,
the VFD pump shall be turned off.
E. Skid Wiring:
All wiring from control panels to motors shall be in liquid -tight conduit with
copper conductors rated not less than 600 volts AC and of proper size to
carry the full load amperage of the motors without exceeding 70%
capacity of the conductor. A grounding cable shall be included in the
liquid- tight conduit. There shall be no splices between the motor starters
and the motor connection boxes.
Wiring to flow sensors and pressure transducer shall be multi -conductor
shielded cable suitable for Class II low voltage controls.
F. Lightning Arrestor:
The main power supply feeding the pumping station shall be equipped with a 3
phase secondary lighting arrestor having a breakdown current rating of not less
that 60,000 amps at 14,000 volts discharge. Power supplies, 300 volts and less
shall use 300 volt rated arrestor with an 800 volt spark -over voltage. Power
supplies 301-600 volts shall use 600 volt rated arrestors with a 1,000-volt spark -
over voltage.
G. Misc. Electrical Comoonents:
Main Station Disconnect:
A three -pole main station disconnect shall be mounted in a separate
NEMA 3S enclosure to completely isolate the electrical system from
incoming power. The disconnect shall conform to the requirements of the
NEC and applicable local codes. The main station disconnect shall have
an operating handle on the front of the panel.
2. Secondaryy Control Circuit Fuses:
Single -pole secondary distribution fuses with appropriate ratings shall
supply power to each pump starter coil circuit, the control system, and to
other circuits as required.
3. Phase Failure - Low Voltage Safety Shutdown:
A phase failure - low voltage system dropout relay shall be provided to
de -energize the individual pump controls and motor sequencing control in
case of either low voltage or phase failure after a 5.0 second time delay.
The resetting shall be automatic after full power is restored for 5.0
seconds, with pumps sequentially restarting. The phase failure - low
Voltage indicator light is to remain illuminated until manually reset.
4. Low System Pressure Safety Shutdown:
Low discharge pressure is to be sensed by the pump starting set point.
When the station discharge pressure decreases to this point and
maintain$ a start signal for a preset time, the pumps will be de -energized
and remains so until the circuit is manually reset. An indicator light shall
illuminate to indicate a low discharge pressure shutdown has occurred.
5. Low Water Level Safety Shutdown:
Furnish liquid level probes and controls to prevent operation of the pumps
when water levels in the wet well are insufficient. Furnish shutdown with
automatic restart after an adjustable delay. Low water level indicator
lamp shall remain lit until manually reset.
6. Corrosion Inhibiting Modules:
Corrosion inhibiting modules shall be installed in all electrical enclosures
in accordance with the manufacturer's recommendations.
H. Standards:
All wiring shall conform to the National Electrical Code Standards.
Flexible conduit sections shall be under 5 feet in length. All conduit to
devices shall be attached securely to avoid trip hazards.
2. The manufacturer shall provide a wiring schematic. The schematic shall
show all devices, connections and wire numbers.
3. All controls and electrical equipment shall be thoroughly inspected and
tested before shipment.
2.10 FLEXIBLE CONNECTIONS:
A. Furnish coupling if transition between pipe materials due to distance or elevation
is required between pump station discharge piping and existing irrigation piping
in pump building. Coupling must be rated for minimum working pressure of 600
PSI. Use Dresser, Ford, Metraflex, or Owner approved equal.
2.11 PIPE SUPPORT STAND:
A. Furnish manufactured steel pipe support stand as shown on the drawings and
details. Support must be capable of supporting 500 lbs. dead load and be
adjustable within the range shown on the pump piping detail.
B. Furnish Standon Model S89 or S92 as required, with red oxide primer, as
manufactured by Material Resources, Hillsboro, Oregon, (503) 693-0727 or
approved equal.
2.12 FLOW METER:
A. Provide a velocity sensing electromagnetic type, microprocessor based signal
converter, sealed housing, flanged tube meter for 150 psi working pressure, and
CSA approved meter.
B. Acceptable manufacturers are KROHNE and BADGER.
Packaged Pumping System
Metron, Inc., 1505 West Third Avenue, Denver, Colorado, 80223
Phone: (303) 592-1903 Fax: (303) 534-1947
Date: December 4, 2005
Project: Southridge GC
Quotation
E-mail: khulse@metroninc.com
Quotation No.: 20061211
Location: Fort Collins, CO
Metron has been a leading manufacturer of Pump Controllers and Packaged Pumping Systems for more
than 50 years. Our commitment to high standards of quality and reliability include U.L. certification of the
skid mounted Packaged Pumping System. Only Metron, Inc. can offer the Rocky Mountain region's;
Largest and most qualified pump station service organization with the quickest solutions during all phases
of the project.
Largest pump panel and package manufacturer with unequaled sales and technical experience and
support.
Metron. Inc. is the world's largest supplier of fire pump controls. Our standards for quality, reliability and
responsiveness are unsurpassed.
General Note:
The Packaged Pumping Station described in this quotation is designed and manufactured in accordance
with Metron's standards for use in turf irrigation applications in the State of Colorado.
This quotation is to Bid proposal #6010 and per site visit and addendum #1 with the following
clarifications:
1. Based on previous experience of system retrofits within the City of Fort Collins, the only permits
which will be necessary will be for the electrical connection to the pump system.
2. 2.09 Refers to multiple panels with different Nema ratings. All components to be located in one
Nema 12 panel.
3. 2.18.6 Refers to system paint. This makes reference to a "tank". There is no "tank" necessary or
provided with the system.
Metron, Inc. is pleased to offer you the following prefabricated Variable Frequency Drive
Packaged Vertical Turbine Pumping System:
VWP-IRR-3.0-VFD-100011251250-5015013-48013160-N12HX-BP50-PM-AA-SQS50150-FILT-AIR RLS-
2LCF-MM-UL
Each of the two Metron Packaged Pumping Systems is designed to deliver 1000 GPM at a station
discharge pressure of 1250PSI using two (2) main vertical turbine pumps with variable frequency drive
(VFD) start and one (1) pressure maintenance submersible pump with across -the -line start. All pumps
extend 10-feet into a 11-foot deep, 5-foot diameter wet well. Incoming power to the pumping station is
480-volts, 3-phase, and 60-hertz.
The following features listed are per station.
This proposal includes delivery, installation and connection to existing electrical and mechanical
connections.
Flush line from filter to lake or drain provided by others (optional adder below).
QTY. DESCRIPTION SELLING PRICE
Page 1, December 4, 2005 Quotation No. 20061211
2.13 AUTOMATIC BACKWASHING SCREEN FILTER:
A. Provide automatic self cleaning suction scanning filter with 300-micron screen, or
approved equal. Filter must be capable of an automatic backwash cycle based
on pressure differential and time interval.
B. Provide check valve on discharge pipe downstream of filter device.
C. Acceptable manufacturers are Valve and Filter and Amiad.
2.14 REMOTE MONITORING:
A. Provide necessary interface compatible with the remote monitoring software
provided by pump station manufacturer.
B. Use wireless communication between pump stations and existing central control
system computer. Furnish and install all necessary radios, antennas, conduit,
and conductors.
C. Furnish and install all necessary software and peripherals at the central control
system computer.
2.16 SKID MOUNTED HEATER:
Provide a thermostatically controlled skid mounted heater completely wired and
permanently mounted on the skid.
2.16 POWER SUPPLY:
Provide a power supply suitably rated and sized for operating the existing NAIAD
injection systems.
2.17 ACCESS HATCH:
Provide hatch as a hinged component of the pump -mounting skid for access to wet well.
2.18 PAINTING:
A. Painting of the entire unit shall consist of a multi -step coating system which
includes metal preparation, rust inhibitive prime coat, and a two part
polyurethane finish having a total dry film thickness of not less that 4 mils.
B. Pump station components shall be painted the manufacturer's standard color. All
electrical enclosures, tank, and accessory panels shall be painted to a minimum
thickness of 3 mils and baked at 160-180 F.
C. Provide a 1-quart can of the finish paint with the system for job site touch up use.
PART 3: EXECUTION
3.01 INSPECTIONS AND REVIEWS:
A. Site Inspections:
1. Verify site conditions and note irregularities affecting work of this section.
Report irregularities to the Owner's Representative prior to beginning
work.
2. Beginning work of this section implies acceptance of existing conditions.
3. Protect existing pump station buildings during construction and repair or
replace any damaged item.
3.02 INSTALLATION:
A. Shipping, off-loading and the technical start up shall be furnished by the pump
station manufacturer. The pump station manufacturer shall furnish location and
mounting details to Owner's Representative.
B. Anchor pump system to concrete mounting pad and complete all piping
connections prior to startup and operation of the pump system.
C. Electrical connection shall consist of a single conduit from 3 phase 460 volt 200
ampere disconnect to the pump station main disconnect.
D. Technical start up procedures by the pump station manufacturer shall include the
following:
1. Station start up and pressurization
2. Pressure, flow, and programming adjustments
3. Monitoring of irrigation cycle when possible. Technician will instruct
operations personnel as to the operation, adjustment and maintenance of
the pump station.
3.03 OPERATION AND MAINTENANCE MANUALS:
A. Furnish four (4) copies of the bound Pump System Operation and Maintenance
manuals as described in the specifications to the Owner's Representative prior to
the start up.
B. Tools and Spare Parts: Prior to the Pre -Maintenance Review, supply to the
Owner operating keys, servicing tools, test equipment, and any other items
indicated on the drawings.
C. Other Materials: Install other materials or equipment shown on the drawings or
installation details to be part of the pumping system, even though such items
may not have been referenced in these specifications.
3.04 PROJECT RECORD DRAWINGS:
A. The Contractor is responsible for documenting changes to the design. Maintain
on -site and separate from documents used for construction, one complete set of
contract documents as Project Documents. Keep documents current. Do not
permanently cover work until as -built information is.
Record pumping system alterations. Record work, which is installed differently
than shown on the construction drawings. Record accurate reference
dimensions.
C. Prior to completion of project, obtain from the Owner a reproducible mylar copy
of the drawings. Mylars or CAD data files compatible with AutoCAD software,
can be purchased from the Owner. Cost of mylar reproducible drawings is $50
per set and the cost of AutoCAD data files on diskette is $100 per project set.
Using technical drafting pen, duplicate information contained on the project
drawings maintained on site. Label each sheet "Record Drawing". Completion
of the Record Drawings will be a prerequisite for the Final Review.
3.05 MAINTENANCE:
A. Upon completion of completion of project, maintain system for a duration of 30
calendar days. Make periodic examinations and adjustments to irrigation system
components as necessary.
Following completion of the Contractor's maintenance period, the Owner will be
responsible for maintaining the system in working order during the remainder of
the guarantee/warranty period, and for performing necessary minor maintenance.
3.06 CLEANUP:
A. Upon completion of work, remove from the site all machinery, tools, excess
materials, and rubbish.
B. Manufacturer's Representative shall clean all surfaces and touch up scratches
with factory paint to match original.
SERVICES AGREEMENT
THIS AGREEMENT made and entered into the day and year set forth below by and
between THE CITY OF FORT COLLINS, COLORADO, a Municipal Corporation, hereinafter
referred to as the "City" and , hereinafter referred to as "Service Provider'.
WITNESSETH:
In consideration of the mutual covenants and obligations herein expressed, it is agreed by
and between the parties hereto as follows:
Scope of Services. The Service Provider agrees to provide services in accordance
with the scope of services attached hereto as Exhibit "A", consisting of
page and incorporated herein by this reference.
2. The Work Schedule. The services to be performed pursuant to this Agreement shall
be performed in accordance with the Work Schedule attached hereto as Exhibit "B", consisting of
) page, and incorporated herein by this reference.
3. Contract Period. This Agreement shall commence , and shall continue in
full force and effect until 200 , unless sooner terminated as herein provided.
In addition, at the option of the City, the Agreement may be extended for additional one year
periods not to exceed
) additional one year periods. Renewals and pricing
changes shall be negotiated by and agreed to by both parties. The Denver Boulder Greeley CPIU
published by the Colorado State Planning and Budget Office will be used as a guide. Written
notice of renewal shall be provided to the Service Provider and mailed no laterthan ninety (90) days
prior to contract end.
4. Delay. If either party is prevented in whole or in part from performing its obligations
by unforeseeable causes beyond its reasonable control and without its fault or negligence, then the
party so prevented shall be excused from whatever performance is prevented by such cause. To
the extent that the performance is actually prevented, the Service Provider must provide written
SA 09/01/06
24
notice to the City of such condition within fifteen (15) days from the onset of such condition.
[Early Termination clause here as an option.
5. Early Termination by City/Notice. Notwithstanding the time periods contained herein,
the City may terminate this Agreement at any time without cause by providing written notice of
termination to the Service Provider. Such notice shall be delivered at least fifteen (15) days prior to
the termination date contained in said notice unless otherwise agreed in writing by the parties. All
notices provided under this Agreement shall be effective when mailed, postage prepaid and sent to
the following addresses:
City:
Service Provider:
In the event of early termination bythe City, the Service Provider shall be paid for services rendered
to the date of termination, subject only to the satisfactory performance of the Service Provider's
obligations under this Agreement. Such payment shall be the Service Provider's sole right and
remedy for such termination.
6. Contract Sum. The City shall pay the Service provider for the performance of this
Contract, subject to additions and deletions provided herein, per the attached Exhibit "C", consisting
of ( ) page(s), and incorporated herein by this reference.
7. City Representative. The City will designate, prior to commencement of the work, its
representative who shall make, within the scope of his or her authority, all necessary and proper
decisions with reference to the services provided under this agreement. All requests concerning
this agreement shall be directed to the City Representative.
8. Independent Service provider. The services to be performed by Service Provider are
those of an independent service provider and not of an employee of the City of Fort Collins. The
City shall not be responsible for withholding any portion of Service Provider's compensation
SA 09/01/06
25
hereunder for the payment of FICA, Workmen's Compensation or other taxes or benefits or for any
other purpose.
9. Personal Services. It is understood that the City enters into the Agreement based on
the special abilities of the Service Provider and that this Agreement shall be considered as an
agreement for personal services. Accordingly, the Service Provider shall neither assign any
responsibilities nor delegate any duties arising under the Agreement without the prior written
consent of the City.
10. Acceptance Not Waiver. The City's approval or acceptance of, or payment for any
of the services shall not be construed to operate as a waiver of any rights or benefits provided to
the City under this Agreement or cause of action arising out of performance of this Agreement.
11. Warranty.
(a) Service Provider warrants that all work performed hereunder shall be
performed with the highest degree of competence and care in accordance
with accepted standards for work of a similar nature.
(b) Unless otherwise provided in the Agreement, all materials and equipment
incorporated into any work shall be new and, where not specified, of the
most suitable grade of their respective kinds for their intended use, and all
workmanship shall be acceptable to City.
(c) Service Provider warrants all equipment, materials, labor and other work,
provided underthis Agreement, except City -furnished materials, equipment
and labor, against defects and nonconformances in design, materials and
workman ship/workwomanship for a period beginning with the start of the
work and ending twelve (12) months from and after final acceptance under
the Agreement, regardless whether the same were furnished or performed
by Service Provider or by any of its subcontractors of any tier. Upon receipt
of written notice from City of any such defect or nonconformances, the
affected item or part thereof shall be redesigned, repaired or replaced by
Service Provider in a manner and at a time acceptable to City.
12. Default. Each and every term and condition hereof shall be deemed to be a material
element of this Agreement. In the event either party should fail or refuse to perform according to
the terms of this agreement, such party may be declared in default thereof.
13. Remedies. In the event a party has been declared in default, such defaulting party
SA 09/01 /06
26
shall be allowed a period of ten (10) days within which to cure said default. In the event the default
remains uncorrected, the party declaring default may elect to (a) terminate the Agreement and seek
damages; (b) treat the Agreement as continuing and require specific performance; or (c) avail
himself of any other remedy at law or equity. If the non -defaulting party commences legal or
equitable actions against the defaulting party, the defaulting party shall be liable to the non -
defaulting party for the non -defaulting party's reasonable attorney fees and costs incurred because
of the default.
14. Binding Effect. This writing, together with the exhibits hereto, constitutes the entire
agreement between the parties and shall be binding upon said parties, their officers, employees,
agents and assigns and shall inure to the benefit of the respective survivors, heirs, personal
representatives, successors and assigns of said parties.
15. Indemnity/Insurance. a. The Service Provider agrees to indemnify and save
harmless the City, its officers, agents and employees against and from any and all actions, suits,
claims, demands or liability of any character whatsoever brought or asserted for injuries to or death
of any person or persons, or damages to property arising out of, result from or occurring in
connection with the performance of any service hereunder.
b. The Service Provider shall take all necessary precautions in performing the work
hereunder to prevent injury to persons and property.
c. Without limiting any of the Service Provider's obligations hereunder, the Service Provider
shall provide and maintain insurance coverage naming the City as an additional insured underthis
Agreement of the type and with the limits specified within Exhibit , consisting of
( ) pages[s], attached hereto and incorporated herein by this reference. The
Service Provider before commencing services hereunder, shall deliver to the City's Director of
Purchasing and Risk Management, P. O. Box 580 Fort Collins, Colorado 80522 one copy of a
certificate evidencing the insurance coverage required from an insurance company acceptable to
SA 09/01/06
27
the City.
16. Entire Agreement. This Agreement, along with all Exhibits and other documents
incorporated herein, shall constitute the entire Agreement of the parties. Covenants or
representations not contained in this Agreement shall not be binding on the parties.
17. Law/Severability. The laws of the State of Colorado shall govern the construction
interpretation, execution and enforcement of this Agreement. In the event any provision of this
Agreement shall be held invalid or unenforceable by any court of competent jurisdiction, such
holding shall not invalidate or render unenforceable any other provision of this Agreement.
18. Prohibition Against Employing Illegal Aliens. This paragraph shall apply to all
Contractors whose performance of work under this Agreement does not involve the delivery of a
specific end product other than reports that are merely incidental to the performance of said work.
Pursuant to Section 8-17.5-101, C.R.S., et. seq., Contractor represents and agrees that:
A. As of the date of this Agreement:
1. Contractor does not knowingly employ or contract with an illegal alien; and
2. Contractor has participated or attempted to participate in the basic pilot
employment verification program created in Public Law 208, 104th
Congress, as amended, and expanded in Public Law 156, 108th
Congress, as amended, administered by the United States Department of
Homeland Security (the "Basic Pilot Program") in order to verify that
Contractor does not employ any illegal aliens.
B. Contractor shall not knowingly employ or contract with an illegal alien to
perform works under this Agreement or enter into a contract with a
subcontractor that fails to certify to Contractor that the subcontractor shall not
knowingly employ or contract with an illegal alien to perform work under this
Agreement.
C. Contractor shall continue to apply to participate in the Basic Pilot Program and
shall in writing verify same every three (3) calendar months thereafter, until
Contractor is accepted or the public contract for services has been completed,
whichever is earlier. The requirements of this section shall not be required or
effective if the Basic Pilot Program is discontinued.
D. Contractor is prohibited from using Basic Pilot Program procedures to
undertake pre -employment screening of job applicants while this Agreement is
being performed.
SA 09101 /06
28
ATTEST:
City Clerk
APPROVED AS TO FORM:
Assistant City Attorney
SA 09/01 /06
CITY OF FORT COLLINS, COLORADO
a municipal corporation
By:----------- ------------- ----
James B. O'Neill ll, CPPO, FNIGP
Director of Purchasing and Risk Management
Date: --------1 Zf- LIM-----------
PRINT NAME
RATE PRESIDENT OR VICE PRESIDENT
Corporate Seal)
30
E. If Contractor obtains actual knowledge that a subcontractor performing work
under this Agreement knowingly employs or contracts with an illegal alien,
Contractor shall:
1. Notify such subcontractor and the City within three days that Contractor
has actual knowledge that the subcontractor is employing or contracting
with an illegal alien; and
2. Terminate the subcontract with the subcontractor if within three days of
receiving the notice required pursuant to this section the subcontractor
does not cease employing or contracting with the illegal alien; except that
Contractor shall not terminate the contract with the subcontractor if during
such three days the subcontractor provides information to establish that
the subcontractor has not knowingly employed or contracted with an illegal
alien.
F. Contractor shall comply with any reasonable request by the Colorado
Department of Labor and Employment (the "Department") made in the course
of an investigation that the Department undertakes or is undertaking pursuant
to the authority established in Subsection 8-17.5-102 (5), C.R.S.
G. If Contractor violates any provision of this Agreement pertaining to the duties
imposed by Subsection 8-17.5-102, C.R.S. the City may terminate this
Agreement. If this Agreement is so terminated, Contractor shall be liable for
actual and consequential damages to the City arising out of Contractor's
violation of Subsection 8-17.5-102, C.R.S.
H. The City will notify the Office of the Secretary of State if Contractor violates
this provision of this Agreement and the City terminates the Agreement for
such breach.
SA 09/01/06
29
Packaged Pumping System Quotation
STANDARD MECHANICAL FEATURES INCLUDE:
1 Structural steel skid with "diamond" plate decking; continuous welds.
1 Wet well access hatch.
1 Steel pump mounting plate.
1 Schedule 40 piping and fittings.
1 Two (2) drains x 3/4-inch with one (1) hose bib.
1 Steel grit blasted to near white metal finish before the application of protective coatings.
1 Multi -Step Coating System — fast dry multi -purpose epoxy base coat and gloss aliphatic
polyurethane finish coat; amine -cured coal -tar epoxy applied to the underside of the skid for
corrosion resistance to moisture from the wet well.
1 Meter Run - 5 / 2 pipe diameters in length in accordance with the flow meter manufacturer's
recommendation for optimal accuracy.
1 Station Pressure Relief Valve - isolation valve on the inlet side; discharge piped to the wet well.
1 Station Discharge Isolation Valve - lug style butterfly valve with lever operator and locking plate.
1 Spare Parts: packing for the main vertical turbine pumps and touch-up paint.
STANDARD ELECTRICAL FEATURES INCLUDE:
1 PLC based controls with non-volatile memory, line side fuses, PLC by-pass, and 256-event log.
1 Operator Interface Device (OID) — facilitates operation and monitoring of the pumping system;
features a large, high contrast display for excellent readability.
1 Control Power Transformer (CPT) — steps the voltage down for the control circuit components.
1 Lightning / Surge Arrestor — rated for categories "B" and "C".
1 Alarm Pilot Devices.
1 Hand -Off -Auto (HOA) Selector Switch — for the system.
1 On -Off Selector Switches — one (1) for each pump in the system.
1 General Fault Light — red, identifying information displayed on the OID.
1 Pump Run Lights — green; one (1) for each pump in the system.
1 Reset — acknowledges pumping station alarms, silences horn, and lamp test.
1 Low Discharge Pressure Override — through the OID; disables low discharge pressure alarm.
1 Elapsed Time Meters — in the PLC; one (1) for each pump in the system.
1 Speed Potentiometer — in system manual mode allows the operator to adjust the VFD pump
speed.
1 Pressure Transducer — 0 to 300 PSI; stainless steel wetted components; ±.2% accuracy; 4-20
mAmp output signal; loop powered device.
1 Printer Port — RS-232 connection.
1 Power Control Monitor — low voltage, phase imbalance, etc.
1 Discharge Pressure Gauge — liquid filled; 2-1/2" diameter; isolation valve; panel mounted with
flexible connection to the sensing point.
1 Control panel manufactured and labeled per U.L. 508 Industrial Control Equipment standards.
ADDITIONAL FEATURES INCLUDE:
2 50 HP, 1770 RPM, variable frequency drive (VFD) vertical turbine pump. Requires a net positive
suction head of 15-feet to meet design performance of 500 GPM @ 138 PSI to account for static
lift and frictional losses on the skid. Wafer style silent check valve, isolation butterfly valve, and
premium efficiency vertical hollow -shaft motor with WPI enclosure and NRR provided.
1 3 HP, 3450 RPM, across -the -line start submersible pressure maintenance pump. 40 GPM @ 138
PSI to account for static lift and frictional losses on the skid. Wafer style silent check valve,
isolation butterfly valve, and submersible motor provided.
Page 2, December 4, 2005 Quotation No. 20061211
EXHIBIT B
INSURANCE REQUIREMENTS
1. The Service Provider will provide, from insurance companies acceptable to the City, the
insurance coverage designated hereinafter and pay all costs. Before commencing work under this
bid, the Service Provider shall furnish the City with certificates of insurance showing the type,
amount, class of operations covered, effective dates and date of expiration of policies, and
containing substantially the following statement:
"The insurance evidenced by this Certificate will not be cancelled or materially altered,
except after ten (10) days written notice has been received by the City of Fort Collins."
In case of the breach of any provision of the Insurance Requirements, the City, at its option, may
take out and maintain, at the expense of the Service Provider, such insurance as the City may
deem proper and may deduct the cost of such insurance from any monies which may be due or
become due the Service Provider under this Agreement. The City, its officers, agents and
employees shall be named as additional insureds on the Service Provider's general liability and
automobile liability insurance policies for any claims arising out of work performed under this
Agreement.
2. Insurance coverages shall be as follows:
A. Workers' Compensation & Employer's Liability. The Service Provider shall maintain
during the life of this Agreement for all of the Service Provider's employees engaged in work
performed under this agreement:
Workers' Compensation insurance with statutory limits as required by
Colorado law.
2. Employer's Liability insurance with limits of $100,000 per accident, $500,000
disease aggregate, and $100,000 disease each employee.
B. Commercial General & Vehicle Liability. The Service Provider shall maintain during
the life of this Agreement such commercial general liability and automobile liability insurance
as will provide coverage for damage claims of personal injury, including accidental death, as
well as for claims for property damage, which may arise directly or indirectly from the
performance of work under this Agreement. Coverage for property damage shall be on a
"broad form" basis. The amount of insurance for each coverage, Commercial General and
Vehicle, shall not be less than $500,000 combined single limits for bodily injury and property
damage.
In the event any work is performed by a subcontractor, the Service Provider shall be
responsible for any liability directly or indirectly arising out of the work performed underthis
Agreement by a subcontractor, which liability is not covered by the subcontractors
insurance.
SA 09/01/06
31
—
Packaged Pumping System Quotation
1
IRR
Pump station is designed for use in a turf irrigation application; method of operation
and automatic sequencing functions are in accordance with Metron's standards.
1
VFD
Variable Frequency Drive - with DC choke for harmonic mitigation; modulates the
speed of the main pump motors.
1
N12HX
NEMA 12 Electrical Enclosure - with through the door disconnect and heat
exchanger for cabinet cooling.
1
BP50
VFD By -Pass Switch — enables the station to operate if the VFD is not operative.
1
PM
Phase Monitor — protects three-phase equipment against phase loss, under voltage,
and phase reversal; when fault is sensed the monitor output relay opens to turn the
equipment off and/or cause an alarm; automatic reset; LED indicator light.
1
AA
Automatic Alternation — balances the run time on each of the main pumps.
1
SQS50/50
Sequential Start— of the main pumps with lead / lag option.
1
SUBTROL
Subtrol submersible motor protection.
1
SFAF/TDP
Skid Filter Auto -Flush - time and differential pressure cycling.
1
AIR RLS
Air Release Valve — located on the pump discharge manifold; automatic float
operated valve designed to release accumulated air from a piping system while the
system is in operation and under pressure; cast iron body; stainless steel trim and
float; synthetic seating.
1
2LCF
2-point level control for the wet well.
1
TRANS
Upgraded pressure transducer
1
MM
Badger Magnetic Flow Meter - display of flow rate and total flow is through the
Operator Interface Device (OID).
1
PLC
5 year PLC warranty
1
BN
Buna N seats for check valves
1
FILT
Automatic skid mounted filter.
1
POWER
120 Volt, 5 amp (to be confirmed) power supply for Niad equipment
1
HEAT
Heater for pump system
1
COMM
Wireless communication between pump station and Rainbird control system.
Includes radio and Comm Box.
1
PVC
PVC shroud for PMP.
1
MAN
Manual/Auto selector switch for VFD
1
UL
Packaged Pumping Skid and Control Panel are U.L. listed.
Selling Price for each Packaged Pumping System
$ 71,782.00
Recommended adders and deducts
1. Remove heater for pump system scope of supply.
($ 625.00)
2. Upgrade system filter to an automatic scanner suction filter which is likely the best filtration fit for this
application. (Note: Price is per pump system) $ 3,019.00
3. Provide skid filter flush piping back to lake or drain up to 50 Feet away, buried 6" underground. To be
fabricated of schedule 40 steel pipe. Note: This will require utility notification and desired location prior to
beginning of work. $ x,xxx.00
Price to be provided for filter flush piping based on time and materials since there is currently no
specific scope of supply
COMMODITY METAL PRICE DISCLAIMER
Page 3, December 4, 2005 Quotation No. 20061211
Packaged Pumping System Quotation
Due to highly unstable commodity metal prices related to factors beyond our control, Metron is
unable to hold our prices firm for longer than 10 days. We are making every effort to minimize the
impact of such variations and appreciate your understanding. Orders placed later than 10 days
after quotation are subject to a price revision based on most current metal commodity pricing.
The selling price includes freight to the installation site in Fort Collins. COo, but does not include
the cost for on -site delays.
The selling price includes off-loading the pumping station
The selling price includes installation.
The selling price one day of start-up assistance and customer training.
The selling price includes four (4) copies of Submittals.
The selling price includes two (2) bound O & M manuals.
All Metron stations are supported by unlimited access to 24-hour product technical telephone support and
local factory authorized service centers.
EXTENDED WARRANTY — Metron , Inc., offers an extended five (5) year prorated limited warranty and
maintenance contract for packaged pump systems of our own manufacture. The extended limited
warranty provides protection against defects in material and workmanship. The coverage includes
replacement parts, labor, travel expenses, and labor to remove/reinstall defective material. Please
contact Metron to for additional information regarding this extended warranty.
Signed:
Kris Hulse
Applications Engineer
Please help us expedite your order by providing the following information:
Is this sale taxable? (Circle one) Yes No
If the sale is non taxable, a tax exemption certificate for the "ship to" state must be submitted with your purchase
order.
I agree to the scope, terms, and conditions as described in this quotation.
Price Total $
Signed:
Title:
Billing Entity and Address:
(to reflect selections)
Dated:
Page 4, December 4, 2005 Quotation No. 20061211
Packaged_ Pumping System Quotation
Contact Phone Number:
Please return one (1) signed copy of this quotation on acceptance. Merchandise delivered or shipped is
due and payable to: Metron, Inc., 1605 West 3rd Ave., Denver, Colorado U.S.A., 80223. Phone: (303) 592-
1903 Fax: (303) 534-1947
Page 5, December 4, 2005 Quotation No. 20061211
r Packaged Pumping System
Terms and Conditions of Sale
CONDITIONS
1. This quotation is valid for ten (10) days from the date on the quotation, due to the cost fluctuation on
commodity steel, unless extended in writing by the manufacturer, Metron, Inc.
2. This Quotation does not include any applicable taxes, tariffs, permits, license fees, and/or duties unless
specifically stated they are elsewhere in this Quotation. These items are the responsibility of the
Contractor/Owner.
3. Off-loading and installation of the Goods are not included in the selling price unless specifically
stated otherwise in this Quotation.
4. Installation shall conform to the instructions in the IOM Manual.
5. It is the responsibility of the Contractor/Owner to provide the electrical hook-up to the Electrical Panel of the
Pumping System.
Note: Do NOT bump the motors. Manufacturer's representative will do this during start-up.
6. It is the responsibility of the Contractor/Owner to make the final connection to the suction and outlet pipes of
the Pumping System.
7. It is the responsibility of the Contractor/Owner to anchor the skid to the concrete pad. Anchor bolts are not
included in the selling price, they are responsibility of the Contractor/Owner,
6. Two (2) copies of Submittals will be sent to the Contractor/Owner no later than twenty-one (21) working
days after the manufacturer receives the Purchase Order.
9. The Packaged Pumping System is normally ready to ship within 6-12 weeks after the manufacturer, Metron,
Inc., receives the approved Submittal and release to production. The delivery date shall be confirmed after
release.
10. Contractor/Owner shall coordinate the location of the roof access hatch over all of the pumps so they can
be removed when necessary.
11. Service, Training, Technical Support, and Warranty help is available from the manufacturer any time.
Page 6, December 4, 2005 Quotation No. 20061211
Packaged Pumping System
Terms and Conditions of Sale
Metron, Inc. (the "Seller") and the company or individual named on the face of this invoice (the "Buyer") agree to the following terms and conditions:
1. NONCONFORMING TERMS. No terms contained in any purchase order or other document received from the Buyer, either prior or subsequent to the date of this
invoice, shall be binding upon the Seller unless expressly accepted in writing by an authorized representative of the Seller.
2. TAXES. Except as otherwise provided on the face of this invoice, the price does not include federal, state or local taxes which may be payable with respect to the
manufacture, sale or delivery or use of the goods. The Buyer agrees to pay all such taxes.
3. SHIPMENT. All prices are F. O. B. Seller's factory, Denver, Colorado, prepay and add. The Seller reserves the right, in its sole discretion, to determine the method
and route of shipment. The Buyer assumes the risk of loss or damage upon delivery of the goods to the carver at point of shipment.
4. PAYMENT PERMS. Unless otherwise specified by the Seller in writing, the terms of payment shall be 50% with purchase order and prior to procurement of
materials, 50% prior to shipment. The Seller reserves the right at any time and in its sole discretion to require payment in full in advance or C.O.D. or to otherwise
modify the payment terms. Past due amounts shall bear interest at the rate of 18% per annum or the highest rate permitted by law, whichever is less. For business
outside the U. S., and irrevocable confirmed letter of credit for 100% of the project's value is required before production will commence.
5. MINIMUM BILLING. All orders of $50.00 net or less will be invoices at the minimum rate ($50.00 net) with transportation charges added.
6. DELIVERY. Delivery dates are not guarantied and are based on normal expectancies only. In no event shall the Seller be liable for any failure or delay in delivery
due to fire, flood, accident, civil unrest, acts of God, war, governmental interference or embargoes, strikes, labor difficulties, shortage of labor, fuel, power or
materials or any cause beyond its reasonable control. Quoted deliveries are based on conditions at the time of the quote and are subject to product availability at time
of the approved purchase order and approval of submittals with release to production by Seller.
If Buyer is unwilling to accept delivery on the mutually agreed upon date at the time of the sale, then the delivery shall be considered as complete at Seller's factory
for purposes of billing and payment, transfer of ownership, risk of loss or damage, and insurance responsibility. Buyer is responsible for any additional costs
incurred for storage and handling, with a minimum cost of $500.00.
7. CANCELLATION AND CHANGE. Orders are subject to cancellation, partial cancellation or change only with the consent of the Seller and only upon such terms
as the Seller may impose. Prices are set on the basis of the total quantity ordered, even though shipment may be in stages. Cancellation of a portion of an order after
an earlier portion has been shipped and invoiced will result in an adjustment to the purchase price and an additional charge to the Buyer.
8. LIMITED WARRANTY. Seller's Limited Warranty is valid only with a Metron, Inc. Installation, Start-up and Training Commencement Certificate that has been
signed off by Seller's certified Service Representative and registered with the Seller. The Seller warrants that all goods manufactured and sold by it are and will be
free from defects in materials and workmanship for a period of one year from the initial operation not to exceed 18 months from the date of shipment, whichever
comes fast. Goods which are found defective will be replaced or repaired, at the option of the Seller. The Seller shall be under no obligation to the Buyer if the
goods have not been used under normal operating conditions or have been altered, modified or repaired without the Seller's prior written consent. The Seller shall
also be under no obligation to the Buyer if the goods have been subjected to carelessness or abuse, not used in accordance with Metron's recommendations or
industry standards, or not used for intended purposes. Seller is not responsible for the design or repercussions of a faulty design or specification of auxiliary
equipment, pipe, pipe thmst block, building, building foundation, leveling of skid, anchoring of skid, soil compaction, environmental control (ambient temperature
should be maintained between 40-100 degrees Fahrenheit), ventilation, drainage or any other components that are not part of the packaged system. Furthermore,
Seller is not responsible for damage to equipment by forces outside of our control such a acts of nature, vandalism, faulty installation, or inadequate support
equipment. In no event will the Seller be liable for consequential or special damages or for transportation, installation, adjustment or other expenses which the Buyer
may incur in exercising its right under this limited warranty. THIS WARRANTY IS EXPRESSLY MADE IN LIEU OF ANY AND ALL OTHER
WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
USE OR PURPOSE.
9. DEFECTIVE GOODS AND TESTING. If the Buyer believes that goods purchased from the Seller are defective, it must notify the Seller immediately in writing.
The goods shall not be returned to the Seller without the prior written authorization of the Seller. If the Buyer wishes to conduct tests to determine whether the goods
are conforming, it must notify the Seller prior to conducting the tests, endeavor to reach agreement with the Seller on testing procedures and provide the Seller with
an opportunity to witness such tests.
10. INFRINGEMENT. The Seller agrees to defend any suit brought against the Buyer to the extent that such suit is based on a claim that the goods, or any part thereof,
in the particular form sold by the Seller, infringe a United States patent, provided such goods were not manufactured by the Seller pursuant to designs or
specifications furnished by the Buyer, but only on condition that the Buyer shall promptly notify the Seller in writing of any such claim, shall give the Seller full
authority for the conduct of such and shall render to the Seller whatever information and assistance may be reasonably required for such defense. Subject to such
conditions, the Seller shall pay damages and costs, if any, awarded against the Buyer in such suit and in the event the goods are held to infringe and the use of the
goods is enjoined, the Seller shall have the option of procuring for the Buyer the right to continue using the goods, replacing the goods with noninfringing product,
modifying the goods so as to avoid infringement or removing the goods and refunding the purchase price. The Seller shall have no further liability for patent
infringement. The Buyer agrees to indemnify and hold the Seller harmless from and against all claims, liability, loss, damage, including attorney fees, arising from
or related in any way to any actual or claimed patent, trademark or copyright infringement involving goods manufactured by the Seller pursuant to designs or
specifications furnished by the Buyer.
11. COMPLIANCE WITH LAW. The Seller agrees that in manufacturing, selling and delivering the goods it has complied with all applicable laws and governmental
regulations, including the provisions of the Fair Labor Standards Act of 1938.
12. GOVERNMENT CONTRACTS AND SUBCONTRACTS. If a government contract number appears on the face of this invoice, clauses contained in the Armed
Services Procurement Regulations of the Federal Acquisition Regulations which the government requires be included in subcontracts to which the contractor is a
party shall be incorporated in this invoice by reference.
13. DEFAULT. In the event the Buyer fails to make payment in the amounts and at the time required by the Seller pursuant to this invoice or is in default under any
other provisions of this invoice or any sales order, invoice or other agreement between the Buyer and the Seller, or in the event of any proceedings, voluntary, in
bankruptcy or insolvency by or against the Buyer, the inability of the Buyer to meet its debts as they come due or the appointment, with or without the Buyer's
consent, of an assignee for the benefit of creditors or a receiver, then the Seller shall have the right, in addition to all the other rights it may possess at any time, to
withhold shipments, in whole or in part, and to recall goods in transit, retake same and repossess all goods which may be stored with the Seller for the Buyer's
account, without the necessity of instituting any other proceedings. The Buyer agrees that all goods so recalled, retaken of repossessed shall become the absolute
property of the Seller, provided that the Buyer is given full credit therefor. The Seller shall also have all of the rights and remedies available to it under the Uniform
Commercial Codes and other laws in effect.
14. WAIVER. No waiver of any provision of this invoice by the Seller shall be valid unless in writing and signed by an authorized representative of the Seller. No delay
on the part of the Seller in exercising any right of remedy available to it shall be valid unless in writing and signed by an authorized representative of the Seller. No
delay on the part of the Seller in exercising any right or remedy available to it shall operate as a waiver of such right or remedy.
15. GOVERNING LAW. This invoice shall be governed by the laws of the State of Colorado.
Metron, Inc. is an Equal Opportunity Employer as required by Executive Order 11246, as amended.
Page 7, December 4, 2005 Quotation No. 20061211