Loading...
HomeMy WebLinkAboutLANDINGS PUD FOURTH SECOND REPLAT - Filed GR-GEOTECHNICAL REPORT/SOILS REPORT -REPORT OF A GEOTECHNICAU INVESTIGATION FOR THE JETTY FORT COLLINS, COLORADO FAI RFIELD HOMES LAKEWOOD, COLORADO PROJECT NO. 8045-89 BY EMPIRE LABORATORIES, INC. 301 NORTH HOMES STREET FORT COLLINS, COLORADO 80521 TABLE OF CONTENTS Table of Contents .............................................. i Letter of Transmittal ........ • • .............. ............ ...... 1 Report .......................................................... A-1 Appendix A ..... ..... ..... Test Boring Location Plan .................................... A-2 A-3 Key to Borings ................................................ A-4 Log of Borings ............................................... B-1 Appendix B.................................. .................. B-2 Consolidation Test Data ... • ... B-3 Hveem Stabilometer Data ..................................... Summary of Test Results ..................... ....... • • • • • • • • B-4 C-1 Appendix C ........ Empire Laboratories, Inc. GEOTECHNICAL ENGINEERING 8 MATERIALS TESTING June 9, 1989 Fairfield Homes 2618 Deframe Circle Lakewood, Colorado 80228 Attention: Mr. Ken Slyziuk Gentlemen: CORPORATE OFFICE P.O. Box 503 a (303) 464-0359 301 No. Howes • Fort Collins, Colorado 80522 We are pleased to submit our Report of a Geotechnical Investigation pre- pared for the proposed residential development, located at the Northeast corner of Landings and Boardwalk Drives, Fort Collins, Colorado. Based upon our findings in the subsurface, it is our opinion the site is suitable -for the proposed construction, providing the design criteria and recommendations set forth in this report are met. The accompanying report presents our findings in the subsurface and our recommendations based upon these findings. Very truly yours, EMPIRE LABORATOR INC. Alf Neil R. S lerrod Senior Engineering Geologist Reviewed by. - Chester C. Smith, P.E. President t/s Branch Orykes C. 9 V, ERA 1 P.O. Box 16859 P.O. Boa 1135 P.O. Boss 1744 Colorado Springs, CO 80935 Longmont, CO 80502 Greeley, CO 80632 719) 597.2116 (303) 776.3921 (3031 151.0460 Member of Consul)ing Engineers Cow P.O. Box 5659 Cheyenne. WY 82003 307) 632-9224 REPORT OF A GEOTECHNICAL INVESTIGATION SCOPE This report presents the results of a geotechnical evaluation prepared for the proposed residential development located at the northeast corner of Landings and Boardwalk Drives in south Fort Collins, Colorado. The investigation included test borings and laboratory testing of samples obtained from these borings. The objectives of this study were to (1) evaluate the subsurface conditions at the site relative to the proposed construction, (2) make recommendations regarding the design of the substructures, (3) recommend certain precautions which should be taken because of adverse soil and/or ground water conditions, and (4) make recommendations regarding pavement types and thicknesses for the proposed streets to be constructed at the site. SITE EXPLORATION The field exploration, carried out on June 5, 1989, consisted of drilling, logging, and sampling five (5) test borings. The test borings were located by Empire Laboratories, Inc. from the existing street intersections using conventional chaining methods. The locations of the test borings are shown on the Test Boring Location Plan included in Appendix A of this report. Boring logs prepared from the field logs are shown in Appendix A. These logs show soils encountered, location of sampling, and ground water at the time of the exploration. The borings were advanced with a four -inch diameter, continuous - type, power -flight auger drill. During the drilling operations, a geotechnical engineer from Empire Laboratories, Inc. was present and made continuous observations of the soils encountered. SITE LOCATION AND DESCRIPTION The site is located at the northeast corner of Boardwalk and Landings Drives in south Fort Collins, Colorado. More particularly, the site is described as The Jetty, a subdivision situate in the Southwest 1 /4 of Section 36, Township 7 North, Range 69 West of the Sixth P.M., City of Fort Collins, Larimer County, Colorado. The site consists of a vacant tract of land 'vegetated with grass and, weeds. The property is relatively flat to gently rolling and has positive drainage to the north-northwest toward the Larimer County Canal, which forms the north boundary of the site. A narrow ridge, approximately ten (10) to twenty (20) feet wide and three (3) to five (5) feet high, parallels Boardwalk and Landings Drives. The canal at the north edge of the site is approximately ten (10) feet deep. LABORATORY TESTS AND EVALUATION Samples obtained from the test borings were subjected to testing in the laboratory to provide a sound basis for evaluating the physical properties of the soils encountered. Moisture contents, dry unit weights, unconfined compressive strengths, water soluble sulfates, sulfides, pH, resistivity, oxidation-reduction potential, swelling potentials, and the .Atterberg limits were determined. A summary of the test results is included in Appendix B. Swell -consolidation and Hveem stabilometer characteristics were also determined, and curves showing this data are included in Appendix B. SOIL AND GROUND WATER CONDITIONS The soil _ profile at the site consists of strata of materials arranged in different combinations. In order of increasing depths, they are as follows: 1) Silty Topsoil: The area tested is overlain by a six (6) inch layer of silty topsoil. The topsoil has been penetrated by root a growth and organic matter and should not be used as a bearing soil or as a fill and/or backfill material. 2) Silty Clay: This stratum underlies the topsoil and extends to the sandy gravelly silty clay and/or the bedrock below. The silty clay is moderately to highly plastic,' is dry to damp and exhibits moderate bearing characteristics. When wetted, the clay stratum exhibits high swell potential; and upon loading, minor consolidation occurs. 3) Sandy Gravelly Silty Clay: This stratum was encountered below the upper clay in Boring 5 at a depth of three (3) feet below the surface and extends to greater depths. The silty clay is plastic, contains varying amounts of sand and/or gravel and exhibits moderate bearing characteristics in its dry natural condition. 4) Claystone-Siltstone Bedrock: The bedrock was encountered in all borings at depths of one and one-half (1-1/2) to seven and one-half (7-1 /2) feet below the surface and extends to greater depths. The upper one and one-half (1 -1/2) to two and one-half (2-1 /2) feet of the bedrock is highly weathered; however, the underlying claystone interbedded with siltstone is firm and exhibits high bearing characteristics. When wetted, the claystone and Siltstone bedrock exhibits high swell potential. 5) Ground Water: Three days after drilling, no free ground water was encountered at the site to the depths explored. Water levels in this area are subject to change due to seasonal variations and irrigation demands on and/or adjacent to the site. In addition, it is our opinion that surface water may percolate through the upper subsoils and become trapped on the relatively impervious bedrock, forming a perched ground water condition. 3- RECOMMENDATIONS AND DISCUSSION It is our understanding that single-family residences are to be constructed at the site. The residences will be served by a local residenti a street. Site Grading, Excavation and Utilities Specifications pertaining to site grading are included below and in Appendix C of this report. It is recommended that the upper six (6) ' inches of topsoil sbelow building, filled and paved areas be stripped and stockpiled for reuse in planted areas. The upper six (6) inches of the subgrade below building, paved and filled areas should be scarified and recompacted two percent (2%) wet of optimum moisture to at least ninety-five percent (95%) of Standard Proctor Density ASTM D 698-78. See Appendix C.) Fill should consist of the on -site soils oe imported - granular material approved by the geotechnical engineer. Fill should be placed in uniform six (6) to eight (8) inch lifts and mechanically compacted two percent (2%) wet of optimum moisture to at least ninety =five percent (9.5%) of Standard Proctor Density ASTM D 698-18. For stability, cut and fill slopes should be designed on grades no steeper than 3:1. Bedrock encountered at the site may be used as fill material in selected areas. Heavy-duty construction equipment equivalent to a D-8 tractor and/or track mounted excavator having a gross weight of ninety thousand (90,000) pounds may be needed to excavate the firm bedrock, and bedrock used as fill should be broken into pieces less than six (6) inches in diameter. Proper placement of the bedrock as fill may be difficult, and a' disc or other mixing equipment may be needed to obtain uniform moisture and proper compaction. The bedrock should be used in open and planted areas or in the lower portion. of fill below paved areas. In computing earthwork quantities, an estimated shrinkage factor of eighteen percent (18%) to twenty-three percent (23%) may be used for the on -site clays compacted to the above -recommended density. All excavations should be dug on safe and stable slopes. It is suggested that excavated soil slopes be on minimum grades of 1-1 /2:1 or. 4- flatter, Firm bedrock may be excavated on near -vertical slopes. The slope of the sides of the excavations should comply with local codes or_: OSHA regulations. The side slopes of the excavation should be maintained under safe conditions until completion of backfilling. In addition, heavy construction equipment should be kept a safe distance from the edge of the excavation. Where utilities are excavated below ground water, dewatering will be needed during placement of pipe and backfilling for proper construction. All piping should be adequately bedded for proper load distribution. Backfill placed in utility trenches in open and planted areas should be compacted in uniform lifts at optimum moisture to at least ninety percent 90%) of Standard Proctor Density ASTM D 698-78 the full depth of the trench. The upper four (4) feet of backfill placed in utility trenches under roadways and paved areas should be compacted at or near optimum moisture to at least ninety-five percent (95%) of Standard Proctor Density ASTM D 698-78, and the lower portion of these trenches should be compacted to at least ninety percent (90%) of Standard Proctor Density ASTM D 698-78. Addition of moisture to and/or drying of the subsoils may be needed for proper compaction. Proper placement of the bedrock as backfill may be difficult. Stripping, grubbing, subgrade preparation, and fill and backfill placement should be accomplished under continuous observation of the geotechnical engineer. Field density tests should be taken daily in the compacted subgrade, fill, and backfill under the. direction of the geotechnical engineer. Laboratory resistivity tests, pH, oxidation-reduction and sulfide tests performed in the laboratory indicate that the subsoils at the site are slightly corrosive, and protection of metal utility pipe, in our opinion, should be considered. Foundations In view of the loads transmitted by the proposed residential construction and the soil conditions encountered at the site, it is recommended that the structure be supported by a drilled -pier MMI foundation system. Using this type of foundation system, the structure is supported by piers drilled into the bedrock stratum and structural grade beams spanning the piers. Piers should be straight -shaft and should be drilled within plumb tolerances of one and one-half percent 1-1 /2%) relative to the length of the pier. The piers are supported by the bedrock stratum partially through end bearing and partially through skin friction. It is recommended that all piers have minimum ten (10) foot lengths and that they be drilled a minimum of three, (3) feet into the firm bedrock stratum. Piers founded at the above level may be designed for a maximum allowable end bearing pressure of fifteen thousand (15,000) pounds per square foot. It is estimated that a skin friction of one thousand five hundred (1500) pounds per square foot will be developed for that portion of the pier embedded three (3) feet into the firm bedrock stratum. To counteract swelling pressures which will develop if the subsoils become wetted, all piers should be designed for a minimum dead load of seven thousand five hundred (7500) pounds per square foot. Where this minimum dead load requirement cannot be satisfied, it is recommended that skin friction from additional embedment into the firm bedrock be used to resist uplift. To help provide the required skin friction, the sides of the pier drilled into the bedrock stratum should be. roughened. All piers should be reinforced their full length to resist tensile stresses created by swelling pressures acting on the pier. It is recommended that all grade beams have a minimum four 4) inch void between the bottom of the beam and the soil below. The predicted settlement under the above maximum loading should be negligible. Drilled piers should be designed to resist all induced lateral forces. It is recommended all piers should have minimum ten (10) inch diameters. it is strongly recommended that: the geotechnical engineer be present during the drilling operations to (1) identify the firm bedrock stratum, (2) assure that proper penetration is obtained into the sound bedrock stratum, (3) ascertain that all drill holes are thoroughly roughened, cleaned and dewatered prior to placement of any foundation concrete, (4) check all drill holes to assure that they are plumb and of 4- the proper diameter, and (5) ensure proper placement of concrete and reinforcement. Basements, Dewatering Systems and Slabs on Grade Since no free ground water was encountered at the site to the depths explored, it is our opinion the proposed basement construction is feasible. However, since the potential for a perched water table- to develop on top of the bedrock exists at the site, it is recommended that all structures founded in or within three (3) feet of the bedrock stratum be provided with a complete dewatering system. Basements should be excavated on safe and stable slopes as discussed in the "Site Grading, Excavation and Utilities" section of this report. The dewatering system should contain a four (4) inch diameter perforated pipe, underslab gravel, a sump and pump, and/or other suitable drain outlet. The perforated pipe should be placed around the entire perimeter of the lower basement area or any portions of the structure placed in or within three (3) feet of the bedrock stratum. All piping in the perimeter trench should be surrounded by clean, graded gravel' from three -fourths (3/4) inch to the #4 sieve in accordance with ASTM C 33-78, Size No. 67. The gravel should extend from at least three (3) inches below the. bottom of the pipe to a minimum of two (2) feet above the bedrock above the pipe, the full width of the trench. To minimize the cost of gravel backfil.l, it is suggested that the excavation be limited to the area necessary for construction; however, the trench should be a minimum of twelve (12) to eighteen (18) inches wide. The top of the gravel backfill adjacent to foundation walls should be covered with an untreated building paper to help minimize clogging of the medium with earth backfill. To minimize the potential for surface water to enter the system, it is recommended that a clay backfill be placed over the system and compacted at or near optimum moisture to at least ninety percent (90%) of Standard Proctor. Density ASTM D 698-78. (See Appendix C.) We recommend that the drainage pipe be placed at least one (1) foot below finished slab and have a minimum grade of one -eighth 1 /8) inch per foot. All lower level slabs surrounded by perimeter 7- drains should be underlain by a minimum of eight (8) inches of clean, graded gravel or crushed rock devoid of fines. The drainage system should empty into a sewer underdrain or storm drain adequately sized to accept the anticipated flows at the site, or the water from the dr an should empty into a sump provided in the lower basement area. The sump should be a minimum of eighteen (18) inches in diameter and three 3) feet deep. A minimum of one (1) foot of clean, graded gravel meeting the above specifications should be placed adjacent to the bottom and sides of the sump. The sump should be provided with a pump designed to discharge all flow to the sump. Water from the sump should be pumped into an adequate storm drain or sewer underdrain. Due to the swelling pressures exerted by the materials at subgrade, it is our opinion that the only pi)sitive solution for construction of the sla b where movement will not occur is a structural floor with a void beneath it. However, the cost of this ty pe of system may be prohibitive. It is our opinion that, with certain precautions and knowing that some` - risk is involved, a floating floor slab may be a reasonable alternative. If -the owner is willing to assume the risk of future slab movement and. related structural damage, the following recommendations may reduce slab movement and its adverse effects. Subgrade below slabs on grade at the upper level should be prepared in accordance with the recommendations .discussed in the "Site Grading, Excavation and Utilities" section of this report. If the subgrade below slabs on grade is allowed to cfry below the required moisture, the subgrade should be rescarified and recompacted to two percent (2%) wet of optimum moisture to the required density just prior to placement of underslab gravel and concrete. Slabs on grade at the upper level should be underlain by a minimum, of four (4) inches of clean, graded gravel or crushed rock devoid of fines. Slabs surrounded by perimeter drains should be underlain by a minimum of eight. (8) inches of clean, graded gravel or crushed rock devoid of fines. Garage slabs should be. reinforced with wire mesh running through the control joints. Slabs on: grade should be designed and constructed structurally independent of bearing members. Ma To minimize and control shrinkage cracks which may develop in slabs on grade, we suggest that control joints be placed every fifteen (15) to twenty (20) feet and that the total area contained within these joints be no greater than four hundred (400) square feet. In addition, if building construction is done during winter months, it is recommended. that slabs on grade not be placed on frozen ground and that they be protected from freezing temperatures until they are properly cured. We further recommend that nonbearing partitions placed on floor slabs be provided with a slip joint (either top or bottom). Slip joints reduce pressure applied by heaving floor slabs and thus minimize damage to the portion of the structure above. It is emphasized that if the subsoils are kept dry, movement of slabs on grade should be minimal. However, if moisture is permitted to reach the subsoils •below the slabs., heaving will probably occur. Pavement It is our opinion that flexible pavement is suitable for the proposed street construction at the site. A flexible pavement alternate should consist of asphalt concrete underlain by crushed aggregate base course and subbase or asphalt concrete underlain by plant mix bituminous base course. Using the City of Fort Collins "Design Criteria and Standards for Streets". dated July 1986, a serviceability index of 2, a regional factor of 1, an. "R" value of 5, a twenty (20) year design life, eighteen 18) kip equivalent daily load applications of 5 for the majority of the street area and 10 for the entrance portion of the street area, and weighted structural numbers of 2.35 and 2.65, respectively, the following minimum pavement thicknesses are recommended: Maiority of Street Asphalt Concrete 3" Crushed Aggregate Base Course 4" Select Subbase 6" Total Pavement Thickness 13" . 9- To minimize and control shrinkage cracks which may develop in slabs on grade, we suggest that control joints be placed every fifteen (15) to twenty (20) feet and that. the total area contained within these joints be no greater than four hundred (400) square feet. In addition, if building construction is done during winter months, it is recommended that slabs on grade not be placed on frozen ground and that they be protected from freezing temperatures until they are properly cured. We further recommend that nonbearing partitions placed on floor slabs be provided with a slip joint (either top or bottom). Slip joints reduce pressure applied by heaving floor slabs and thus minimize damage to the portion of the structure above. It is emphasized that if the subsoils are kept dry, movement of slabs on grade should be minimal. However, if moisture is permitted to reach the subsoils below the slabs, heaving will probably occur. Pavement It is our opinion that flexible pavement is suitable for the proposed street construction at the site.. A flexible pavement alternate should consist of. asphalt concrete underlain by crushed aggregate base course and subbase or asphalt concrete underlain by plant mix bituminous base course. Using the City of Fort Collins "Design Criteria and Standards for Streets" dated July 1986, a serviceability index of 2, a regional factor of 1 , an "R" value of 5, a twenty (20) year design life, eighteen 18) kip equivalent daily load applications of 5 for the majority of the street area and 10 for the entrance portion of the street area, and weighted structural numbers of 2.35 and 2.65, respectively, the following minimum pavement thicknesses are recommended: Maioritv of Street Asphalt Concrete 3" Crushed Aggregate Base Course 4" Select Subbase 6" Total Pavement Thickness 13" 9- Asphalt Concrete 2" Plant Mix Bituminous Base Course 41 ' Total Pavement Thickness 6J" Entrance Portion of Street , Asphalt Concrete 3" Crushed Aggregate Base Course 4" Select Subbase 9" Total Pavement Thickness 16" Asphalt Concrete 2" Plant Mix Bituminous Base Course 5" Total Pavement Thickness 7" The select subbase should meet City. of Fort Collins Class 1 specifications, and the crushed aggregate base course should meet City of Fort Collins Class 5 or 6 specifications. The subgrade below the proposed asphalt pavement should be prepared in accordance with the recommendations discussed in the "Site Grading, Excavation and Utilities" section of this report. It is extremely important that the subgrade be at or slightly wet of optimum moisture just prior to placement of the pavement to minimize swell potential of the clay soil. Due to the plastic nature of the clay soils at the site, consideration should - be given to reducing the plasticity and swell potential of the soil by stabilizing the subgrade with lime, fly ash or kiln dust. This will reduce the potential for swelling of the subgrade and may increase the life of the pavement structure. Use of the stabilizing material may also increase the "R" value characteristics of the subgrade allowing for reduction in the pavement section. Additional laboratory tests will be required to determine the "R" value characteristics if stabilization is utilized. Finished subgrade below pavement sections should be placed a minimum of three (3) feet above the bedrock. stratum. Where bedrock is encountered within three (3) feet of street subgrade, it is recommended that subdrains be constructed' to intercept potential perched water. ` The drainage system should empty 10- into a storm drain, a sewer underdrain, the existing irrigation ditch or be disposed of by other suitable means. It is recommended that the asphalt concrete and/or plant mix bituminous base course be placed in two (2) to three (3) inch lifts. All plant mix bituminous base course and asphalt concrete shall meet City of Fort Collins specifications and should be placed in accordance with these specifications. All subbase material shall have an "R" value between 50 and 69, the crushed aggregate base course shall have an "R" value between 70 and 77, the plant mix bituminous base course shall have an Rt value of 90 or greater, and the asphalt concrete shall have an Rt value of 95 or greater. The "R" value of the pavement materials used should be verified by laboratory tests. Field density tests should be taken in the aggregate base course, bituminous base course, and asphalt concrete under the direction of the geotechnical engineer. . Rigid Pavement A feasible pavement alternate at the site would be rigid pavement. Using the eighteen (18) kip equivalent daily load application described above, a modulus of subgrade reaction of one hundred (100) pounds per square inch per inch based on an "R" value of 5, a design life of twenty 20) .years, and concrete designed with a modulus of rupture of six hundred (600) pounds per square inch, the following minimum pavement thickness recommended: All Streets within Subdivision Nonreinforced Concrete - 5" Subgrade below proposed streets should be prepared in accordance with the recommendations discussed above and in the "Site Grading, Excavation and Utilities" section of this report. Concrete pavement should be placed directly on the subgrade that has been uniformly and properly prepared in accordance with the above recommendations. All concrete used in the paving shall meet ASTM specifications, and all aggregate shall conform to ASTM C-33 specifications. The concrete 11- should be designed with a minimum modulus of rupture of six hundred 600) pounds per square inch in twenty-eight (28) days. it is recommended that laboratory mix designs be done to determine the proper proportions of aggregates, cement, and water necessary -to meet these requirements. It is essential that the concrete have a low water -cement ratio, an adequate cement factor, and sufficient quantities of entrained air. Joints should be carefully designed and constructed in accordance with the City of Fort Collins "Design Criteria and Standards for Streets" to ensure good performance of the pavement. It is recommended that all concrete pavement be placed in accordance with City of Fort Collins specifications. If paving is done during cold weather, acceptable cold weather procedures as 'outlined in the City specifications should be utilized. The concrete pavement should be properly cured and protected in accordance with the above specifications. Concrete injured by frost should be' removed and replaced. It is recommended that the pavement not be opened to traffic until a flexural strength of four hundred (400) pounds per square inch is obtained or a minimum of fourteen (14) days after the concrete has been placed. GENERAL RECOMMENDATIONS 1) Laboratory test results indicate that water soluble sulfates in the soil are negligible, and a Type 1-11 cement may be used in concrete exposed to subsoils. Slabs on grade subjected to de-icing chemicals should be composed of a more durable concrete with low water -cement ratios and higher air contents. 2) Finished grade should be sloped away from the structures on all sides to give positive drainage. Ten percent (10%) for the first ten (10) feet away from the structures is the suggested slope. 3) Backfill around the outside perimeter of the structures should be mechanically compacted at optimum moisture to at least ninety percent (90%) of Standard Proctor Density ASTM D 698-78. 12- See Appendix C.) Puddling should not be permitted as a method of compaction. 4) Gutters 'and downspouts should be designed to carry roof runoff water well beyond the backfill area. 5) Underground sprinkling systems should be designed such that piping is placed a minimum of five (5) feet outside the backfill of the structures. Heads should be designed so that irrigation water. is not sprayed onto the foundation walls. These recommendations should be taken into account in the landscape planning. 6) Plumb,ilg under slabs should be eliminated wherever possible since plumbing failures are quite frequently the source of free water which may cause slab heave. 7) Pier -sizes should be proportioned . to equalize the unit loads applied to the soil and thus minimize differential settlements. 8) It is recommended that compaction requirements specified herein be verified in the .field with density tests performed under the direction of the geotechnical engineer. 9) It is recommended that a registered professional engineer design the substructures and that he take into account the findings and recommendations of this report. G MERAL COMMENTS This report has been prepared to aid in the evaluation of the property and to assist the architect and/or engineer in the design of this project. In the event that any changes in the design of the structures or their locations are planned, the conclusions and recommendations contained in this report will not be considered valid 13- unless said changes are reviewed and conclusions of this report modified or approved in writing by Empire -Laboratories, Inc., the geotechnical engineer of record. Every effort was made to provide comprehensive site coverage through careful locations of the test borings, while keeping the site investigation economically viable. Variations in soil and ground water cond.itions between test borings may be encountered during construction. In order to permit correlation between the reported subsurface conditions and the actual conditions encountered during construction and to aid in carrying out the plans and specifications as originally contemplated, it is recommended that Empire Laboratories, Inc. be retained to perform continuous construction review during the excavation and foundation phases of the work. Empire Laboratories, Inc. assumes no responsibility for compliance with the recommendations included in this report unless they have been retained to perform adequate on -site construction review during the course of construction. 14- APPENDIX A. PEST BORING LOCATION PLAN 5•r! GoR•t 2 LLA® 0 0 n :'ti• A-? KEY TO BORING LOGS TOPSOIL GRAVEL FILL SAND & GRAVEL J-* SILT e i A SILTY SAND & GRAVEL i71 CLAYEY SILT ono COBBLES DSANDY SILT SAND, GRAVEL & COBBLES CLAY WEATHERED BEDROCK SILTY CLAY SILTSTONE BEDROCK SANDY CLAY CLAYSTONE BEDROCK SAND SANDSTONEBEDROCK SILTY SAND LIMESTONE CLAYEY SAND GRANITE SANDY SILTY CLAY SHELBY TUBE SAMPLE STANDARD PENETRATION DRIVE SAMPLER WATER TABLE 3 DAYS AFTER DRILLING C T HOLE CAVED 5/12 Indicates that 5 blows of a 140 pound hammer falling 30 inches was required to penetrate 12 inches. A-3 LOG OF 901 NG4 95 90 85 75 -- 10111 southwest corner of intersection., elevation= 100.0'. A-4 EMPIRE LABORATORIES, INC. Q LOG Of BORINGS 95 ER 1 m 75 8 A-5 EMPIRE LABORATORIES, INC. APPENDIX B. 640 60 560 20 SWELL - CONSOLIDATION TEST PRE. 8045 25,20111MOISTURE: MEN 110 INII e m m 0.1 0.25 0.5 1.0 5 10 APPLIED PRESSURE — TSF 8 .'0 J J W 4.'0 ifj X 0.0 WRTER ADDED 16 .0 0.1 0.25 0.5 1.0 5 APPLIED PRESSURE - TSF 10 F'IFIP.E LABORATORIES INC B-2 RESISTANCE R-VALUE AND EXPANSION PRESSURE OF COMPACTO SOIL ASTM — D 2844 CL I EllT: FA I RF I ELD HOMES PROJECT: THE JETTY — BOARDWALK & LANDINGS DRIVE LOCATI011 OF SAMPLE: COMPOSITE SAMPLE BORING 1-10. 5 @ 0.5' — 4.0' SAMPLE DATA TEST SPECIMEN 1 2 3 COMPACTION PRESSURE PSI 0 0 0 DENSITY - PCF 91.8 98.0 102.2 MOISTURE - 28.7 25.1 22.8 EXPANSION PRESSURE PSI 0.00 0.00 0.00 HORIZONTAL PRESSURE @ 160 Psi 154 151 148 SAMPLE HEIGHT - in. 2.48 2.50 2.50 EXUDATION PRESSURE PSI 139 239 438 UNCORRECTED R=VALUE 2.4 4.2 5.8 CORRECTED R-VALUE 2.4 4.2 5.8 R-VALUE AT 300 PSI EXUDATION PRESSURE = 5.1 100 80 Q! 41_i 20 3.........................................;.......... s......... ... ...................:...........:;.........................;....,........_.;.... i 1: ....................... i....... ..... ;........ » _............. - 4.::. .-....... r j............ -. ........ 1........._..:..........;................ » ..i... r.......... 1..::. s 3 3 3 E i 3 3 r{:.::::::.............. ..... ...»... _ - ... ... .:...... .................. i i E • i............. ....».......3.......................... j'....... ...::.;:............ ........... ........ i c e:........... i. ....... .......:::.::.......i..................._....»i..»....... i.. i.............y.... i S 3 : L ----- ....................................... i-i i Lrrrirrrrir r,rr,r,rrli 100 200 300 400 500 600 EXUDATION PRESSURE — psi ElIFIRE LABORATORIES INC B-3 700 800 C G a N N CV O N N V N N tV N N m r 00 N M M O 111 Id,%0 r N N r!f qzr cm N CDr\ M O to q t Qxo G Go Y = VA Q u 2 o O 9 Tr v x G — W. v J W cc a F- N W U. H 00 U") O O N O O CD O aLL co N r N CilHaN to ` O. CL t o ac O r\ O N O w a G N C7 w E M tLL M 00 M LO d O C d r ct t ll1 O ` N co r r-- 00 C r 00 ' 00 N Icr N O LO M m N 00 Ln co N Caj to to 01 n M. Ln m m r E 00 O O G7 Ln O O O LO O O O O Ln O O O O 17 U7rU 00 r U; 00 CT r M n CO O 0 r 0 r 0 t 0 r LA r O O O O r O Lf O O O i O r O E 01 O M C r` Kr O m ct n 00 V O N m l0 n d GJ O C O O Z r0 C 0 C N N N N N N N r•- CYI 6.0 r- O N OCciODOOcoO m N N In Ln h Ln M LA n ffi2 U QO 1 00 w u V1 ON V w N v iti Q to Q V 1 v 1 1 Q Q IL q O 19 c ap N t0 w O d N N Y N W p N W U. O p2ppx N y LLaN d Q CLL ale N CcC ® IL O e 00 e* N t • f Cl. b— n 00 cod O q' O l0 w co O O O O O 0 0 0 0 O o r- N LO 0% Q r- N LA A r- 0 0 0 O O Ln O O Cl O O to O 00 O N VI (U C m ze a m Ln cn ob ob U t.X SUMMARY OF TEST RESULTS Boring Depth % Oxidation -Reduction Resistivity Flo. (ft) Moi.sture Potential W ohm -cm Sulfide pH 4 0.5-4.0 33.8 .261 1200 trace 7.8 B-6 APPENDIX C. APPENDIX C. Suggested Minimum Specifications for Placement of Compacted Earth Fill and/or Backfills GENERAL The geotechnical engineer shall be the owner's, architect's, engineer's or contractor's representative to observe placement of compacted fill and/or backfill on the project. The geotechnical engineer or his representative shall approve all earth materials prior to their use, the method of placement and the degree of compaction. MATERIALS - Soils used for all compacted fill and backfill shall be approved by the geotechnical engineer or his representative- prior to their use. Fill material shall be free from organic matter, frozen material and other unsuitable substance and shall not contain rocks or lumps having a diameter greater than six (6) inches. SUBGRADE PREPARATION All topsoil, vegetation, trees, brush, timber, debris, rubbish and all other unsuitable material shall be removed to a depth satisfactory to the geotechnical engineer or his representative. The material shall be disposed of by suitable means prior to beginning preparation of the subgrade. The subgrade shall be scarified a minimum depth of six (6) Inches, moisture conditioned as necessary and compacted In a suitable manner prior to placement of fHl material. Fill shall not be placed until approval by the geotechnical engineer or his representative; and in no case, shall fill material be placed on frozen or unstable ground. Subgrade which is not stable may require the use of imported granular material, geotextiles or other methods for stabilization as approved by .the geotechnical engineer. FILL PLACEMENT Fill material shall not be placed during unfavorable weather conditions. Material geotechnical engineer proposed for use as fill shall be or his representative prior to use. approved by the Proposed import material shall be approved by the geotechnical Fill engineer or his material shall berepresentativepriortohaulingtotheprojectsite. C-2 uniformly mixed such as to preclude the formation of lenses of material differing from the surrounding material. All clods shall be broken .into small pieces. The contractor shall construct the fill in approximately horizontal lifts extending the entire length of the fill. The thickness of the layers before compaction shall not be greater than eight (8) inches. Fill being placed on slopes or hillsides shall be benched into the existing slope. A minimum two (2) foot horizontal bench shall be cut into the existing excavated slope for each four (4) feet vertical of fill, or each lift should be benched slightly into the existing grade. MOISTURE CONTROL Prior to and during compaction operations, the fill material being placed shall be maintained within the range of optimum moisture specified. A general recommendation is to maintain the fill material within two-- percent (2%) plus or minus of optimum moisture so that proper compaction to the specified density may be obtained with a minimal effort. In building pad and paved areas, material exhibiting swelling potential shall be maintained between optimum moisture and two percent (2%) wet of optimum moisture content. The moisture content of the fill material shall be maintained uniform throughout the fill. The contractor may be required to add necessary moisture to the fill material and to uniformly mix the water with the fill material if, in the opinion of the geotechnical engineer, it is not possible to obtain uniform moisture content by adding water on the fill surface. If,. in the opinion of the geotechnical engineer, . the material proposed for use in the compacted fill is too wet to permit adequate compaction, it shall be dried in an acceptable manner prior to placement and compaction. Uniform mixing may require discing, blading or other methods approved by the geotechnical engineer or his representative. Adjustments of moisture content shall be made on the basis of determinations of moisture content by field tests as construction progresses. COMPACTION The contractor shall furnish and operate the necessary types and kinds of equipment to perform the operations required to obtain the specified compaction. This equipment may include approved tamping rollers, rubber. tired rollers, smooth wheeled rollers and vibratory rollers. If a sKeepsfoot roller is used, it shall be provided with cleaner bars so attached as to prevent the accumulation of. material between the tamper feet. Fill areas which are not accessible to full-sized construction equipment shall be placed in maximum four (4) inch lifts and compacted, with power tampers to the specified density. C-3 Compaction should meet the minimum percentages of maximum density as set forth in the project specifications or the recommendations .of the report. The contract specifications supercede the recommendations. given in this report. MOISTURE DENSITY RELATIONSHIP DETERMINATION Samples of representative fill materials to be placed shall be furnished by the contractor to the geotechnical engineer for determination of maximum density and optimum moisture or relative density. Sufficient laboratory moisture density or relative density curves will be made to determine the optimum moisture content and -maximum density for the various soils placed as . fill. Tests for this determination will. be made using the appropriate method conforming to the requirements of ASTM D 698 (Standard Proctor) ; --ASTM- D-1557 (Modified Proctor)- -or--ASTM 0-4253, - D 4254 (Relative Density). The materials used for fill shall be classified In accordance with ASTM D 2487 in order to permit correlation between the moisture -density relationship data and the material being placed and compacted.- Copies of the results of these tests; will be furnished to the client and others as directed by the client. These test results shall be the basis of control for all compaction effort. FIELD DENSITY AND MOISTURE TESTS The In -place density and moisture content of compacted fill will be determined by the geotechnical engineer or his representative in accordance with ASTM D 1556 (sand cone method) or ASTM D 2922, D 3011 (nuclear methods). Material not meeting the required compaction and/or moisture specifications shall be recompacted and/or moisture conditioned until the required percent compactlone and/or moisture content Is obtained. Sufficient compaction tests shall be made and submitted to support the geotechnical engineer's or his representative's recommendations. The results of density tests will also be furnished to the client and others as directed. C- 4