HomeMy WebLinkAboutCOMPACTION TESTING - Filed CT-CONCRETE TEST - (13)Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 807 Sidewalk Subgrade: Greenfields Dr. - Tie-in north of roundabout (west side of street) approximately 60 feet north of crosswalk at roundabout 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 808 Sidewalk Subgrade: Greenfields Dr. - Tie-in north of roundabout (west side of street) approximately 15 feet north of crosswalk at roundabout 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 809 Sidewalk Subgrade: Greenfields Dr. - east side of street, center of ramp, SE side of International Blvd. 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 810 Sidewalk Subgrade: Greenfields Dr. - east side of street, center of ramp, SE side of Sykes Dr. 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 811 Aggregate Base Course: Robud Farms Dr. - Eastbound curb, approximately station 85+50 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 812 Aggregate Base Course: Robud Farms Dr. - Eastbound curb, approximately station 87+25 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 813 Aggregate Base Course: Robud Farms Dr. - Eastbound curb, south approximately station 12+65 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 814 Aggregate Base Course: Robud Farms Dr. - Eastbound curb, east side of cul-de-sac, approximately station 11+75 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 807 03/19/24 4 698B Granular 12.5 118.0 13.3 115.7 131.1 12 98 95 A 808 03/19/24 4 698B Granular 12.5 118.0 14.5 115.9 132.7 12 98 95 A 809 03/19/24 4 698B Granular 12.5 118.0 14.4 116.3 133.1 12 99 95 A 810 03/19/24 4 698B Granular 12.5 118.0 13.2 115.3 130.5 12 98 95 A 811 03/19/24 15 698C Granular 7.5 129.0 5.6 123.0 129.9 4 95 95 A 812 03/19/24 15 698C Granular 7.5 129.0 5.7 123.8 130.9 4 96 95 A 813 03/19/24 15 698C Granular 7.5 129.0 5.5 122.7 129.5 4 95 95 A 814 03/19/24 15 698C Granular 7.5 129.0 5.8 123.4 130.6 4 96 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 1 of 9 Compaction Testing Test Method: ASTM D 6938 Report Date: 04/04/2024 Report #: SNG-000021 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 815 Aggregate Base Course: Robud Farms Dr. - westbound curb, north side of cul-de-sac, approximately station 10+75 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 816 Aggregate Base Course: Robud Farms Dr. - westbound curb, approximately station 87+00 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 817 Aggregate Base Course: Robud Farms Dr. - westbound curb, approximately station 86+00 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 818 Sidewalk Subgrade: Greenfields Dr. - east side of street, tie-in north of roundabout, approximately 100 feet north of crosswalk 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 819 Sidewalk Subgrade: Greenfields Dr. - east side of street, tie-in north of roundabout, approximately 50 feet north of crosswalk 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 820 Sidewalk Subgrade: Greenfields Dr. - east side of street, center of ramp north of roundabout, at the ashplant/concrete transition 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 821 Sidewalk Subgrade: Greenfields Dr. - west side of street, center of ramp north of roundabout, at the ashplant/concrete transition 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 822 Sidewalk Subgrade: Northwest corner of site, private sidewalk north of Barnstormer, approximately 15 feet north of city sidewalk 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 815 03/19/24 15 698C Granular 7.5 129.0 5.6 123.6 130.5 4 96 95 A 816 03/19/24 15 698C Granular 7.5 129.0 5.7 122.0 129.0 4 95 95 A 817 03/19/24 15 698C Granular 7.5 129.0 6.1 123.6 131.1 4 96 95 A 818 03/20/24 4 698B Granular 12.5 118.0 14.5 117.4 134.4 12 99 95 A 819 03/20/24 4 698B Granular 12.5 118.0 12.4 118.1 132.8 12 100 95 A 820 03/20/24 4 698B Granular 12.5 118.0 11.2 119.8 133.2 12 102 95 A 821 03/20/24 4 698B Granular 12.5 118.0 10.6 117.1 129.5 12 99 95 A 822 03/20/24 20 698B Cohesive 15.0 114.0 17.5 108.7 127.7 10 95 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 2 of 9 Compaction Testing Test Method: ASTM D 6938 Report Date: 04/04/2024 Report #: SNG-000021 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 823 Sidewalk Subgrade: Northwest corner of site, private sidewalk north of Barnstormer, approximately 75 feet north of city sidewalk 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 824 Aggregate Base Course: Robud Farms Dr. - curb and gutter radius at Aria Way, north side of street 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 825 Aggregate Base Course: Robud Farms Dr. - curb and gutter radius at Aria Way, south side of street 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 826 Aggregate Base Course: Robud Farms Dr. - curb and gutter tie-in, east of inlet E3.1 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 827 Aggregate Base Course: Robud Farms Dr. - curb and gutter tie-in, east of inlet E3.1A 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 828 Aggregate Base Course: Robud Farms Dr. - center of street between inlets E3.1 and E3.1A 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 829 Sidewalk Subgrade: Tie -in on the east side of Greenfields Dr. - north of roundabout, approximately 15 feet north of crosswalk 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 830 Sidewalk Subgrade: Tie -in on the east side of Greenfields Dr. - north of roundabout, adjacent to ramp at asphalt/concrete transition 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 823 03/20/24 20 698B Cohesive 15.0 114.0 16.3 112.2 130.5 10 98 95 A 824 03/22/24 15 698C Granular 7.5 129.0 5.6 122.5 129.3 4 95 95 A 825 03/22/24 15 698C Granular 7.5 129.0 6.7 124.1 132.4 4 96 95 A 826 03/22/24 15 698C Granular 7.5 129.0 7.9 122.6 132.3 4 95 95 A 827 03/22/24 15 698C Granular 7.5 129.0 7.8 122.5 132.0 4 95 95 A 828 03/22/24 15 698C Granular 7.5 129.0 7.7 123.9 133.4 6 96 95 A 829 03/26/24 4 698B Granular 12.5 118.0 10.6 117.3 129.7 10 99 95 A 830 03/26/24 4 698B Granular 12.5 118.0 12.7 120.8 136.2 10 102 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 3 of 9 Compaction Testing Test Method: ASTM D 6938 Report Date: 04/04/2024 Report #: SNG-000021 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 831 Aggregate Base Course: Aria Way - (south of Sykes Dr.) northbound lane, approximately station 35+50 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 832 Aggregate Base Course: Aria Way - (south of Sykes Dr.) northbound lane, approximately station 36+70 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 833 Aggregate Base Course: Aria Way - (south of Sykes Dr.) northbound lane, approximately station 38+25 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 834 Aggregate Base Course: Aria Way - (south of Sykes Dr.) northbound lane, approximately station 40+25 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 835 Aggregate Base Course: Aria Way - (south of Sykes Dr.) northbound lane, approximately station 41+50 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 836 Aggregate Base Course: Aria Way - (south of Sykes Dr.) curb and gutter, southbound lane, approximately station 40+75 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 837 Aggregate Base Course: Aria Way - (south of Sykes Dr.) curb and gutter, southbound lane, approximately station 38+75 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 838 Aggregate Base Course: Aria Way - (south of Sykes Dr.) curb and gutter, southbound lane, approximately station 37+75 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 831 03/27/24 15 698C Granular 7.5 129.0 5.6 128.5 135.7 4 100 95 A 832 03/27/24 15 698C Granular 7.5 129.0 6.1 122.9 130.4 4 95 95 A 833 03/27/24 15 698C Granular 7.5 129.0 5.7 127.2 134.4 4 99 95 A 834 03/27/24 15 698C Granular 7.5 129.0 6.1 128.9 136.8 4 100 95 A 835 03/27/24 15 698C Granular 7.5 129.0 5.8 126.9 134.3 4 98 95 A 836 03/27/24 15 698C Granular 7.5 129.0 5.5 128.2 135.3 4 99 95 A 837 03/27/24 15 698C Granular 7.5 129.0 5.9 129.1 136.7 4 100 95 A 838 03/27/24 15 698C Granular 7.5 129.0 5.9 131.5 139.2 4 102 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 4 of 9 Compaction Testing Test Method: ASTM D 6938 Report Date: 04/04/2024 Report #: SNG-000021 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 839 Aggregate Base Course: Aria Way - (south of Sykes Dr.) curb and gutter, southbound lane, approximately station 36+40 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 840 Aggregate Base Course: Aria Way - (south of Sykes Dr.) curb and gutter, southbound lane, approximately station 35+00 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 841 Sidewalk Subgrade: Private sidewalk, northwest corner of site, north of Barnstormer St. - approximately 20 feet north of city sidewalk 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 842 Sidewalk Subgrade: Private sidewalk, northwest corner of site, north of Barnstormer St. - approximately 100 feet north of city sidewalk 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 843 Sidewalk Subgrade: Private sidewalk, northwest corner of site, north of Barnstormer St. - approximately 150 feet north of city sidewalk 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 844 Aggregate Base Course: Comet St. - curb and gutter, west bound laner, approximately station 116+00 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 845 Aggregate Base Course: Comet St. - curb and gutter, west bound laner, approximately station 114+00 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 846 Aggregate Base Course: Comet St. - curb and gutter, westbound lane, approximately station 112+00 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 839 03/27/24 15 698C Granular 7.5 129.0 5.7 130.7 138.1 4 101 95 A 840 03/27/24 15 698C Granular 7.5 129.0 5.7 133.0 140.6 4 103 95 A 841 03/27/24 20 698B Cohesive 15.0 114.0 16.1 108.8 126.3 10 95 95 A 842 03/27/24 20 698B Cohesive 15.0 114.0 16.2 109.1 126.8 10 96 95 A 843 03/27/24 20 698B Cohesive 15.0 114.0 16.2 112.1 130.3 10 98 95 A 844 03/28/24 15 698C Granular 7.5 129.0 5.8 132.1 139.8 4 102 95 A 845 03/28/24 15 698C Granular 7.5 129.0 6.4 122.8 130.7 4 95 95 A 846 03/28/24 15 698C Granular 7.5 129.0 5.9 128.0 135.6 4 99 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 5 of 9 Compaction Testing Test Method: ASTM D 6938 Report Date: 04/04/2024 Report #: SNG-000021 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 847 Aggregate Base Course: Comet St. - curb and gutter, westbound lane, approximately station 110+75 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 848 Aggregate Base Course: Comet St. - curb and gutter, eastbound lane, approximately station 111+00 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 849 Aggregate Base Course: Comet St. - curb and gutter, eastbound lane, approximately station 113+00 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 850 Aggregate Base Course: Comet St. - curb and gutter, eastbound lane, approximately station 114+50 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 851 Aggregate Base Course: Comet St. - curb and gutter, eastbound lane, approximately station 115+75 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 852 Aggregate Base Course: Roselyn St. - curb and gutter, southbound lane, approximately station 100+50 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 853 Aggregate Base Course: Roselyn St. - curb and gutter, southbound lane, approximately station 102+50 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 854 Aggregate Base Course: Roselyn St. - curb and gutter, southbound lane, approximately station 104+00 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 847 03/28/24 15 698C Granular 7.5 129.0 6.9 124.0 132.5 4 96 95 A 848 03/28/24 15 698C Granular 7.5 129.0 7.2 124.6 133.6 4 97 95 A 849 03/28/24 15 698C Granular 7.5 129.0 6.3 127.9 135.9 4 99 95 A 850 03/28/24 15 698C Granular 7.5 129.0 7.5 122.0 131.1 4 95 95 A 851 03/28/24 15 698C Granular 7.5 129.0 6.8 128.6 137.4 4 100 95 A 852 03/28/24 15 698C Granular 7.5 129.0 6.0 130.9 138.8 4 101 95 A 853 03/28/24 15 698C Granular 7.5 129.0 5.8 123.4 130.6 4 96 95 A 854 03/28/24 15 698C Granular 7.5 129.0 5.6 123.7 130.6 4 96 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 6 of 9 Compaction Testing Test Method: ASTM D 6938 Report Date: 04/04/2024 Report #: SNG-000021 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 855 Aggregate Base Course: Roselyn St. - curb and gutter, northbound lane, approximately station 104+50 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 856 Aggregate Base Course: Roselyn St. - curb and gutter, northbound lane, approximately station 102+50 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 857 Aggregate Base Course: Roselyn St. - curb and gutter, northbound lane, approximately station 100+50 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 858 Aggregate Base Course: Robud Farms Dr. - cul-de-sac, adjacent to Lot 23 Block 1 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 859 Aggregate Base Course: Robud Farms Dr. - cul-de-sac, center of cul-de-sac 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 860 Aggregate Base Course: Robud Farms Dr. - cul-de-sac, adjacent to Lot 24 Block 1 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 861 Aggregate Base Course: Robud Farms Dr. - westbound lane, adjacent to Lot 22 Block 1 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 862 Aggregate Base Course: Robud Farms Dr. - westbound lane, adjacent to Lot 21 Block 1 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 855 03/28/24 15 698C Granular 7.5 129.0 5.6 124.2 131.1 4 96 95 A 856 03/28/24 15 698C Granular 7.5 129.0 5.7 127.3 134.5 4 99 95 A 857 03/28/24 15 698C Granular 7.5 129.0 5.5 124.5 131.4 4 97 95 A 858 03/28/24 15 698C Granular 7.5 129.0 8.1 130.4 140.9 4 101 95 A 859 03/28/24 15 698C Granular 7.5 129.0 6.2 126.6 134.4 4 98 95 A 860 03/28/24 15 698C Granular 7.5 129.0 5.8 132.1 139.8 4 102 95 A 861 03/28/24 15 698C Granular 7.5 129.0 6.1 126.8 134.5 4 98 95 A 862 03/28/24 15 698C Granular 7.5 129.0 6.2 131.5 139.6 4 102 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 7 of 9 Compaction Testing Test Method: ASTM D 6938 Report Date: 04/04/2024 Report #: SNG-000021 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 863 Aggregate Base Course: Robud Farms Dr. - eastbound lane, adjacent to Lot 27 Block 1 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 864 Aggregate Base Course: Robud Farms Dr. - eastbound lane, adjacent to Lot 30 Block 1 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 865 Curb and Gutter Subgrade: Curb & Gutter hand pours, Aria Way, Station 34+80, right side of street 0.0 below grade(feet)XPLORER / 3500 / 3383 / 01/24/2018 Braun, Frederick 866 Curb and Gutter Subgrade: Curb & Gutter hand pours, Aria Way, Station 34+80, left side of street 0.0 below grade(feet)XPLORER / 3500 / 3383 / 01/24/2018 Braun, Frederick 867 Curb and Gutter Subgrade: Curb & Gutter hand pours, Aria Way, Station 36+30, right side of street 0.0 below grade(feet)XPLORER / 3500 / 3383 / 01/24/2018 Braun, Frederick 868 Curb and Gutter Subgrade: Curb & Gutter hand pours, Aria Way, Station 36+30, left side of street 0.0 below grade(feet)XPLORER / 3500 / 3383 / 01/24/2018 Braun, Frederick 869 Curb and Gutter Subgrade: Curb & Gutter hand pours, Aria Way, Station 38+90, left side of street 0.0 below grade(feet)XPLORER / 3500 / 3383 / 01/24/2018 Braun, Frederick 870 Curb and Gutter Subgrade: Curb & Gutter hand pours, Aria Way, Station 40+00, left side of street 0.0 below grade(feet)XPLORER / 3500 / 3383 / 01/24/2018 Braun, Frederick Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 863 03/28/24 15 698C Granular 7.5 129.0 6.9 131.0 140.1 4 102 95 A 864 03/28/24 15 698C Granular 7.5 129.0 5.9 126.2 133.6 4 98 95 A 865 03/29/24 15 698C Granular 7.5 129.0 7.5 129.2 138.9 6 100 95 A 866 03/29/24 15 698C Granular 7.5 129.0 6.9 126.7 135.4 6 98 95 A 867 03/29/24 15 698C Granular 7.5 129.0 5.8 130.5 138.1 6 101 95 A 868 03/29/24 15 698C Granular 7.5 129.0 5.8 126.8 134.2 6 98 95 A 869 03/29/24 15 698C Granular 7.5 129.0 5.9 130.0 137.7 6 101 95 A 870 03/29/24 15 698C Granular 7.5 129.0 5.7 125.3 132.4 6 97 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 8 of 9 Compaction Testing Test Method: ASTM D 6938 Report Date: 04/04/2024 Report #: SNG-000021 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 871 Curb and Gutter Subgrade: Curb & Gutter hand pours, Aria Way, Station 41+00, left side of street 0.0 below grade(feet)XPLORER / 3500 / 3383 / 01/24/2018 Braun, Frederick 872 Curb and Gutter Subgrade: Curb & Gutter hand pours, Aria Way, Station 41+40, right side of street 0.0 below grade(feet)XPLORER / 3500 / 3383 / 01/24/2018 Braun, Frederick 873 Curb and Gutter Subgrade: Curb & Gutter hand pours, Aria Way, Station 41+75, right side of street 0.0 below grade(feet)XPLORER / 3500 / 3383 / 01/24/2018 Braun, Frederick 874 Curb and Gutter Subgrade: Curb & Gutter hand pours, Aria Way, Station 41+70, left side of street 0.0 below grade(feet)XPLORER / 3500 / 3383 / 01/24/2018 Braun, Frederick Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 871 03/29/24 15 698C Granular 7.5 129.0 6.1 124.7 132.3 6 97 95 A 872 03/29/24 15 698C Granular 7.5 129.0 7.1 123.6 132.4 6 96 95 A 873 03/29/24 15 698C Granular 7.5 129.0 6.2 125.0 132.8 6 97 95 A 874 03/29/24 15 698C Granular 7.5 129.0 6.1 128.8 136.6 6 100 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 9 of 9 Compaction Testing Test Method: ASTM D 6938 Report Date: 04/04/2024 Report #: SNG-000021 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins