HomeMy WebLinkAboutCOMPACTION TESTING - Filed CT-CONCRETE TEST - (10)Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 943 Sidewalk Subgrade: Private sidewalk, between Lots 12 and 13 Block 1, east end of path, approximately 8 feet west of storm culverts 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 944 Sidewalk Subgrade: Private sidewalk, between Lots 12 and 13 Block 1, west end of path, north of storm manhole at city sidewalk 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 945 Alley Subgrade: Tract J/Block 6 alleys, west alley, adjacent to Lot 14 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 946 Alley Subgrade: Tract J/Block 6 alleys, west alley, adjacent to Lot 25 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 947 Alley Subgrade: Tract J/Block 6 alleys, west alley, center of west parking area 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 948 Alley Subgrade: Tract J/Block 6 alleys, center alley, adjacent to Lot 25 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 949 Alley Subgrade: Tract J/Block 6 alleys, center alley, adjacent to Lot 29 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 950 Alley Subgrade: Tract J/Block 6 alleys, east alley, adjacent to Lot 9 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 943 04/16/24 7 698B Granular 9.5 126.0 8.7 120.7 131.2 12 96 95 A 944 04/16/24 7 698B Granular 9.5 126.0 9.0 122.3 133.3 12 97 95 A 945 04/17/24 4 698B Granular 12.5 118.0 10.8 113.5 125.8 12 96 95 A 946 04/17/24 4 698B Granular 12.5 118.0 10.5 113.8 125.8 12 96 95 A 947 04/17/24 4 698B Granular 12.5 118.0 10.7 118.9 131.6 12 101 95 A 948 04/17/24 4 698B Granular 12.5 118.0 10.7 116.0 128.4 12 98 95 A 949 04/17/24 4 698B Granular 12.5 118.0 10.7 117.0 129.5 12 99 95 A 950 04/18/24 4 698B Granular 12.5 118.0 11.2 111.9 124.4 12 95 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 1 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 951 Alley Subgrade: Tract J/Block 6 alleys, east alley, adjacent to Lot 30 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 952 Alley Subgrade: Tract J/Block 6 alleys, east alley, center of east parking area 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 953 Street Subgrade: Comet St. - eastbound lane, approximately station 17+50, along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 954 Street Subgrade: Comet St. - eastbound lane, approximately station 18+00, center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 955 Street Subgrade: Comet St. - eastbound lane, approximately station 119+00, along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 956 Street Subgrade: Comet St. - eastbound lane, approximately station 119+50, center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 957 Street Subgrade: Comet St. - westbound lane, approximately station 120+00, along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 958 Street Subgrade: Comet St. - westbound lane, approximately station 119+25, center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 951 04/18/24 4 698B Granular 12.5 118.0 11.7 113.3 126.5 12 96 95 A 952 04/18/24 4 698B Granular 12.5 118.0 11.7 112.8 126.0 12 96 95 A 953 04/22/24 14 698C Granular 10.0 123.5 10.1 118.4 130.4 10 96 95 A 954 04/22/24 14 698C Granular 10.0 123.5 10.8 120.8 133.8 10 98 95 A 955 04/22/24 14 698C Granular 10.0 123.5 9.4 125.1 136.8 10 101 95 A 956 04/22/24 14 698C Granular 10.0 123.5 10.6 121.2 134.1 10 98 95 A 957 04/22/24 14 698C Granular 10.0 123.5 11.6 117.7 131.4 10 95 95 A 958 04/22/24 14 698C Granular 10.0 123.5 11.8 120.8 135.0 10 98 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 2 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 959 Street Subgrade: Comet St. - westbound lane, approximately station 118+50, along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 960 Street Subgrade: Comet St. - westbound lane, approximately station 117+75, center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 961 Street Subgrade: Comet St. - SSMH 1.3A-1, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 962 Street Subgrade: Comet St. - SSMH 1.3A-1, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 963 Street Subgrade: Comet St. - SSMH 1.3A-2, west side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 964 Street Subgrade: Comet St. - SSMH 1.3A-2, east side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 965 Street Subgrade: Comet St. - SDMH I2-A.6, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 966 Street Subgrade: Comet St. - SDMH I2-A.6, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 959 04/22/24 14 698C Granular 10.0 123.5 12.0 117.7 131.8 10 95 95 A 960 04/22/24 14 698C Granular 10.0 123.5 10.1 122.3 134.7 10 99 95 A 961 04/22/24 14 698C Granular 10.0 123.5 10.2 117.1 129.0 10 95 95 A 962 04/22/24 14 698C Granular 10.0 123.5 10.4 118.7 131.0 10 96 95 A 963 04/22/24 14 698C Granular 10.0 123.5 8.4 120.8 131.0 10 98 95 A 964 04/22/24 14 698C Granular 10.0 123.5 9.9 117.3 128.9 10 95 95 A 965 04/22/24 14 698C Granular 10.0 123.5 8.5 117.3 127.3 10 95 95 A 966 04/22/24 14 698C Granular 10.0 123.5 8.5 117.5 127.5 10 95 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 3 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 967 Street Subgrade: Flourish Ln. - SSMH 1.1A.5, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 968 Street Subgrade: Flourish Ln. - SSMH 1.1A.5, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 969 Street Subgrade: Flourish Ln. - SDMH I2-A.5, west side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 970 Street Subgrade: Flourish Ln. - SDMH I2-A.5, east side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 971 Street Subgrade: Flourish Ln. - SSMH 1.1A-4, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 972 Street Subgrade: Flourish Ln. - SSMH 1.1A-4, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 973 Street Subgrade: Flourish Ln. - SDMH I2-A.4, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 974 Street Subgrade: Flourish Ln. - SDMH I2-A.4, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 967 04/22/24 14 698C Granular 10.0 123.5 10.8 116.9 129.5 10 95 95 A 968 04/22/24 14 698C Granular 10.0 123.5 10.1 117.9 129.8 10 95 95 A 969 04/22/24 14 698C Granular 10.0 123.5 11.1 117.5 130.5 10 95 95 A 970 04/22/24 14 698C Granular 10.0 123.5 10.8 118.5 131.3 10 96 95 A 971 04/22/24 14 698C Granular 10.0 123.5 10.4 118.7 131.0 10 96 95 A 972 04/22/24 14 698C Granular 10.0 123.5 10.4 117.4 129.6 10 95 95 A 973 04/22/24 14 698C Granular 10.0 123.5 9.4 116.8 127.8 10 95 95 A 974 04/22/24 14 698C Granular 10.0 123.5 10.0 117.8 129.6 10 95 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 4 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 975 Street Subgrade: Flourish Ln. - SDMH I2-A.3, west side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 976 Street Subgrade: Flourish Ln. - SDMH I2-A.3, east side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 977 Street Subgrade: Flourish Ln. - SDMH I2-A.2, west side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 978 Street Subgrade: Flourish Ln. - SDMH I2-A.2, east side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 979 Street Subgrade: Flourish Ln. - SDMH I2-A.21, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 980 Street Subgrade: Flourish Ln. - SDMH I2-A.21, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 981 Street Subgrade: Flourish Ln. - SSMH 1.1A-3, west side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 982 Street Subgrade: Flourish Ln. - SSMH 1.1A-3, east side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 975 04/22/24 14 698C Granular 10.0 123.5 10.7 117.7 130.3 10 95 95 A 976 04/22/24 14 698C Granular 10.0 123.5 11.5 118.2 131.8 10 96 95 A 977 04/22/24 14 698C Granular 10.0 123.5 10.6 118.2 130.7 10 96 95 A 978 04/22/24 14 698C Granular 10.0 123.5 10.9 116.8 129.5 10 95 95 A 979 04/22/24 14 698C Granular 10.0 123.5 10.2 117.2 129.1 10 95 95 A 980 04/22/24 14 698C Granular 10.0 123.5 10.5 117.6 130.0 10 95 95 A 981 04/22/24 14 698C Granular 10.0 123.5 10.1 117.9 129.8 10 95 95 A 982 04/22/24 14 698C Granular 10.0 123.5 9.9 118.6 130.3 10 96 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 5 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 983 Street Subgrade: Flourish Ln. - southbound lane, approximately station 120+50, along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 984 Street Subgrade: Flourish Ln. - southbound lane, approximately station 121+25, center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 985 Street Subgrade: Flourish Ln. - southbound lane, approximately station 122+25, along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 986 Street Subgrade: Flourish Ln. - southbound lane, approximately station 122+80, center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 987 Street Subgrade: Flourish Ln. - southbound lane, approximately station 123+50, along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 988 Street Subgrade: Flourish Ln. - southbound lane, intersection of Crusader St. - center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 989 Street Subgrade: Flourish Ln. - northbound lane, approximately station 131+00 - along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 990 Street Subgrade: Flourish Ln. - northbound lane, approximately station 124+00 - center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 983 04/22/24 14 698C Granular 10.0 123.5 9.9 117.8 129.5 10 95 95 A 984 04/22/24 14 698C Granular 10.0 123.5 11.5 121.8 135.8 10 99 95 A 985 04/22/24 14 698C Granular 10.0 123.5 11.1 118.5 131.7 10 96 95 A 986 04/22/24 14 698C Granular 10.0 123.5 11.1 121.6 135.1 10 98 95 A 987 04/22/24 14 698C Granular 10.0 123.5 12.0 117.9 132.1 10 95 95 A 988 04/22/24 14 698C Granular 10.0 123.5 8.7 118.1 128.4 10 96 95 A 989 04/22/24 14 698C Granular 10.0 123.5 11.1 117.3 130.3 10 95 95 A 990 04/22/24 14 698C Granular 10.0 123.5 11.0 121.9 135.3 10 99 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 6 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 991 Street Subgrade: Flourish Ln. - northbound lane, approximately station 123+25 - along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 992 Street Subgrade: Flourish Ln. - northbound lane, approximately station 122+25 - center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 993 Street Subgrade: Flourish Ln. - northbound lane, approximately station 121+25 - along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 994 Street Subgrade: Flourish Ln. - northbound lane, intersection of Comet St. - center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 995 Street Subgrade: Crusader St. (east of Aria Way) - westbound lane, approximately station 129+50, along curb 0.0 Below top of foundation wall (feet) XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 996 Street Subgrade: Crusader St. (east of Aria Way) - westbound lane, approximately station 129+25, center of lane 0.0 Below top of foundation wall (feet) XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 997 Street Subgrade: Crusader St. (east of Aria Way) - westbound lane, approximately station 128+00, along curb 0.0 Below top of foundation wall (feet) XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 998 Street Subgrade: Crusader St. (east of Aria Way) - westbound lane, approximately station 127+25, center of lane 0.0 Below top of foundation wall (feet) XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 991 04/22/24 14 698C Granular 10.0 123.5 11.7 119.4 133.4 10 97 95 A 992 04/22/24 14 698C Granular 10.0 123.5 8.5 117.1 127.1 10 95 95 A 993 04/22/24 14 698C Granular 10.0 123.5 10.8 119.0 131.8 10 96 95 A 994 04/22/24 14 698C Granular 10.0 123.5 10.6 119.3 132.0 10 97 95 A 995 04/23/24 14 698C Granular 10.0 123.5 10.1 118.3 130.3 12 96 95 A 996 04/23/24 14 698C Granular 10.0 123.5 11.5 117.4 130.9 12 95 95 A 997 04/23/24 14 698C Granular 10.0 123.5 8.8 117.7 128.0 8 95 95 A 998 04/23/24 14 698C Granular 10.0 123.5 11.8 117.4 131.2 8 95 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 7 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 999 Street Subgrade: Crusader St. (east of Aria Way) - eastbound lane, approximately station 127+35, along curb 0.0 Below top of foundation wall (feet) XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1000 Street Subgrade: Crusader St. (east of Aria Way) - eastbound lane, approximately station 128+00, center of lane 0.0 Below top of foundation wall (feet) XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1001 Street Subgrade: Crusader St. (east of Aria Way) - eastbound lane, approximately station 129+00, along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1002 Street Subgrade: Crusader St. (east of Aria Way) - eastbound lane, approximately station 129+50, center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1003 Street Subgrade: Crusader St. (east of Aria Way) - SDMH I3, west side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1004 Street Subgrade: Crusader St. (east of Aria Way) - SDMH I3, east side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1005 Street Subgrade: Crusader St. (east of Aria Way) - SDMH I-3A, west side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1006 Street Subgrade: Crusader St. (east of Aria Way) - SDMH I-3A, east side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 999 04/23/24 14 698C Granular 10.0 123.5 9.0 118.7 129.4 8 96 95 A 1000 04/23/24 14 698C Granular 10.0 123.5 11.2 117.2 130.3 8 95 95 A 1001 04/23/24 14 698C Granular 10.0 123.5 9.8 119.0 130.7 8 96 95 A 1002 04/23/24 14 698C Granular 10.0 123.5 11.5 119.0 132.7 8 96 95 A 1003 04/23/24 14 698C Granular 10.0 123.5 10.9 118.3 131.2 8 96 95 A 1004 04/23/24 14 698C Granular 10.0 123.5 11.2 117.6 130.8 8 95 95 A 1005 04/23/24 14 698C Granular 10.0 123.5 10.4 119.3 131.7 8 97 95 A 1006 04/23/24 14 698C Granular 10.0 123.5 10.0 118.6 130.5 8 96 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 8 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 1007 Street Subgrade: Crusader St. (east of Aria Way) - SSMH 1.1A-2, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1008 Street Subgrade: Crusader St. (east of Aria Way) - SSMH 1.1A-2, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1009 Street Subgrade: Crusader St. (east of Aria Way) - SSMH 1.1A-1, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1010 Street Subgrade: Crusader St. (east of Aria Way) - SSMH 1.1A-1, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1011 Street Subgrade: Flourish Ln. - fire line repair for building 5, east side of storm sewer 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1012 Street Subgrade: Flourish Ln. - fire line repair for building 5, west side of storm sewer 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1013 Alley Subgrade: Tract J/Block 6 alleys (retest after rain), west alley adjacent to Lot 25 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1014 Alley Subgrade: Tract J/Block 6 alleys (retest after rain), west alley adjacent to Lot 14 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 1007 04/23/24 14 698C Granular 10.0 123.5 11.0 117.7 130.7 8 95 95 A 1008 04/23/24 14 698C Granular 10.0 123.5 10.6 120.3 133.0 8 97 95 A 1009 04/23/24 14 698C Granular 10.0 123.5 9.2 123.1 134.4 8 100 95 A 1010 04/23/24 14 698C Granular 10.0 123.5 10.2 119.7 131.9 8 97 95 A 1011 04/23/24 14 698C Granular 10.0 123.5 8.5 120.6 130.8 8 98 95 A 1012 04/23/24 14 698C Granular 10.0 123.5 10.3 119.7 132.0 8 97 95 A 1013 04/23/24 4 698B Granular 12.5 118.0 12.5 112.9 127.0 12 96 95 A 1014 04/23/24 4 698B Granular 12.5 118.0 10.5 119.4 131.9 12 101 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 9 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 1015 Alley Subgrade: Tract J/Block 6 alleys (retest after rain), center of west parking area 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1016 Alley Subgrade: Tract J/Block 6 alleys (retest after rain), center alley, adjacent to Lot 13 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1017 Alley Subgrade: Tract J/Block 6 alleys (retest after rain), center alley, adjacent to Lot 10 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1018 Alley Subgrade: Tract J/Block 6 alleys (retest after rain), east alley, adjacent to Lot 30 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1019 Alley Subgrade: Tract J/Block 6 alleys (retest after rain), east alley, adjacent to Lot 9 Block 6 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1020 Alley Subgrade: Tract J/Block 6 alleys (retest after rain), center of east parking area 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1021 Street Subgrade: Crusader St. - (west of Aria Way) SDMH I4, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1022 Street Subgrade: Crusader St. - (west of Aria Way) SDMH I4, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 1015 04/23/24 4 698B Granular 12.5 118.0 10.8 119.4 132.3 12 101 95 A 1016 04/23/24 4 698B Granular 12.5 118.0 11.3 119.1 132.5 12 101 95 A 1017 04/23/24 4 698B Granular 12.5 118.0 11.4 117.9 131.3 12 100 95 A 1018 04/23/24 4 698B Granular 12.5 118.0 11.1 115.7 128.6 12 98 95 A 1019 04/23/24 4 698B Granular 12.5 118.0 11.5 116.6 130.0 12 99 95 A 1020 04/23/24 4 698B Granular 12.5 118.0 11.5 114.1 127.2 12 97 95 A 1021 04/24/24 14 698C Granular 10.0 123.5 8.0 118.3 127.8 8 96 95 A 1022 04/24/24 14 698C Granular 10.0 123.5 8.8 117.6 127.9 8 95 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 10 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 1023 Street Subgrade: Crusader St. - (west of Aria Way) SDMH I4.1, west side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1024 Street Subgrade: Crusader St. - (west of Aria Way) SDMH I4.1, east side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1025 Street Subgrade: Crusader St. - (west of Aria Way) SDMH I4.2, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1026 Street Subgrade: Crusader St. - (west of Aria Way) SDMH I4.2, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1027 Street Subgrade: Crusader St. - (west of Aria Way) SSMH 1.1, west side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1028 Street Subgrade: Crusader St. - (west of Aria Way) SSMH 1.1, east side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1029 Street Subgrade: Crusader St. - (west of Aria Way) SSMH 1.1-1, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1030 Street Subgrade: Crusader St. - (west of Aria Way) SSMH 1.1-1, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 1023 04/24/24 14 698C Granular 10.0 123.5 9.0 116.9 127.4 8 95 95 A 1024 04/24/24 14 698C Granular 10.0 123.5 8.5 119.0 129.1 8 96 95 A 1025 04/24/24 14 698C Granular 10.0 123.5 9.2 119.2 130.2 8 97 95 A 1026 04/24/24 14 698C Granular 10.0 123.5 9.9 117.0 128.6 8 95 95 A 1027 04/24/24 14 698C Granular 10.0 123.5 9.1 118.3 129.1 8 96 95 A 1028 04/24/24 14 698C Granular 10.0 123.5 11.1 118.6 131.8 8 96 95 A 1029 04/24/24 14 698C Granular 10.0 123.5 9.7 118.9 130.4 8 96 95 A 1030 04/24/24 14 698C Granular 10.0 123.5 8.7 118.6 128.9 8 96 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 11 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 1031 Street Subgrade: Crusader St. - (west of Aria Way) SSMH 1.1-2, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1032 Street Subgrade: Crusader St. - (west of Aria Way) SSMH 1.1-2, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1033 Street Subgrade: Crusader St. - (west of Aria Way) SSMH 1.1-3, west side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1034 Street Subgrade: Crusader St. - (west of Aria Way) SSMH 1.1-3, east side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1035 Street Subgrade: Crusader St. - (west of Aria Way) SSMH 1.1-4, north side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1036 Street Subgrade: Crusader St. - (west of Aria Way) SSMH 1.1-4, south side 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1037 Street Subgrade: Crusader St. - (west of Aria Way), westbound lane, intersection of Aria Way, center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1038 Street Subgrade: Crusader St. - (west of Aria Way), westbound lane, approximately station 125+75, along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 1031 04/24/24 14 698C Granular 10.0 123.5 9.2 116.9 127.6 8 95 95 A 1032 04/24/24 14 698C Granular 10.0 123.5 9.3 117.9 128.9 8 95 95 A 1033 04/24/24 14 698C Granular 10.0 123.5 9.1 117.2 127.9 8 95 95 A 1034 04/24/24 14 698C Granular 10.0 123.5 8.8 117.7 128.0 8 95 95 A 1035 04/24/24 14 698C Granular 10.0 123.5 9.2 118.3 129.2 8 96 95 A 1036 04/24/24 14 698C Granular 10.0 123.5 10.4 117.0 129.2 8 95 95 A 1037 04/24/24 14 698C Granular 10.0 123.5 9.2 119.3 130.3 8 97 95 A 1038 04/24/24 14 698C Granular 10.0 123.5 8.7 120.6 131.1 8 98 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 12 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins Test Information Test #Test Location Elevation Reference Gauge Make / Model / SN / Calibrated Field Technician 1039 Street Subgrade: Crusader St. - (west of Aria Way), westbound lane, approximately station 125+25, center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1040 Street Subgrade: Crusader St. - (west of Aria Way), westbound lane, approximately station 124+50, along curb 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1041 Street Subgrade: Crusader St. - (west of Aria Way), westbound lane, intersection of Roselyn Rd. - center of lane 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan 1042 Street Subgrade: Crusader St. - (west of Aria Way), westbound lane, approximately station 123+25 0.0 Below final grade (feet)XPLORER / 3500 / 3812 / 07/18/2019 Matte, Ryan Remarks A: Test results comply with specifications. Comments Tests are "Direct Transmission" (Method A) unless probe depth is noted as "Backscatter". Gauge calibration data on file with the testing agency. Test Results Test # Retest Of Test Date Proctor ID Method Soil Classification Optimum Moisture (%) Maximum Dry Density (pcf) In Place Moisture (%) In Place Dry Density (pcf) In Place Wet Density (pcf) Probe Depth (in) Percent Compaction Min Comp. (%)Remark 1039 04/24/24 14 698C Granular 10.0 123.5 9.6 124.0 135.9 8 100 95 A 1040 04/24/24 14 698C Granular 10.0 123.5 8.7 118.8 129.1 8 96 95 A 1041 04/24/24 14 698C Granular 10.0 123.5 10.2 118.7 130.8 8 96 95 A 1042 04/24/24 14 698C Granular 10.0 123.5 9.3 118.1 129.1 8 96 95 A This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project specifications. Our test results, observations and opinions do not constitute acceptance of the work. Page 13 of 13 Compaction Testing Test Method: ASTM D 6938 Report Date: 05/23/2024 Report #: SNG-000023 Client: Hartford Homes Construction Timnath, CO 80547 4801 Goodman St Project: Bloom Filing 1 FC07733.001F-340 400 North Link Lane Fort Collins, CO 80524 Phone: 970-206-9455 Fort Collins