HomeMy WebLinkAboutBloom Compressive Strength of Concrete - Filed CSS-COMPRESSIVE STRENGTH SUMMARY - (18)Specimen
Number
Test
Age Days
Test
Date
Field / Lab
Cure Days
Average Cylinder
Diameter (in)
Cylinder
Area (in²)
Max Load
(lbs)
Strength
(psi)
Fracture
Type
Break
Remark
Capping
Method
163-5 56 01/02/24 1 / 55 4.00 12.57 67,290 5,350 3 C4 N
Test Age Average Strengths (psi): 56 Day - 5350
C4: Strength is greater than or equal to f'c.
Tested By: Craig Ellis (5)
Checked In : 11/08/2023 (5)
Capping Methods
N: Unbonded Caps (ASTM C1231)
Set #:163
Specimen Size:4" X 8"
Specimens In Set:5
Truck / Ticket #:2028 / 21092813
Contractor:Front Range Concrete
Technician:Juarez-Knudsen, Evan
Cast By:Juarez-Knudsen, Evan
Date Cast:11/07/23
Sampled From:Chute
Placement Method:Curb & Gutter
Sample Details
Batched:11:15 MST
Sampled:12:20 MST
Cast:12:35 MST
Truck Empty:
Placement Time:
Placement Location:Curb and Gutter
Location Details:Curb and gutter, North side of Sykes, Sta 41+50
Sample Location / Notes:Mix 45260
Batch Log
Strength:4500 (psi)
Specifications
Supplier:SRM Concrete
On-Site Admixtures: 10.00 Gal Water (11 yd³)
Location
Field Measurements
Plastic Unit Weight:143.2 (lb/ft³)
Air Content:5.7
Load Volume:11.00 (yd³)
Weather:Slump (in):2
Air Temperature (F):73 Concrete Temp (F):80
Lab Test Results
Testing Lab: Fort Collins, 400 North Link Lane, Fort Collins, CO, 80525
Test results relate only to the sample tested.
Cylinders received in good condition unless noted otherwise. Physical properties of concrete (ASTM C143, C231, C138, C1064).
This Report should not be reproduced, except in full, without the prior authorization of CTL|Thompson Inc.
Page 1 of 1
Client:
Hartford Homes Construction
Timnath, CO 80547
4801 Goodman St
Project:
Bloom Filing 1
FC07733.001F-365
Compressive Strength of Concrete
Test Method: ASTM C 39 Sample: 123434
Report #: CC-000668
Fort Collins
400 North Link Lane
Fort Collins, CO 80524
Phone: 970-206-9455
Report Date: 01/02/2024