Loading...
HomeMy WebLinkAbout2202 ADOBE DR - DISCLOSURES - 10/7/2016BUILDING LEAKAGE TEST Date of Test: 10/7/2016 Test File: 2202 Adobe Dr LC Home REM 14.6.4 tectite Technician: Neal Girard - EnergyLogic, Inc. Project Number: 42421 Customer: LC Home Building Address: 2202 Adobe Dr Ft Collins, CO 80525 Test Results 1. Airflow at 50 Pascals: 684 CFM50 ( +/- 1.1 %) (50 Pa = 0.2 w.c.) 1.86 ACH50 2. Leakage Area: 37.6 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 38.4 ( +/- 16.8 %) Exponent (n) = 0.736 ( +/- 0.044 ) Correlation Coefficient = 0.99819 4. Test Settings: Test Standard: RESNET Multi-Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 39.9 CFM 0.11 ACH 10.0 CFM per person 2. Estimated Design Infiltration Rate: Winter: 75.0 CFM 0.20 ACH Summer: 47.1 CFM 0.13 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate: 54.4 CFM Base Rate: 54.4 CFM BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 10/7/2016 Test File: 2202 Adobe Dr LC Home REM 14.6.4 tectite Building Information Volume 22118 Surface Area 5327 Floor Area 2436 Height 20 # of Bedrooms 3 # of Occupants 4 Year of Construction 2016 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) - Micromanometer Energy Conservatory DG700 6108-5 1/17/2014 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 10/7/2016 Test File: 2202 Adobe Dr LC Home REM 14.6.4 tectite Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 66.0 65.0 5000.0 Data Points Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -1.4 n/a n/a -61.1 -59.7 160.9 752 781 0.3 Ring B -56.9 -55.4 144.2 712 740 0.3 Ring B -53.8 -52.3 129.1 674 701 -0.9 Ring B -48.5 -47.0 110.5 624 649 -0.8 Ring B -43.9 -42.5 96.8 585 608 0.2 Ring B -39.2 -37.8 84.3 546 567 1.9 Ring B -37.4 -35.9 75.7 518 538 0.4 Ring B -32.8 -31.3 59.8 461 478 -1.3 Ring B -1.5 n/a n/a Time Averaging Period: 10 Deviations from Standard RESNET Multi-Point Test - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 10/7/2016 Test File: 2202 Adobe Dr LC Home REM 14.6.4 tectite Comments Connection to: Garage: -45 Pa Mechanicals: -50 Pa