Loading...
HomeMy WebLinkAbout2250 MAID MARIAN CT - DISCLOSURES - 7/20/2016BUILDING LEAKAGE TEST Date of Test: 7/20/2016 Test File: 2250 Maid Marian Ct LC Home REM 14.6.2 TECTITE Technician: Neal Girard - EnergyLogic Project Number: 40995 Customer: LC Home Building Address: 2250 Maid Marian Ct Ft Collins, CO 80524 Test Results 1. Airflow at 50 Pascals: 1129 CFM50 ( +/- 0.5 %) (50 Pa = 0.2 w.c.) 2.27 ACH50 2. Leakage Area: 62.1 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 75.2 ( +/- 7.5 %) Exponent (n) = 0.693 ( +/- 0.020 ) Correlation Coefficient = 0.99959 4. Test Settings: Test Standard: RESNET Multi-Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 60.4 CFM 0.12 ACH 12.1 CFM per person 2. Estimated Design Infiltration Rate: Winter: 102.8 CFM 0.21 ACH Summer: 68.2 CFM 0.14 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate: 69.3 CFM Base Rate: 69.3 CFM BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 7/20/2016 Test File: 2250 Maid Marian Ct LC Home REM 14.6.2 TECTITE Building Information Volume 29827 Surface Area 6811 Floor Area 3183 Height 15 # of Bedrooms 4 # of Occupants 5 Year of Construction 2016 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) - Micromanometer Energy Conservatory DG700 6108-5 1/17/2014 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 7/20/2016 Test File: 2250 Maid Marian Ct LC Home REM 14.6.2 TECTITE Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 78.0 86.0 5000.0 Data Points Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -1.4 n/a n/a -61.0 -59.4 43.5 1196 1268 -0.2 Ring A -57.5 -55.9 39.8 1145 1214 -0.4 Ring A -53.6 -51.9 36.1 1093 1159 0.1 Ring A -49.4 -47.7 32.1 1032 1094 0.1 Ring A -45.7 -44.0 28.8 979 1038 0.4 Ring A -41.7 -40.0 240.4 918 973 0.6 Ring B -36.9 -35.3 199.9 837 888 0.2 Ring B -33.5 -31.8 170.1 773 820 -0.7 Ring B -1.9 n/a n/a Time Averaging Period: 0 Deviations from Standard RESNET Multi-Point Test - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 7/20/2016 Test File: 2250 Maid Marian Ct LC Home REM 14.6.2 TECTITE Comments Connection to: Garage: -45.1 Pa Mechanicals: -50 Pa