HomeMy WebLinkAbout4509 KIT DEN DR - DISCLOSURES - 5/20/2020 (4)BUILDING LEAKAGE TEST
Date of Test: 5/20/2020 Test File: 4509 Kit Den Dr
Technician: Trevor Donnelly (EnergyLogic)
Project Number:
Customer: LC Home
Phone:
Fax:
Building Address: 4509 Kit Den Dr
Ft Collins, CO 80525
Test Results at 50 Pascals:
cfm50 Airflow 1103 (+/- 6.1 %)
ACH50 1.65
Leakage Areas: 94.7 in² (+/- 17.1 %) Canadian EqLA @ 10 Pa
45.4 in² (+/- 28.3 %) LBL ELA @ 4 Pa
Building Leakage Curve: Flow Coefficient (C) = 55.5 (+/- 45.4 %)
Exponent (n) = 0.764 (+/- 0.125)
Correlation Coefficient = 0.99608
Test Standard: E779-10
Test Mode: Depressurization
4 5 6 7 8 9 10 20 30 40 50 60 70
Building Pressure (Pa)
100
200
300
400
500
600
700
800
900
1000
2000
Building
Leakage
(cfm)
Depressurize ____
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 5/20/2020 Test File: 4509 Kit Den Dr
Building Information
Volume (ft³) 40135
Surface Area: (ft²)
Floor Area: (ft²)
Height (ft) 20
Year of Construction 2020
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (110V) -
Micromanometer Energy Conservatory DG700
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 5/20/2020 Test File: 4509 Kit Den Dr
Depressurization Test:
Environmental Data
Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft)
Pre-Test 65.0 75.0
Post-Test 65.0 75.0
Average 65.0 75.0 5000.0
Data Points - Data Entered Manually (TTE 5.0.8.4)
Nominal
Building
Pressure
(Pa)
Baseline
adjusted
Building
Pressure
(Pa)
Fan
Pressure
(Pa)
Nominal
Flow
(cfm)
Adjusted
Flow
(cfm) % Error
Fan
Configuration
0.0 n/a n/a
-60.0 -60.0 45.6 1224 1308 3.2 Ring A
-50.0 -50.0 32.1 1032 1102 -0.1 Ring A
-40.0 -40.0 197.2 832 889 -4.4 Ring B
-30.0 -30.0 137.2 695 743 -0.5 Ring B
-20.0 -20.0 77.3 523 559 2.0 Ring B
0.0 n/a n/a
Deviations from Standard ASTM E779-10 - Test Parameters
- Pressurization test not included.
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 5/20/2020 Test File: 4509 Kit Den Dr
Comments
House to garage: -48 pass