HomeMy WebLinkAbout203 LORIEN LN - DISCLOSURES - 10/23/2020 (7)BUILDING LEAKAGE TEST
EnergyLogic
PO Box N
Berthoud , Colorado 80513
Date of Test: 10/23/2020 Test File: 203 Lorien Lane Unit 206 Signature Construction TECTITE
Technician: Adrian Calderon
Project Number:
Customer: Signature Construction
Phone:
Fax:
Building Address: 203 Lorien Lane Unit 106
Fort Collins, CO 80525
Test Results at 50 Pascals:
cfm50 Airflow 843 (+/- 3.1 %)
ACH50
cfm/ft² (Surface Area) 0.2192
Leakage Areas: 74.1 in² (+/- 10.0 %) Canadian EqLA @ 10 Pa or 0.0193 in²/ft² Surface Area
36.0 in² (+/- 16.4 %) LBL ELA @ 4 Pa or 0.0094 in²/ft² Surface Area
Building Leakage Curve: Flow Coefficient (C) = 44.9 (+/- 26.2 %)
Exponent (n) = 0.749 (+/- 0.071)
Correlation Coefficient = 0.99866
Test Standard: E779-10
Test Mode: Depressurization
4 5 6 7 8 9 10 20 30 40 50 60 70
Building Pressure (Pa)
100
200
300
400
500
600
700
800
900
1000
2000
Building
Leakage
(cfm)
Depressurize ____
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 10/23/2020 Test File: 203 Lorien Lane Unit 206 Signature Construction TECTITE
Building Information
Volume (ft³)
Surface Area: (ft²) 3844.3
Floor Area: (ft²)
Height (ft) 19
Year of Construction 2020
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (110V) -
Micromanometer Energy Conservatory DG700
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 10/23/2020 Test File: 203 Lorien Lane Unit 206 Signature Construction TECTITE
Depressurization Test:
Environmental Data
Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft)
Pre-Test 71.0 18.0
Post-Test 71.0 18.0
Average 71.0 18.0 5030.0
Data Points - Data Entered Manually (TTE 5.0.8.4)
Nominal
Building
Pressure
(Pa)
Baseline
adjusted
Building
Pressure
(Pa)
Fan
Pressure
(Pa)
Nominal
Flow
(cfm)
Adjusted
Flow
(cfm) % Error
Fan
Configuration
0.0 n/a n/a
-60.0 -60.0 31.2 1017 948 -1.9 Ring A
-50.8 -50.8 244.2 925 862 1.0 Ring B
-42.0 -42.0 181.3 798 743 0.5 Ring B
-32.6 -32.6 126.6 668 622 1.7 Ring B
-21.5 -21.5 63.4 474 442 -1.4 Ring B
0.0 n/a n/a
Deviations from Standard ASTM E779-10 - Test Parameters
- An interval between building pressures exceeds 10 Pa.
- Pressurization test not included.
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 10/23/2020 Test File: 203 Lorien Lane Unit 206 Signature Construction TECTITE
Comments
None