HomeMy WebLinkAbout902 JEROME ST - DISCLOSURES - 7/9/2019BUILDING LEAKAGE TEST
Date of Test: 7/9/2019 Test File: Untitled
Technician: Zach Kimbrough - EnergyLogic
Project Number: 57901
Customer: Philgreen
Phone:
Fax:
Building Address: 902 Jerome St Unit 2
Fort Collins, CO 80524
Test Results at 50 Pascals:
cfm50 Airflow 707 (+/- 2.2 %)
ACH50 2.60
Leakage Areas: 79.4 in² (+/- 7.2 %) Canadian EqLA @ 10 Pa
44.4 in² (+/- 11.7 %) LBL ELA @ 4 Pa
Building Leakage Curve: Flow Coefficient (C) = 68.3 (+/- 18.7 %)
Exponent (n) = 0.598 (+/- 0.051)
Correlation Coefficient = 0.99894
Test Standard: E779-10
Test Mode: Depressurization
4 5 6 7 8 9 10 20 30 40 50 60 70 80
Building Pressure (Pa)
100
200
300
400
500
600
700
800
900
Building
Leakage
(cfm)
Depressurize ____
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 7/9/2019 Test File: Untitled
Building Information
Volume (ft³) 16335
Surface Area: (ft²)
Floor Area: (ft²)
Height (ft) 30
Year of Construction 2019
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (110V) -
Micromanometer Energy Conservatory DG700
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 7/9/2019 Test File: Untitled
Depressurization Test:
Environmental Data
Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft)
Pre-Test 80.0 84.0
Post-Test 80.0 84.0
Average 80.0 84.0 5000.0
Data Points - Data Entered Manually (TTE 5.0.8.4)
Nominal
Building
Pressure
(Pa)
Baseline
adjusted
Building
Pressure
(Pa)
Fan
Pressure
(Pa)
Nominal
Flow
(cfm)
Adjusted
Flow
(cfm) % Error
Fan
Configuration
1.7 n/a n/a
-59.1 -60.7 166.0 764 786 -1.0 Ring B
-50.4 -52.0 141.2 705 726 0.3 Ring B
-40.0 -41.6 111.1 626 644 1.7 Ring B
-31.3 -32.9 79.4 530 546 -0.9 Ring B
-20.5 -22.1 49.9 421 433 -0.1 Ring B
1.5 n/a n/a
Deviations from Standard ASTM E779-10 - Test Parameters
- An interval between building pressures exceeds 10 Pa.
- Pressurization test not included.
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 7/9/2019 Test File: Untitled
Comments
Detatched Garage