HomeMy WebLinkAbout2181 YEARLING DR - DISCLOSURES - 11/26/2018BUILDING LEAKAGE TEST
GS Services, LTD.
2000 S College Ave #308
Fort Collins, CO 80525
Email: buildingperformance@gsservices.com Website: gsservices.com
Date of Test: 11/26/2018 Test File: Bellisimo - 2181 Yearling Drive Unit 1 - BD1
Technician: Paul Higman
Project Number:
Customer: Bellisimo
Building Address: 2181 Yearling Drive
Unit 1
Fort Collins, CO
Test Results
1. Airflow at 50 Pascals: 663 CFM50 ( +/- 1.0 %)
(50 Pa = 0.2 w.c.) 2.97 ACH50
2. Leakage Area: 36.5 in2 LBL ELA @ 4 Pa
3. Building Leakage Curve: Flow Coefficient (C) = 40.4 ( +/- 7.4 %)
Exponent (n) = 0.715 ( +/- 0.020 )
Correlation Coefficient = 0.99959
4. Test Settings: Test Standard: RESNET Multi-Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 11/26/2018 Test File: Bellisimo - 2181 Yearling Drive Unit 1 - BD1
Building Information
Volume 13416
Surface Area
Floor Area 1522
Height
# of Bedrooms
# of Occupants
Year of Construction
Wind Shield M
Location Climate Information
Ventilation Weather Factor 0.87
Energy Climate Factor 17.00
Heating Degree Days 6128
Cooling Degree Days 297
Design Winter Wind Speed 7.3 mph
Design Summer Wind Speed 9.4 mph
Design Winter Temp Diff 73 deg F
Design Summer Temp Diff 15 deg F
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (110V) 19247 -
Micromanometer Energy Conservatory DG700 42530 1/22/2016
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 11/26/2018 Test File: Bellisimo - 2181 Yearling Drive Unit 1 - BD1
Depressurization Test:
Environmental Data
Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft)
84.0 34.0 5000.0
Data Points
Nominal
Building Pressure
(Pa)
Baseline Adjusted
Building Pressure
(Pa)
Fan
Pressure
(Pa)
Nominal
Flow
(cfm)
Adjusted
Flow
(cfm) % Error
Fan
Configuration
-0.2 n/a n/a
-60.4 -59.8 176.5 787 752 -0.3 Ring B
-54.1 -53.6 150.4 727 695 -0.3 Ring B
-48.1 -47.5 125.5 665 635 -0.7 Ring B
-42.2 -41.6 106.1 612 584 0.4 Ring B
-36.1 -35.5 84.7 547 523 0.5 Ring B
-30.3 -29.7 65.4 482 460 0.6 Ring B
-24.4 -23.8 48.2 414 395 1.3 Ring B
-18.2 -17.6 29.5 324 310 -1.5 Ring B
-0.9 n/a n/a
Time Averaging Period: 10
Deviations from Standard RESNET Multi-Point Test - Test Parameters
None
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 11/26/2018 Test File: Bellisimo - 2181 Yearling Drive Unit 1 - BD1
Comments
House WRT Garage = -46.3 Pa