Loading...
HomeMy WebLinkAbout6132 EAGLE ROOST DR - DISCLOSURES - 1/7/2020BUILDING LEAKAGE TEST Date of Test: 1/7/2020 Test File: 6132 Eagle Roost Drive final Technician: Jay- Burgess Construction Consultants Project Number: Customer: Fort Collins Phone: Fax: Building Address: 6132 Eagle Roost Drive Hockley, Colorado 80528 Test Results at 50 Pascals: cfm50 Airflow 1774 (+/- 0.9 %) ACH50 2.04 cfm/ft² (Floor Area) 0.3467 cfm/ft² (Surface Area) 0.1606 Leakage Areas: 155.5 in² (+/- 4.9 %) Canadian EqLA @ 10 Pa or 0.0141 in²/ft² Surface Area 75.5 in² (+/- 7.9 %) LBL ELA @ 4 Pa or 0.0068 in²/ft² Surface Area Building Leakage Curve: Flow Coefficient (C) = 93.8 (+/- 12.5 %) Exponent (n) = 0.751 (+/- 0.033) Correlation Coefficient = 0.99928 Test Standard: E779-10 Test Mode: Depressurization 4 5 6 7 8 9 10 20 30 40 50 60 70 80 Building Pressure (Pa) 200 300 400 500 600 700 800 900 1000 2000 3000 Building Leakage (cfm) Depressurize ____ BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 1/7/2020 Test File: 6132 Eagle Roost Drive final Building Information Volume (ft³) 52076 Surface Area: (ft²) 11046 Floor Area: (ft²) 5118 Height (ft) 20 Year of Construction 2019 Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) - Micromanometer Energy Conservatory DG700 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 1/7/2020 Test File: 6132 Eagle Roost Drive final Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) Pre-Test 66.0 33.0 Post-Test 66.0 33.0 Average 66.0 33.0 4918.0 Data Points - Data Entered Manually (TTE 5.0.8.4) Nominal Building Pressure (Pa) Baseline adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -4.7 n/a n/a -65.0 -60.1 140.6 2120 2053 0.8 Ring A -60.0 -55.1 118.4 1950 1888 -1.1 Ring A -55.0 -50.1 103.4 1825 1768 -0.6 Ring A -50.0 -45.1 89.9 1705 1651 0.5 Ring A -45.0 -40.1 75.0 1560 1511 0.5 Ring A -40.0 -35.1 60.9 1410 1365 0.4 Ring A -35.0 -30.1 47.2 1245 1206 -0.5 Ring A -5.1 n/a n/a Deviations from Standard ASTM E779-10 - Test Parameters - Pressurization test not included. BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 1/7/2020 Test File: 6132 Eagle Roost Drive final Comments Garage with Respect to House @50PA= 45.7 Pa