HomeMy WebLinkAbout6132 EAGLE ROOST DR - DISCLOSURES - 1/7/2020BUILDING LEAKAGE TEST
Date of Test: 1/7/2020 Test File: 6132 Eagle Roost Drive final
Technician: Jay- Burgess Construction Consultants
Project Number:
Customer: Fort Collins
Phone:
Fax:
Building Address: 6132 Eagle Roost Drive
Hockley, Colorado 80528
Test Results at 50 Pascals:
cfm50 Airflow 1774 (+/- 0.9 %)
ACH50 2.04
cfm/ft² (Floor Area) 0.3467
cfm/ft² (Surface Area) 0.1606
Leakage Areas: 155.5 in² (+/- 4.9 %) Canadian EqLA @ 10 Pa or 0.0141 in²/ft² Surface Area
75.5 in² (+/- 7.9 %) LBL ELA @ 4 Pa or 0.0068 in²/ft² Surface Area
Building Leakage Curve: Flow Coefficient (C) = 93.8 (+/- 12.5 %)
Exponent (n) = 0.751 (+/- 0.033)
Correlation Coefficient = 0.99928
Test Standard: E779-10
Test Mode: Depressurization
4 5 6 7 8 9 10 20 30 40 50 60 70 80
Building Pressure (Pa)
200
300
400
500
600
700
800
900
1000
2000
3000
Building
Leakage
(cfm)
Depressurize ____
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 1/7/2020 Test File: 6132 Eagle Roost Drive final
Building Information
Volume (ft³) 52076
Surface Area: (ft²) 11046
Floor Area: (ft²) 5118
Height (ft) 20
Year of Construction 2019
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (110V) -
Micromanometer Energy Conservatory DG700
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 1/7/2020 Test File: 6132 Eagle Roost Drive final
Depressurization Test:
Environmental Data
Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft)
Pre-Test 66.0 33.0
Post-Test 66.0 33.0
Average 66.0 33.0 4918.0
Data Points - Data Entered Manually (TTE 5.0.8.4)
Nominal
Building
Pressure
(Pa)
Baseline
adjusted
Building
Pressure
(Pa)
Fan
Pressure
(Pa)
Nominal
Flow
(cfm)
Adjusted
Flow
(cfm) % Error
Fan
Configuration
-4.7 n/a n/a
-65.0 -60.1 140.6 2120 2053 0.8 Ring A
-60.0 -55.1 118.4 1950 1888 -1.1 Ring A
-55.0 -50.1 103.4 1825 1768 -0.6 Ring A
-50.0 -45.1 89.9 1705 1651 0.5 Ring A
-45.0 -40.1 75.0 1560 1511 0.5 Ring A
-40.0 -35.1 60.9 1410 1365 0.4 Ring A
-35.0 -30.1 47.2 1245 1206 -0.5 Ring A
-5.1 n/a n/a
Deviations from Standard ASTM E779-10 - Test Parameters
- Pressurization test not included.
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 1/7/2020 Test File: 6132 Eagle Roost Drive final
Comments
Garage with Respect to House @50PA= 45.7 Pa