HomeMy WebLinkAbout6008 SAPLING CT - DISCLOSURES - 11/13/2018 (4)BUILDING LEAKAGE TEST
Date of Test: 11/13/2018 Test File: 6008 Sapling Court TECTITE
Technician: Burgess Construction Consultants, Inc. - Jay Bundy
Project Number:
Customer: Toll Brothers
Phone:
Fax:
Building Address: 6008 Sapling Court
Fort Collins, Colorado 80528
Test Results at 50 Pascals:
cfm50 Airflow 1054 (+/- 2.3 %)
ACH50 2.02
cfm/ft² (Floor Area) 0.3750
cfm/ft² (Surface Area) 0.1312
Leakage Areas: 99.5 in² (+/- 14.7 %) Canadian EqLA @ 10 Pa or 0.0124 in²/ft² Surface Area
50.4 in² (+/- 23.5 %) LBL ELA @ 4 Pa or 0.0063 in²/ft² Surface Area
Building Leakage Curve: Flow Coefficient (C) = 66.8 (+/- 36.8 %)
Exponent (n) = 0.705 (+/- 0.096)
Correlation Coefficient = 0.99303
Test Standard: E779-10
Test Mode: Depressurization
4 5 6 7 8 9 10 20 30 40 50 60 70 80
Building Pressure (Pa)
100
200
300
400
500
600
700
800
900
1000
2000
Building
Leakage
(cfm)
Depressurize ____
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 11/13/2018 Test File: 6008 Sapling Court TECTITE
Building Information
Volume (ft³) 31313
Surface Area: (ft²) 8034
Floor Area: (ft²) 2811
Height (ft) 11
Year of Construction 2018
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (110V) -
Micromanometer Energy Conservatory DG700
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 11/13/2018 Test File: 6008 Sapling Court TECTITE
Depressurization Test:
Environmental Data
Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft)
Pre-Test 70.0 33.0
Post-Test 70.0 33.0
Average 70.0 33.0 4737.0
Data Points - Data Entered Manually (TTE 5.0.8.4)
Nominal
Building
Pressure
(Pa)
Baseline
adjusted
Building
Pressure
(Pa)
Fan
Pressure
(Pa)
Nominal
Flow
(cfm)
Adjusted
Flow
(cfm) % Error
Fan
Configuration
-2.7 n/a n/a
-65.0 -61.6 481.7 1295 1248 2.2 Ring B
-60.0 -56.6 399.2 1180 1137 -1.1 Ring B
-55.0 -51.6 346.5 1100 1060 -1.6 Ring B
-50.0 -46.6 321.5 1060 1021 1.9 Ring B
-45.0 -41.6 246.9 930 896 -3.1 Ring B
-40.0 -36.6 222.9 884 852 0.8 Ring B
-35.0 -31.6 181.8 799 770 1.1 Ring B
-4.2 n/a n/a
Deviations from Standard ASTM E779-10 - Test Parameters
- Pressurization test not included.
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 11/13/2018 Test File: 6008 Sapling Court TECTITE
Comments
Garage with Respect to House 45.0 Pa