Loading...
HomeMy WebLinkAbout2915 HARVEST VIEW WAY - DISCLOSURES - 8/15/2018BUILDING LEAKAGE TEST Date of Test: 08/15/2018 Test File: 2915 Harvest View Way Technician: Jay Bundy Project Number: Customer: Toll Brothers 10 Inverness E Dr Ste 125 Englewood, CO 80112 Phone: 303-708-0730 Building Address: 2915 Harvest View Way Fort Collins, Colorado 80528 Test Results 1. Airflow at 50 Pascals: 2259 CFM50 (+/- 1.3 %) (50 Pa = 0.2 w.c.) 2.05 ACH50 0.3648 CFM50/ft2 floor area 0.1689 CFM50/ft2 surface area 2. Leakage Areas: 247.2 in2 (+/- 9.7 %) Canadian EqLA @ 10 Pa 136.1 in2 (+/- 15.1 %) LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 204.8 (+/- 23.4 %) Exponent (n) = 0.614 (+/- 0.060) Correlation Coefficient = 0.97696 4. Test Settings: Test Standard: CGSB Test Mode: Depressurization Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 2. Estimated Design Infiltration Rate: Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 08/15/2018 Test File: 2915 Harvest View Way Building Information Volume 66110 Surface Area 13376 Floor Area 6193 Height # of Bedrooms 5 # of Occupants Year of Construction Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6020 Cooling Degree Days 287 Design Winter Wind Speed 9.0 mph Design Summer Wind Speed 7.0 mph Design Winter Temp Diff 69 deg F Design Summer Temp Diff 16 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) - Micromanometer Energy Conservatory DG700 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 08/15/2018 Test File: 2915 Harvest View Way Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) 63.0 85.0 Data Points - Data Entered Manually (TT 4.0.53.0) Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -3.4 n/a n/a -65.0 -62.9 214.5 2605 2659 2.3 Ring A -60.0 -57.9 191.5 2465 2516 1.8 Ring A -55.0 -52.9 153.1 2210 2256 -3.5 Ring A -50.0 -47.9 135.9 2085 2129 -3.2 Ring A -45.0 -42.9 119.7 1960 2001 -2.6 Ring A -40.0 -37.9 108.7 1870 1909 0.2 Ring A -35.0 -32.9 99.4 1790 1828 4.7 Ring A -0.9 n/a n/a Deviations from Standard CGSB - Test Parameters - Correlation coefficient (0.977) outside of acceptable limits. - Test data was not collected at all 8 recommended target building pressures. - The % Error of the Equivalent Leakage Area is greater than or equal to 7.0% BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 08/15/2018 Test File: 2915 Harvest View Way Comments Garage with Respect to House @50PA= 49.0 PA