HomeMy WebLinkAbout2275 CUTTING HORSE DR - DISCLOSURES - 12/6/2018 (4)BUILDING LEAKAGE TEST
GS Services, LTD.
2000 S College Ave #308
Fort Collins, CO 80525
Email: buildingperformance@gsservices.com Website: gsservices.com
Date of Test: 12/6/2018 Test File: Bellisimo - 2275 Cutting Horse Dr Unit 2 - BDma
Technician: Nick Hiseler
Project Number:
Customer: Bellisimo Inc
Building Address: 2275 Cutting Horse
Unit 2
Fort Collins, CO
Test Results
1. Airflow at 50 Pascals: 672 CFM50 ( +/- 0.7 %)
(50 Pa = 0.2 w.c.) 2.80 ACH50
2. Leakage Area: 36.9 in2 LBL ELA @ 4 Pa
3. Building Leakage Curve: Flow Coefficient (C) = 22.8 ( +/- 5.5 %)
Exponent (n) = 0.865 ( +/- 0.015 )
Correlation Coefficient = 0.99985
4. Test Settings: Test Standard: RESNET Multi-Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 12/6/2018 Test File: Bellisimo - 2275 Cutting Horse Dr Unit 2 - BDma
Building Information
Volume 14372
Surface Area
Floor Area 1520
Height
# of Bedrooms
# of Occupants
Year of Construction
Wind Shield M
Location Climate Information
Ventilation Weather Factor 0.87
Energy Climate Factor 17.00
Heating Degree Days 6128
Cooling Degree Days 297
Design Winter Wind Speed 7.3 mph
Design Summer Wind Speed 9.4 mph
Design Winter Temp Diff 73 deg F
Design Summer Temp Diff 15 deg F
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (110V) 19247 Default
Micromanometer Energy Conservatory DG700
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 12/6/2018 Test File: Bellisimo - 2275 Cutting Horse Dr Unit 2 - BDma
Depressurization Test:
Environmental Data
Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft)
77.0 32.0 5000.0
Data Points - Data Entered Manually
Nominal
Building Pressure
(Pa)
Baseline Adjusted
Building Pressure
(Pa)
Fan
Pressure
(Pa)
Nominal
Flow
(cfm)
Adjusted
Flow
(cfm) % Error
Fan
Configuration
-1.7 n/a n/a
-60.5 -60.7 200.6 839 803 1.1 Ring B
-53.5 -53.7 157.8 745 713 -0.2 Ring B
-48.7 -48.9 132.8 684 655 -0.6 Ring B
-41.0 -41.2 99.9 594 568 0.1 Ring B
-36.9 -37.1 81.8 538 515 -0.8 Ring B
-32.2 -32.4 65.3 481 460 -0.2 Ring B
-26.3 -26.5 311.7 407 390 0.5 Ring C
-17.9 -18.1 163.2 292 279 0.2 Ring C
2.1 n/a n/a
Time Averaging Period: 10
Deviations from Standard RESNET Multi-Point Test - Test Parameters
None
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 12/6/2018 Test File: Bellisimo - 2275 Cutting Horse Dr Unit 2 - BDma
Comments
House WRT Garage = -46.1 Pa