Loading...
HomeMy WebLinkAbout2202 Friar Tuck Ct - Disclosures/Blower Door Test - 08/23/2017BUILDING LEAKAGE TEST Date of Test: 8/23/2017 Test File: Untitled Technician: Zach Kimbrough - EnergyLogic Project Number: 47349 Customer: LC Home Building Address: 2202 Friar Tuck Ct Ft Collins , CO 80524 Test Results 1. Airflow at 50 Pascals: 1167 CFM50 ( +/- 0.8 %) (50 Pa = 0.2 w.c.) 2.34 ACH50 2. Leakage Area: 64.2 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 69.1 ( +/- 5.7 %) Exponent (n) = 0.722 ( +/- 0.016 ) Correlation Coefficient = 0.99976 4. Test Settings: Test Standard: RESNET Multi-Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 68.0 CFM 0.14 ACH 17.0 CFM per person 2. Estimated Design Infiltration Rate: Winter: 127.9 CFM 0.26 ACH Summer: 80.3 CFM 0.16 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 8/23/2017 Test File: Untitled Building Information Volume 29882.56 Surface Area Floor Area 3262.1 Height 20 # of Bedrooms 3 # of Occupants 4 Year of Construction 2017 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 26986-7 8/2/2010 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 8/23/2017 Test File: Untitled Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 70.0 75.0 5200.0 Data Points Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -1.4 n/a n/a -61.1 -59.6 47.2 1245 1314 -0.8 Ring A -55.2 -53.7 40.8 1160 1224 -0.4 Ring A -49.6 -48.1 35.2 1079 1139 0.4 Ring A -43.2 -41.7 28.4 972 1026 0.2 Ring A -37.7 -36.3 221.3 881 930 0.5 Ring B -31.0 -29.5 163.7 759 801 0.6 Ring B -25.3 -23.8 119.9 650 686 0.5 Ring B -19.5 -18.0 77.4 523 552 -1.1 Ring B -1.6 n/a n/a Time Averaging Period: 10 Deviations from Standard RESNET Multi-Point Test - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 8/23/2017 Test File: Untitled Comments Garage: -45 PA Mech: -50 PA