HomeMy WebLinkAbout615 E PLUM ST - DISCLOSURES - 12/18/2017BUILDING LEAKAGE TEST
Date of Test: 12/18/2017 Test File: 615 E Plum tectite Passing
Technician: Greydon Studer
Project Number:
Customer:
Building Address: 615 E Plum
Fort Collins, CO 80524
Test Results
1. Airflow at 50 Pascals: 1571 CFM50 ( +/- 0.6 %)
(50 Pa = 0.2 w.c.) 2.95 ACH50
2. Leakage Area: 86.4 in2 LBL ELA @ 4 Pa
3. Building Leakage Curve: Flow Coefficient (C) = 131.6 ( +/- 4.1 %)
Exponent (n) = 0.634 ( +/- 0.012 )
Correlation Coefficient = 0.99983
4. Test Settings: Test Standard: RESNET Multi-Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 12/18/2017 Test File: 615 E Plum tectite Passing
Building Information
Volume 31939
Surface Area
Floor Area 3480
Height
# of Bedrooms
# of Occupants
Year of Construction
Wind Shield M
Location Climate Information
Ventilation Weather Factor 0.87
Energy Climate Factor 17.00
Heating Degree Days 6128
Cooling Degree Days 297
Design Winter Wind Speed 7.3 mph
Design Summer Wind Speed 9.4 mph
Design Winter Temp Diff 73 deg F
Design Summer Temp Diff 15 deg F
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (110V) Default
Micromanometer Energy Conservatory DG700
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 12/18/2017 Test File: 615 E Plum tectite Passing
Depressurization Test:
Environmental Data
Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft)
70.0 51.0 5000.0
Data Points - Data Entered Manually
Nominal
Building Pressure
(Pa)
Baseline Adjusted
Building Pressure
(Pa)
Fan
Pressure
(Pa)
Nominal
Flow
(cfm)
Adjusted
Flow
(cfm) % Error
Fan
Configuration
-0.7 n/a n/a
-60.0 -59.4 96.3 1763 1754 0.1 Ring A
-54.0 -53.4 84.1 1650 1641 0.2 Ring A
-48.0 -47.4 71.9 1529 1521 0.1 Ring A
-42.0 -41.4 60.1 1401 1394 -0.0 Ring A
-36.0 -35.4 48.1 1257 1250 -0.9 Ring A
-30.0 -29.4 38.5 1128 1122 -0.0 Ring A
-24.0 -23.4 29.1 984 979 0.8 Ring A
-18.0 -17.4 185.4 807 803 -0.2 Ring B
-0.5 n/a n/a
Time Averaging Period: 10
Deviations from Standard RESNET Multi-Point Test - Test Parameters
None
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 12/18/2017 Test File: 615 E Plum tectite Passing
Comments
None