Loading...
HomeMy WebLinkAbout225 GREEN LEAF DR - DISCLOSURES - 2/6/2018BUILDING LEAKAGE TEST Date of Test: 2/6/2018 Test File: 225 Green Leaf Dr Unit 6 Philgreen V2.2.3 Multi Point Tectite Technician: Neal Girard - EnergyLogic, Inc. Project Number: 47580 Customer: Philgreen Construction Building Address: 225 Green Leaf Dr Unit 6 Ft. Collins, CO 80524 Test Results 1. Airflow at 50 Pascals: 531 CFM50 ( +/- 1.1 %) (50 Pa = 0.2 w.c.) 2.43 ACH50 2. Leakage Area: 29.2 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 28.7 ( +/- 17.5 %) Exponent (n) = 0.746 ( +/- 0.046 ) Correlation Coefficient = 0.99810 4. Test Settings: Test Standard: RESNET Multi-Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 35.0 CFM 0.16 ACH 11.7 CFM per person 2. Estimated Design Infiltration Rate: Winter: 58.2 CFM 0.27 ACH Summer: 36.5 CFM 0.17 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate: 35.2 CFM Base Rate: 35.2 CFM BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 2/6/2018 Test File: 225 Green Leaf Dr Unit 6 Philgreen V2.2.3 Multi Point Tectite Building Information Volume 13090 Surface Area Floor Area 1271 Height 30 # of Bedrooms 2 # of Occupants 3 Year of Construction 2018 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) - Micromanometer Energy Conservatory DG700 36002-7 11/15/2012 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 2/6/2018 Test File: 225 Green Leaf Dr Unit 6 Philgreen V2.2.3 Multi Point Tectite Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 65.0 45.0 5000.0 Data Points Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -3.5 n/a n/a -63.9 -59.8 103.2 603 602 -0.8 Ring B -59.2 -55.2 91.3 568 566 -0.8 Ring B -55.8 -51.7 86.1 552 550 1.1 Ring B -51.7 -47.6 74.4 513 512 0.0 Ring B -46.6 -42.5 64.8 479 478 1.6 Ring B -43.5 -39.5 55.5 444 443 -0.5 Ring B -39.4 -35.3 47.9 413 412 0.5 Ring B -36.3 -32.2 40.4 379 378 -1.2 Ring B -4.6 n/a n/a Time Averaging Period: 10 Deviations from Standard RESNET Multi-Point Test - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 2/6/2018 Test File: 225 Green Leaf Dr Unit 6 Philgreen V2.2.3 Multi Point Tectite Comments Connection to: Garage: -45 Pa Mechanicals: -50 Pa