Loading...
HomeMy WebLinkAbout209 COLLEGIATE WAY - DISCLOSURES - 8/2/2017 (6)BUILDING LEAKAGE TEST Date of Test: 8/2/2017 Test File: Multi Point Tectite Unit 2 Re Test Technician: Trevor Donnelly- EnergyLogic Project Number: 46187 Customer: Capstone Collegiate Building Address: 209 Collegiate Way unit 2 Fort Collins, CO 80525 Test Results 1. Airflow at 50 Pascals: 1276 CFM50 ( +/- 1.9 %) (50 Pa = 0.2 w.c.) 4.66 ACH50 2. Leakage Area: 70.2 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 102.5 ( +/- 36.0 %) Exponent (n) = 0.645 ( +/- 0.093 ) Correlation Coefficient = 0.98973 4. Test Settings: Test Standard: RESNET Multi-Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 2. Estimated Design Infiltration Rate: Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 8/2/2017 Test File: Multi Point Tectite Unit 2 Re Test Building Information Volume 16443 Surface Area Floor Area Height # of Bedrooms # of Occupants Year of Construction 2017 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 7170-5 10/9/2008 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 8/2/2017 Test File: Multi Point Tectite Unit 2 Re Test Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 75.0 85.0 5000.0 Data Points Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -8.0 n/a n/a -68.4 -62.9 63.3 1436 1505 1.8 Ring A -65.2 -59.6 58.2 1379 1445 1.1 Ring A -61.1 -55.5 49.7 1277 1339 -1.9 Ring A -55.0 -49.4 41.7 1172 1228 -3.0 Ring A -53.1 -47.6 42.5 1183 1240 0.4 Ring A -48.2 -42.6 37.6 1115 1168 1.5 Ring A -42.8 -37.2 29.5 991 1038 -1.6 Ring A -41.5 -36.0 30.4 1004 1052 2.0 Ring A -3.1 n/a n/a Time Averaging Period: 10 Deviations from Standard RESNET Multi-Point Test - Test Parameters None - * correlation coefficient outside of normally accepted limits. * n value and/or correlation coefficient limits are not officially part of the RESNET Multi-Point Test Standard. BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 8/2/2017 Test File: Multi Point Tectite Unit 2 Re Test Comments Connection to: Garage: Mechanicals: -50 Pa