BUILDING LEAKAGE TEST
Date of Test 8/23/2017
Test File Multi Point Tectite 2050
Customer DR Horton
Technician Trevor Donnelly- EnergyLogic
Project Number 47030
Building Address 2050 Blue Yonder Way
Fort Collins, CO 80525
Test Results
1 Airflow at 50 Pascals
1580 CFM50 (+/- 0 7 %)
(50Pa=02wc)
232ACH50
2 Leakage Area
86 9 in2 LBL ELA @ 4 Pa
3 Building Leakage Curve
Flow Coefficient (C) = 123 6 (+/- 12 5 %)
Exponent (n) = 0 651 ( +/- 0 033 )
Correlation Coefficient = 0 99874
4 Test Settings
Test Standard RESNET Multi -Point Test
Test Mode Depressurization
5 Accuracy Level
Standard Level of Accuracy Test
Infiltration Estimates
1 Estimated Average Annual Infiltration Rate 92 1 CFM
0 14 ACH
18 4 CFM per person
2 Estimated Design Infiltration Rate Winter 173 2 CFM Summer 108 7 CFM
0 25 ACH 0 16 ACH
Cost Estimates
1 Estimated Cost of Air Leakage for Heating
2 Estimated Cost of Air Leakage for Cooling
Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010)
Recommended Whole Bldg Rate 74 6 CFM
Base Rate 79 1 CFM
Infiltration Credit <4 5, CFM>