Loading...
HomeMy WebLinkAbout2050 BLUE YONDER WAY - DISCLOSURES - 8/23/2017 (12)(9nergyLogic analysis Insight, answers. www uglogic.com , BUILDING LEAKAGE TEST Date of Test 8/23/2017 Test File Multi Point Tectite 2050 Customer DR Horton Technician Trevor Donnelly- EnergyLogic Project Number 47030 Building Address 2050 Blue Yonder Way Fort Collins, CO 80525 Test Results 1 Airflow at 50 Pascals 1580 CFM50 (+/- 0 7 %) (50Pa=02wc) 232ACH50 2 Leakage Area 86 9 in2 LBL ELA @ 4 Pa 3 Building Leakage Curve Flow Coefficient (C) = 123 6 (+/- 12 5 %) Exponent (n) = 0 651 ( +/- 0 033 ) Correlation Coefficient = 0 99874 4 Test Settings Test Standard RESNET Multi -Point Test Test Mode Depressurization 5 Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1 Estimated Average Annual Infiltration Rate 92 1 CFM 0 14 ACH 18 4 CFM per person 2 Estimated Design Infiltration Rate Winter 173 2 CFM Summer 108 7 CFM 0 25 ACH 0 16 ACH Cost Estimates 1 Estimated Cost of Air Leakage for Heating 2 Estimated Cost of Air Leakage for Cooling Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate 74 6 CFM Base Rate 79 1 CFM Infiltration Credit <4 5, CFM> J No Text No Text No Text