BUILDING LEAKAGE TEST
Date of Test: 5/3/2016
Test File: 2015 Yearling Dr Multi Point Tectite
Customer: DR Horton
Technician: Brad Smith - EnergyLogic
Project Number: 38046
Building Address: 2015 Yearling Dr
Fort Collins, CO 80525
Test Results
1. Airflow at 50 Pascals:
1599 CFM50 (+/- 5.1 %)
(50 Pa = 0.2 w.c.)
2.79 ACH50
2. Leakage Area:
87.9 in2 LBL ELA @ 4 Pa
3. Building Leakage Curve:
Flow Coefficient (C) = 100.1 (+/- 70.1 %)
Exponent (n) = 0.708 ( +/- 0.186 )
Correlation Coefficient = 0.96706
4. Test Settings:
Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
5. Accuracy Level
Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate: 93.2 CFM
0.16 ACH
18.6 CFM per person
2. Estimated Design Infiltration Rate: Winter: 175.3 CFM Summer: 110.0 CFM
0.31 ACH 0.19 ACH
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010)
Recommended Whole Bldg Rate: 60.5 CFM
Base Rate: 72.3 CFM
Infiltration Credit: <11.8 CFM>